CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR UNDERGROUND PIPING
Procedure
Upon completion of work, inspection and tests shall be made: by contractor's representative and witnessed by an owner's representative. All defects
shall be corrected and system left in service before contractor'spersonnel finally leave job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. Itis
understood the owner's representative's signature in no way prejudices any claim againstcontractor for faulty material, poor workmanship,or failure
to comply with approving authority's requirements or local ordinances.
rnvrU, r ,vnrv,c City Of Hope I un, -12/5/19
rMUMM I r rruurtcaa 1601 Avocado Ave. NewportBeachGA.
S
e,
-r
PE
PE
ACCEPTED BY APPROVING AUTHORITY('S) NAMES
Newport Beach Fire Dept
ADDRESS
100 Civic Center Dr, