SPECIAL INSPECTION REPORT
Project Address: Miller Residence, 2006 Leeward, Newport Beach
Permit Number: S2018-0216
Inspection Type (s): Reinforced Concrete
Inspection Date (s):01111/2019
EJPeriodic MContinuous
Observed the placement and consolidation of 38 cubic yards of 4500 psi Shotcrete, Cemex mix design
#1419319 at pool and spa. All rebar and hardware was securely tied in place at time of pour, and all
required clearances and coverages were maintained.
as
two 6"x12" cylinders were taken from load 1 ticket #28188592 Slump = 2" Concrete temperature = 72 F
77' fi. 7777777777,',7711'A-
01/11/2019 '' .., Totaf,IbspYtt(oti;'[IIi.O SackDa ,
01/11/2019
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
51" bff.Pe WM.Ift OW25/2015
01/11/2019
Christopher J. Whelan
NB -0661
51" bff.Pe WM.Ift OW25/2015
Continuous Inspection & Materials Testing
SOUTHWEST 0000000000000®O
Inspection & Testing, Inc. 441 Commercial Way, La Habra, CA 90631-6168
(562)941-2990 - (714)526-8441
FAX (562)946-0026
SAMPLE IDENTIFICATION:
FIELD DATA ON TEST SPECIMENS
DOTOW
AGE DAYS:
28+
,2006 / CCW0rd `n
--- ASTM
C31, C138, C143, C172, C173, C231,
C1064 - --
CONCRETE: MORTAR: SHOTCRETE: X CORES:
GUNITE:
ADDRESS: 2006 LEEWARD, NEWPORT BEACH JOB #:
DATE: 04/12/2019
JOB NAME: MILLER RESIDENCE
PERMIT M S2018-0216
ISSUED BY: NEWPORT BEACH
ARCHITECT:
ENGINEER: POOL ENGINEERING
INC.
CONTRACTOR: MATA
SUB:
HEIGHT -DIAMETER RATIO:
LOCATION IN STRUCTURE: POOL
AND SPA
CORRECTION FACTOR:
TRACT:
PHASE:
LOT #:
CONCRETE SUPPLIER: CEMEX
PLANT: 4486A
MIX #: 1419319
TYPE OF CEMENT:
ADMIXTURE:
TICKET M 28188592
SLUMP: 2.00 in.
WATER ADDED: 0 gal.
AIR TEMP: 62 F
CONCRETE TEMP: 72 F
MIXING TIME:
TIME CAST: 13:35
DATE CAST: 01/11/2019
RECEIVED AT LAB: 04/01/2019
SPECIMENS MADE BY:
SPECIFIED PSI @ 28 Days: 4500
LAB M 138106
CLIENT: CHRIS WHELAN INSPECTIONS
TESTING INFORMATION:
SAMPLE IDENTIFICATION:
1811756
1811757
AGE DAYS:
28+
28+
DATE TEST:
04/02/2019
04/02/2019
SIZE (in.): Height X Diameter
12.000 X 6.000
12.000 X 6.000
AREA (in.A2):
28.27
28.27
CRUSH LOAD (lbs.):
204590
202580
COMPRESSIVE STRENGTH (psi.):
7240
7170
HEIGHT -DIAMETER RATIO:
CORRECTION FACTOR:
CORRECTED STRENGTH (psi.):
BREAK TYPE:
III
I
C.T.M. USED:
BK
BK
REMARKS:_ ( OVER 28 DAYS)
ASTM C39, C174, C192, C470, C617, C42
COMPLIES: X DOES NOT COMPLY: FOR INFORMATION:
THIS REPORT SHALL NOT BE REPRODUCED, EXCEPT IN FULL, WITHOUT THE APPROVAL OF SOUTHWEST INSPECTION AND TESTING, INC.
SAMPLES CAST BY OTHERS:
NOTICE:These test results are from samples cast by inspectors
or technicians not employed by our firm. They were
either delivered to our laboratory or picked up by our
driver. We will accept no responsibility for the inspection
made on the jobsite by the inspector, furthermore we
do not take responsibility for any information on this
report other than the strength as tested and reported.
ASTM C39 BREAKS: 1=CONE - 11=CONE AND SPLIT -
RESPECTFULLY SUBMITTED
SOUTHWEST INSPECTION AND TESTING
ZAFAR AHMED
PRINCIPAL EN R
111=COLUMNAR - IV=SHEAR - V=SIDE FRACTURES - VI=POINTED
W/9 OV
20061-eeworj Zrl
19/080
CHRISTOPHER JEAN & ASSOCIATES, INC.
ACOUSTICAL CONSULTING SERVICES
May 2, 2019 Business License: #BT30044674
MR. JESUS MARTINEZ
MATA CONSTRUCTION
910 E. 4th Street
Santa Ana, California 92704
SUBJECT: RESULTS OF ACOUSTICAL CERTIFICATION MEASUREMENT
FOR 2006 LEEWARD LANE -- CITY OF NEWPORT BEACH
Dear Mr. Martinez:
We are pleased to inform you that the pool equipment installation located at 2006
Leeward Lane in the City of Newport Beach complies with the City's 55 dBA noise limit. No
additional noise mitigation is necessary.
The installation was measured on Thursday, May 2, 2019, using a Larson Davis Model
700 Type 2 Sound Level Meter. The installation was observed to consist of one Jandy E -Pump
variable speed pump, one Jandy Stealth pump, and a Jandy JXi heater, all located in a side yard
setback. The measurement microphone was placed just over the top of the nearest property line
wall directly opposite the pool equipment. The measurement reported a level of 52 dBA for both
pumps and the heater operating simultaneously. This level complies with the City's 55 dBA
noise limit.
Thank you, and if there are any questions, please do not hesitate to call.