LIGHTING CONTROL ACCEPTANCE DOCUMENT
Automatic Shut-off Controls: Automatic Time Switch Control and Occupant Sensor
Intent: Lights are turned off or set to a lower level when not needed per Section 110.9(a) & 130.1(c).
A. Construction Inspection
Fill out Section A to cover spaces I through 3 that are functionally tested under Section B.
Instruments needed to perform tests include, but are not limited to: hand-held amperage meter, power meter, or light meter
1: Automatic Time Switch Controls Construction Inspection—confirm for all listed in Section B
a. All automatic time switch controls are programmed for (check all):
i' Weekdays r Weekend r Holidays
b. Document for the owner automatic time switch programming (check all):
F Weekday settings r Weekend settings I— Holidays settings Set-up settings
F Preference program setting F Verify the correct time and date is properly set in the time switch
Verify the battery is installed and energized r- Override time limit is no more than 2 hours
r Occupant Sensors and Automatic Time Switch Controls have been certified to the Energy Commission in accordance with
the applicable provision in Section 110.9 of the Standards, and model numbers for all such controls are listed on the Commission
database as Certified Appliance and Control Devices
2. Occupancy Sensor Construction Inspection—confirm for all listed in Section B
P7 Occupancy sensors are not located within 4 feet of any HVAC diffuser
lu Ultrasonic occupancy sensors do not emit audible sound 5 feet from source
This is page 1 of 23
cxr•Yxa.r�tvzncy�axcxu
B. Functional Testing of Lighting Controls
For every space in the building, conduct functional tests 1 through 5 below if applicable. If there are several geometrically similar spaces
that use the same lighting controls, test only one space and list in the cells below which "untested spaces" are represented by that
tested space. EXCEPTION: For buildings with up to seven (7) occupancy sensors, all occupancy sensors shall be tested. (NA7.6.2.3)
Representative Spaces Selected
Tested space/room name: Esthetician #3
Space Type (office, corridor, etc)
Medical Office
Untested areas/rooms
Confirm compliance for all control system types (1-5) present in each space:
2. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a, All lights can be turned on and off by their respective area control switch r
b. Verify the switch only operates lighting in the ceiling -height partitioned area in
which the switch is located. r -
Step 2: Simulate unoccupied condition
a. All lighting, Including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)l and 130.1(a)i, r
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type) r
_, Step 3:
System returned to initial operating conditions T
2. Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
from start of an unoccupied condition per Standard Section 110.9(b)
b. The occupant sensor does not trigger a false 'onfrom movement in an area
adjacent to the controlled space or from HVAC operation. r.
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly r
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually r
This is page 2 of 23
Step 3:
System returned to initial operating conditions _ r.
gffmmva,
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack. r
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method.
Light level may be used as a proxy for lighting power when measurements are taken r
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition r
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to
70% of the lighting automatically. F
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually
deactivate all of the lights. r
Step 2. Simulate an unoccupied condition
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation.
This is page 3 of 23
5 Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
250 ft , to Qualify for a Dower Adjustment Factor (PAF)
Step 0: First, complete Functional Test 2 (above) for each controlled zone.
Step 1: Verify area served and compare actual PAF with claimed RAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c). r
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces r
f. All steps are conducted in Functional Test 2'Occupancy Sensor (On Off Control)'
and all answers are Yes. r
This is page 4 of 23
1. Automatic Time Switch Controls (all answers must be Yes). r
2. Occupancy Sensor (On Off Control) (all answers must be Yes). r-
3.
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2. r
4. Partial On Occupant Sensor for PAF (all answers must be Yes). 17-
5.
5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must r
pass Test 2.
Representative Spaces Selected
Tested space/room name: Office 2
Space Type (office, corridor, etc) Office
Untested areas/rooms
Confirm compliance for all control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch r
b. Verify the switch only operates lighting in the ceiling -height partitioned area in r
which the switch is located.
Step 2: Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)l. and 130.1(a)1. r
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type). r
Step 3:
System returned to initial operating conditions r
2, Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
This is page 5 of 23
_16.
from start of an unoccupied condition per Standard Section 110.9(b)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. F
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly r
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually
Step 3:
System returned to initial operating conditions
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack. 17-
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method. r,
Light level may be used as a proxy for lighting power when measurements are taken
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to r
70°% of the lighting automatically.
