HomeMy WebLinkAboutOC_RS982477 - CalcsJTL DESIGN & ENGINEERING R
20351 Irvine Ave. Suite 92 15
Santa Ana Heights, CA 92707 �/
Tel: (714) 545-8470
Fax: (714) 545-8446 Cover sheet of
. STRUCTURAL CALCULATIONS
FOR
PROJECT: June e Richard Cbao's residence
Retaining wall design at stair well
PROJECT NO: 98-AO60C
PROJECT ADDRESS: 15 Sailcrest
Newuort Coast Califomia
"Pelican Crest"
CLIENT June & Richard Chao
ADDRESS: 14 Hexham
Irvine, Califomia 92614
DATE: Jan. 5. 1999
V jk FESS/py
C-3
TAR
iy 4G�Fy�
C m
"' C 35023 m
Exp. 9 99
z}
�TqT �P
F CALIF
��AN , 3
I WIN=
Irmoi
JTL DESIGN & ENGINEERING
20351 Irvine Ave. Suite 42
Santa Ana Heights, CA 92707
Tel: (714) 545-8470 Fax: (714) 545-8446
June & Richard Chaos residence
Retaini zy wall design
15 Sailcrest Newport Coast, California
Design criteria
TYPE 1 RETAINING WALLS (located at stair well)
Soil pressure (equivalent fluid pressure)
Passive
Friction coefficient
Soil bearing
Concrete
Reiinforcing steel
Masonry (CMU)
Grout
Date:
Jan.S 1999
Job No:
98-A060C
By
P L
Sheet No:
R - 1
68 pd for free standing at top and restraint at base
250 psf per ft
0.3
1800 psf
f c= 3000 psi at 28 days
fy= 60000 psi
fm = 1500 psi
3000 psi
TYPE 2 RETAINING WALL(located at stair well)
Soil pressure(EFP) 68 pcf for restraint at both top and base
Remainders are the same as type 1
NOTES
1.All retaining wall shall be solid grout with special inspection.
2.The geologist and soil engineer shall review the retaining wall drawings and
Shall inspect the retaining wall footing excavation and compaction.
JTL DESIGN & ENGINEERING Date: Jan5. 1999
20351 Irvine Ave. Suite 92 Job No: 98-AO60C
Santa Ana Heights, CA 92707 By P L
Tel: (714) 545-8470 Fax: (714) 545-8446 Sheet No; w -
June & Richard Chaos residence retaining wall design
Mr.& Mrs Richard Chao's residence RW H=149:)l JOB NO. 98-AO60A
RETAINING WALL DESIGN..... STANDARD RETAINING WALL
-------------------------------------------------
RETAINING HEIGHT (ABOVE LOWEST GRADE) = 16.25 FT.
DEPTH TO BOTTOM OF FOOTING = 36.00 IN.
LENGTH OF HEEL = 68.00 PCF
ACTIVE SOIL PRESSURE _
ALLOWABLE SOIL BEARING PRESSURE = 1800.00 PSF
ADDITIONAL VERTICAL LOAD ON WALL = 1800.00 PPF
FOOTING STABILITY CHECK WITH FOOTING WIDTH = 12.50 FT
DIST. TOE TO RESULTANT = 5.70 FT.> B/3
SOIL BEARING =1765.56 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 55.68 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = 6.23 SQ.IN./FT
SHEAR AT BASE = 38.09 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 38.42 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = 1.44 SQ.IN./FT
<DONE> if
FORCE
ARM
MOMENT
(LBS)
(FT)
(FT,LBS)
W1
4148.0
8.50
35258.0
W2
1906.3
6.25
11914.1
W3
750.0
3.75
2812.5
W4
3774.7
12.50
47183.9
W5
5100.0
11.00
56100.0
RACT11324.1
-6.08
-68888.4
DIST. TOE TO RESULTANT = 5.70 FT.> B/3
SOIL BEARING =1765.56 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 55.68 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = 6.23 SQ.IN./FT
SHEAR AT BASE = 38.09 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 38.42 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = 1.44 SQ.IN./FT
<DONE> if
JTL DESIGN & ENGINEERING Date: Jan.5, 1999
20351 Irvine Ave. Suite 42 Job No: 98-A060C
Santa Ana Heights, CA 92707 BY P L
Tel: (714) 545-8470 Fax: (714) 545-8446 Sheet No: R -[L
June & Richard Chaos residence retaining wall design
Mr.& Mrs Richard Chao's residence RW H=14 JOB NO. 98-A060A
RETAINING WALL DESIGN..... STANDARD RETAINING WALL
-------------------------------------------------
RETAINING HEIGHT (ABOVE LOWEST GRADE) = 15.00 FT.
DEPTH TO BOTTOM OF FOOTING = 17.25 FT.
LENGTH OF HEEL = 36.00 IN.
ACTIVE SOIL PRESSURE = 68.00 PCF
ALLOWABLE SOIL BEARING PRESSURE = 1800.00 PSF
ADDITIONAL VERTICAL LOAD ON WALL = 1800.00 PPF
FOOTING STABILITY CHECK WITH FOOTING WIDTH = 11.75 FT
DIST. TOE TO RESULTANT = 5.36 FT.> B/3
SOIL BEARING =1753.94 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 46.42 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = 2.92 SQ.IN./FT
SHEAR AT BASE = 33.74 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 31.04 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = 1.13 SQ.IN./FT
<DONE>
FORCE
ARM
MOMENT
(LBS)
(FT)
(FT,LBS)
W1
3904.0
7.75
30256.0
W2
1791.9
5.88
10527.3
W3
675.0
3.38
2278.1
W4
3372.4
11.75
39625.4
W5
4800.0
10.25
49200.0
RACT10117.1
-5.75
-58173.5
DIST. TOE TO RESULTANT = 5.36 FT.> B/3
SOIL BEARING =1753.94 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 46.42 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = 2.92 SQ.IN./FT
SHEAR AT BASE = 33.74 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 31.04 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = 1.13 SQ.IN./FT
<DONE>
'p?
JTL DESIGN & ENGINEERING
20351 Irvine Ave. Suite 92
Santa Ana Heights, CA 92707
Tel: (714) 545-8470 Fax: (714) 545-8446
June & Richard Chaos residence retaining wall design
Date: Jan5, 1999
Job No: 98-AO60C
By P L
Sheet No: RW - S
Mr.& Mrs Richard Chao's residence RW H=1i}l JOB NO. 98-A060A
RETAINING WALL DESIGN..... STANDARD RETAINING WALL
-------------------------------------------------
RETAINING HEIGHT (ABOVE LOWEST GRADE) = 14.00 FT.
DEPTH TO BOTTOM OF FOOTING = 16.25 FT.
LENGTH OF HEEL = 36.00 IN.
ACTIVE SOIL PRESSURE = 68.00 PCF
ALLOWABLE SOIL BEARING PRESSURE = 1800.00 PSF
ADDITIONAL VERTICAL LOAD ON WALL = 1800.00 PPF
FOOTING STABILITY CHECK WITH FOOTING WIDTH = 11.00 FT
DIST. TOE TO RESULTANT = 5.01 FT.> B/3
SOIL BEARING =1755.55 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 38.25 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = 1.56 SQ.IN./FT
SHEAR AT BASE = 29.65 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 24.63 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = .87 SQ.IN./FT
<DONE>
cid 3.�,c. t/ -7,k '
4-y
FORCE
ARM
MOMENT
(LBS)
(FT)
(FT,LBS)
W1
3660.0
7.00
25620.0
W2
1677.5
5.50
9226.3
W3
600.0
3.00
1800.0
W4
2992.7
11.00
32919.8
W5
4500.0
9.50
42750.0
RACT
8978.1
-5.42
-48631.5
DIST. TOE TO RESULTANT = 5.01 FT.> B/3
SOIL BEARING =1755.55 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 38.25 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = 1.56 SQ.IN./FT
SHEAR AT BASE = 29.65 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 24.63 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = .87 SQ.IN./FT
<DONE>
cid 3.�,c. t/ -7,k '
4-y
JTL DESIGN & ENGINEERING Date: Jan5, 1999
20351 Irvine Ave. Suite #2 Job No: 98-AO60C
Santa Ana Heights, CA 92707 By P L
Tel: (714) 545-8470 Fax: (714) 545-8446 Sheet No: Rw -�/
June & Richard Chaos residence retaining wall design
Mr.& Mrs Richard Chao's residence RW H=15 I JOB NO. 98-AO60A
RETAINING WALL DESIGN..... STANDARD RETAINING WALL
-------------------------------------------------
RETAINING HEIGHT (ABOVE LOWEST GRADE) = 13.00 FT.
DEPTH TO BOTTOM OF FOOTING = 15.25 FT.
LENGTH OF HEEL = 36.00 IN.
ACTIVE SOIL PRESSURE = 68.00 PCF
ALLOWABLE SOIL BEARING PRESSURE = 1800.00 PSF
ADDITIONAL VERTICAL LOAD ON WALL = 1800.00 PPF
FOOTING STABILITY CHECK WITH FOOTING WIDTH = 10.25 FT
DIST. TOE TO RESULTANT = 4.64 FT.> B/3
SOIL BEARING =1773.89 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 31.10 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = .85 SQ.IN./FT
SHEAR AT BASE = 25.83 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 19.11 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = .67 SQ.IN./FT
<DONE>
`7 y ". C ✓-)
FORCE
ARM
MOMENT
(LBS)
(FT)
(FT,LBS)
W1
3416.0
6.25
21350.0
W2
1563.1
5.13
8011.0
W3
525.0
2.63
1378.1
W4
2635.7
10.25
27016.0
W5
4200.0
8.75
36750.0
RACT
7907.1
-5.08
-40194.6
DIST. TOE TO RESULTANT = 4.64 FT.> B/3
SOIL BEARING =1773.89 PSF < ALLOWABLE
SLIDING RESISTED BY RESTRAINT AT LOWER GRADE
REINFORCEMENT DESIGN FOR 24.00 INCH BLOCK WALL WITH:
----------------------------------------------------
DEPTH TO REINF. = 2.50 IN. FM = 1500.0 PSI
INSPECTION REQUIRED
MOMENT AT BASE OF WALL = 31.10 FT KIPS/FT
AREA OF REINFORCEMENT IN WALL = .85 SQ.IN./FT
SHEAR AT BASE = 25.83 PSI < ALLOWABLE = 42.60 PSI
MOMENT IN FOOTING AT FACE OF WALL = 19.11 FT KIPS/FT
REINF. IN 15.0 INCH THICK FTG = .67 SQ.IN./FT
<DONE>
`7 y ". C ✓-)
JTL DESIGN & ENGINEERING Date: Jan.5. 1999
20351 Irvine Ave. Suite 42 Job No: 98-AO60C
Santa Ana Heights, CA 92707 By P L
Tel: (714) 545-8470 Fax: (714) 545-8446 Sheet No: R - -�
June & Richard Chaos residence retaining wall design
TYPE 2 RETAINING WALL (restraint at both top and base)
2- 64 BARS CONTINJOV5 O TOP
•4 DOHELS 6 16' O.G.
LAP BI ENE OVER TOP 1
OF WAL t WATERPROOFIN6�
F'c (GONG. STRENGTH): 3000 Psi B
6' CMU. WALL
25 DAYS
D, (MASONRY STRENGTH)- 1500 PSI
�¢nk>"SYS
go
FULLY GROUTED
'MIRAFI' MIRADRAIN o/
GARAGE SLAB PER PLAN
VIIIVIII
' SEE FRAMING PLANS FOR REFERENCES
_
TO TOP OF WALL CONNECTIONS
2-
•4 BARS o 16' O.G.
_
ALL CELLS HI ION FROM
VIII
VERTICAL
�a
g ea8
e�°$ a8_�SIII
SSB
So SSS
4' DIA. MIN. PVC SCHED. 40
PERFORATED PIPE n/ 12' WIDE
COLUMN OF GRAVEL TO 2/5 OF
64 BARS o 24' O.G.
HALL HEIGHT HRAPPED IN
�g
'MIRAFI' 14ON FILTER FABRIC
HORIZONTAL
15 BAR 6-j=!`4<--
c�
05 BARS a 12' O.G.
E31TUTHERE O/
FOOTING
2- •5 BARS CONT.
n/ 112 TIES o I6' O.G.
a
a
J
12' G.M.U. WALL
n
FULLY GROUTED
x
•5 BARS O 24' O.G.
HORIZONTAL
REBAR 'A'
t8)t
-t:61
HOUSE SLAB PER PLAN
H/ M4 DOWELS o 24' O
36'
C�
.,
T-
EO. EO.
.N. r
•4 DOHELS 6 16' O.G.
LAP BI ENE OVER TOP 1
OF WAL t WATERPROOFIN6�
F'c (GONG. STRENGTH): 3000 Psi B
36'
25 DAYS
D, (MASONRY STRENGTH)- 1500 PSI
�¢nk>"SYS
go
0
'MIRAFI' MIRADRAIN o/
GARAGE SLAB PER PLAN
VIIIVIII
' SEE FRAMING PLANS FOR REFERENCES
_
TO TOP OF WALL CONNECTIONS
•ALL WALLS TO BE SOLID GROUT
_
ALL CELLS HI ION FROM
VIII
GOVERN NG A&ENC r
�a
g ea8
e�°$ a8_�SIII
SSB
EO. EO.
.N. r
F'c (GONG. STRENGTH): 3000 Psi B
og ,q q>g
S a —_
25 DAYS
D, (MASONRY STRENGTH)- 1500 PSI
�¢nk>"SYS
0-4
'MIRAFI' MIRADRAIN o/
&!� a
MIRAD ZI HATERPROOFING
o�
00
VIII
°oo�
12' NIDE CONT. CONCRETE
STEM WALL FOOTING
SSB
So SSS
4' DIA. MIN. PVC SCHED. 40
PERFORATED PIPE n/ 12' WIDE
COLUMN OF GRAVEL TO 2/5 OF
HALL HEIGHT HRAPPED IN
�g
'MIRAFI' 14ON FILTER FABRIC
a
15 BAR 6-j=!`4<--
c�
05 BARS a 12' O.G.
E31TUTHERE O/
FOOTING
EO. EO.
.N. r
JTL DESIGN & ENGINEERING
20351 Irvine Ave. Suite 42
Santa Ana Heights, CA 92707
J P77 Tel: (714) 545-8470 Fax: (714) 545-8446
June & Richard Chaos residence retaining wall design
TYPE 2 RETAINING WALL (restraint at both top and base)
H
positive moment
11'
7321 ft -lbs
10'
5500 ft -lbs
9'
4010 ft -lbs
8' 2816 ft -lbs
7' 1887 ft -lbs
6' 1188 ft -lbs
5' 688 ft -lbs
4' 352 ft -lbs
reinforcing steel
Date:
Jan.5, 1999
Job No:
98-A060C
By
P L
Sheet No:
RW _A
+M = (0,1)(P)(H) = 5.5 (H) (H) (H)
- M = (0.185)(P)(H) = 10.2 (H)(H)(H)
Where P = horizontal force from soil presssure
_ (EFP) (H)(H)/2
EFP = 110 pcf per soil report
P= (55)(H)(H)
98 @16"OC (12"CMU)
#7 @16"OC(12"CMU)
96 @16"OC(12"CMU)
#5 @16"OC(12"CMU)
#5 @16"OC(12"CMU)
#5 @16 "OC( 8"CMU)
#4 @16"OC( 8"CMU )
#4 @24"OC(8" CMU)
negative moment
13757 ft -lbs
10200 ft -lbs
7436 ft -lbs
5222 ft -lbs
3499 ft -lbs
2204 ft -lbs
1275 ft -lbs
653 ft -lbs
reinforcing steel
#9 @16"OC (12"CONC.)
#8 @16"OC(12" CONC.)
#7@16"OC(12" CONC. )
47 @16"OC(12" CMU )
#6 @16"OC(12" CMU )
95 @16"OC(12"CMU )
45 @16"OC" (8" CMU.)
94 @16"OC.(8" CMU)
JTL DESIGN & ENGINEERING Date: Jan.S 1999
20351 Irvine Ave. Suite 42 Job No: 98-AO60C
Santa Ana Heights, CA 92707 By P L
Tel: (714) 545-8470 Fax: (714) 545-8446 Sheet No: RW - cJ
June & Richard Chaos residence retaining wall design
Active soil pressure
110 pcf
Allowable soil bearing
1800 psf
Alowable passive pressure 250 psf per ft
Friction coefficient
0.3
Concrete strength
f c=4000 psi at 28 days
Reinforcing steel
fy=60000 psi
CMU
fm=1500 psi
TYPE 2 RETAINING WALL DESIGN (restraint at top and bot)
H
W
Hl
H2
Rebar "A" (negative Mo)
Rebar `B" (positive Mo)
11'
7'-0"
3'-0"
5"-0"
# 90,16"1C
# 8 @16"OC
10'
6'-0"
2'-0"
5'-0"
#8@16"OC
47 @16"OC
9'
5'-6"
1'-0"
5'-0"
#7x,16"OC
961@ 1 6"OC
8'
4'-6"
-----
5'-0"
47a_.] 6"0
95icaW'OC
7'
4'-0"
-----
4'-0"
46n,16"OC
95(2,16"0C
6'
3'-6"
-----
3'-0"
95 L&I6"OC
95 16"OC
5
3'-0"
-----
2'-0"
#5ru)16"OC
#4g 16"0
4'
2'-6"
-----
----
94(a),16"0C
#4 24"OC
-P
0
O
V
s
0
0
>0
�z5mq 2U 11
15 SGS I vi'S K
AERO ENERGY
TITLE 24 CALCULATIONS
12711 NEWPORT AVE., SUITE G
TUSTIN, CALIF. 92780
(714) 505-4207
DATE: 8-4-98
OWNER: MR. & MRS. RICHARD CHAD
14 HEXHAM
IRVINE, CA. 92612
714-854-5202
DESIGNER: DENNIS CHERRY & ASSOCIATES
20351 IRVINE AVENUE, SUITE #1
SANTA ANA HEIGHTS, CA. 92707
714-641-1505
PROJECT: CUSTOM RESIDENCE
15 SAILCREST
"PELICAN CREST"
NEWPORT COAST, CA.
STATEMENT OF COMPLIANCE
The energy conservation standards for new residential
buildings as set forth in Title 24, Part 2, Chapter 2-53; and
Title 20, Chapter 2, Subchapter 4, Article 1, of the
California Administrative Code, have been reviewed. This
design conforms to all requirements as they apply in Zone 6
using MICRDPAS 4, VERSION 4.50, A California Energy
Commission approved computer performance method program.
PREPARED BY
W-
TdRRY M. STATUM
** SUMMARY SHEET **
Project: MR. & MRS. RICHARD CHAD Zone: 6
Plan: CUSTOM
Wall Insulation: R-13
Ceiling Insulation: R-19 in True -Sloping / R-30 with Attic above
Raised Floor Insulation: R-19
Slab Edge Insulation: None
Glazing Type: All glass is single pane, except the following,
which is dual:
SKYLIGHTS
Shading Devices! No shading devices required.
Hard Surface Flooring: 1970.0 / 2564.0 total sq. ft.
1 3 5 5.000RT: 1885.0 BATH(S): 85.0
�) LAUNDRY: 39.0 ENTRY/FOYER: 346.0
LIBRARY: 262.0 G.HALL: 427.0
HALL(S): 266.0 DINING: 272.0
M. ROOM: 189.0 KITCHEN: 355.0
M.BATH: 292.0 BATH(S): 116.0
Minimum Furnace S.E.: 80.0 AFUEX
Maximum Furnace Sonnet Capacity: NIA BTUE
Minimum AIC S. E. E. R, : 10.0
A/C Tonnage: 25.0
Infiltration: Standard
Minimum R-4.2 insulation required on ducts in unconditioned spaces.
EQUIPMENT SCHEDULE
PROSECT: MR. & MRS. RICHARD CHAO
15 SAILCREST
NEWPORT COAST, CA.
ARCHITECT: DENNIS CHERRY & ASSOCIATES
20351 IRVINE AVE., #1
SANTA ANA HEIGHTS, CA. 92707
714-641-1505
H. V. A. C.
HEATING: BASEMENT
BRYANT
COMPANY
FURNACE #363KAVO36045
* SPORTS
CT.
