FIRE SPRINKLERS & FIRE ALARMS -
C16 -805026
June 20, 2019
UPTOWN NEWPORT
SOUTH BUILDING
4201 JAMBOREE RD.
NEWPORT BEACH, CA 92660
Page 1 of 1
u097-0979
ool Samboree :�'
This letter is to confirm that all fire sprinkler heads installed have been verified to be the
proper model & temperature rating at Uptown Newport south building. Please see below for
fire sprinkler head model & temperature required & approved for this project.
Garage:
• TY313 -175° F
• TY5137 -175° F
• TY3331-1750 F
Residential:
• TY2234 -155° F
• TY2234 -175° F
• TY323 - 155° F
• TY313 -175° F
QGf2Z�n l�,Rw.,
Shawn Price / General Manager Business Development
Sundance Fire Protection Inc.
1060 N BATAVIA I ORANGE, CA 982671(714)639-3170
New Construction Flow Test Combination/Fire Pumps.
Wet/Dry Standpipes Automatic Sprinklers
Fire DoorslFire Alarms L.A.F.D.I24-003 Fire Escapcs/Drop Ladders
State #0349
AAAA
Test Company
19516 Blythe Street
Reseda, CA 91335
(818)886-5508
Fax(818)886-5586
Date: 4-22-19
r Sundance Fire Protection
1060 N. Batavia St. Ste. D
L Orange Ca. 92867 J
JOB ADDRESS:
4201 Jamboree Rd. Newport Beach
On Monday 4-22-19 a new construction 1000 GPM flush and flow test was
conducted at the above address.
System consists of one - 4 way FDC that services the Auto/ Sprinkler System and 5 Standpipes.
Flow required is 1000 GPM with 100 PSI residual.
Flow achieved was 1000 GPM with 105 PSI residual.
PASSED THE FLOW TEST.
PAID ON SITE CK# 1717 THANK YOU
Amount of Invoice and Terms: --------
850_00 _ --30 DAYS
Please return rile copy with payment Thank you
STANDPIPE FLOW AND FLUSH TEST (ACCEPTANCE TEST)
AAAA Test Company Date. 4-22-19 Inspection Tlme 0600
19516 Blythe Street
Reseda, Ca 91335
Bus.# (818) 886-5508
Fax # (818)886-5586
3uilding Description
System Description
Nitnessed By:.
standpipe Test Results
=DC
_OCATION:
JOB ADDRESS 4201 Jamboree Rd. Newport Beach
Floors
Stairs
Elevator
Aprox size
Rooms
Year Built
5
4
4
OK
4
2019
Qty, of
Repairs
Riser Size
Roof
Outlets -
Roof
Drains
-FDC Inlets
Combined'
N/A
4"
4
OK
4
Yes
Truck
Pressure
Roof
Static
GPM '
Residual
PSI
Pitot
Pass/Rall
175
145
1000
105
31,8&8
Passed
ONJAMBOREE
/ALVE
_OCATION In Stairwells and roof
JOTATIONS: Flow test of 1000 GPM with 105 PSI residual Stair # 1,2 and no number center
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR A BOVEGROUND PIPING
PROCEDURE
Upon completion of work, Inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be
corrected and system (eft in service before contractor's personnel finally leave the Job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the
ownees representative's signature In no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving
authority's requirements or local ordinances.
PROPERTY NAME:
Date:
PROPERTY ADDRESS:
l7
t ,
/V l:
C�
ACCEPTED BY APPROVING AUTHORITY('S) NAMES:
N
7
/22 IJ '
AHJ ADDRESS
e
INSTALLATION CONFORMS TOO ACCEPTED PLANS
25 YES ❑ NO
PLANS
EQUIPMENT USED IS APPROVED
I$ YES ❑ NO
IF NO, EXPLAIN
DEVIATIONS:
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION
OF CONTROL
YES ❑ NO
VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO, EXPLAIN:
INSTRUCTIONS
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENTS INSTRUCTIONS
® YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS
® YES ❑ NO
3. NFPA26
® YES ❑ NO
LOCATION
SUPPLIES
OF SYSTEM
BUILDING: ' Al
MAKE MODEL YEAROF
MANUFACTURE
K
FACTOR
SIN QUANTITY TEMPERATURE
RATING
,
SPRINKLERS
PIPE AND
TYPE OF PIPE: _ G PVG �
FITTINGS
TYPE OF FITTINGS: _e, P G 4�T`cr
ALARM VALVE
ALARM DEVICE
MAXIMUM TIME TO OPERATE THRU TEST CONNECTION
OR FLOW
TYPE MAKE MODEL
MIN.