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually i
deactivate all of the lights.
Step 2. simulate an unoccupied condition
This is page 6 of 23
OFACCEPTANCE
At.
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a)
N
h. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
This is page 7 of 23
%Adqtional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
P 1M, Qualify forPower Adjustment Factor't
Step O: First, complete Functional Test 2 (above) for each controlled zone.
Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF -0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c). r-
e.
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces r
f. All steps are conducted in Functional Test 2'Occupancy Sensor (On Off Control)'
and all answers are Yes. r
This is page 8 of 23
ACCEPTANCE
N.. skin
RIBTMZ,I�
1. Automatic Time Switch Controls (all answers must be Yes). r
2. Occupancy Sensor (On Off Control) (ail answers must be Yes).
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2.
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r
5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must
pass Test 2. r
Representative Spaces Selected
"rested space/room name: Esthetician #2
Space Type (office, corridor, etc)
Medical Office
Untested areas/rooms
Confirm compliance for all control system types (1-5) present in each space:
t r t a
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch r
b. Verify the switch only operates lighting in the ceiling -height partitioned area in
which the switch is located. r
Step 2: Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)1 and 130.1(a)l, r
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type). r
Step 3:
System returned to initial operating conditions r-
2.
2. Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
This is page 9 of 23
ACCEPTANCE
;NY�YNyJ4l'11NtiYn9SN;.l
from start of an unoccupied condition per Standard Section 110.9(b)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly r
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually
Step 3:
System returned to initial operating conditions l
'+' MM ' .r ��,
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a) r
J. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack.
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method. f„
Light level may be used as a proxy for lighting power when measurements are taken
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition r�
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between SO to r
70% of the lighting automatically.
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually
deactivate all of the lights. r7 -
Step
Step 2. Simulate an unoccupied condition
This is page 10 of 23
CERTIFICATE OF ACCEPTANCE NRCA-LTI-02-A
Lighting Control
Project Name: skin Bo huge
Enforcement Agency: CITY OF NEWPORT BEACH
N.RNumber: X2019-0083
Project Address: 449 Newpurt Blvd.
City: Newport Beam
IZi, Code: 92663
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a)
r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
This is page 11 of 23
d..r .�a s i;: w,.moi .':• � �:'r. ♦-
1t�0
Step 0: First, complete Functional Test 2 (above) for each controlled zone.
Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
17
b. Enter PAF corresponding to controlled area from line (a) above (<12S ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c). r-
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces r -
f. All steps are conducted in Functional Test 2 'Occupancy Sensor (On Off Control)'
and all answers are Yes. f -
This is page 12 of 23
1. Automatic Time Switch Controls (all answers must be Yes), f.-
2. Occupancy Sensor (On Off Control) (all answers must be Yes). r
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2. r
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r
5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must
pass Test 2. r
Representative Spaces Selected
Tested space/room name: Reception
Space Type (office, corridor, etc)
Medical Office
Untested areas/rooms Treatment Rm. 1, 2, 3, 4, Kitchen , Office
Confirm compliance for ail control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch
It. Verify the switch only operates lighting in the ceiling -height partitioned area in
which the switch is located. r
Step 2: Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)1 and 130.1(a)1. F -
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type). r
Step 3:
System returned to initial operating conditions r
2. Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes r
This is page 13 of 23
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly r_
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually r
Step 3:
System returned to initial operating conditions r
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack.
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells In which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method.
Light level may be used as a proxy for lighting power when measurements are taken
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled r -
Step
Immediately upon an occupied condition J
r r r
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to
70% of the lighting automatically.
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually
deactivate all of the lights. r
Step 2. Simulate an unoccupied condition
This is page 14 of 23
166WA
Code: 92663
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(x)
A
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. F
This is page 15 of 23
Ad(:qtional test for•: ♦.. .. as � • . • Spaces
1 • !1 • .: I• • Adjustment ,,.
Step 0: First, complete Functional Test 2 (above) for each controlled zone.
Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from fine (a) above (<125 ft2 for
PAF -0.4, 126-250 ft2 for PAF= 0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c).
e. Sensors shall not trigger in response to movement in adjacent walkways of
workspaces 1•-
f. All steps are conducted in Functional Test 2'Occupancy Sensor (On Off Control)'
and all answers are Yes.
This is page 16 of 23
OFACCEPTANCE
C. Testing Results
1. Automatic Time Switch Controls (all answers must be Yes). r
2. Occupancy Sensor (On Off Control) (all answers must be Yes). r
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2. r
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r
5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must
pass Test 2. r
Representative Spaces Selected
Tested space/room name: Esthetician #1
Space Type (office, corridor, etc) Medical Office
Untested areas/rooms
Confirm compliance for ail control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch r
b. Verify the switch only operates lighting in the ceiling -height partitioned area in
which the switch is located. r
Step 2: Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)1 and 130.1(a)1, r
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type). r
Step 3:
System returned to initial operating conditions r
2. Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
This is page 17 of 23
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. P
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly r
b, Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually 7r -
Step
3:
System returned to initial operating conditions I
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack, r
c In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method. rLight level may be used as a proxy for lighting power when measurements are taken
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to
70% of the lighting automatically. F
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually r,
deactivate all of the lights,
Step 2. Simulate an unoccupied condition
This is page 18 of 23
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a)
r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
This is page 19 of 23
AdVional test forOccupancy Sensorsr. Small Zones Office Spaces
( to Qualify forPower Adjustment Factor• t
Step 0: First, complete Functional Test 2 (above) for each controlled zone.
Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAP corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF -0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c), r-
e.
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces
f. All steps are conducted in Functional Test 2'Occupancy Sensor (On Off Control)'
and all answers are Yes. r
This is page 20 of 23
Y
1. Automatic Time Switch Controls (all answers must be Yes). T-
2.
2. Occupancy Sensor (On Off Control) (all answers must be Yes). r
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2.
4. Partial On Occupant Sensor for PAF (all answers must be Yes).
5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must
pass Test 2.
®. Evaluation
P- PASS: All applicable Construction Inspection responses are complete and all applicable
Equipment Testing Requirements responses are positive.
This is page 21 of 23
BEACH
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Acceptance doelimentation Is good, ste and complete.
Documentation Author Tom Blanchard Company Name
Name
Address 2546 N Berkeley St City
Zip Code 92665
CEA/ATT Certification TC -A819250
Id entifica ti
a pplicab e ( /�►���\\
V r 1
Date of Signature: 03/15/2919
Phone
Author Signature
1st l'itle 24 Testing
Orange
(714)334-3383
WIELD TECHNICIAN'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Acceptance is true and correct.
2. 1 am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). -
3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and
specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference
Nonresidential Appendix NA7.
0. 1 have confirmed that the Cat tlficate(s) of Installation for [he construction or installation identified on this Certificate of Acceptance has been completed and
signed by the responsible build,/installer and has been posted or made available with the building permit(,) issued for the building.
Rend Ischnnclan Name Company Name
"fom Blanchard list Title 24 Testing
Address: 2546 N Berkeley St
City
Orange
Zip Code 92865 Phone (714)334-3383
ATT Certification Position with Company
Identification T— A81;210 (Title, C'
Field Tech n ignatu
Date of Signature: 93/15/2919
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this
Certificate Of Acceptance.
2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system resign, c.O t, O,tion
or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the
declarations in this statement (responsible acceptance person).
3. The infornatlon provided on this Certificate of Acceptance subOtantlatas that the construction or Installation Identified on this Certiflcate of Acceptance complies
with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance
requirements and procedures specified in Reference Nonresidential Appendix NA7.
4, 1 have confirmed that the Certificate(,) of Installation far the construction or Installation identified on this Certificate of Aeceptance has been completed and e
posted or made available with the building permits) issued for the building.
5. 1 will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permlt(s) Issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is
required to be Included with the documentation the builder provides to the building owner at occupancy.
Responsible Acceptance Company Name
Tom Blanchard 1st Title 24 Testing
Person Name
Address: City
2546 N Berkeley St Orange
Zip Code 92865 Phone (714)334-3383
CSLB License Position with Company
822811 (Title) Owner
Responsl n Signature
Date ofSIgnatu e. 03/t5/2019
This is page 22 of 23
This is page 23 of 23