BRYANT
COMPANY
FURNACE #383KAV060111
FIRST
FLOOR:
BRYANT
COMPANY
FURNACE 4383KAVOGOIII
FIRST
FLOOR:
BRYANT
COMPANY
FURNACE #363KAV060111
SECOND
FLOOR:
BRYANT
COMPANY
FURNACE #373LAV060115
MASTER
BED.
BRYANT
COMPANY
FURNACE #373LAVO24050
COOLING: BASEMENT
BRYANT
COMPANY
COND. #561NO36
• SPORTS
CT.
BRYANT
COMPANY
COND. #561NOGO
FIRST
FLOOR:
BRYANT
COMPANY
CONE). 4561NO60
FIRST
FLOOR:
BRYANT
COMPANY
COND. #561N060
SECOND
FLOOR:
BRYANT
COMPANY
CONE). #561NO60
MASTER
BED. .
BRYANT
COMPANY
COND. #561NO24
•1005 CFM/HR MINIMUM VENTILATION REQUIRED
WATER HEATER:
AMERICAN STANDARD MODEL (2)4G52-10OT88-4NV
CERTIFICATE OF COMPLIANCE: RESIDENTIAL Page 1 CF -1R
-------------------------------------------------------------------------------
Project Title.......... MR. & MRS. RICHARD CHAO Date........ 08/04/98
Project Address........ 15 SAILCREST****** ---------------------
NEWPORT COAST, CA. •v4.50w 1 I
Documentation Author... Terry Statum ►•tt•+• I Building Permit # I
Aero Energy 1 1
12711 Newport Ave, Suite G I Plan Check / Date I
Tustin, CA 92780 1 1
714-505-4207 1 Field Check/ Date I
Climate Zone........... 06 ---------------------
Compliance Method...... MICROPAS4 v4.50 for 1995 Standards by Enercomp, Inc.
I MICROPAS4 v4.50 File-CHAO Wth-CTZ06S92 Program -FORM CF -1R I
User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO
-------------------------------------------------------------------------------
GENERAL INFORMATION
Conditioned Floor Area.....
Building Type ..............
Construction Type .........
Building Front Orientation.
Number of Dwelling Units...
Number of Stories..........
Floor Construction Type....
Glazing Percentage.........
Average Glazing U -value....
11540 of
Single Family Detached
New
Front Facing 90 deg (E)
1
3
Slab On Grade
13.9 % of floor area
0.94 Btu/hr-sf-F
BUILDING SHELL INSULATION
-------------------------
Component Frame Cavity Sheathing Insul Assembly
Type Type R -value R -value R -value U -value
----------------------------------- ------- -------
Wall n/a R-13 R-n/a R-13 0.068
Wall n/a R-0 R-n/a R-0 0.190
Roof
n/a
R-30
R-n/a
R-30
0.031
Roof
n/a
R-19
R-n/a
R-19
0.051
F1oorExt
n/a
R-19
R-n/a
R-19
0.048
Door
n/a
R-0
R-n/a
R-0
0.330
SlabEdge
n/a
R-0
R-n/a
R -O
0.900
SlabEdge
n/a
R-0
R-n/a
R -O
0.720
SlabEdge
n/a
R-0
R-n/a
R-0
0.550
SlabEdge
n/a
R -O
R-n/a
R-0
0.500
Location/Comments
------------------------
Front 2x4 Wall
Left 2x4 Wall
Gar. 2x4 Wall
Back 2x4 Wall
Right 2x4 Wall
Front B1k.Wall
Left B1k.Wall
Back B1k.Wall
Right Blk. Wall
Vented Attic
Vaulted Roof
Over Garage
Over Outside
Garage Door
Back Door
Exp to Outside
Cvd to Outside
Exp. to Garage
Cvd. to Garage
CERTIFICATE OF COMPLIANCE: RESIDENTIAL Page 2 CF -IR
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 08/04/98
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
I MICROPAS4 v4.50 File -CHAD Wth-CT206S92 Program -FORM CF -IR
1 User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO
-------------------------------------------------------------------------------
FENESTRATION
# of
Interior
Over -
Area
U-
Pan-
Shading/
Exterior
hang/
Framing
Orientation
(sf)
Value
es
Description
Shading
Fins
Type
-------------------
Window
Front
(E)
-----
60.0
-----
0.920
----
1
---------------
CEC
Std.
-----------
None
----
None
---------
WoodDiv
Door
-Front
(E)
128.0
0.990
1
CEC
Std.
None
None
Wood
Door
Front
(E)
72.0
0.990
1
CEC
Std.
None
None
Wood
Window
Front
(E)
33.3
1.040
1
CEG
Std.
None
None
WoodDiv
Window -Front
(E)
8.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Front
(E)
24.0
0.920
1
GEC
Std.
None
None
WoodDiv
Window
Left
(S)
16.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
66.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
31.5
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
36.0
0.600
2
CEC;
Std.
None
None
WoodDiv
Window
Left
(S)
18.0
0.570
2
CEC
Std.
None
None
WoodDiv
Door
Left
(S)
20.0
0.990
1
CEC;
Std.
None
None
Wood
Window
Left
(S)
14.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
18.0
0.920
1
CEG
Std.
None
None
WoodDiv
Window
Left
(S)
16.5
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
3.0
0.920
1
GEC
Std.
None
None
WoodDiv
Window
Back
(W)
24.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
8.0
1.040
1
CEC
Std.
None
None
WoodDiv
Door
Back
(W)
162.0
0.990
1
CEC
Std,
None
None
Wood
Window
Back.
(W)
57.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
45.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
30.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
33.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
22.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
35.0
0.920
1
CEC
Std,
None
None
WoodDiv
Window
Back
(W)
66.0
0.920
1
CEC
Std.
None
None
WoodDiv
Door
Back
(W)
37.5
0.990
1
CEC
Std,
Nene
None
Wood
Window
Back
(W)
15.0
1.040
1
CEC
Std.
None
None
WoodDiv
Door
Back
(W)
22.5
0.990
1
CEC
Std.
None
None
Wood
Window
Back
(W)
22.0
0.920
1
CEC
Std,
None
None
WoodDiv
Window
Right
(N)
40.5
0.920
1
CEC
Std,
None
None
WoodDiv
Door
Right
(N)
63.0
0.990
1
CEC
Std.
None
None
Wood
Door
Right
(N)
41.0
0.990
1
GEC
Std.
None
None
Wood
Window
Right
(N)
75.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Right
(N)
95.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Right
(N)
16.5
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Right
(N)
76.8
0.920
1
CEC
Std.
None
None
WoodDiv
Skylight
Front
(E)
8.4
0.470
2
CEC
Std.
Tinted Glas
None
Metal
Skylight
Left
(S)
25.8
0.470
2
CEC
Std.
Tinted Glas
None
Metal
Skylight
Back
(W)
4.2
0.470
2
CEC
Std.
Tinted Glas
None
Metal
Skylight
Right
(N)
17.4
0.470
2
CEC
Std.
Tinted Glas
None
Metal
CERTIFICATE OF COMPLIANCE: RESIDENTIAL
-------------------------------------------------------------------------------
Page 3 CF -1R
Project Title.......... MR. S MRS.
-------------------------------------------------------------------------------
RICHARD
CHAO
Date........ 08/04/90,
-------------------------------------------------------------------------------
I MICRDPAS4
v4.50 File-CHAO Wth-CT2:06592
Program -FORM CF -1R I
1 User#-MP1751 User -Aero
-------------------------------------------------------------------------------
Energy
Run -MR.
8 MRS. RICHARD CHAO I
THERMAL
------------
MASS
Area Thickness
Type
------------
Exposed
-------------- ------
(sf)
---------
(in)
Location/Comments
SlabOnGrade
Yes
1970
3.5
------------------------
Exposed Concrete Slab
S1abOnGrade
No
1226
3.5
Covered Concrete Slab
InteriorHorz
Yes
40
4.0
Brick/Masonry (Horz.)
InteriorVert
Yes
35
4.0
Brick/Masonry (Vert.)
InteriorVert
Yes
3417
8.0
Exposed 8 in. Block
InteriorHorz
Yes
322
1.0
Ceramic Tile (Horz.)
InteriorVert
Yea
290
1.0
Ceramic Tile (Vert.)
InteriorHorz
Yes
2564
0.8
Exposed Lt.Wt. Conc.Slab
InteriorHorz
No
5780
0.8
Covered Lt.Wt. Conc.Slab
HVAC SYSTEMS
Minimum Duct Duct Thermostat
Equipment Type Efficiency Location R -value Type
--------------- ------------ ------------- ------- ------------
Gas 0.800 AFUE Attic R-4.2 Setback
AirCond 10.00 SEER Attic R-4.2 Setback
WATER HEATING SYSTEMS
---------------------
Number Tank
in Energy Size
Tani: Type Heater Type Distribution Type System Factor (gal)
------------ ----------- ------------------- -------------- ------
Storage Gas Recirc/TimeTemp 2 .44 EF 100
SPECIAL FEATURES/REMARKS
------------------------
1) The water heaters specified will require an external
insulation blanket of R-12 or greater.
2) The water heaters for this house will require a recirculation
pump with a time clock - temp controller.
3) The water heaters shall be: (2) American *G52-10OT88-4NV
External
Insulation
R -value
R-1'2
CERTIFICATE OF COMPLIANCE: RESIDENTIAL Page 4 CF -SR
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 06/04/98
-------------------------------------------------------------------------------
MICROPAS4 v4.50 File -CHAD Wth-CTZ0GS92 Program -FORM CF-iR
1 User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
COMPLIANCE STATEMENT
--------------------
This certificate of compliance lists the building features and performance
specifications needed to comply with Title -24, Parts 1 and 6 of the
California Code of Regulations, and the administrative regulations to
implement them. This certificate has been signed by the individual with
overall design responsibility. When this certificate of compliance is
submitted for a single building plan to be built in multiple orientations,
any shading feature that is varied is indicated in the Special Features/
Remarks section.
DESIGNER or OWNER
Name.... DENNIS CHERRY
Company. DENNIS CHERRY & ASSOC.
Address. 20351 IRVINE AVE., #1
SANTA ANA HTS., CA. 92707
Phone... 714-641-1505
License.
Signed..
ENFORCEMENT AGENCY
Name....
Title...
Agency..
Phone...
(date)
Signed.
(date)
f �Ir[$l1MM�ii 617I1i i�� /\1111}. [�.�
Name.... Terry Statum
Company. Aero Energy
Address. 12711 Newport Ave, Suite G
Tustin, CA 92760
Phone... 714-505-4207 /�
Signed. 9-A- I/�
f
(date)
MANDATORY MEASURES CHECKLIST: RESIDENTIAL MF -1R
Note: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance
approach used. Items marked with an asterisk (') may be superseded by more stringent compliance requirements
listed on the Certificate of Compliance. When this checklist is incorporated into the permit documents, the features
noted shall be considered by all parties as binding minimum component performance specifications for the
mandatory measures whether they are shown elsewhere in the documents or on this checklist only.
Instructions: Check or initial applicable boxes when completed or enter N/A if not applicable.
DESUIPTION
I DESIGNER I ENF5RCEMENT
Building
Envelope Measures:
• 1150(8): Minimum R-19 ceiling insulation. -
✓
II50(b): Loose fill insulation manufacturer's labeled R -Value.
• {150(c): Minimum R-13 wall insulation in wood famed walls or equivalent U -value in ;a inuric walls
(does not apply to exterior mass walls).
• 5150(d): Minimum R-13 raised floor insulation in famed Boors; minimum R4 in raised cenaete floors.
I150(q : Slab edge insulation - water absorption nue no greater than 0.3% water vapor transmission rate
0o greater than 2.0 pemJnch.
4118: Insulation specified or installed mats insulation quality standads. Indicate type and torn.
1116.17: Fenestration Products, Exterior Doors, and Intiltration/Exfiltntion Controls
1. Doors and windows between conditioned and unconditioned spaces designed to limn air leakage.
2. Manufactured fenestration products have label with certified U -value, and infiltration certification.
✓
3. Exterior doors and windows weathersnipped; all joints and penetrations caulked and sealed.
1150(8): Vapor barriers mandatory in Climate Zones 14 and 16 only.
l
4]50(1): Special infiltration barrier installed to comply with § 151 mats Commission quality standards.
A
I I We): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.
1. Masonry and factory -built fireplaces have:
L Closeable metal or glass door
b. Outside air intake with dapper and control
e. Fim damper and Control
2. No continuous burning gas pilot lights allowed.
SiDace Conditioning, Water Heating and Plumbing System Measures:
1110-13: HVAC equipmcnt, water heaters, showerheads and faucets certified by the Commission.
v/
I I50(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA or RCCA.
1150(1): Setback thermostat on all applicable heating and/or cooling systems.
V
1150(1): Pipe and tank insulation
1. First 5 fat of pipes closest to water beater tank, non -simulating systems, insulated (R4 w greater)
2. Back-up rooks for sola system, unfired storage tanks, or other indirect hot water tanks have R-12
external insulation or R-16 combined IntemaVextemal 'insulation.
3. All buried or exposed piping insulated in recirculating sections of hot water systems.
4. Cooling system piping below 55• F insulated.
5. Piping insulated between heating source and indirect hot water tack.
• 1150(m): Ducts and Fans
1. Duets constructed, installed and sealed to comply with (IMC sections 601 and 603; duan insulated to a
minimum installed R4.2 or duets enclosed entirely within conditioned space.
2. Exhaust fan systems have back draft or automatic dampers.
3. Gravity ventilating systems serving conditioned space have either automatic or readily accessible,
manually operated dampers.
In Pool and Spa Heating Systems and Equipment.
t. System is certified with 780% thermal efficiency, on-off switch, weatherproof operating
IaWunxims, no electric resistance heating and no pilot light.
2. System is installed with:
✓
L At lent 36" of pipe between filter and beater for fume solar heating.
Is. Cover for outdoor pools or outdoor spas.
3. Pool system has directional inlets and a circulation pump time switch.
1115: Gas fired central furnaces, pool beaters, spa heaters or bouubold cooking appliances have on
✓
continuously burning pilot light. (Exception: Non-olectrial cooking appliances with Pilot < 150 BmPor)
Lighdag Measures:
I I30(k): 40 lumens/wan or greater for genes] lighting in kitcAem and rooms with water Cheats; and
✓
inowd calling fixtures are IC (inflation cover)
Revised Match 1,19%
COMPUTER METHOD SUMMARY Page 1 C -2R
Project Title.......... MR. & MRS. RICHARD CHAO Date........ 08/04/98
Project Address........ 15 SAILCREST ******* ---------------------
NEWPORT COAST, CA. *v4.50* I I
Documentation Author... Terry Statum ******* 1 Building Permit # I
Aero Energy 1 1
12711 Newport Ave, Suite G I Plan Check / Date I
Tustin, CA 92780 1 1
714-505-4207 1 Field Check/ Date I
Climate Zone........... 06 ---------------------
Compliance Method...... MICROPAS4 v4.50 for 1995 Standards by Enercomp, Inc.
I MICROPAS4 v4.50 File-CHAO Wth-CTZ06S92 Program -FORM C -2R
1 User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
----------------------------
----------------------------
MICROPAS4 ENERGY USE SUMMARY
= Energy Use
Standard
Proposed
Compliance =
_ (kBtu/sf-yr)
-----------
Design
Design
----------
Margin =
---------- -
-----------------------
= Space Heating..........
4.32
4.92
-0.60 =
- Space Cooling..........
2.83
0.37
2.46 =
= Water Heating..........
2.26
3.49
-1.23 =
= Total
9.41
8.78
0.63 =
_ *** Building complies
-----------------------------------------------------------------
-----------------------------------------------------------------
with Computer
Performance
GENERAL INFORMATION
Conditioned Floor Area.....
Building Type ..............
Construction Type .........
Building Front Orientation.
Number of Dwelling Units...
Number of Building Stories.
Weather Data Type..........
Floor Construction Type....
Number of Building Zones...
Conditioned Volume.........
Footprint Area .............
Ground Floor Area..........
Slab -On -Grade Area.........
Glazing Percentage.........
Average Glazing U -value....
Average Ceiling Height.....
11540 sf
Single Family Detached
New
Front Facing 90 deg (E)
1
3
ReducedYear
Slab On Grade
1
126940 cf
5268 sf
3196 sf
3196 sf
13.9 % of floor area
0.94 Btu/hr-sf-F
11 £t
COMPUTER METHOD SUMMARY Page 2 C -2R
-------------------------------- - ---
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 08/04/96
1 MICROPAS4 v4.50 File -CHAD Wth-CT206692 Program -FORM C -2R I
1 User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
BUILDING ZONE INFORMATION
Floor
# of
Area
Vent
Special
Area
Volume Dwell
Cond- Thermostat
Height
Vent Area
Zone Type (ef)
---------
(cf) Units
--------- -----
itioned Type
-------------------
(ft)
------
(sf)
---------
--------------
HOUSE
Comments
----------------
--------------
HOUSE
U-
Act
Residence 11540
126940 1.00
Yes Setback
8.0
n/a
OPAQUE SURFACES
PERIMETER LOSSES
Length
Area
U-
Insul
Act
Soler
Form 3
Location/
Surface
(sf)
------
value
-----
R-val
-----
Azm
---
Tilt Gains
---- -----
Reference
------------
Comments
----------------
--------------
HOUSE
U-
Act
Glass
Int
17 SlabEdge
196
0.900
1
Wall
1835
0.086
13
90
90
Yes
None
Front 2x4 Wall
2
Wall
1100
0.190
0
90
90
Yes
None
Front B1k.Wall
3
Wall
1714
0.086
13
180
90
Yes
None
Left 2x4 Wall
4
Wall
882
0.190
0
180
90
Yes
None
Left B1k.Wall
5
Wall
498
0.088
13
180
90
No
None
Gar. 2x4 Wall
6
Wall
1481
0.088
13
270
90
Yes
None
Back 2x4 Wall
7
Wall
827
0.190
0
270
90
Yes
None
Back B1k.Wall
8
Wall
27
0.088
13
270
90
No
None
Gar. 2x4 Wall
9
Wall
1785
0.088
13
0
90
Yes
None
Right 2x4 Wall
10
Wall
1044
0.190
0
0
90
Yes
None
Right B1k.Wall
11
Roof
5375
0.031
30
n/a
0
Yes
None
Vented Attic
12
Roof
150
0.051
19
0
27
Yes
None
Vaulted Roof
13
FloorExt
1910
0.046
19
n/a
0
No
None
Over Garage
14
Floor'Ext
162
0.048
19
n/a
0
No
None
Over Outside
15
Door
24
0.330
0
90
90
No
None
Garage Door'
16
Door
24
0.330
0
270
90
Yes
None
Back Door'
PERIMETER LOSSES
FENESTRATION SURFACES
Length
F2
Insul
Solar
Vent
Surface
(ft)
Factor
R-val
Gains
Location/Comments
Area
HOUSE
Frame
Open
U-
Act
Glass
Int
17 SlabEdge
196
0.900
R-0
No
Exp
to
Outside
16 SlabEdge
69
0.720
R -O
No
Cvd
to
Outside
19 SlabEdge
17
0.550
R-0
No
Exp.
to
Garage
20 SlabEdge
45
0.500
R-0
No
Cvd.
to
Garage
FENESTRATION SURFACES
# of
Vent
SC
SC
Interior
Area
Pan-
Frame
Open
U-
Act
Glass
Int
Shading/
Surface
(sf)
as
Type
Type
value
Azm
---
Tlt
---
Only
----
Shade
----
Description,
---------------
-----------
HOUSE
-----
----
---------
------
-----
1
Window
60.0
1
WoodDiv
Slider
0.920
90
90
1.00
0.78
CEC Std.
2
Door
128.0
1
Wood
Slider
0.990
90
90
1.00
0.78
CEC Std.
3
Door
72.0
1
Wood
Slider
0.990
90
90
1.00
0.78
CEC Std.
4
Window
33.3
1
WoodDiv
Slider
1.040
90
90
1.00
0.78
CEC Std.
