City of Newport Beach Special Inspector Manual Contractor: United Construction
Sub -contractor: FS Construction
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive I P.O. Box 1768 i Newport Beach, CA 92658
www.newportbeachca.gov i (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address: Speaker Residence -2632 Basswood St.
Permit Number: X2019-1607 _
Inspection Type (s): Epoxy
Inspection Date (s): 6/5/2019 (x ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
-Observed epoxy placement of #5 rebar dowels into existing grade beam for
new osts atool house with -_8"embedment length pe_r plan page S2 details--
8/SD-1 and 16/SD-1.
.List Tests Made:
Total Inspection Time Each Day: I-
Date: 6/5/2019
Hours: " 4
List: All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
-Rebar free from rust and deleterious materials.
All holes wire brushed and blown cleannprior to epoxy placement____---_„
Sim son Set XP -22N: 1000031146 Exp: 2/16/2021
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
49 ecial Inspector Signature:
Date:
6/5/2019
Print. Full Name:
Newport Beach Registration: No.:
Charles Beardslee
NB -0692
SpedallnspectlonRep n 09/25/2015
67
�-yy Continuous Inspection & Materials Testing
S ST
Itispecl1011 c`':. Testing, hic. 441 Commercial Way, La Habra,: C:4 90531-6163
(562)941-2990 - (714)52.6-8441
FAX (562)046-0026
FIELD DATA ON TEST SPECIMENS 5'�O/q-ODI8
--- ASTM C31, C138, C143, C172, C173, C231, C1064 -.-93Z 13usswOd6 5E
CONCRETE: MORTAR: SHOTCRETE: X CORES: GUNITE:
ADDRESS: 2632 BASSWOOD DT. NEWPORT BEACH JOB #: DATE: 05/13/2019
JOB NAME: SPRAKER PERMIT M S2019-0018 ISSUED BY:
ARCHITECT: ENGINEER: LACHER ENGINEERING
CONTRACTOR: FUSION POOLS SUB: WEST COAST SHOTCRETE
LOCATION IN STRUCTURE: FLOOR OF THE POOL
TRACT: PHASE:LOT #:
CONCRETE SUPPLIER: GARY BALE PLANT: MIX #: 71/2 -1
TYPE OF CEMENT V ADMIXTURE: TICKET #: 290722
SLUMP: 0.00 in. WATER ADDED: 0 gal. AIR TEMP: 0 F
CONCRETE TEMP: MIXING TIME: TIME CAST: 08:20
DATE CAST: 04/05/2019 RECEIVED AT LAB: 04/11/2019
SPECIMENS MADE BY: ERIC LUIZ SPECIFIED PSI @ 28 Days: 4500
LAB #: 139904 CLIENT: RICHARD LUIZ
TESTING INFORMATION:
SAMPLE IDENTIFICATION:
1819045
1819046
1819047
AGE DAYS:
28
28
28
DATE TEST:
05/03/2019
05/03/2019
05/03/2019
SIZE (in.): Height X Diameter
8.000 X 4.000
8.000 X 4.000
8.000 X 4.000
AREA (in.A2):
12.57
12.57
12:57
CRUSH LOAD (Ibs.):
59100
58320
59410
COMPRESSIVE STRENGTH (psi.):
4700
4640
4730
HEIGHT -DIAMETER RATIO:
CORRECTION FACTOR:
CORRECTED STRENGTH (psi.):
BREAK TYPE:
III
I
i'
C.T.M. USED:
Forney
Forney
Forney
REMARKS:
ASTM C39, C174, C192, C470, C617, C42
COMPLIES: X
DOES NOT COMPLY:
FOR INFORMATION:
THIS REPORT SHALL NOT BE REPRODUCED, EXCEPT IN FULL,. WITHOUT THE APPROVAL OF SOUTHWEST INSPECTION AND TESTING, INC.
SAMPLES CAST BY OTHERS:
NOTICE:Thesetest results are from samples cast by inspectors
or techniciansnot employed: by our firm. They were
either delivered to our laboratory or picked ❑p by our
driver. We will accept no responsibility for the inspection
made on the jobsite by the: inspector, furthermore we
do not take responsibility for any information onthis
report other than the strength as tested and. reported.