SEC.
INDICATOR
oD 7,,,
r
DRYVALVE
O.O.D..
MAKE MODEL
SERIAL NO.
MAKE
MODEL
SERIAL NO,
TIME TO TRIP
THRU TEST WATER PRESSURE
AIR PRESSURE TRIP POINT AIR
TIME WATER
REACHED
ALARM
OPERATED
CONNECTION'
PRESSURE
TESTOUTLET'
PROPERLY
DRY PIPE
MIN. SEC. PSI
PSI
PSI
MIN, SEC.
YES NO
OPERATING
Without
TEST
O.O.D.
❑ ❑
Wth
O.O.D.
❑ ❑
IF NO,
EXPLAIN:
(OVER)
(BACK)
OPERATION: ❑ PNEUMATIC ❑ ELECTRIC ❑ HYDRAULIC
PIPING SUPERVISED: ❑ YES ❑ NO I DETECTING MEDIA SUPERVISED: ❑ YES ❑ NO
DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS: ❑ YES ❑ NO
DELUGE &
18 THERE AN ACCESSIBLE FACILITY IN ❑ YES IF NO,
PREACTION
EACH CIRCUIT FOR TESTING: ❑ NO EXPLAIN:
VALVES
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUITOPERATE MAXIMUM TIME TO
MAKE
MODEL
SUPERVISION LOSS ALARM? A VALVE RELEASE? OPERATE RELEASE
YES
NO YES NO MIN.
SEC.
❑
❑ ❑ ❑
Hydrostatic tests shall be meds at not lase than 200 psi (13.6 bars) for two hours or 50 psi (3.4 hers) above stage pressure in excess of
HYDROSTATIC:
160psl(10.2bms)forhvohours. Differential dry -pipe valve clappers shell be left open during test to prevent damage. All aboveground
TEST
piping leakage shall be stopped.
DESCRIPTION
PNEUMATIC:
Establish 40 psi (2.7 bars) air pressure and measure drop which shell not exceed 1-1/2 psi (0.1 bare) in 24 hours. Test pressure tanks at
normal water level and air pressure and measure air pressure drop which shell not exceed 1.1/2 psi (0.1 hers) In 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR 2.00 XX jIF NO,
DRY PIPING PNEUMATICALLY TESTED: [I YES NO / STATEN'1h
EQUIPMENT OPERATES PROPERLY: C, YES ❑ NO REASON:
00 YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR ($ YES ❑ NO
TESTING SYSTEMS OR STOPPING LEAKS?
TESTS
DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TEST RESIDUAL PRESSURE WITH VALVE IN TEST
TEST CONNECTION: PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAIN AND LEAD IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING:
VERIFIED BY COPY OF THE U FORM NO. 856 2 YES ❑ NO
FLUSHED BY INSTALLER OF UNDER- OTHER
a YES ❑ NO EXPLAIN
GROUND SPRINKLER PIPING
BLANK
NUMBER
NUMBER REMOVED
TESTING
USED LOCATIONS:
GASKETS
WELDED PIPING: IN YES ❑ NO IFYES: fxpo'S� )P ye gra D(' Q('XT
(WELDING
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT PROCEDURES OMPLY WITH THE REQUIREMENTS YES [3 NO
OF AT LEAST AWS B2.1 ?
WELDING
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE R YES ❑ NO
REQUIREMENTS OF AT LEAST AWS 82.1 ?
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL
PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND ®,YES ❑ NO
OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED?
CUTOUTS DISCS
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS(DISCS) ARE RETRIEVED? ®YES [I NO
HYDRAULIC DATA NAME PLATE PROVIDED: K YES ❑ NO IF NO,
I
NAMEPLATE EXPLAIN:
REMARKS
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
NAME OF SPRINKLER CONTRACTOR:jo,r
TESTS WITNESSED BY '
-FOR- ROS RTY OWNER (SIGNED)
TITLE` '
�N�
TE
9>>•�'��
.�.� �-�
Q}dPt,53'7L.1Z=TIde�, �"
FOR SPRINKLER CO ACTOR (SIGNED)
SIGNATURES
FOR LOCAL FIRE MARSHAL (SIGNED)
TITLE
DATE
FOR RESPONSIBLE MANAGING EMPLOYEE (SIGNED)
TITLE
DATE
ADDITIONAL EXPLANATION AND NOTES REMARKS