COMPUTER METHOD SUMMARY Page 3 C -2R
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 08/04/98
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
1 MICROPA134 v4.50 File -CHAD Wth-CT206S92 Program -FORM C -'R I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
Surface
5 Window
6 Window
7 Window
8 Window
9 Window
10 Window
11 Window
12 Door
13 Window
14 Window
15 Window
16 Window
17 Window
18 Window
19 Door
20 Window
21 Window
22 Window
23 Window
24 Window
25 Window
26 Window
27 Door
28 Window
29 Door
30 Window
31 Window
32 Door
33 Door
34 Window
35 Window
36 Window
37 Window
38 Skylight
39 Skylight
40 Skylight
41 Skylight
EXTERIOR SHADING
Area
FENESTRATION SURFACES
SC of
Surface
(of)
Type
Ext Shade
HOUSE
# of
---------------------
Vent
38 Skylight
8.4
Tinted Glass
SC
SC
Interior
Area
Pan-
Frame
Open
U-
Act
41 Skylight
Glass
Int
Shading/
(ef)
es
Type
Type
value
Azm
Tlt
Only
Shade Description
-----
8.0
----
1
---------
WoodDiv
------
Slider
-----
1.040
---
90
---
90
----
1.00
----
0.78
---------------
CEC
Std.
24.0
1
WoodDiv
Slider
0.920
90
90
1.00
0.78
CEC
Std.
16.0
1
WoodDiv
Slider
1.040
180
90
1.00
0.78
CEC
Std.
66.0
1
WoodDiv
Slider
0.920
180
90
1.00
0.78
CEC
Std.
31.5
1
WoodDiv
Slider
1.040
180
90
1.00
0.78
CEC
Std.
36.0
2
WoodDiv
Slider
0.600
180
90
0.88
0.76
CEC
Std.
18.0
2
WoodDiv
Slider
0.570
180
90
0.88
0.78
CEC
Std.
20.0
1
Wood
Slider
0.990
180
90
1.00
0.78
CEC
Std.
14.0
1
WoodDiv
Slider
1.040
180
90
1.00
0.78
CEC
Std.
18.0
1
WoodDiv
Slider
0.920
180
90
1.00
0.78
CEC
Std.
16.5
1
WoodDiv
Slider
0.920
180
90
1.00
0.78
CEC
Std.
3.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
24.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
8.0
1
WoodDiv
Slider
1.040
270
90
1.00
0.78
CEC
Std.
162.0
1
Wood
Slider
0.990
270
90
1.00
0.78
CEC
Std.
57.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
45.0
1
WoodDiv
Slider
1.040
270
90.1.00
0.78
CEC
Std.
30.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
33.0
1
WoodDiv
Slider
1.040
270
90
1.00
0.78
CEC
Std.
22.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
35.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
66.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
37.5
1
Wood
Slider
0.990
270
90
1.00
0.78
CEC
Std.
15.0
1
WoodDiv
Slider
1.040
270
90
1.00
0.78
CEL"
Std.
22.5
1
Wood
Slider
0.990
270
90
1.00
0.78
CEC
Std.
22.0
1
WoodDiv
Slider
0.920
270
90
1.00
0.78
CEC
Std.
40.5
1
WoodDiv
Slider
0.920
O
90
1.00
0.78
CEC
Std.
63.0
1
Wood
Slider
0.990
O
90
1.00
0.78
CEC
Std.
41.0
1
Wood
Slider
0.990
0
90
1.00
0.78
CEC
Std.
75.0
1
WoodDiv
Slider
1.040
0
90
1.00
0.76
CEC
Std.
95.0
1
WoodDiv
Slider
0.920
0
90
1.00
0.78
CEC
Std.
16.5
1
WoodDiv
Slider
1.040
0
90
1.00
0.78
CEC
Std.
76.8
1
WoodDiv
Slider
0.920
0
90
1.00
0.78
CEC
Std.
8.4
2
Metal
Slider
0.470
90
27
0.82
1.00
CEC
Std.
25.8
2
Metal
Slider
0.470
180
27
0.82
1.00
CEC
Std.
4.2
2
Metal
Slider
0.470
270
27
0.82
1.00
CEC
Std.
17.4
2
Metal
Slider
0.470
0
27
0.82
1.00
CEC
Std.
EXTERIOR SHADING
Area
Shading
SC of
Surface
(of)
Type
Ext Shade
HOUSE
38 Skylight
8.4
Tinted Glass
1.00
39 Skylight
25.8
Tinted Glass
1.00
40 Skylight
4.2
Tinted Glass
1.00
41 Skylight
17.4
Tinted Glass
1.00
COMPUTER METHOD SUMMARY Page 4 C -2R
--------------------------------
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 08/04/98
1 MICROPAS4 v4.50 File -CHAD Wth-CT20GS92 Program -FORM C -2R I
1 User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
YIP.I�T:iwlf>lyL�
HVAC SYSTEMS
Minimum
Area
Thick
Heat
Conduct-
Surface
Location
-------------
R -value
-------
Mass Type
---------------
(sf)
------
(in)
-----
Cap
-----
ivity
--------
R -value
--------
Location/Comments
--------------------------
HOUSE
Attic
R-4.2
0.880
AirCond
10.00 SEER
Attic
R-4.2
1
S1abOnGrade
1970
3.5
28.0
0.98
R-0.0
Exposed
Concrete Slab
2
SlabOnGrade
1226
3.5
28.0
0.98
R-2.0
Covered
Concrete Slab
3
InteriorHorz
40
4.0
21.0
0.59
R-0.0
Brick/Masonry (Hort.)
4
InteriorVert
35
4.0
21.0
0.59
R-0.0
Brick/Masonry (Vert.)
5
Inter-iorVert
3417
6.0
28.0
0.98
R-0.0
Exposed
8 in. Block
6
InteriorHorz
322
1.0
24.0
0.67
R-0.0
Ceramic
Tile (Harz.)
7
InteriorVert
290
1.0
24.0
0.67
R-0.0
Ceramic
Tile (Vert.)
8
InteriorHorz
2564
0.8
24.0
0.61
R-0.0
Exposed
Lt.Wt. Conc.Slab
9
InteriorHarz
5780
0.8
24.0
0.61
R-2.0
Covered
Lt.Wt. Conc.Slab
HVAC SYSTEMS
WATER HEATING SYSTEMS
---------------------
Number
in
Tank Type Heater Type Distribution Type System
1 Storage Gas Recirc/TimeTemp 2
SPECIAL FEATURES/REMARKS
------------------------
Tank External
Energy Size Insulation
Factor (gal) R -value
.44 100 R-12
1) The water heaters Specified will require an external
insulation blanket of R-12 or greater.
2) The water heaters for this house will require a recirculation
pump with a time clock - temp controller.
3) The water heaters shall be: (2) American #G52-100T88-4NV
Minimum
Duct
Duct
Duct
System Type
----------------
Efficiency
------------
Location
-------------
R -value
-------
Efficiency
----------
HOUSE
Gas
0.800 AFUE
Attic
R-4.2
0.880
AirCond
10.00 SEER
Attic
R-4.2
0.870
WATER HEATING SYSTEMS
---------------------
Number
in
Tank Type Heater Type Distribution Type System
1 Storage Gas Recirc/TimeTemp 2
SPECIAL FEATURES/REMARKS
------------------------
Tank External
Energy Size Insulation
Factor (gal) R -value
.44 100 R-12
1) The water heaters Specified will require an external
insulation blanket of R-12 or greater.
2) The water heaters for this house will require a recirculation
pump with a time clock - temp controller.
3) The water heaters shall be: (2) American #G52-100T88-4NV
HVAC SIZING Page 1 HVAC
Project Title.......... HOUSE LOADS Date........ 08/04/98
Project Address........ 15 S'AILCREST ******* ---------------------
NEWPORT COAST, CA. *v4.50* I I
Documentation Author... Terry Statum ******* I Building Permit # I
Aero Energy 1 1
12711 Newport Ave, Suite G I Plan Check / Date I
Tustin, CA 92780 1 1
714-505-4207 1 Field Check/ Date I
Climate Zone........... 06 ---------------------
Compliance Method...... MICROPAS4 v4.50 for 1995 Standards by Enercomp, Inc.
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
i MICROPAS4 v4.50 File-CHAOHSE Wth-CTZ06S92 Program -HVAC SIZING I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAD I
-------------------------------------------------------------------------------
GENERAL INFORMATION
Floor Area .................
Volume .....................
Front Orientation..........
Sizing Location............
Latitude ...................
Winter Outside Design......
Winter Inside Design.......
Summer Outside Design......
Summer Inside Design.......
Summer Range ...............
Interior Shading Used......
Exterior Shading Used......
Overhang Shading Used......
Latent Load Fraction.......
9532 of
104852 cf
Front Facing 90 deg (E)
NEWPORT BEACH
33.6 degrees
39 F
70 F
80 F
78 F
12 F
No
No
No
0.30
HEATING AND COOLING LOAD SUMMARY
Heating Cooling
Description (Btuh) (Btuh)
-------------------------------------------- -----------
Opaque Conduction and Solar...... 134194 70014
Glazing Conduction ............... 46778 3018
Glazing Solar. ................... n/a 62146
Infil.tration..................... 55758 1325
Internal Gain .................... n/a 3900
Ducts ............................ 23673 14040
Sensible Load ....................
Latent Load ......................
Minimum Total Load
26040'3
n/a
154442
46333
260403 200775
Note: The loads shown are only one of the criteria affecting the selection
of HVAC equipment. Other relevant design factors such as air flow
requirements, outdoor design temperatures, coil sizing, availability of
equipment, oversizing safety margin, etc., must also be considered. It is
the HVAC designer's responsibility to consider all factors when selecting
the HVAC equipment.
HVAC SIZING Page 1 HVAC
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
Project Title.......... SPORTS COURT Date........ 08/04/98
Project Address........ 15 SAILCREST «xxxxxx ---------------------
NEWPORT COAST, CA. xv4.50x I I
Documentation Author... Terry Statum xxxxxxx I Building Permit # I
Aero Energy 1 1
12711 Newport Ave, Suite G 1 Plan Check / Date I
Tustin, CA 92780 1 1
714-505-4207 1 Field Check/ Date I
Climate Zone........... 06
---------------------
Compliance Method...... MICROPAS4 v4.50 for 1995 Standards by Enercomp, Inc.
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
I MICROPAS4 v4.50 File-CHADSPRT Wth-CTZ06S92 Program -HVAC SIZING I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAD i
-------------------------------------------------------------------------------
GENERAL INFORMATION
Floor Area .................
Volume .....................
Front Orientation..........
Sizing Location............
Latitude ...................
Winter Outside Design......
Winter Inside Design.......
Summer Outside Design......
Summer Inside Design.......
Summer Range ...............
Interior Shading Used......
Exterior Shading Used......
Overhang Shading Used......
Latent Load Fraction.......
2008 of
40150 cf
Front Facing 90 deg (E)
NEWPORT BEACH
33.6 degrees
39 F
70 F
80 F
78 F
12 F
No
No
No
0.30
HEATING AND COOLING LOAD SUMMARY
--------------------------------
Heating Cooling
Description (Btuh) (Btuh)
-------------------------------------------------------
Opaque Conduction and Solar......
20833
6451
Glazing Conduction... ............
0
0
Glazing Solar ....................
n/a
0
Infiltration .....................
21351
507
Internal Gain... .................
n/a
22500
Ducts ............................
4218
2946
Sensible Load ....................
46402
32405
Latent Load ......................
-----------
n/a
9721
-----------
Minimum Total Load
46402
42126
Note: The loads shown are only one of the criteria affecting the Belectilor,
of HVAC equipment. Other relevant design factors such as air flow
requirements, outdoor design temperatures, coil suing, availability of
equipment, oversizing safety margin, etc., must also be considered. It is
the HVAC designer's responsibility to consider all factors when selecting
the HVAC equipment.
MICROPAS4
Table 2-2: Manufactured Fenestration Product Default U -Values
(this table to be used by manufacturer's to establish a U -value rating without performance testing)
For all dual -glazed fenestration products:
• Subtract 0.05 for spacers of 7/16" or wider.
• Subtract 0.05 for Lowe glazing.
• Add 0.05 for products with between the panes dividers, if the spacer is less than 7/16" wide.
• Add 0.05 to the U -value of any product with true divided lites [through the pane(s) dividers].
1. The minimum design characteristics to qualify as Thermal -Break Product are:
a. The material used as the thermal -break must have a thermal conductivity of not mote than
3.6 BTU-in/hr fti/'F, and,
b. Thermal -break must produce a gap of not less than 0210", and;
c. All metal members of the product exposed to interior and exterior air must incorporate a thermal -break
meeting the criteria in (1) and (2) above.
In addition, the product must be clearly labeled by the manufacturer that it qualifies as a thermally broken
product in accordance with CEC requirements.
2. Non meta] products can include metal fasteners, hardware and door thresholds.
3. Add 0.04 to the listed U -value for any products that have metal cladding in any configuration.
Table 2.3: Site Built Fenestration Product Default U -Values
(this table to be used to establish a U -value rating without performance testing)
Framing Materials
Any Metal, Including Non Metall
Cladding (Wood, V-myl or other)
Single Double Single Double
Fixed 1.19 0.72 1.04 0S7
Operable 132 0.93 0.99 - 0S5
1. Non-metal excludes hardware or door thresholds.
2 m 3 2 COMPLIANCE 711592 0 1992 by Eneiwmp, Inc.
Framing Materials
Any Metal
Thermal Break]
Non Metal
(Wood, Vmyl or other)
single
Doable
Dmble
Single Dmbk
Operable Windows
128
0.87
0.71
0.92 0.60
" Fixed Windows
1.19
0.72
0.60
1.04 0.57
Patio Doors
1.25
0.77
0.68
0.99 0.55
Skylights
1.26
0.80
0.70
0.91 0S5
Greenhouse Windows
2.26
1.40
1.12
1.94 1.06
For all dual -glazed fenestration products:
• Subtract 0.05 for spacers of 7/16" or wider.
• Subtract 0.05 for Lowe glazing.
• Add 0.05 for products with between the panes dividers, if the spacer is less than 7/16" wide.
• Add 0.05 to the U -value of any product with true divided lites [through the pane(s) dividers].
1. The minimum design characteristics to qualify as Thermal -Break Product are:
a. The material used as the thermal -break must have a thermal conductivity of not mote than
3.6 BTU-in/hr fti/'F, and,
b. Thermal -break must produce a gap of not less than 0210", and;
c. All metal members of the product exposed to interior and exterior air must incorporate a thermal -break
meeting the criteria in (1) and (2) above.
In addition, the product must be clearly labeled by the manufacturer that it qualifies as a thermally broken
product in accordance with CEC requirements.
2. Non meta] products can include metal fasteners, hardware and door thresholds.
3. Add 0.04 to the listed U -value for any products that have metal cladding in any configuration.
Table 2.3: Site Built Fenestration Product Default U -Values
(this table to be used to establish a U -value rating without performance testing)
Framing Materials
Any Metal, Including Non Metall
Cladding (Wood, V-myl or other)
Single Double Single Double
Fixed 1.19 0.72 1.04 0S7
Operable 132 0.93 0.99 - 0S5
1. Non-metal excludes hardware or door thresholds.
2 m 3 2 COMPLIANCE 711592 0 1992 by Eneiwmp, Inc.
MICROPAS4
Standard Shading Coe$tciews for Glaring Alone
Single.......... _.... .._.._.._...... ................... ...........
Double............... ...._.._....................................... ....
the Table G-11 a in
Figure 1-17: Suggested Names forInterior Shading devices
Description
Interior Shade
Drapes.Std
Non-white drapes (CEC Standard for windows
and French doors).
Dtapes.Wht
Drapery with a white or off-white liner
None
No interior drapes (CEC Standard for skylights)
Blinds.Med
Medium Colored venetian blinds
Blinds.Lt
Lightcolor d venetian blinds
Roller -Dark
Opaque, dark colored roller blinds
Roller.Wht
Opaque, white interior roller shades
Roller.Lt
Translucent, white roller shades
Special
Interior shade not represented by the types above.
Table 2-7: Shading Coefficients for Interior Shading Devices Alone(Shades Close )
Drapery:
Standard............ __................................................. 0.781
White/Off-White .._................................................ 0.62
Venetian Blinds:
Medium Color.._....................................................0.63
LightColor ....... _....... _.._...................................... 0.58
Roller Shades:
Opaque
Dark....................... _......................................... 0.81
White................................................................ 0.402
Translucent
Light............ . .......................................... ....... 0.44
1. 0.78 is the default value used when there is no interior shading device installed on
vertical fenestration products.
2. No interior shading device may be given a shading coefficient value lower
than 0.40
Note that the values above are from the row labeled 'Interior Shade' in Table G -Ila in
2-42 COMPLIANCE 7/1692 c1992byEnercomp, Inc.
Table G-18: Standard U -Values of Wood Frame
Raised Floor -sl
Floor
Imul.
Condition
Reference
Name2 U -Value
R-03
No C.S.4
FXO.2X6.16 0,239
R-03
With C.S.4
FC0.2X6.16 0.097
R-113
No C.S.
FXI1.2X6.16 0.071
R-113
With C.S.
FCI1.2X6.16 0.049
R-13
No C.S.
FX13.2X6.16 0.064
R-13
With C.S.
FC13.2X6.16 0.046
R-19
No C.S.
FX 19.2X8.16048
i R-19
With C.S.
FC19.2X8.16.037
R-21
No C.S.
FX21.2X8.16 5
R-21
With C.S.
FC21.2X8.16 0.035
R-30
No C.S.
FX30.2.(10.16034
I R•30
With C.S.
FC30.2XI0.16 21
1. Based on ASHRAE Parallel Heat Flow
Calculation, 1989 <ASHRAE Handbook of
Fundamentals.
2. The names given to the standard assemblies used
to calculate these U -values in Appendix H.
J. Dors not meet the minimum level required as a
mandatory measure (see Section 2.2).
4. No C.S. = No Crawl Space, With C.S. _
With Crawl Space
Table G-19: Standard U -Values of Wood Foam
Panel Roofs/Ceilings and Wallsl
Roof/
Ceiling Framing Reference
Instill. Spacing Name2 U -Value
R-143 48' o.c. RP.14.2X4.48 0.064
R-22 48' o.c. RP.22.2X6.48 0.044
R-28 48' o.c. RP.28.2X8.48 0.035
R-36 48' o.c. RP.36.2X10.48 0.028
Walt Framing Reference
Instil. Spacing Name U -Value
R-14 48' o.c. WP. 14.2X4.48 0.071
R-22 48- o.c. WP.22.2X6.48 0.049
1. Based on ASHRAE Parallel Heat Flow
Calculation, 1989 ASHRAE Handbook of
Fundamentals.
2. The names given to the standard assemblies used
to calculate these U -values in Appendix H.
3. Does not meet the minimum level required as a
mandatory measure (see Section 2.2).
Glossary January 1, 1995 G-55
Table G-16: Standard U -Values of Wood Frame
Framing
Spacing
Roofs and CesMWI
U -Value
Ceiling
Framing
Reference
I nsul.
Spacing
Name2
U -Value
R-03
16' o.c.
R.0.2X6.16
.299
R-03
24' o.c.
R.0.2X4.244
0.306
R-113
16' o.c.
R.11.2X6.16
0.077
R-113
24' o.c.
R.I1.2X4.24
0.076
R-133
16' o.c.
R. 13.2X6.16
0.069
R-133
24' o.c.
R. 13.2X4.24
0.068
R-19
16' o.c.
R. 19.2X8.16A51
R-19
24' o.c.
R.19.ZX4.24
R-22
16' o.c.
R.22.2X10.16
R-22
24' o.c.
R.22.2X4.24
0.041
R-30
16' o.c.
A.30.2XI0.16
6
n R-30
16' o.c.
R.30.2X12.16
.035
R-30
24' o.c.
R.30.2X4.24
1
R-38
16' o.c.
R.38.2X12.16
.029
R-38
16' o.c.
R.38.2X14.16
0.028
R-38
24' o.c.
R.38.2X4.24
(PO,
R-49
16' o.c.
R.49.2X4.16
R-39
24' o.c.
R.24.2X4.24
0.019
1. Based on ASHRAE Parallel Heat Flow
Calculation, 1989 A3HRAEHanalbook of
Fundamentals.