ASTM C39 BREAKS: 1=CONE - 11=CONE ANDSPLIT -
RESPECTFULLY SUBMITTED
SOUTHWEST INSPECTION AND TESTING
ZAFAR AHMED
PRINCIPAL ENGINEER
III=COLUMNAR - IV=SHEAR - V=SIDE FRACTURES - VI=POINTED
RICHARD LUIZ
5071 LOYOLA AVENUE
WESTMINSTER, CA 92683
Report of Special Inspection
Project Name & Address
Permit Number `7
Inspection Type(s)
Inspection Dates)
List Tests Made:
Total Inspection Time Each Day:
[ J Periodic j
J Continuous
ewre"4 o -P
i Date
I
Hours
I
i_.ist items Requiring Correction, include uncorrected items previously listed
Woe.
Comments:
To the best of my knowledge, the wort: inspected was in accordance with the Building Department
approved design drawings, specifications and applicable workmanship provisions or the U.B.C.
I
xcept as noted?,aBove.
Signed: Date
Print Full A`ame: YL Registration No. lle-#V-? 'g74i7
c
,ZG 3,2 �sSGv00 d
DL Acoustics
14301 Middletown Lane Westminster, CA 92683
Re5eINch&C0nsu/%Vh7Ab0"5 CS Voice/Fax 714.373.3050 dlubman@dlacoustics.com
Homeowner July 29, 2019
2632 Basswood St.
Newport Beach, CA, 92660 Report emailed to: eric@fusionpoolandspa.com
Pool and or Spa Noise report for residence at 2632 Basswood St., Newport Beach, CA
Dear Homeowner:
At about 11:30 a.m. Monday, July 29, 20191 measured the pool and or spa equipment noise at
your nearest neighbor's residence to test for compliance with the Newport Beach noise
regulation (10.26.025).
Newport Beach Residential Noise Standard
For Noise Zone 1 (residential) the N. B. regulation's daytime noise level standard (maximum
noise level from 10 p.m. to 7 a.m.) is 55 dBA— corrected for ambient noise. The nighttime noise
standard (max noise level from 7 a.m. to 10 p.m.) is 50 dBA. The measurement is corrected for
ambient noise and rounded to the nearest decibel as shown below.
I am pleased to report that measured pool and or spa apparatus noise meets the Newport
Beach noise standard for 24-hour use. Pertinent details of my findings are reported below.
Locations and values of daytime noise measurements
Uncorrected pool and or spa noise + ambient noise measured at property line: 49.42 dBA
Ambient noise level measured at this location: not needed
Pool and or spa equipment noise corrected for ambient noise: not applicable
Pool and or spa equipment noise rounded to the nearest decibel: 49 dBA
49 dBA (Pass for 24 hour use)
The currently installed pool and or spa apparatus noise of 49 dBA meets the Newport Beach
noise code for both "daytime" use (7 a.m. to 10 p.m.) and "nighttime" use (10 p.m. to 7 a.m.),
since the noise corrected for ambient does not exceed 50 dBA.
If you have any questions about this report, please do not hesitate to contact me at (714) 373-
3050 or by email at dlubman(a)dlacoustics.com
Sincerely yours,
f" L.t iT'Y!' MVM
David Lubman, FASA, FINCE
Acoustical Consultant
Orange County Certification #200524
APPENDIX A:
Measurement Instrumentation
Equipment
August 8, 2019
The acoustical equipment used in the performance of this test is in accordance with
ASTM and ANSI (American National Standards Institute) requirements. Key elements
are as follows:
Critical sound measuring instruments (sound analyzer, calibrator, and microphone) are
annual calibrated by an independent NAVLAP certified laboratory. All calibration
documents are available for inspection upon request.
Critical instruments employed were:
Bruel & Kjaer— Type 2270 Type I Precision Sound Analyzer SN # 3006674
The most recent calibration was on 02/25/19.
Bruel & Kjaer - Type 4189 microphone, SN # 2906915
The most recent calibration was on 02/25/19.
Larson Davis - CAL200, SN # 12148
The most recent calibration was on 05/22/19.