2. The names given to the standard assemblies used
to calculate these U -values in Appendix H.
3. Does not meet the minimum level required as a
mandatory measure (see Section 2.2).
4. Roof/ceiling assemblies whose reference names
list 2X4 framing include an attic space.
Table G-17: Standard U -Values of Wood Frame
Wafls1
Wall
Ltsul.
Framing
Spacing
Reference -
Name2
U -Value
R-03
16' o.c.
W.0.2X4.16
MD
R-03
24' o.c.
W.0.2X4.24
0.393
R-73
16' o.c.
W.7.2X4.16
0.130
R-73
24' o.c.
W.7.2X4.24
0.127
R-113
16' o.c.
W. 11.2X4.16
0.098
R-113
24' o.c.
W.11.2X4.24
0.094
R-13
16' o.c.
W.13.2X4.11X.O77
R-13
24' o.c.
W.132X4..4
R-15
16' o.c.
W. 15.2X
R-15
24' o.c.
W.15.2X4.24
R-19
16' o.c.
W.19.2X6.160.065
R-19
4' o.c.
W. 19.2X6.24
0.063
R-21
16' o.c.
W.21.2X6.16
0.059
R-21
24' o.c.
W.21.2X6.24
�6
R-25
16' o.c.
W.25.2X6.16
0.046
R-29
16' o.c.
W.29.2X4.16
0.035
Solid cots wood D.O.SCW
0.330
door (no insulation)
2.
ER
Based on ASHRAE Parallel Heat Flow
Calculation. 1989 ASHRAE Handbook of
Fundamentals.
The names given to the standard assemblies used
to calculate these U -values in Appendix H.
Does not meet the minimum level required as a
mandatory measure (see Section 2.2).
G-54 January 1, 1995 Residential Manual
2.4 LIGHTING MEASURES
Lighting §150(k)
Installing energy-efficient lamps and futures
can reduce lighting energy costs without
sacrificing the quality or quantity of light
available. As indicated in Table 2-5, a 40 watt
standard fluorescent lamp is over four times as
efficient as a 100 watt standard incandescent
lamp.
Kitchen Lighting
The Standards require that general lighting in
kitchens have an efficacy of at least 40 lumens
per wan and be controlled by the most
accessible switch(es) in the kitchen. The light
switch location determines how the occupant
will use the lighting. If more than one set of
light fixtures exist which provide general
lighting, those controlled by the most accesible
switch are considered general lighting.
Luminaries used only for specific decorative
effects (and which are not the only luminaries in
the kitchen) need not meet this requirement.
General lighting is lighting designed to provide
a substantially uniform level of light distribution
throughout a space. This can be achieved by
light fixtures in the ceiling or around the
perimeter of the room. Lighting fixtures under
cabinets may meet the general lighting
requirements if they provide uniform light
distribution in the kitchen (see Figure 2-11). A
luminaire which is the only lighting in a kitchen
will be considered general lighting.
Bathroom Lighting
The Standards require that each room
containing a water closet must have at least one
luminaire with lamps with an efficacy of at least
40 lumens per wart. As an alternative, this
requirement may be met by installing the high
efficacy luminaire in an adjacent room that has
complementary plumbing fixtures.
If there is more than one luminaire in the room,
the high -efficacy luminaire must be switched at
an entrance to the room.
General
Luminaries installed to meet the 40 lumens per
watt requirements cannot contain medium base
incandescent lamp sockets, and must be on
separate switches from incandescent lighting.
Table 2.5. Typical Efficacy of Luminaries
Rated Lamp Typical Efficacy
Light Source Type Watts Lumens/Wattl
Incandescent Standard 40-100 14- 18
Halogen 40-250 See Note 2
Fluorescent Full -Sire, 4' Long 32-40 69-913
(Lamp/Ballast U -Shaped T-8 Bipin 16-31 79-90
Systems) Compact Fluorescent 5-9 26-38
Compact Fluorescent 13 + 42-58
Metal Halide Metal Halide 32-175 50-90
High Pressure Sodium White High Pressure Solium 35 - 100 36-55
1 Includes power consumed by ballasts where applicable.
2 Halogen capsule incandescent lamps may be the most efficient light source for highlighting applications. Most
halogen lamps are designed to produce a beam of directed light. Manufacturer's data typically list the
.candlepower' intensity of that beam, rather than lumens (lumens measure total light output -in all directions).
The standard halogen capsule lamps will not exceed a maximum of 20 lumens/watt. A new technology using
infrared reflecting films on the halogen capsules has increased output up to 30 lumens/watt for some high
wattage lamps.
3 Efficacy of fluorescent lighting varies depending on lamp and ballast types.
Mandatory Measures January 1, 1995 2-17
"A" must be fluorescent
All of "C" must be fluorescent
"A"must be fluorescent
All of "A" or "C" must be fluorescent.
If "C" then "C" must be the most accessible
switch
Figure 2-11: Kitchen Lighting Examples
2-18 January 1, 1995 Residential Manual
0
A" must be fluorescent
'A' or B' must be fluorescent
0
oa
A' must be fluorescent;
D' can be incandescent
'B' or 'E' must be fluorescent
Figure 2-12: Bathroom Lighting Examples
Mandatory Measures January 1, 1995 2-19
JTL DESIGN & ENGINEERING
20351 Irvine Ave. Suite #2
Santa Ana Heights, CA 92707
Tel: (714) 545-8470
Fax: (714) 545-8446 Cover sheet of 3�
STRUCTURAL CALCULATIONS
FOR
.. t,•
PROJECT NO: 98-AO60
PROJECT ADDRESS: 15 Sailcrest Newport coast -California
"Pelican Crest"
CLIENT:
M01I ;7�T.X`�
197.11121
Ms June Chao
14 Hexham Irvine. California
July 7 , 1998
AUG 25 1998
?V EES 4
6-
Lai
`2
C 35023 m
Exp. 30-9Q �
��
IJP!
DESIGN CRITERIA
JTL DESIGN & ENGINEERING
20351 Irvine Ave. Suite #2
Santa Ana Heights, CA 92707
Tel: (714) 545-8470 Fax: (714) 545-8446
Date:I /99 S
Job No: —,eS
By PL
Sheet No:
Building Code: 1994 UBC
Wind Pressure P=(Ce)(Cq)(Qs) (I) 70 MPH Exposue "C" H= 40'-0" P= 21.5 psf
Seismic factor P= ZIC/Rw = 0.183
VERTICAL LOADS
ROOFLOADS
ROOFING -----------10 psf
/Z" PLYWD---------- ---2.5 psf
RAFTERS ----------2.0 psf
INSULATION --- ------- I.0 psf
CEILING & MISC ---3.0 psf
BEAMS & GIRDERS --2.0 psf
DEAD LOAD -----------21 psf
LIVE LOAD
MATERIALS
16 psf @ 4:12
FLOOR LOADS
FLOORING ------------------ 1.0 psf
1-1/2" LT WT CONC ---- 13.75 psf
PLYWD----------------------2.5 psf
JOISTS----------------------- 3.5 psf
CEILING &MISC---------- 1.25 psf.
BEAMS & GIRDERS ------- 2.0 psf
DEAD LOAD --------------24 psf
LIVE LOAD ----------------40 psf
CONCRETE ----------------- 3000 psi @ 28 DAYS TYPICAL U.N.O.
2500 psi @ 28 DAYS FOR FOUNDATIONS & SLABS
STEEL REINFORCING -------60000 psi FOR GRADE 60, #4 AND LARGER.
40000 psi FOR GRADE 40, #3 AND SMALLER.
LUMBER: ----------------------DOUGLAS FIR N041 (Fb=1000 psi) FOR F'b SEE SHT 2,3,4
GLUED LAM BEAMS ------ —COMB. 24-F (F'b=2400 psi)
STRUCTURAL STEELS -----ASTM A36 (Fy=36 ksi) TYPICAL A-500 FOR TUBE COLUMNS,
SOIL INFORMATION ---------1500 psf SOIL BEARING PER SOIL REPORT
1
z
3
6
5
6
8
9
10
1z
13
14
Is
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
a
w 4 33
K�
ao034
0
w035
W
IZ
36
wn
JTL DESIGN & ENGINEERING DATE fuL�l l9gB
20351 IRVINE AVE. SUITE #2 CONT. NO.
SANTA ANA HEIGHTS CA 92707 ev L CNK'D
TEL: (714)545-8470 FAX: (714)545-8446 sN ET NO. Z
2 3 4 5 6 7 8 9 10 1I 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
Timber Chart
Allowable Bending Stresses (F'b)
Nominal
Size
Cf
Size
OF No. 2
Fb=875 psi
OF No. 1
Fb=1000 psi
OF No. 1 8
Better
OF Select
Stnutural
(bxd)
Factor
Fb=1150 psi
Fb=1450 psi
2 x 3
1.5
1313
1500
1725
2175
2x 4
1.5
1313
1500
1725
2175
2x 5
1.4
1225
1400
1610
2030
2x 8
1.3
1138
1300
1495
1885
2 x 8
1.2
1075
1200
1380
1740
2 x 10
1.1
983
1100
1285
1595
2 x 12
1.0
875
1000
1150
1450
1300
1495
2 x 14
1.0
875
1075
.1000
1150
1450
4 x 12
1.1
3 x 4
1.5
1313
1595
1500
1725
2175
1000
1150
3 x 5
1.4
1225
875
1400
1810
2030
3 x 6
1.3
1138
1300
1495
1885
3 x 8
1.2
1075
1200
1380
1740
3 x 10
1.1
963
1100
1265
1595
3 x 12
1.0
875
1000
1150
1450
3 x 14
1.0
675
1000
1150
1450
3 x 18
1.0
875
1000
1150
1450
4 x 4
1.5
1313
1500
1725
2175
4 x 5
1.4
1225
1400
1810
2030
4 x 8
1.3
1138
1300
1495
1885
2 3 4 5 6 7 8 9 10 1I 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
4 x 8
1.3
1138
1300
1495
1885
4 x 10
1.2
1075
- 1200
1380
1740
4 x 12
1.1
963
1100
1285
1595
4 x 14
1.0
875
1000
1150
1450
4 x 18
1.0
875
1000
1150
1450
If
I:
le
,e
Ifi
17
18
19
20
21
22
23
24
25
26
27
25
29
30
31
y 32
a
w<33
¢h
c234
0
W w35
F�
o ¢ 36
46
JTL DESIGN & ENGINEERING DATE fug /998
20351 IRVINE AVE. SUITE #2 CONT. NO. q8 L�aCi�d
SANTA ANA HEIGHTS CA 92707 er pL CHWO
TEL: (714)545-8470 FAX: (714)545-8446 SHEET NO. 2
co ._
W G
NN
IA 10W wNorlwmn-
cW
btn to toN�nbt7r
bbNCAnb m
Wmm'^^n
In NJmr-wn-
f0
oil
rr rrr
r rrr r r
O n n� N
btO t70m coLn
OO nn.m N b
po
bl7 co co to t7
LL a
bbto bbin PVP
In
m bb b U3 PPPP
U)U3 bio PP P
bb U3P PPP
c LL
rrrrr r rr
�N-. r r r
�
r r r r r r r
U
o
N �Qgn 88S
a°i�C3 �tOWf00b n to ��au3 t��mlbn�Pan� wtr3Pn�1b
��N m V co t�fiN UN1b P ntn M co
rr r rrrrr r rr r �-e-r rr r Ln Lo.b-1 �b U) bbr�
o r r r r r
W
il
LL LL
0
N
Z n
to tnb to Pr GOON
nnn ccb Nr
to bto NPr MOON
nn n n 0 U3
bb 0)00
MON
po
CD N
OOOOn n0/N
b p
to Nb t1++11
Q
I� nON m
poo p1o0 mmt0 M
N 10 IA [�1
O n n� N
btO t70m coLn
OO nn.m N b
po
bl7 co co to t7
Cm
bbto bbin PVP
In
m bb b U3 PPPP
U)U3 bio PP P
bb U3P PPP
nIL
rrrrr r rr
�N-. r r r
�
r r r r r r r
LL LL
n
N
r Q
to tnb to Pr GOON
nnn ccb Nr
to bto NPr MOON
nn n n 0 U3
bb 0)00
MON
O�j
Nt0o l0n tMo l`�]�rnmmtn
pp
Ntp to tnM NW mO CD LO
Ob
0
pp/7Ntn Obt7
�r
SMP] Mf0 i7 N^NN
err � � N� NN
LO M,0
D1 m m
r'17N
C11co m mb
P3 l7 n N N N N
nIL
rrrrr r rr
�N-. r r r
�
r r r r r r r
❑ a
LL
N G
Ob
to tnb to Pr GOON
nnn ccb Nr
to bto NPr MOON
nn n n 0 U3
bb 0)00
MON
Z oo
w0P_
0 wco
W m m W W W W W W W
co C`''77 N r
m m m m W m m W m W
0r
mm m mm m N
W m W W W W W
r -0r0
nmto = M Nr
m m W m m m W
LL II
nIL
�O nNaomnW
().L4 U nNOmnm t, c,4 O]mn nN 03m nm
mnb Pon N to n b Pon N co r, b Pm co I, U3 P[ON
0) Cc 000 0010 C)Co 03 0 O 00000 O W m co O 0010 m W m 0 0 c 03C) 0m
IL --:^ rOO OOOO r X000 OO -� 000000
l6
.� N x 0 mO N_ <mmoiNNN m mONP_(Dm0 N P _O NP m _m ON N C 0<00NP
p W x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x -
Z m m m m m m m m m m m m m m m m m m m m 0000000 N r r r
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 79
i
1
1;
1t
1;
IE
IS
2C
21
zz
23
24
Z5
26
27
26
Z9
30
31
m 32
w<33
< 34
O
h=
c W 35
W
IH
0¢
36
LL
J.T.L. Design & Engineering
20351 Irvine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
K
CALCULATIONS and SKETCHES
DATE f(J�yI Jig
===CHWO
SHEET NO
oil
rvMvi mdtomNinaimy�Mm��Fi9AS
of �r
�1 N. ry,00, 5, H,U.��e�,�9,91�,
NNN _ FrvRtl F�Mv6iffi -_ _
os o�LL
Z V5 U
M N^ m M u7 n a1 VS n N
y L%% k X N X �V0XI VV%�� Y kW�Wk N NNY N .... Y k
Www
ry vmm���m
Oy fmm��.f- f mm�� ter!
— ry ry ry ry ry ry M M M M M M M f v f a f f v
N V1 N, � 1.j Nn01 N N Vf � M N tM1 Ol b
Y
N m N 00
N N N N N V I b V f N V I
Y1 VIN N N N N vi n ti n n n ti n n n
mmxxxmmiamm O.^m m R.
X X X Z Y% X Z X X Y Y Y Y Y% X - -
bmmmmmmm mmmmmmmmm
1 2 3 4 5 6 7 B 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Z4 25 26 27 28 29
YI gm.
F - § PM
o M1
�
'
L7
LL
N
rymry�IAA ym�
AA pmpm
mF {pNgy
r�(9j sN
{m�mg mp pv��
Y}ZSj jay�nR
4 *C'n
OO
'N{= 000
---
N CI'�O
.: Q
$A
OOQ O. n�i x.01 y
^
O 0
00O.m
O Q $j
gI LSA �i
LLV
000
OOOOO
2wl
RSi$o6eA4
8;2spquRq
Oz.
LL
O
zm 1
O Q=
of r MFA g
ON Fi Vf n iQi
n O
i�V i0 m �v m N 2tl
R^$ p A a V�
N
—
r
z
1
zM
ww�ts>szs
mmombm
wle����ry
m�"11MA9
wwAA� s�
iasv.wwwwww
iv.igw.wawwww
ao
z
-
—
'—
Z V5 U
M N^ m M u7 n a1 VS n N
y L%% k X N X �V0XI VV%�� Y kW�Wk N NNY N .... Y k
Www
ry vmm���m
Oy fmm��.f- f mm�� ter!
— ry ry ry ry ry ry M M M M M M M f v f a f f v
N V1 N, � 1.j Nn01 N N Vf � M N tM1 Ol b
Y
N m N 00
N N N N N V I b V f N V I
Y1 VIN N N N N vi n ti n n n ti n n n
mmxxxmmiamm O.^m m R.
X X X Z Y% X Z X X Y Y Y Y Y% X - -
bmmmmmmm mmmmmmmmm
1 2 3 4 5 6 7 B 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Z4 25 26 27 28 29
JTL DESIGN & ENGINEERING
20351 Irvine Ave. Suite 92
Santa Ana Heights, CA 92707
Tel: (714) 545-8470 Fax: (714) 545-8446
ertical load ana]yAis
1. Roof framinR
Rafter #1 L=20'-0"
w=1.33 (16+21)= 49.2 # / ft
M= 49.2 (20)(20)/ 8 = 2460 ft -lbs
Date: ,�i1Ly/ /A98
Job No:
By L
Sheet No:
3
S req'd = 2460 X 12/ (1385) = 21.3 in
4 3 4
Ireq'd =49.2X5(20X12)X240 =110.6 in
384 X 1600000 X 20 X 12
2
A req'd = 1.5 X 49.2 X 10 = 8 in
95
USE 2 X 10 roof rafters Qr� 12 " oc
RAFTER DESIGN SCHEDULE PER DOUGLAS FIR NO #2
F'b
Spacing
Loading
Max. span
1260 psi
2 X 12 @ 16 "oc
49.2 lb/ft
23'-0"
1385 psi
2 X 10 @ 16 "oc
49.2 lb/ft
19'-0"
1510 psi
2 X 8 @ 16 " oc
49.2 lb/ft
15'-0"
1635 psi
2 X 6 @ 16 "oc
49.21b/ft -
III -011
NOTE: Allowable bending stress has included 1.25 increase facter.
19
19
2°
21
22
23
24
25
26
27
25
29
30
31
p 32
a
w 33
¢ ui
c 2 34
N-
O
WW 35
fz
0 36
�a
J.T.L. Design & Engineering
20351 Irvine Avc. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-3446
CALCULATIONS and SKETCHES
OATS 1 /998
CONT NO. ,8 A � L
er L CHWO
SH ET NO.
,
5
6
7
2
3
HEADER SCHEDULE
4
5
AT NON BEARING
PYA S ( ROOF &
FLOOR )
2
jf4r SPAN
SIZE
-
3'-0"
4 x 4
4'-0"
4 x 6
'
5'-0"
4 x 6
°
6'-0"
4 x 8
2
3
/�✓/� /V �YV �
C[� LK��i�/
AT BEARING
LVA S
/700,7
/LOOK
LOAD
GHJ _< 500 /bs/ll
<_ 104D /6 /r
11AY SPIN
MY
ME
3' - 0 "
4x4
4x6
4' - 0 "
4x6
4x8
5' - 0 "
4x8
4x10
6' - 0 "
4x 10
4x 12
.< is 1e 17 id 19 20 21 22 23 24 25 26 27 23 29
1
2
3
4
5
6
7
6
9
10
11
12
13
14
15
16
17
I6
19
20
2,
22
23
24
25
26
27
20
29
30
tl
m
p 32
W< 33
¢h
c 2 34
0
w W 35
2�
02 36
LLC
J.T.L. Design 3 Engineering
20351 Imine Ave. Suite 42
Santa Ana Heights CA92707
Tel: (714)545-3470
Fav (714)545-5446
CALCULATIONS and SKETCHES
1 � �
L=20'=0"
W=1.33(5+10)=201bs/il
M=20(20)2/8= 1000 it-/bs
S req'd = 1000 x 12
1 re 'd = 5(20)(204XI23) in 3
req'd
6U06)30.12 =
240
A req'D = 1.540X10 = 3.16 in 2
95
DATE SIL
CON T. NY. ,A
BY CHWO
SHEET NO.
x -# 2
tJ67-a
CEILING ,101ST SCHEDULE
l A111X. S 14,IK
2 x 12 @16"OC s6' -o"
2 x 10 @16"OC D-* -o
2 x 8 @1FOC o
2 x 6 @16"OC
l�/oP�l 2 x 4 @16"OC
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 2B 29
1:
li
1E
,B
19
2C
21
22
23
24
25
26
27
28
29
30
31
p 32
w a 33
J.T.L. Design & Engineering
?0351 Imine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
,A)
w� (�fLLj yZ
V. Lam
CALCULATIONS and SKETCHES
GATE, AJL}/ /���
CONT. NO.
BY pL CHK'0
SH ET NO.
L=20'-0"
P=20xlox 0.5(16+21)=3700lbs
M=3700(20)/6=12333tllbs
S re 'd = 12333x12
req'd 125
I req d , = 604.74011„—;= = 501 k a
A req'd = 1.5470 4.595 = 29.2 in z
U,Sz'xr2oc91
I■ ■
SMI
, IdX SPAN
6 x
14
DFJI
25' - 0”
6 x
12
DFil
,
off
4 x
14
DF11
4 x
12
DF#1
4 x
10
DFJ 1
4 x
8
DF#1
10' - 0"
�C
2 x
12
DF11
10' - 0"
d7�
o i is II 1z 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 25
J.T.L. Design & Engineering
20351 Irvine Ave. Suite 42
Santa Ana Heights CA92707
Tel: (714)545-8470
Fae:(714)545-8446
DATE
CALCULATIONS and SKETCHES
Q \ 1 l LOADING:
PPsP'3 -TPs_e9 d-
J f r%ypC/9�/5L A d -
CHK'D
LENGTH' /9 /
7o—l�xtyl� - B in%�
7�X A5�/ 5 = //.,7 .,v3
req'd 38f�C/.6�/0 �C/9�/
USE:2r::::4* _
L�,C t� J - - - ',�41 Wog 4 R= 74ec
USE;
LOADING:
ENGTH: / S/
5req'd-/6�X/�/� _/i✓3
Ireq'd— //?j /n/`/ -
LOADING;
LENGTH:
K=-555'
/n/2�
Sreq.d=3496X/y6lG� 6
Areq d /R s/
Ireq,d J
USE: cJA/O Y' f
6-314 tl 44C/a r- C R=�d6
BEAM 140: LOADING: LENGTH; x`75/
P=I15C37�=�
req'd
7 ;req d- 7I/Jr%
].T.L. Design & Engineering
20351 In'ine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
CALCULATIONS and SKETCHES
P=- 3!�7—)=3IP7/-AA
LOADING:
DATE 1/'!.11 /�
CON T. NO.
BY / CHK'D
LENGTH: /5 /
3
5_e'd z
967cfx/�� =/i6 Nli,
req'd
USE:
vJ w��jvc37� 333��/
M�33C9i�P-
USF-: /
AM N0:
LOADING: LENGTH: i /
A q•d=6
r
I
req'd=
LOADING;
Areq'd-
�/�3��/ Ire9d=
BEAM NO: (j3) LOADIi4G:
�e q'd—
��'
req'd-
Ireq'd=
U SE;
K=- /449q
ENGTH; /-SCS
37 ::L -1,.f4
44
LENGTH;
F -k=
J.T.L. Design & Engineering
20351 Irvine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fac (714)545-8446
CALCULATIONS and SKETCHES
LOADING:
DATE /
CONT.N� .
By �y,� TCHK'O
SHIET NO.
LENGTH: S
SI -e9 d= q7-c!5Sx /? /anc .= S,a=
1661 N=�.��8 (/6.5req d
Rr = 976$ i-eq'd=�/
USE:vC/s- off/
LOADING: LETGTH: /� s.'
=/D/X 37 = 373% regId= 1�3�� DC / /0
-3737 C/;ZS��SL Areq d
/63��0/ Iregd= s>Si.1fiG�
USE; 455 ,LL y,r -IV'
AM NO:
w /67 #�!
M=16 -7C/
USE: yx/;;� Z�p * /
BEAM INO:
LOADING: LENGTH: /34,�'
Ireq'd= /0�4>A'14
LOADING: LENGTH;
�eq.d= %d/7SSC/�/tea
A eq'd= ��� /i✓Z
Ireq•d= ?v44/
USE; boC/1 ate" /
/n/46
1.41
941->A13
f-,2.,= /
I
I
II
2(
21
22
23
24
25
26
27
28
29
30
31
19 32
v
W a 33
Qo Z 34
o -
W 0 3S
F�
0 ¢ 31
as
J.T.L. Design & Engineering
20351 Irvine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
2< 3
1 2 3 4 5
CALCULATIONS and SKETCHES
i
DATE 7/gyp
C ON T. N O. 78-}!� G('•3�
BY ty� CHWO
SHEftT NO.
L=20'-0"
W=1.33(10+40)=77,.jIbs//!
M = 77:2 ( 20 )2 / 8 = 3860 /!-Ibs
irk
S req'd = 3860 x 12 /B75 = 53 in
3
1 req'd _ c5u77_1(204XI23)in4
384x1dr104x3=
A req'd = l.sx95alo
aaisr scHrnu� F
SWIM,
2 x 12 @16"OC
2 x 10 @16"OC
2 x 8 @16"OC
� —�-�C 13 Pil for GLS
af4:.�L
,!/rLY. SPAiY
i
:3
- - .v .1 11 i4 14 15 16 17 18 19 20 21 22 23 24 25 26 27 2B 29
I.T.L. Design 3 Engineering
20351 Inine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)535-8470
Fax: (713)535-8336
CALCULATIONS and SKETCHES
OATE juL.� /,:I,
CON�T...�N/�O. ��
BY i4 CHK'D
SH ET N0. /3
PFAM N -Q: nia LOADING: LENGTH: /Z,S/
p S
/;6N.57
= s I cf,o -)�6 /
I -eq d- /� 97.7
�
eq'd= �zf-
-eq' d= y7-'7- /ice'
USE: j2p:a1 /
Ri= / fi
LENGTH:
kh)�-z . 3c,c3 • 5 = /91=ts.$4
PI.=7� Areq d_ —
of
BEAM NO: S) LOADING:
/WS.
l/Ap
LENGTH: /p /
P�3C3�J=x-33/ S = �S-���/
r� d /nom//`
A
USE_ 5, j,. ! Ld<Sd�
BEAM NO:
LOADUJG:
LENGTH; /j`5
7 req'd
T req'd
s77
USE_,��y bc�1�
J.T.L. Design & Engineering
20351 mine Ave. Suite K2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
CALCULATIONS and SKETCHES
DATE - //.f.Ltl 41'.6
Co, T.N
BV � CHWO
SH ET NO. /
=AM N0: (/'7) LOADING: LENGTH: /44S/
—/ 5 eq d
_ i
I SMS C/tfs���,G req'd
req• d- / /Aj
USE:
USS:
AM NO:
LOADING:
ENGTH: /:�tG
reqId-1���X/-��/ =-RA6�
f / _Wq d-176
LOADING:
--
PP=-7 S -
/7-1co) Ar d-
pC22 Ire 'd-
_ .� q
USE: yy/y.►t/
BEAM IJO:
I"!
LOADkG:
�eq'd-
A eq'd-
I
req'd-
-
USE g/e --j- C-1�
LENGTH!
7��
R - /tea
LENGTH; .a /
J.T.L. Design & Engincering
20351 Irvine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)535-3470
Far (714)545-8446
CALCULATIONS and SKETCHES
KAM NQO' LOADING:
Py P,
p�
� 78 S_eq d=
GATE�1(1/j1, 9l7
CON TJ.NO. !3&
BY F� CHK'D
SHEET NO. /5
LENGTH: //.S
rec{'d_
M =1,0144 /s ib I = 7
T' I-r78&c_1.5-
USE:
'
USE 2 iP
U,:r:
�f I
M N0:
pr -93/#
LOADING: LENGTH: /As/
Sreq'd= /1b79xl = /o.23p�3
XC i7�- Are
S-AKVq'd- s/78�r✓.s�/�
f3o�c37.=,���s�,�C�'# I =<8> +7 5
H.=m�oXS SSregd 7L `�
LOADING:
w�= 7MIf-,,) r�sa��/i,�/3
P` �'y3 Sreq.d= %/SSI X7��.jtpD =�3a7
.LEriGTH: '
BEAM NO: LOAD[i4G:
! -/
W=&(6ot-1,� j-� =s7gs =
re q'd
LENGTH i
3
USE; g6r�/� R! 14-%x% ,r
J.T.L. Design & Engineering onrE u /
20351 [nine Ave. Suite N2 CALCULATIONS and SKETCHES CON T. N07,
Santa Ana Heights CA92707 ev CHK•O
Tel: (714)545-8470
Fax: (714)545-8146
USE:
dgy
vJ
AM NO:
('S1 LOADING: LENGTH: .
rnJ_ p z j 4AS- - 3o87.4>
a7=.�)a t cq'd
E's=x37=/33� �'` �eq d=
M 7`c roc; d= , /nf�d-/.✓`/�
f i33� x870
-,i
LOADING: LENGTH:
35X3.-3��b reqd= �'�•--,�f-
7°3=3�7h'� Areq.d=
Ircq•d=
/
P�nx�� =yas
USE:
JKAM No:
LOADING:
E Nr, -I /g /
Sreq.d=
Ar
Ircq•d- /4SG f
R=/--AdD
yj� LOADUJG: LENGTH; 7.S/
4AJ�S1>cf44f1_rD=/44r�
�req•d__
A -1^112-
re d -
*441#
97*44/# Ireq•d=
USE:
'
R-2-=
J.T.L. Design & Engineering
20351 Inine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8136
CALCULATIONS and SKETCHES
DATE .10
CONT.NO. �8—tea
CHK'O
SHEET N0. /'7
LENGTH: /
p 75X37 z77s f /,✓3
0:--3-77Sx7s/%S��J
Ae* d-�Z
�eq.d=
USE;
NO:
tp
AM NO:
M
USE.:�G1C��. D
BEAM 140:
Pr
R=ia7S-41
l) LOADING: LENGTH: lys'
��775 fi3/q /N�
'A�� t/tDsreq'd- az�,,3 �
req
f�ssrs�c�/�'�
/
LOADING: LEN, : /6
r-eq'd- ��%X//Da �c��✓/.t/-�
(3j-) LOAOU41S:_
�req•d
A, -
�f)S- A
/"/=-fin (l���d'' /��eq•d=
req .d-
USE__—fz�C I� !�>• /
LENGTH /�4
j off.-fix/�� �-. � 96 i.✓3
4z�t-/A/_7-
z16 �/�G = 3rfp/•`/�
F�= 'L
J.T.L. Design 8 Engineering onre i /t z-1 9(f--
20351 Im ne Ave. Suite N2 CALCULATIONS and SKETCHES CONTA. "g —A2m4a
Santa Ana Heights CA92707 `'
Tel: (711)515-8170 sH Eo. CNK'0
Fax: (711)515-8-116 /�
e0; 4✓a LOADING: LENGTH: /sc/
vJ w=Solite=85��' S �q d �as�DXl��tdo = X03
-eq' d=
USE; R=s
LOADING: LaGTH."
Sreq.d= 37s�C/lop = $"-/ /AVS
REAM NO:
V J Pj
p3 = i3or-;X3
USE: r6x77 —663'
BEAM NO:
r 5 i6'
R/
LOADING: LEtK;7K —=j!!!Z49
Ll//
5req d
A -
rezl•d-
Ireq,d=
P/=17*/,t "+S
=-)-� �e7�5*
_LOADu4G:
req d_
/r/ /6) C/A 54!5A eq'd_
Ireq•d--"
LENGTH 355/
„,s «7-0-,L D
USE:6p//b,C9z _
P-4/MV
J.T.L. Design & Engincering
20351 Ir\ine Acc. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Far (711)515-8116
USE: 4VIL-1
USE:
M NO:
CALCULATIONS and SKETCHES
LOADING:
eq'd-
A
eq'd- M/A/b�
DATE
CONTCONT.NO.
9V�CHK'D
SH ETSH ET N��
LENGTH: 95
7 IW3
R= 77s-*
lNG : LENGTH: )q/
S %/
S-
��'=r%3�f req'd-
�7
41oge.I �
/6/--I
Aq
USE:
BEAM NO:
H7=SWXX33r-
A�eq•d= aSz /�
V=/
%
LOADING: LENGTH:
irecl' 795
d=
L /ADVgG: LENGT}ii y/ /
.791-
s 7
9,d= oC�
e
H
R� 127, req'd--�9�-� 39S
USE; � " 237A7 * /
Ri=333-z
J.T.L. Design & Engineering
20351 mine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (711)515-8470
Fax: (714)545-8446
USE
h!j$aCgJ
AM N0:
CALCULATIONS and SKETCHES
LOAD+NG :
DATE
CONT`IO.
BY CHK'D
SH ET NO.
LENGTH: 'S r
00
P=65�x =�5i/zeq d_
req cj
_
fa22
req'cj=6.6/���-�'
4L ti - wain
LOADING: LaGTH:
6riJf��e re d
f37JC/0=2�'e •d=
9
uN,�Ii2M_/ Gqd
/671 IA4 'Ito
LOADING: LENGTH: /q
4L req'd �•� "�
BEAM NO:
P P�
USE; Ajj a2! .
C- /�yyn�/yam
Ps6�tc5
l3
LOADUNG: LENGTH;
�eq,d=
Ireq•d= M!r✓bi�
i/
J.T.L. Design & Engineering
20351 In'ine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
CALCULATIONS and SKETCHES
DATE
�0Eton
CONT Nb..
Syp_ CMK'O
SH ET NO. Z/
1
2
3 BEARING STUD WAILS
a
5
1 i x `f sTUos cis ac
NET WALL HT. 6' - 0"
' ALLOWABLE LOAD
e 0.3(10'XI.7)
(84213.5)2 5.75 = af,c� /bs/1!
8 J� �/
416� /4 /
12
13
° MAX. LOAD
5 W = to
,
�6
17
I
20
21 WAIL FOOTING
22 FOOTING SIZE
23
24
25 X
26
27
26
40
28 /sF' /e"1111%� x_7.5�BF/0I� CR�OF.
30 1/%TH I - ?f TOP if' 907 /ONT/NOUS
31
q
p 32
P
w < 33
¢r
< 34
0
WW 35
I�
36
w
JTL DESIGN & ENGINEERING Date:
20351 Irvine Ave. Suite 42 Job No:
Santa Ana Heights, CA 92707 By
Tel: (714) 545-8470 Fax: (714) 545-8446 Sheet No:
'OSTS and FOUNDATIONS
A.posts
type
max height
column loads
column sizes
capacity remark
1
8'-0"
6000 lbs
4 x 4
7800 lbs
2
10'-0"
8000 lbs
4 x 6
9800 lbs
3
11'-0"
16000 lbs
6 x 6
200001bs
4
11'-0"
200001bs
3" dia steel
25000 lbs pipe
B.foundations
type descriptions soil bearing footing capacity
1 2'-0"SQ x 12" footing with 1500 psf 4000 lbs
#4 rebars @ 12"oc each way
2 2'-6"SQ x 12" footing with 1500 psf 6000 lbs
#4 rebars @12"oc each way
3 3'-0"SQ x 12" footing with 1500 psf 12000 lbs
#4"rebars@12" oc eah way
4 3'-6"SQ x 12" footing with 1500 psf 18000 lbs
#4 rebars @ 12"oc each way
5 4'-0"SQ x12"footing with 1500 psf 220001bs
45 rebars@ 12"oc each way
1
z
3
6
5
6
7
8
9
10
11
12
13
14
15
16
17
is
19
20
21
22
23
24
25
26
27
28
29
30
31
32
<33
Cn
< 34
N�
O
wW35
F�
00 ¢ 36
,a
J.T.L. Design & Engineering
20351 Irvine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
CALCULATIONS and SKETCHES
DATE ! Z44
-
C ON T. NO.>�
BV � CHK'D
SH ET NO. ��
ALLOWABLE LOADS ON D. F. # 1 WOOD COLUMNS IN KIPS
Area
9 X 4
6 X 6
8 X 8
10 X 10
12 X 12
12.75 in'
30.25 int
56.25 in'
90.25 int
132.25 in'
L-netn
Weak
SLrona
Weak
Strong
Weak
1'
13.5 I
33.3
61.9
99.3
145.5
2'
13.5
33.3
61.9
99.3
145.5
3'
13.5
33.3
61.9
99.3
145.5
4'
13.2
33.3
61.9
99.3
145.5
5'
12.7
I 33.3
61.9
99.3
145.5
6
11.9
32.6
61.9
99.3
145.5
7'
10.6
32.1
61.2
99.3
145.5
8'
7.8
31.3
60.8
99.3
145.5
9' .
6.2
30.1
60.2
98.2
145.5
10'
5.0
28.4
59.3
97.6
145.5
11'
4.1
26.1
58.0
96.9
143.8
12'"
3.5
23.2
56.4
95.9
143.2
13'
3.0
18.0
54.4
94.6
142.3
14'
2.6
15.6
51.8
93.0
141.2
15'
--
13.6
48.6
91.0
139.8
16'
--
11.9
44.7
88.6
138.2
17'
--
1 10.6
36.5
85.6
136.2
18'
--
9.4
32.6
82.1
133.8
19'
--
8.4
29.2
78.0
131.0
20'
--
7.6
26.4
73.1
127.6
21'
--
6.9
23.9
67.5
123.8
22'
--
6.3
21.8
56.1
119.4
23'
-F4
--
--
19.9
51.3
114.3
'
--
--
18.3
47.1
108.5
25'
--
I --
16.9
43.4
101.9
26'
--
I --
15.6
40.2
86.2
27'
--
--
14.5
37.2
79.9
28'
--
I --
13.5
34.6
I a a e 5 7 e 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
3
5
6
25
26
2)
26
29
30
31
P
32
3.
Cn
ao 3:
o-
3'
J' 3c
�i
J.T.L. Dcsi_n & Engineering
20351 lr%mc Atc. Suit -- r2
Santa Ana Hcihts CA92707
Tc1. 17 14)54-5170
Fax: (714)i45-8446
CALCULATIONS and SKETCHES
OaTE /u!� 70
CSN 7 .No.9
gv CNK'O
SH ET NO. 1�
I 2 3 a - 6 7 a 9 10 II 12 13 14 15 16 1) 18 i9 20 21 ,. 23 24 25 26 Z 25
E
E
IC
11
1:
I]
14
15
16
1]
1e
19
20
21
22
23
2<
25
26
n
26
29
30
31
p 32
P
y� < 33
Rh
ao Z 34
u1_
0
al W 35
IH
0 ¢ 36
LL
J.T.L. Design & Engineering
2W51 Imine Ave. Suite k2
Santa Ana Heights CA92707
Tel: (714)545-8470
5-
3/4' THICK STEL BASE
PLATE W 4- 3/4' DIA,
ANCHOR BOLTS
PIPE COLUMN PER PLAN
3/4' THICK 5TIs1 BASE
PLATE H/ 4- 3/4' DIA.
ANCHOR BOLTS —
1-1/2' DFZTPACK---\
CONCRETE SLAB PER
FOUNDATION PLAN �
CALCULATIONS and SKETCHES
000
111M
s
IN
DATE C /u4>
CONT. No. L94>
BY CHWD
SH ET NO.
3/5' THK. STIFFENER
PLATE 80TH 51DE5 OF
BEAM a SUPPORTS
STEEL BEAM PER PLAN
/ TOP PLATES PER STEEL
B
/ BEAM NOTE
1/2' THK. STEEL PLATE
W 2-3/4' DIA. M5.'S
T - STEEL PIPE COLUMN
PER PLAN
d
5151V
CONCRETE PAD FOOTING
W REINFORCING PER RAN
Ja � a a I�III
' '. �a 18 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 2
1
2
3
4
5
6
7
JTL DESIGN & ENGINEERING
20351 IRVINE AVE. SUITE #2
SANTA ANA HEIGHTS CA 92707
TEL: (714)545-8470 FAX: (714)545-8446
DATE !% �R
CON T. NO.
BY CH K'D
SH ET NO.
BI9
�N 116
19
20
21
22
23
24
25
26
27
28
29
30
31
32
a
W < 33
d'N
c Z 34
m_
0
WW 35
E�
Q ¢ 36
1 a
�-------j
/.moi .�� }/7
-1�+8-7 XS--= Y7dK6
9677
3 j
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 20
JTL DESIGN & ENGINEERING
20351 IRVINE AVE. SUITE #2
SANTA ANA HEIGHTS CA 92707
TEL: (714)545-8470 FAX: (714)545-8446
DATE
CONT. O.
6Y CHWO
SH ET NO. -n -7
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
a
W < 33
d6
ao Z 34
WW 35
E�
0 ¢ 36
w
/0 GIS ►f�lo'�OG h.�/
If
1;
1:
lE
Ii
16
19
2C
21
22
23
24
25
26
27
26
29
30
31
T
p 32
W<33
a�
ci34
o -
WW 35
2�
0 ¢ 36
4a
J.T.L. Design & Engineering
20351 Irvine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
CALCULATIONS and SKETCHES
' 111 1 i t 1 1
Normal
Plywood
Tbiclrness /Inches)
5/16
3/8
1/2
3/4
C -D
lolerior
E, & erior C/ue
20/0
24/0
32 / 16
42/20
48/24
( 4 ) SHEAR WALLS ( SW No.)
i
DATE. IOLV
CONT. 4 �6a
BY J� CHK•D
SH ET NO.
Slruclural Slruclural
C -C
C -D
C -C
xlerior
_w./Fxlerior au, -
lue20/0
20 0
20/0
20/0
24/0
24/0
24/0
32 / 16
32 / 16
32 / 16
42 / 20
42 / 20
42 / 20
48/24
48/24
48/24
1. LEGEND
SW = SHEAR WALLS
= SHEAR WALL DETAIL SEE SHEETS, 3�
HD = SIMPSON HOLD DOWN
2. ALL PLYWOOD SHALL BE CONTINUOUS AT PARTY WALL.
.v 1. i4 14 14 15 15 17 id 19 20 21 2: 23 24 25 26 27 28 20
E
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
3
32
a
w ¢ 33
X
¢o z 34
m_
0 35
WW
MF
mz 36
wm
JTL DESIGN & ENGINEERING
20351 IRVINE AVE. SUITE #2
SANTA ANA HEIGHTS CA 92707
TEL: (714)545-8470 FAX: (714)545-8446
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 20
r
2
JTL DESIGN & ENGINEERING
20351 IRVINE AVE. SUITE #2
SANTA ANA HEIGHTS CA 92707
TEL: (714)545-8470 FAX: (714)545-8446
I
DATE `I
Co
T.NO.
BY CHK'D
SM ET NO. �Q
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
26
29
30
31
32
a
'WG 33
d' N
Qo Z 34
W0351
W
E� I
O ¢ 36
LL6
33,)l.5 1KYF/
N�
19
20
21
22
23
24
25
26
27
28
29
30
31
V 32
w < 33
Q N
c, 34
N�
0
w W 35
F�
Q 36
Ln
• J.T.L. Design & Engineering DATE 4411
20351 Irvine Ave. Suite #2 CALCULATIONS and SKETCHES ppNT.- L�—Q��w
Santa Ana Heights CA92707
Tel: (714)545-8470 sH L CHKFO
SN ET NO.
Fax: (714)545-8446
SEE NOTE 1
P71p SHS Xd/ IffM & N LIM,
ALLOF.19LE
ANof/o.P
JYML
S11DIF
60MY
/see nole 7)
1.
1/2" DRYWALL WITH 5d CODDLER NAILS @ 7"
100 p/ft
5/8"
dia.
x 12"
160 16"oc
0/C EDGE AND FIELD ( TABLE UBC)
'see note 6
@ 48"
on
center
2.
5/8" DRYWALL WITH 6d COOOLER NAILS @ 7"
100 R/ft
5/8"
'dia.
x 12"
16d@ 16"oc
0/C EDGE AND FIELD ( TABLE UBC)
@ 48".
on
center
3.
1/2" DRYWALL WITH 5d CODDLER NAILS @ 4"
125 ✓f/ft
5/8"
dia.
x 12"
16d@ 12"oc
0/C EDGE AND FIELD ( TABLE UBC)
@ 48"
on
center
4.
5/8" DRYWALL WITH 6d CODDLER NAILS @ 4"
125 k/fl
5/8"
dia.
x 12"
16d@ 12"oc
O/C EDGE AND FIELD ( TABLE UBC)
@ 48"
on
center
5.
1/2" BLOCKED DRYWALL WITH 5d COOLER
150 N/fl
5/8"
dia.
x 12"
16d@ 8"oc
NAILS @ 4" 0/C EDGE AND FIELD
@ 48"
on center
( TABLE UBC )
6.
5/8" BLOCKED DRYWALL. WITH 6d COOLER
175 #/fl
5/8"
dia.
x 12"
16d@ 8"oc
NAILS @ 4" 0/C EDGE AND FIELD
@ 48"
on center
( TABLE UBC )
7.
7/8" STUCCO OVER PAPER BACKED LATH
180 #/ft
5/8"
dia,
x 12"
16d@ 8"oc
W/16 GAUGE STAPLES @ 6" O/C AT TOP
@ 48"
on
center
AND BOTTOM PLATES, EDGES AND
BOUNDARIES AND FIELD ( 1CBO REPORT
No. 1823. 1972 OR No. 1318, 1973 )
8.
7/8" STUCCO OVER PAPER BACKED LATH
325 #/fl
5/8"
dia,
x 12"
16d@ 4"oc
W/I6 GAUGE STAPLES @ 0/C AT TOP
@ 24"
on
center
AND BOTTOM PLATES, EDGES AND
BOUNDARIES AND 6"O/C FIELD ( ICBO
No. 1823, 1972 OR No. 1318, 1973)
99.
3/8" STRUCTURAL Il PLYWOOD WITH 8d
260-#/fL
5/8"
dia.
x 12"
16d@ 6"oc
NAILS @ 6"O/C @ BOUNDARIES AND EDGES
@ 36"
on
center
AND 12"0/C FIELD ( TABLE33—I-K-1
10.•
3/8" STRUCTURAL 11 PLYWOOD WITH Bd
380 #/fL
5/8"
dia.
x 12"
16d@ 4"oc
NAILS @ 4"0/C @ BOUNDARIES AND EDGES
@ 24"
on
center
AND 12"O/C FIELD ( TABLE I)
II.
3/8" STRUCTURAL Il PLYWOOD WITH 8d
490 If/ft
5/8"
dia.
x 12"
I6d@ 3"oc
NAILS @ 3"0/C @ BOUNDARIES AND EDGES
@ 16"
on
center
AND 12"O/C FIELD ( TABLE 0
4 1 a 4 5 5 1 n 9 10 11 12 13 14 15 16 17 IS 19 20 21 22 23 24 25 26 27 28 29
I'
u
2:
2'1
22
2]
2<
25
26
27
26
29
30
31
Q
v
32
a 33
ao 2 34
0
W�35
F�
OT
36
,n
J.T.L. Design & Engineering
20351 Irvine Ave. Suite #2
Santa Ana Heights CA92707
Tel: (714)545-8470
Fax: (714)545-8446
2I TYP6 S/!G!R A'ALG U8'/�1/L N.4/L/NC
3
CALCULATIONS and SKETCHES
12. 3/8" STRUCTURAL II PLYWOOD WITH 8d
NAILS @ 2" 0/C @ BOUNDARIES AND EDGES
AND 12" 0/C FIELD ( 23—) — t<-- I )
13. 15/32" STRUCTURAL II PLYWOOD WITH 8d
NAILS @ 2" 0/C @ BOUNDARIES AND EDGES
AND 12" O/C FIELD ( =3-1—Ie— I )
14. 19/32" STRUCTURAL 11 PLYWOOD WITH 8d
NAILS @ 2"O/C @ BOUNDARIES AND EDGES
AND 12"0/C FIELD
ALw,r49zL'
SHF✓1R
630 #/fL
770 #/fl
870 1/fl
i
OATE�� 444-y -96
CONT. �
BV 43I CHK -0
SH ET NO. jllig
ANCHOR
.90L7S
3/4" dia. x 12"
@ 24" on center
3/4 dia. x 12"
@ 24" on center
3/4" dia. x 12"
@ 16" on center
Notes:
1. THESE VERTICAL DIAPHRAGMS SHALL NOT BE USED TO RESIST LOADS IMPOSED BY
MASONRY OR CONCRETE CONSTRUCTION.
NA/!S
see ?ole 7 f
I6d@ 2 i "oc
16d@ 2"oc
16d@ 2"oc
2. FRAMING SHALL BE 3 — INCH NOMINAL OR WIDER AND NAILS SHALL BE STAGGERED WHEERE
NAILS ARE SPACED 2 INCHES IN CENTER, AND WHERE 10d NAILS HAVING PENETRATION INTO
FRAMING OF MORE THAN 1 — 5/8 INCHES ARE SPACED 3 INCHES ON CENTER.
3. WHEERE PLYWOOD IS APPLIED ON BOTH FACES OF WALL AND NAIL 'SPACING IS LESS THAN 6
INCHES ON CENTER ON EITHER SIDE. PANEL JOINT'S SHALL BE OFFSET TO FALL ON
DEFFERENT FRAMING MEMBERS OR FRAMING SHALL BE 3 — INCH NOMINAL OR THICKER AND
NAILS ON EACH SIDE SHALL BE STAGGERED.
4. ALL STUDS SHALL BE SPACED AT 16 INCHES ON CENTER.
5. SILLS & TOP PLATES AND STUDS AT WALL NO'S 12. 13 AND 14 SHALL BE 3 — INCH NOMINAL
OR WIDER.
6. 'VALUES OF CAPACITY ARE FOR SHORT TERM LOADING DUE TO WIND. VALUES MUST BE
REDUCED 25 PERCENT FOR NORMAL LOADING. THE VALUES FOR GYPSUM PRODUCTS MUST
BE REDUCED 50 PERCENT FOR DYNAMIC LOADING DUE TO EARTHQUAKE IN SEISMIC ZONES
NO'S 3 AND 4.
7. COMMON NAILS AT UPPER FLOOR SILL PLATES.
- - - - Iv a 14 a 14 1e 16 17 1tl 19 20 21 22 23 24 25 26 27 28 29
10
15
16
17
16
19
20
21
22
23
24
25
29
30
31
a 32
v
3
W<3
<� 34
0
0
wW35
i'-
0¢36
0m
TTL DESIGN & ENGINEERING
20351 IRVINE AVE. SUITE k2
SANTA ANA HEIGHTS CA 92707
TEL: (714)545-8470 FAX: (714)545-8446
A DATE moi/ 1-495
N0.
CONT. �g Ad6�
BY (,{ _ CHK'D
SH ET NO.�
OnLp -Sip- 41
-- - +
Q�6FESS/0M
QFo , (ARA/
w . C 35023
Exp.9 -99
P
OF CAI
LAI
HO
LV ,
VG
oC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 IS 19 20 21 21 11 1n I 1. — 1. --
CALCULATIONS aid SKETCHES
20
21
22
22
24
.r SY zs
26
27
2a
29
70
]2
W ^,
OA7E
CONT. NO.
a*SGL CHK o
SHEET NO.
Go
_ C 3502'
/ 4NG-_ 9T OF CAl
0
?,pie
04 vx • b
. �Vgv-lae7r
3l
/-x
- .4AJI --ese��
srM
9
,a
„z
20
21
22
22
24
.r SY zs
26
27
2a
29
70
]2
W ^,
OA7E
CONT. NO.
a*SGL CHK o
SHEET NO.
Go
_ C 3502'
/ 4NG-_ 9T OF CAl
0
?,pie
04 vx • b
. �Vgv-lae7r
3l
/-x
- .4AJI --ese��
srM
♦
011
0
20
21
22
22
24
.r SY zs
26
27
2a
29
70
]2
W ^,
OA7E
CONT. NO.
a*SGL CHK o
SHEET NO.
Go
_ C 3502'
/ 4NG-_ 9T OF CAl
0
?,pie
04 vx • b
. �Vgv-lae7r
3l
/-x
- .4AJI --ese��
srM
1
2
3
4
5
6
7
8
9
,o
4
5
76
17
18
19
2.0
21
JTL DESIGN & ENGINEERING
20351 IRVINE AVE. SUITE 92
SANTA ANA HEIGHTS CA 92707
TEL: (714)545-8470 FAX: (714)545-8446
ADATE !� <9-7S
CONT. NO. Ufa.-�Q,f6JJ
SH ET NO. 22:-�D
SS/p�{
IARly
0 C T 2 6 1996
�j� E3�k� CUh ui C 35023
Exp. 0-99
ZJ=-9>C144�x14� =7�s/ FCAIIF
sJ
"Al7,1
_.
22
23
24
25
_._.
29
30
31
v 32
a
W 33
QN
4o Z 34
0
wW35
3�
oR 36
Yl
r cl�
2 3 4 5 6 7 6 9 10 11 12 13 14 15 16 17 IS 19 20 71 11 11 7n I .c 11 1. •-
I
2
L. II.M l
II K, IW
L cT1i Li 6
7
a c, io
B
9
,o
fi
2
IS
16
17
13
I9
20
21
22
2]
.K
24
LY 25
B; imH
26
27
23
29
70
]I
32
w ^.
33
02]
op
wti ]S
Z.
.
0
O i J6
yl
z
CAL-CULATIONS and SKETCHES
OTE
CONT. No,
8 pL CHK o
SHEET NO. i1
. �y
W
C.35023
CD
?a
_ .
G�uar�p/YZfiY/L �D ct/l�i�� {�99 z�
`aF CAUt".
3
���
AERO ENERGY
TITLE 24 CALCULATIONS
12711 NEWPORT AVE., SUITE G
TUSTIN, CALIF. 92780
(714) 505-4207
DATE: 8-4-98
OWNER: MR. & MRS. RICHARD CHAO
14 HEXHAM
IRVINE, CA. 92612
714-854-5202
DESIGNER: DENNIS CHERRY & ASSOCIATES
20351 IRVINE AVENUE, SUITE #1
SANTA ANA HEIGHTS, CA. 92707
714-641-1505
PROJECT: CUSTOM RESIDENCE
15 S'AILCREST
"PELICAN CREST"
NEWPORT COAST, CA.
STATEMENT OF COMPLIANCE
The energy conservation standards for new residential
buildings as set forth in Title 24, Part 2, Chapter 2-53; and
Title 20, Chapter 2, Subchapter 4, Article 1, of the
California Administrative Code, have been reviewed. This
design conforms to all requirements as they apply in Zone 6
using MICROPAS 4, VERSION 4.50, A California Energy
Commission approved computer performance method program.
PREPARED BY• Q
1�
kRY M. STATUM
** SUMMARY SHEET **
Project: MR. S MRS. RICHARD CHAO Zone: 6
Plan: CUSTOM
Wall Insulation: R-13
Ceiling Insulation: R-19 in True -Sloping / R-30 with Attic above
Raised Floor Insulation: R-19
Slab Edge Insulation: None
Glazing Type: All glass is single pane, except the following,
which is dual:
SKYLIGHTS
Shading Devices: No shading devices required.
Hard Surface Flooring: 1970.0 / 2564.0 total sq. ft.
''
I 3 5� S. COURT: 1885.0 BATH(S): 85.0
11 LAUNDRY: 39.0 ENTRY/FOYER: 346.0
.16 LIBRARY: 262.0 G.HALL: 427.0
HALL(S): 266.0 DINING: 272.0
M. ROOM: 189.0 KITCHEN: 355.0
M. BATH: 292.0 BATH(S); 116.0
Minimum Furnace S.E.: 80.0 AFUE%
Maximum Furnace Bonnet Capacity: N/A BTUH
Minimum A/C S.E.E.R.: 10.0
A/C Tonnage: 25.0
Infiltration: Standard
Minimum R-4.2 insulation required on ducts in unconditioned spaces,
EQUIPMENT SCHEDULE
PROSECT: MR. & MRS. RICHARD CHAD
15 SAILCREST
NEWPORT COAST, CA.
ARCHITECT: DENNIS CHERRY & AS'SOCIATES
20351 IRVINE AVE., #1
SANTA ANA HEIGHTS, CA. 52707
714-641-1505
H. V. A. C.
HEATING: BASEMENT
BRYANT
COMPANY
FURNACE *383KAV036045
* SPORTS
CT.
BRYANT
COMPANY
FURNACE #383KAV060111
FIRST
FLOOR:
BRYANT
COMPANY
FURNACE #383KAV060111
FIRST
FLOOR:
BRYANT
COMPANY
FURNACE #383KAV060111
SECOND
FLOOR:
BRYANT
COMPANY
FURNACE #373LAV060115
MASTER
BED.
BRYANT
COMPANY
FURNACE #373LAV02405O
COOLING: BASEMENT
BRYANT
COMPANY
GOND. #561N036
• SPORTS
CT.
BRYANT
COMPANY
COND. #561N06D
FIRST
FLOOR:
BRYANT
COMPANY
COND. #561N060
FIRST
FLOOR:
BRYANT
COMPANY
COND. #561N060
SECOND
FLOOR:
BRYANT
COMPANY
COND. #561N060
MASTER
BED. .
BRYANT
COMPANY
COND. #561N024
*1005 CFM/HR MINIMUM VENTILATION REQUIRED
WATER HEATER:
AMERICAN STANDARD MODEL (2)#G52-100T88-4NV
CERTIFICATE OF COMPLIANCE: RESIDENTIAL
Page 1
CF -IR
--------------------------------------------------------------------------
Project Title..........
MR. & MRS. RICHARD CHAO
Date........ 08/04/98
Roof
Project Address........
15 SAILCREST
******* ---------------------
R-19
0.051
NEWPORT COAST, CA.
*v4.50* I
I
Documentation Author...
Terry Statum
******* 1 Building Permit
# I
n/a
Aero Energy
1
1
0.330
12711 Newport Ave, Suite
G I Plan Check /
Date 1
R-n/a
Tustin, CA 92780
1
1
n/a
714-505-4207
1 Field Check/
Date I
Climate Zone...........
06
---------------------
R-0
Compliance Method......
MICROPAS4 v4.50 for 1995
Standards by Enercomp,
Inc.
1 MICROPAS4 v4.50
File-CHAO Wth-CTZ06S92
Program -FORM CF -IR
I
User#-MP1751
-------------------------------------------------------------------------------
User -Aero Energy Run -MR.
& MRS. RICHARD CHAO
I
GENERAL INFORMATION
-------------------
Conditioned Floor Area.....
Building Type ..............
Construction Type .........
Building Front Orientation.
Number of Dwelling Units...
Number of Stories..........
Floor Construction Type....
Glazing Percentage.........
Average Glazing U -value....
Component
Frame
Type
------------
Type
-------
Wall
n/a
11540 of
Single Family Detached
New
Front Facing 90 deg (E)
1
3
Slab On Grade
13.9 % of floor area
0.94 Btu/hr-af-F
BUILDING SHELL INSULATION
Cavity Sheathing Insul Assembly
R -value R -value R -value U -value Location/Comments___
R-13 R-n/a R-13 0.088
Wall n/a R-0 R-n/a R-0 0.190
Roof
n/a
R-30
R-n/a
R-30
0.031
Roof
n/a
R-19
R-n/a
R-19
0.051
F1oorExt
n/a
R-19
R-n/a
R-19
0.048
Door
n/a
R-0
R-n/a
R -O
0.330
SlabEdge
n/a
R -O
R-n/a
R-0
0.900
SlabEdge
n/a
R -O
R-n/a
R -O
0.720
SlabEdge
n/a
R-0
R-n/a
R -O
0.550
SlabEdge
n/a
R-0
R-n/a
R-0
0.500
Front 2x4 Wall
Left 2x4 Wall
Gar. 2x4 Wall
Back 2x4 Wall
Right 2x4 Wall
Front B1k.Wall
Left B1k.Wall
Back B1k.Wall
Right B1k.Wall
Vented Attic
Vaulted Roof
Over Garage
Over Outside
Garage Door
Back Door
Exp to Outside
Cvd to Outside
Exp. to Garage
Cvd. to Garage
CERTIFICATE OF COMPLIANCE: RESIDENTIAL Page 2 CF -IR
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 08/04/98
I MICROPAS4 v4.50 File-CHAO Wth-CT206S92 Program -FORM CF -IR I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
FENESTRATION
# of
Interior
Over -
Area
U-
Pan-
Shading/
Exterior
hang/
Framing
Orientation
(sf)
Value
es
Description
Shading
Fins
----
Type
---------
-------------------
Window
Front
(E)
-----
60.0
-----
0.920
----
1
---------------
CEC
Std.
-----------
None
None
WoodDiv
Door
Front
(E)
128.0
0.990
1
CEC
Std.
None
None
Wood
Door
Front
(E)
72.0
0.990
1
CEC
Std.
None
None
Wood
Window
Front
(E)
33.3
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Front
(E)
8.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Front
(E)
24.0
0.920
1
GEC
Std.
None
None
WoodDiv
Window
Left
(S)
16.0
1.040
1
CEG
Std.
None
None
WoodDiv
Window
Left
(S)
66.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
31.5
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
36.0
0.600
2
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
18.0
0.570
2
CEC
Std.
None
None
WoodDiv
Door
Left
(S)
20.0
0.990
1
CEC
Std.
None
None
Wood
Window
Left
(S)
14.0
1.040
1
CEC
Std.
None
None
WoodDiv
Windov
Left
(S)
18.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Left
(S)
16.5
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
3.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
24.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
8.0
1.040
1
CEC
Std,
None
None
WoodDiv
Door
Back
(W)
162.0
0.990
1
CEC
Std,
None
None
Wood
Window
Back
(W)
57.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
45.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
30.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
33.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
22.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
35.0
0.920
1
CEC
Std.
None
None
WoodDiv
Window
Back
(W)
66.0
0.920
1
CEC
Std.
None
None
WoodDiv
Door
Back
(W)
37.5
0.990
1
CEC
Std.
None
None
Wood
Window
Back
(W)
15.0
1.040
1
CEC
Std.
None
None
WoodDiv
Door
Back
(W)
22.5
0.990
1
CEC
Std.
None
None
Wood
Window
Back
(W)
22.0
0.920
1
CEC
Std,
None
None
WoodDiv
Window
Right
(N)
40.5
0.920
1
CEC
Std,
None
None
WoodDiv
Door
Right
(N)
63.0
0.990
1
CEC
Std.
None
None
Wood
Door
Right
(N)
41.0
0.990
1
CEC
Std.
None
None
Wood
Window
Right
(N)
75.0
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Right
(N)
95.0
0.920
1
GEC
Std.
None
None
WoodDiv
Window
Right
(N)
16.5
1.040
1
CEC
Std.
None
None
WoodDiv
Window
Right
(N)
76.8
0.920
1
CEC
Std.
None
None
WoodDiv
Skylight
Front
(E)
8.4
0.470
2
CEC
Std.
Tinted
Glas
None
Metal
Skylight
Left
(S)
25.8
0.470
2
CEC:
Std.
Tinted
Glas
None
Metal
Skylight
Back
(W)
4.2
0.470
2
CEC
Std.
Tinted
Glas
None
Metal
Skylight
Right
(N)
17.4
0.470
2
CEC
Std.
Tinted
Glas
None
Metal
CERTIFICATE OF COMPLIANCE: RESIDENTIAL
Page 3 CF -1R
----------------------------------------------------------
Project Title..........
MR. & MRS.
RICHARD
CHAO
Date........ 08/04/98
I MICROPAS4
v4.50 File -CHAD
Wth-CT20GS92
Program -FORM CF-iR I
1 User#-MP1751
-------------------------------------------------------------------------------
User -Aero
Energy
Run -MR.
& MRS. RICHARD CHAD I
THERMAL
MASS
------------
Area Thickness
Type
------------
Exposed
-------------- ------
(sf)
---------
(in)
Location/Comments
------------------------
S1abOnGrade
Yes
1970
3.5
Exposed Concrete Slab
S1abOnGrade
No
1226
3.5
Covered Concrete Slab
InteriorHorz
Yes
40
4.0
Brick/Masonry (Harz.)
InteriorVert
Yes
35
4.0
Brick/Masonry (Vert.)
InteriorVert
Yes
3417
8.0
Exposed 8 in. Block
InteriorHorz
Yes
322
1.0
Ceramic Tile (Harz.)
InteriorVert
Yea
290
1.0
Ceramic Tile (Vert.)
InteriorHorz
Yes
2564
0.6
Exposed Lt.Wt. Conc.Slab
InteriorHorz
No
5780
0.8
Covered Lt.Wt. Conc.Slab
Equipment Type
---------------
Gas
AirCond
HVAC SYSTEMS
Minimum Duct Duct Thermostat
Efficiency Location R -value Type
------------ -------------------- ------------
0.600 AFUE Attic R-4.2 Setback
10.00 SEER Attic R-4.2 Setback
WATER HEATING SYSTEMS
---------------------
Number
in
Tank Type Heater Type Distribution Type System
------------ ----------- ------------------- ------
Storage Gas Recirc/TimeTemp 2
SPECIAL FEATURES/REMARKS
Tank External
Energy Size Insulation
Factor (gal) R -value
-------- ------ ----------
.44 EF 100 R-12
1) The water heaters specified will require an external
insulation blanket of R-12 or greater.
2) The water heaters for this house will require a recirculation
pump with a time clock - temp controller.
3) The water heaters shall be: (2) American #G52-10OT88-4NV
CERTIFICATE OF COMPLIANCE: RESIDENTIAL Page 4 CF -IR
------------------=--------------------
__________________________________
Project Title.......... MR. & MRS. RICHARD CHAO Date........ 06/04/98
1 MICROPAS4 v4.50 File -CHAD Wth-CT206S92 Program -FORM CF -1R I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
COMPLIANCE STATEMENT
--------------------
This certificate of compliance lists the building features and performance
specifications needed to comply with Title -24, Parts 1 and 6 of the
California Code of Regulations, and the administrative regulations to
implement them. This certificate has been signed by the individual with
overall design responsibility. When this certificate of compliance is
submitted for a single building plan to be built in multiple orientations,
any shading feature that is varied is indicated in the Special Features/
Remarks section.
DESIGNER or OWNER
Name.... DENNIS CHERRY
Company. DENNIS CHERRY & ASSOC.
Address. 20351 IRVINE AVE., #1
SANTA ANA HTS., CA. 92707
Phone... 714-641-1505
License.
Signed..
(date)
ENFORCEMENT AGENCY
Name....
Title.. .
Agency..
Phone...
Signed..
(date)
DOCUMENTATION AUTHOR
Name.... Terry Statum
Company. Aero Energy
Address. 12711 Newport Ave, Suite G
Tustin, CA 92780
Phone... 714-505-4207 /
Signed.
(date)
MANDATORY MEASURES CHECKLIST: RESIDENTIAL W -1R
Note: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance
approach used. Items marked with an asterisk (•) may be superseded by more stringent compliance requirements
listed on the Certificate of Compliance. When this checklist is incorporated into the permit documents, the features
noted shall be considered by all parties as binding minimum component performance specifications for the
mandatory measures whether they are shown elsewhere in the documents or on this checklist only.
Instructions: Check or initial applicable boxes when completed or enter N/A if not applicable.
DESCRIPTION
Building Envelope Measures:
• ¢150(a): Minimum R-19 ceiling insulation.
✓
1150(b): Inose fill insulation manufacturer's labeled R -Value.
• §I Wc): Minimum R-13 wall insulation in wood famed walls or equivalent U -value in metal frame walls
(does not apply to exterior mass walls).
• 1150(d): Minimum R-13 raised floor insulation in framed floors; minimum R-8 in raised emhcrete floors.
1150(l): Slab edge insulation - water absorption rue an greater than 0.3% water vapor transmission rate
O/A
no greater than 2.0 punch.
¢l I8: Insulation specified or installed meets insulation quality standards. Indicate type and form.
¢11 .17: Fenestration Products, Exterior Doors, and Infiltruion/Exfilintion Controls
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
2. Manufactured fenestration products have label with certified U -value, and infiltration certification.
✓
_ 3. Exterior doors and windows weuhersttipped; all joints and persetritiont caulked and sealed.
1150(8): Vapor barriers mandatory in Climate Zones 14 and 16 only.
¢150(f): Special infiltration barrier installed to comply with § 151 meets Commission quality standards.
P
_ 1150(e): Installation of Fireplaces, Decorative Gas Appliances and Gras Logs.
1. Masonry and factory -built fireplaces have:
a Closeable metal or glass door
b. Outside air intake with damper and control
a Flue damper and control
2. No continuous burning gas pilot lights allowed.
Space Conditioning, Water Heating and Plumbin S stem Measures:
§110.13: HVAC equipment, water heaters, showerheads and faucets certified by the Commission.
we
§150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA or RCCA.
1150(1): Setback thermostat on cal applicable heating and/or cooling systems.
./
115K): Pipe and tank insulation
1. First 5 feet of pipes closest to water heater tank, nontecirculating systems, insulated (R4 or greater)
2. Back-up tanks for solar system, unfired storage tanks, or other indirect hot water tanks have R-12
coma] insulation or R-16 combined intema /externN insulation.
✓
3. All buried or exposed piping insulated in recirculating sections of hot water systems.
4. Cooling system piping below 550 F insulated.
5. Piping insulated between heating source and indirect hot water tank.
• ¢ 150(m): Ducts and Fans
1. Ducts constructed, installed and sealed to comply with UMC sections 601 and 603; ducts insulated to a
minimum installed R4.2 or duan enclosed entirely within conditioned space.
2. Exhaust fan systems have beck draft or autonomic dampers.
3. Gravity ventilating systems serving conditioned space have either automatic or readily accessible,
manually operated dampers.
¢I Id,: Pool and Spa Heating systems and Equipment.
1. System is certified with 78% dhemsl efficiency, mhoff switch, weatherproof operating
Stanucuom, no electric resistance heating and no pilot light.
2. System is installed with:
Vol
a At lean 36" of pipe between filter and heater for future solar heating.
Ill. Cava for outdoor pools or outdoor spas.
3. Pool ayatwh has directional inlets and a circulation pump that switch.
¢115: Got feed central furnaces, pool hewers, spa beaters or household cooking appliances have no
✓
continuously burning pilot light. (Exception: Nondeeeial cooking appliances whir pilot < ISO BuJlu)
tlnlz Measures:
¢ I50(k): 40 lumens/waa m gnome, for genal lighting in kltehem and mans with water closets; and
✓
reomaed calling fixtures we IC (insulation cover)
Revised March 1,19%
COMPUTER METHOD SUMMARY Page 1 C -2R
-------------------------------------------------------------------------------
Project Title.......... MR. & MRS. RICHARD CHAO Date........ 08/04/98
Project Address........ 15 SAILCREST ******* ---------------------
NEWPORT COAST, CA. *v4.50* I I
Documentation Author... Terry Statum ******* I Building Permit # I
Aero Energy 1 1
12711 Newport Ave, Suite G I Plan Check / Date I
Tustin, CA 92780 1 1
714-505-4207 1 Field Check/ Date I
Climate Zone........... 06 ---------------------
Compliance Method...... MICROPAS4 v4.50 for 1995 Standards by Enercomp, Inc.
--------------------------------------------- -- -
I MICROPAS4 v4.50 File-CHAO Wth-CTZ0GS92 Program -FORM C -2R I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAD I
-------------------------------------------------------------------------------
----------------------------
----------------------------
MICROPAS4 ENERGY USE SUMMARY
= Energy Use
Standard
Proposed
Compliance =
_ (kBtu/s£-yr)
- ----------
Design
Design
----------
Margin =
---------- -
-----------------------
- Space Heating..........
4.32
4.92
-0.60 =
= Space Cooling..........
2.83
0.37
2.46 =
= Water Heating..........
2.26
3.49
-1.23 =
= Total
9.41
8.78
0.63 =
_ *** Building complies
with Computer
Performance
GENERAL INFORMATION
Conditioned Floor Area.....
Building Type ..............
Construction Type .........
Building Front Orientation.
Number of Dwelling Units...
Number of Building Stories.
Weather Data Type..........
Floor Construction Type....
Number of Building Zones...
Conditioned Volume.........
Footprint Area .............
Ground Floor Area..........
Slab -On -Grade Area.........
Glazing Percentage.........
Average Glazing U -value....
Average Ceiling Height.....
11540 of
Single Family Detached
New
Front Facing 90 deg (E)
1
3
ReducedYear
Slab On Grade
1
126940 cf
5268 sf
3196 sf
3196 sf
13.9 % of floor area
0.94 Btu/hr-ef-F
11 ft
COMPUTER METHOD SUMMARY Page 2 C -2R
------------------------------------------------------
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 08/04/98
-------------------------------------------------------------
I MICROPA'34 v4.50 File -CHAD Wth-CTZ06S92 Program -FORM C -2R I
i User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
BUILDING ZONE INFORMATION
OPAQUE SURFACES
Floor
# of
U-
Vent
Special
Area
Volume Dwell
Cond- Thermostat
Height
Vent Area
Zone Type
(sf)
---------
(c£) Units
--------- -----
itioned Type
-------------------
(ft)
------
(s£)
---------
--------------
HOUSE
HOUSE
Shading/
Surface
(s1)
es
Residence
11540
126940 1.00
Yes Setback
8.0
n/a
OPAQUE SURFACES
PERIMETER LOSSES
Length
Area
U-
Insul
Act
Solar
Form 3
Location/
Surface
--------------
(sf)
------
value
-----
R-val
-----
Azm
---
Tilt
----
Gains
-----
Reference
------------
Comments
----------------
HOUSE
Shading/
Surface
(s1)
es
17 S1ahEdge
196
0.900
R -O
1
Wall
1835
0.088
13
90
90
Yes
None
Front 2x4 Wall
2
Wall
1100
0.190
0
90
90
Yes
None
Front B1k.Wall
3
Wall
1714
0.088
13
180
90
Yes
None
Left 2x4 Wall
4
Wall
882
0.190
0
180
90
Yes
None
Left B1k.Wall
5
Wall
498
0.088
13
180
90
No
None
Gar. 2x4 Wall
6
Wall
1481
0.088
13
270
90
Yes
None
Back 2x4 Wall
7
Wall
827
0.190
0
270
90
Yes
None
Back B1k.Well
8
Wall
27
0.088
13
270
90
No
None
Gar. 2x4 Wall
9
Wall
1785
0.088
13
0
90
Yes
None
Right 2x4 Wall
10
Wall
1044
0.190
0
0
90
Yes
None
Right B1k.Wall
11
Roof
5375
0.031
30
n/a
0
Yes
None
Vented Attic
12
Roof
150
0.051
19
0
27
Yes
None
Vaulted Roof
13
F1oorExt
1910
0.048
19
n/a
0
No
None
Over Garage
14
F1oorExt
162
0.048
19
n/a
0
No
None
Over Outside
15
Door
24
0.330
0
90
90
No
None
Garage Door
16
Door
24
0.330
0
270
90
Yes
None
Back Door
PERIMETER LOSSES
FENESTRATION SURFACES
Length
F2
Insul
Solar
Surface
(ft)
Factor
R-val
-------
Gains
-----
Location/Comments
----------------------
Frame
Open
------------
HOUSE
------
--------
Int
Shading/
Surface
(s1)
es
17 S1ahEdge
196
0.900
R -O
No
Exp
to
Outside
18 S1abEdge
69
0.720
R-0
No
Cvd
to
Outside
19 S1abEdge
17
0.550
R-0
No
Exp.
to
Garage
20 S1abEdge
45
0.500
R-0
No
Cvd.
to
Garage
FENESTRATION SURFACES
4 of
Vent
SC
SC
Interior
Area
Pan-
Frame
Open
U-
Act
Glass
Int
Shading/
Surface
(s1)
es
Type
Type
value
-----
Azm
---
Tit
---
Only
----
Shade
----
Description
---------------
-----------
HOUSE
-----
----
---------
------
I Window
60.0
1
WoodDiv
Slider
0.920
90
90
1.00
0.78
CEC Std.
2 Door
128.0
1
Wood
Slider
0.990
90
90
1.00
0.78
CEC Std.
3 Door
72.0
1
Wood
Slider
0.990
90
90
1.00
0.78
CEC Std.
4 Window
33.3
1
WoodDiv
Slider
1.040
90
90
1.00
0.78
GEC: Std.
COMPUTER METHOD SUMMARY Page 3 C -2R
-------------------------------- - -- --
Project Title.......... MR. & MRS. RICHARD CHAD Date........ 08/04/98
I MICROPAS4 v4.50 File-CHAO Wth-CT20GS92 Program -FORM C -2R I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
FENESTRATION SURFACES
---------------------
Surface
------------
HOUSE
38 Skylight
39 Skylight
40 Skylight
41 Skylight
Vent
Open
Type
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
U- Act
value Azm Tlt
1.040
0.920
1.040
0.920
1.040
0.600
0.570
0.990
1.040
0.920
0.920
0.920
0.920
1.040
0.990
0.920
1.040
0.920
1.040
0.920
0.920
0.920
0.990
1.040
0.990
0.920
0.920
0.990
0.990
1,040
0.920
1.040
0.920
0.470
0.470
0.470
0.470
SC SC Interior
Glass Int Shading/
Only Shade Description
---- ---- ---------------
90
90
1.00
# of
CEC
Std.
90
Area
Pan-
Frame
Surface
(sf)
es
Type
5
Window
8.0
1
WoodDiv
6
Window
24.0
1
WoodDiv
7
Window
16.0
1
WoodDiv
8
Window
66.0
1
WoodDiv
9
Window
31.5
1
WoodDiv
10
Window
36.0
2
WoodDiv
11
Window
18.0
2
WoodDiv
12
Door
20.0
1
Wood
13
Window
14.0
1
WoodDiv
14
Window
18.0
1
WoodDiv
15
Window
16.5
1
WoodDiv
16
Window
3.0
1
WoodDiv
17
Window
24.0
1
WoodDiv
18
Window
8.0
1
WoodDiv
19
Door
162.0
1
Wood
20
Window
57.0
1
WoodDiv
21
Window
45.0
1
WoodDiv
22
Window
30.0
1
WoodDiv
23
Window
33.0
1
WoodDiv
24
Window
22.0
1
WoodDiv
25
Window
35.0
1
WoodDiv
26
Window
66.0
1
WoodDiv
27
Door
37.5
1
Wood
28
Window
15.0
1
WoodDiv
29
Door
22.5
1
Wood
30
Window
22.0
1
WoodDiv
31
Window
40.5
1
WoodDiv
32
Door
63.0
1
Wood
33
Door
41.0
1
Wood
34
Window
75.0
1
WoodDiv
35
Window
95.0
1
WoodDiv
36
Window
16.5
1
WoodDiv
37
Window
76.8
1
WoodDiv
38
Skylight
8.4
2
Metal
39
Skylight
25.8
2
Metal
40
Skylight
4.2
2
Metal
41
Skylight
17.4
2
Metal
Surface
------------
HOUSE
38 Skylight
39 Skylight
40 Skylight
41 Skylight
Vent
Open
Type
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
Slider
U- Act
value Azm Tlt
1.040
0.920
1.040
0.920
1.040
0.600
0.570
0.990
1.040
0.920
0.920
0.920
0.920
1.040
0.990
0.920
1.040
0.920
1.040
0.920
0.920
0.920
0.990
1.040
0.990
0.920
0.920
0.990
0.990
1,040
0.920
1.040
0.920
0.470
0.470
0.470
0.470
SC SC Interior
Glass Int Shading/
Only Shade Description
---- ---- ---------------
90
90
1.00
0.78
CEC
Std.
90
90
1.00
0.78
CEC
Std.
180
90
1.00
0.78
CEC
Std.
180
90
1.00
0.78
CEC
Std.
180
90
1.00
0.78
CEC
Std.
180
90
0.88
0.78
CEC
Std.
180
90
0.88
0.78
CEC
Std.
180
90
1.00
0.78
CEC
Std.
180
90
1.00
0.78
CEC
Std.
180
90
1.00
0.78
CEC
Std.
180
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.76
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
270
90
1.00
0.78
CEC
Std.
0
90
1.00
0.78
CEC
Std.
0
90
1.00
0.78
CEC
Std.
0
90
1.00
0.78
CEC
Std.
0
90
1.00
0.78
CEC
Std.
0
90
1.00
0.78
CEC
Std.
0
90
1.00
0.78
CEC
Std.
0
90
1.00
0.78
CEC
Std.
90
27
0.82
1.00
CEC
Std.
180
27
0.82
1.00
CEC
Std.
270
27
0.82
1.00
CEC
Std.
0
27
0.82
1.00
CEC
Std.
EXTERIOR SHADING
----------------
Area Shading
(sf) Type
8.4 Tinted Glass
25.8 Tinted Glass
4.2 Tinted Glass
17.4 Tinted Glass
SC of
Ext Shade
1.00
1.00
1.00
1.00
COMPUTER METHOD SUMMARY Page 4 C -2R
--------------------------------------------- --
Project Title.......... MR. & MRS. RICHARD CHAO Date........ 08/04/98
MICROPAS4 v4.50 File -CHAD Wth-CT206S92 Program -FORM C -2R I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
THERMAL MASS
SPECIAL FEATURES/REMARKS
------------------------
1) The water heaters specified will require an external
insulation blanket of R-12 or greater.
2) The water heaters for this house will require a recirculation
pump with a time clock - temp. controller.
3) The water heaters shall be: (2) American #G52-lOOT88-4NV
Area
Thick Heat Conduct-
Surface
Mass Type
---------------
(ef)
------
(in) Cap ivity
----- -------------
R -value
--------
Location/Comments
--------------------------
HOUSE
1
S1abOnGrade
1970
3.5 28.0 0.98
R-0.0
Exposed
Concrete Slab
2
S1abOnGrade
1226
3.5 28.0 0.98
R-2.0
Covered
Concrete Slab
3
InteriorHorz
40
4.0 21.0 0.59
R-0.0
Brick/Masonry (Hort.)
4
InteriorVert
35
4.0 21.0 0.59
R-0.0
Brick/Masonry (Vert.)
5
InteriorVert
3417
8.0 28.0 0.98
R-0.0
Exposed
8 in. Block
6
InteriorHorz
322
1.0 24.0 0.67
R-0.0
Ceramic
Tile (Harz.)
7
InteriorVert
290
1.0 24.0 0.67
R-0.0
Ceramic
Tile (Vert.)
8
Interio•rHorz
2564
0.8 24.0 0.61
R-0.0
Exposed
Lt.Wt. Conc.Slab
9
InteriorHorz
5780
0.8 24.0 0.61
R-2.0
Covered
Lt.Wt. Conc.Slab
HVAC SYSTEMS
------------
Minimum Duct
Duct
Duct
System
----------------
Type
Efficiency Location
-------------------------
R -value
-------
Efficiency
----------
HOUSE
Gas
0.800 AFUE Attic
R-4.2
0.880
AirCond
10.00 SEER Attic
R-4.2
0.870
WATER HEATING SYSTEMS
---------------------
Number
Tank External
in
Energy
Size Insulation
Tank
Type Heater
Type Distribution Type
-------------------
System
------
Factor
--------
(gal) R -value
------ ----------
------------
-----------
1 Storage Gas
Reeirc/TimeTemp
2
.44
100 R-12
SPECIAL FEATURES/REMARKS
------------------------
1) The water heaters specified will require an external
insulation blanket of R-12 or greater.
2) The water heaters for this house will require a recirculation
pump with a time clock - temp. controller.
3) The water heaters shall be: (2) American #G52-lOOT88-4NV
HVAC SIZING Page 1 HVAC
Project Title.......... HOUSE LOADS Date........ 08/04/98
Project Address........ 15 SAILCREST ******* ---------------------
NEWPORT COAST, CA. *v4.50* I I
Documentation. Author... Terry Statum ******* I Building Permit # I
Aero Energy 1 1
12711 Newport Ave, Suite G I Plan Check / Date I
Tustin, CA 92780 1 1
714-505-4207 1 Field Check/ Date I
Climate Zone........... 06 ---------------------
Compliance Method...... MICROPAS4 v4.50 for 1995 Standards by Enercomp, Inc.
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
I MICROPAS4 v4.50 File-CHAOHSE Wth-CTZ0GS92 Program -HVAC SIZING
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAD I
-------------------------------------------------------------------------------
GENERAL INFORMATION
-------------------
Floor Area ................. 9532 sf
Volume ..................... 104852 cf
Front Orientation.......... Front Facing 90 deg (E)
Siding Location............ NEWPORT BEACH
Latitude ................... 33.6 degrees
Winter Outside Design...... 39 F
Winter Inside Design....... 70 F
Summer Outside Design...... 80 F
Summer Inside Design....... 78 F
Summer Range ............... 12 F
Interior Shading Used...... No
Exterior Shading Used...... No
Overhang Shading Used...... No
Latent Load Fraction....... 0.30
HEATING AND COOLING LOAD SUMMARY
--------------------------------
Heating Cooling
Description (Btuh) (Btuh)
-------------------------------------------------------
Opaque Conduction and Solar...... 134194 70014
Glazing Conduction, .............. 46778 3018
Glazing Solar .................... n/a 62146
Infiltration ..................... 55756 1325
Internal Gain .................... n/s 3900
Ducts ............................ 23673 14040
Sensible Load .................... 260403 154442
Latent Load ...................... n/a 46333
----------- -----------
Minimum Total Load 260403 200775
Note: The loads shown are only one of the criteria affecting the selection
of HVAC equipment. Other relevant design factors such as air flow
requirements, outdoor design temperatures, coil sizing, availability of
equipment, oversizing safety margin, etc., must also be considered. It is
the HVAC designer's responsibility to consider all factors when selecting
the HVAC equipment.
HVAC SIZING Page 1 HVAC
------------------
Project Tit.le.......... SPORTS COURT Date........ 08/04/98
Project Address ........ 15 SAILCREST ******* ---------------------
NEWPORT COAST, CA. *v4.50* I I
Documentation Author... Terry Statum xxx*xxx I Building Permit # I
Aero Energy 1 1
12711 Newport Ave, Suite G I Plan Check / Date I
Tustin, CA 92780 1 1
714-505-4207 1 Field Check/ Date I
Climate Zone........... 06 ---------------------
Compliance Method...... MICROPAS4 v4.50 for 1995 Standards by Enercomp, Inc.
1 MICROPAS4 v4.50 File-CHAOSPRT Wth-CTZ06S92 Program -HVAC SIZING I
I User#-MP1751 User -Aero Energy Run -MR. & MRS. RICHARD CHAO I
-------------------------------------------------------------------------------
GENERAL INFORMATION
-------------------
Floor Area ................. 2006 sf
Volume ..................... 40150 cf
Front Orientation.......... Front Facing 90 deg (E)
Sizing Location............ NEWPORT BEACH
Latitude ................... 33.6 degrees
Winter Outside Design...... 39 F
Winter Inside Design....... 70 F
Summer Outside Design...... 80 F
Summer Inside Design....... 78 F
Summer Range ............... 12 F
Interior Shading Used...... No
Exterior Shading Used...... No
Overhang Shading Used...... No
Latent Load Fraction....... 0.30
Description
HEATING AND COOLING LOAD SUMMARY
--------------------------------
Heating
(Btuh)
Opaque Conduction and Solar......
Glaring Conduction ...............
Glazing Solar ....................
Infiltration .....................
Internal Gain ....................
Ducts ............................
20833
0
n/a
21351
n/a
4218
Sensible Load .................... 46402
Cooling
(Btuh)
6451
0
0
507
22500
2946
32405
Latent Load ...................... n/a 9721
----------- -----------
Minimum Total Load 46402 42126
Note: The loads shown are only one of the criteria affecting the selection
of HVAC equipment. Other relevant design factors such as air flow
requirements, outdoor design temperatures, coil sizing, availability of
equipment, oversizing safety margin, etc., must also be considered. It is
the HVAC designer's responsibility to consider all factors when selecting
the HVAC equipment.
MICROPAS4
Table 2-2: Manufactured Fenestration Product Default U -Values
(this table to be used by manufacturer's to establish a U -value rating without performance testing)
Framing Materials
Any Metal Thermal Breaks Non Meta12.3
(Wood, Vinyl or other)
Single Dwble Doable Uwe Dmbte
Operable Windows 1.28 0.87 0.71 0.92 0.60
Fixed Windows 1.19 0.72 0.60 1.04 0.57
Patio Doors 125 0.77 0.68 0.99 0.55
Skylights 126 0.80 0.70 0.91 0.55
Greenhouse Windows 2.26 1.40 1.12 1.94 1.06
For all dual -glazed fenestration products
• Subtract 0.05 for spacers of 7/16" or wider.
• Subtract 0.05 for Low -c glazing.
• Add 0.05 for products with between the panes dividers, if the spacer is less than 7/16" wide.
• Add 0.05 to the U -value of any product with true divided lites [through the pane(s) dividers).
1. The minimum design characteristics to qualify as Thermal -Break Product are:
a. The material used as the thermal -break must have a thermal conductivity of not more am
3.6 BTU-in/hr ft2/°F, and;
b. Thermal -break must produce a gap of not less than 0210", and;
c. All metal members of the product exposed to interior and exterior air must incorporate a thermal -break
meeting the criteria in (1) and (2) above.
In addition, the product must be clearly labeled by the manufactttna that it qualifies as a thermally broken
product in accordance with CEC requirements.
2. Non metal products can include metal fasteners, hardware and door thresholds.
3. Add 0.04 to the listed U -value for any products that have metal cladding in any configuration.
Table 2-3: Site Built Fenestration Product Default U -Values
(this table to be used to establish a U -value rating without performance testing)
Framing Materials
Any Metal, Including Non Metall
Cladding (Wood, Vinyl or other)
Single Double Single Double
Fixed 1.19 0.72 1.04 0.57
Operable 132 0.93 0.99 - 055
1. Non-metal excludes hardware or door thresholds.
2 m 3 2 COMPLIANCE 711592 0 1992 by Eneroamp, Inc.
MICROPA64
2-26: Standard
Single................ ..._._.... ...... .............................
Double............. __....._....................................... .._
the
Figure 2-27: Suggested Names for Interior Shading devices
Desmpdon
Interior Shade
Dmpes.Std
Non-white drapes (CEC Standard for windows
and French doors).
Dtapes.Wht
Drapery with a white or off-white liner
None
No interior drapes (CEC Standard for skylights)
Blinds.Med
Medium Colored venetian blinds
Blinds.Lt
Light-colored venetian blinds
Roller ark
Opaque, dark colored roller blinds
Roller.Wht
Opaque, white interior roller shades
Roller.Lt
Translucent, white roller shades
Special
Interior shade not represented by the types above.
Table 2-7: Shading Coefficients for Interior
Drapery:
Standard ............
white/off-White
Venetian Blinds:
Medium Color
Light Color.....
Roller Shades:
Opaque
Dark .....
White ...
Translucent
Light ....
Devices Alone(ShadesClose )
............. 0.781
............. 0.62
0.63
OS8
0.81
0.402
0.44
1. 0.78 is the default value used when there is no interior shading device installed on
vertical fenestration products.
2. No interior shading device may be given a shading coefficient value lower
than 0.40
Note that the values above are from the row labeled Interior Shade' in Table G-11 a in
the Residential Manual
2"42 COMPLIANCE 711692 01992 by Ene=rnp, Inc.
Table G -I8: Standard U -Values of Wood Frame
Raised Floors
Floor
Ituul.
Condition
Reference
Name2
U -Value
R-03
No C.S.4
FXO.2X6.16
0.239
R-03
With C.S.4
FC0.2X6.16
0.097
R-113
No C.S.
FXI1.2X6.16
0.071
R-113
With C.S.
FC11.2X6.16
0.049
R-13
No C.S.
FX13.2X6.16
0.064
R-13
With C.S.
FC13.2X6.16
0.046
R-19
No C.S.
FX19.2X8.16
048
R- 19
With C.S.
FCl9.2X8.16
=
R-21
No C.S.
FX21.2X8.16
5
R-21
With C.S.
FC21.M.16
0.035
R-30
No C.S.
FX30.2X10.16034
R-30
With C.S.
FC30.2X10.1628
1. Based on ASHRAE Parallel Heat Flow
Calculation, 1989 <ASHRIE Handbook of
Fundamentals.
2. The names given to the standard assemblies used
to calculate these U -values in Appendix H.
3. Does not meet the minimum level required as a
mandatory measure (see Section 2.2).
4. No C.S. = No Crawl Space, With C.S.
With Crawl Space
Table G-19: Standard U -Values of Wood Foam
Panel Roots/Ceilings and Wallsl
Roof/
Ceiling Framing Reference
Irtsul. Spacing Name2 U -Value
R-143 48' o.c. RP.14.2X4.48 0.064
R-22 48' o.c. RP.22.2X6.48 0.044
R-28 48' o.c. RP.28.2X8.48 0.035
R-36 48' o.c. RP.36.2X10.48 0.028
Will Framing Reference
Insul. Spacing Name U -Value
R-14 48' o.c. WP. 14.2X4.48 0.071
R-22 48- o.c. WP.22.2X6.48 0.0-9
1. Based on ASHRAE Parallel Heat Flow
Calculation, 1989 ASHRAE Handbook of
Fundamentals.
2. The names given to the standard assemblies used
to calculate these U -values in Appendix H.
3. Does not meet the minimum level required as a
mandatory measure (see Section 2.2).
Glossary January 1, 1995 G-:5
Table G-16: Standard U -Values of Wood Frame
Roofs and CeRingsl
Ceiling Framing Reference
Insul. Spacing Name2 U -Value
R-03
16' o.c.
R.0.2X6.16
R-03
24' o.c.
R.0.2X4.244
R-113
16' o.c.
R. 11.2X6.16
R-113
24' o.c.
R. 11.2X4.24
R-133
16' o.c.
R. 13.2X6.16
R-133
24' o.c.
R. 13.2X4.24
R-19
16' o.c.
R.19.2X8.16
R-19
24' o.c.
R.19 ZX4.24
R-22
16' o.c.
R.22.2XI0.16
R-22
24' o.c.
R.22.2X4 24
R-30
16" o.c.
R.30.2XI0.16
R-30
16' o.c.
R.30.2X12.16
R-30
24' o.c.
R.30.2X4.24
R-38
16' o.c.
R.38.2X12.16
R-38
16' o.c.
R.38.2X14.16
R-38
24' o.c.
R.38.2X4.24
R-49
16' o.c.
R.49.2X4.16
R-49
24' o.c.
R.24.2X4.24
I. Based on ASHRAE Parallel Heat Flow
Calculation, 1989 A-SHRAE Handiook of
Fundamentals.
2. The names given to the standard assemblies used
to calculate these U -values in Appendix H.
3. Does not meet the minimum level required as a
mandatory measure (see Section 2.2).
4. Roof/ceiling assemblies whose reference names
list 2X4 framing include an attic space.
Table G-17: Standard U -Values of Wood Frame
Wallsl
Wall Framing Reference -
Instd. Spacing Name2 U -Value
R-03
16' o.c.
W.0.2X4.16
aD
R-03
24' 0.0.
W.0.2X4.24
0.393
R-73
16' o.c.
W.7.2X4.16
0.130
R-73
24" o.c.
W.7.2X4.24
0.127
R-113
16' o.c.
W.11.2X4.16
0.098
R-113
24' o.c.
W.11.2X4.24
0.094
R-13
16' o.c.
W.13.2X4.16
R-13
24" O.C.
W. 13.2X
XOS
R-15
16' o.c.
W.15.2X4.16R-15
24' o.c.
W.15.2X4.24
R-19
16' o.c.
W.19.2X6.160.065
R-19
4" o.c.
W. 19.2X6.24
0.063
R-21
16' o.c.
W.21.2X6.16
0.059
R-21
24' o.c.
W.21.2X6.24
�6
R-25
16' o.c.
W.25.2X6.16
0.046
R-29
16' o.c.
W.29.2X4.16
0.035
Solid cote wood D.O.SCW 0.330
door (no insulation)
1. Based on ASHRAE Parallel Heat Flow
Calculation, 1989 ASHRAE Handbook of
Fundamental[.
2. The mimes given to the standard assemblies used
to calculate these U -values in Appendix H.
3. Does not meet the minimum level required as a
mandatory measure (see Section 2.2).
G-54 January 1, 1995 Residential Manual
2.4 LIGHTING MEASURES
Lighting §150(k)
Installing energy-efficient lamps and futures
can reduce lighting energy costs without
sacrificing the quality or quantity of light
available. As indicated in Table 2-5, a 40 watt
standard fluorescent lamp is over four times as
efficient as a 100 watt standard incandescent
lamp.
Kitchen Lighting
Tbe Standards require that general lighting in
kitchens have an efficacy of at least 40 lumens
per wan and be controlled by the most
accessible switch(es) in the kitchen. The light
switch location determines how the occupant
will use the lighting. If more than one set of
light fixtures exist which provide general
lighting, those controlled by the most accesible
switch are considered general lighting.
Luminaries used only for specific decorative
effects (and which are not the only luminaries in
the kitchen) need not meet this requirement.
General lighting is lighting designed to provide
a substantially uniform level of light distribution
throughout a space. Ibis can be achieved by
light futures in the ceiling or around the
perimeter of the room. Lighting futures under
cabinets may meet the general lighting
requirements if they provide uniform light
distribution in the kitchen (see Figure 2-11). A
luminaire which is the only lighting in a kitchen
will be considered general lighting.
Bathroom Lighting
The Standards require that each room
containing a water closet must have at least one
luminaire with lamps with an efficacy of at least
401umenu per wan. As an alternative, this
requirement may be met by installing the high
efficacy luminaire in an adjacent room that has
complementary plumbing futures.
If there is more than one luminaire in the room,
the high -efficacy luminaire must be switched at
an entrance to the room.
General
Luminaries installed to meet the 40 lumens per
watt requirements cannot contain medium base
incandescent lamp sockets, and must be on
separate switches from incandescent lighting.
I Includes power consumed by ballasts where applicable.
2 Halogen capsule incandescent lamps may be the most efficient light source for highlighting applications. Most
balogen lamps are designed to produce a beam of directed light. Manufacturer's data typically list the
•candlepower' intensity of that beam, rather than lumens (lumens measure total light output -in all directions).
The standard halogen capsule lamps will not exceed a maximum of 20 lumeas/watt. A new technology using
infrared reflecting films on the halogen capsules has increased output up to 30 Lumens/watt for some high
wattage lamps.
3 Efficacy of fluorescent lighting varies depending on lamp and ballast types.
Mandatory Measures January 1, 1995 2-17
Table 2.5. Typical Etricacy of Luminaries
Rated Lamp
Typical Efficacy
Light Source
Type
Watts
Lmnens/Wattl
Incandescent
Standard
40-100
14- 18
Halogen
40-250
See Note 2
Fluorescent
Full -Size, 4' Long
32-40
69-913
(Lamp/Ballast
U -Shaped T-8 Bipin
16-31
79-90
Systems)
Compact Fluorescent
5 - 9
26-38
Compact Fluorescent
13 +
42-58
Metal Halide
Metal Halide
32-175
50-90
High Pressure Sodium
White High Pressure Sodium
35-100
36-55
I Includes power consumed by ballasts where applicable.
2 Halogen capsule incandescent lamps may be the most efficient light source for highlighting applications. Most
balogen lamps are designed to produce a beam of directed light. Manufacturer's data typically list the
•candlepower' intensity of that beam, rather than lumens (lumens measure total light output -in all directions).
The standard halogen capsule lamps will not exceed a maximum of 20 lumeas/watt. A new technology using
infrared reflecting films on the halogen capsules has increased output up to 30 Lumens/watt for some high
wattage lamps.
3 Efficacy of fluorescent lighting varies depending on lamp and ballast types.
Mandatory Measures January 1, 1995 2-17
"A" must be fluorescent
A
"A"must be fluorescent
All of "C" must be fluorescent All of "A"or "C" must be fluorescent.
If "C" then "C" must be the most accessible
switch
Figure 2-11: Kitchen Lighting Ezamples
2-18 January 1, 1995 Residential Manual
0
-N-IS :060,
0
A" must be fluorescent
A' or B' must be fluorescent
0
'A' must be fluorescent;
'D' can be incandescent
'B' or 'E' must be fluorescent
Figure 2-12: Bathroom Lighting Examples
Mandatory Measures January 1, 1995 2-19
issoT W,
[Milli
, Ow
i
'B' or 'E' must be fluorescent
Figure 2-12: Bathroom Lighting Examples
Mandatory Measures January 1, 1995 2-19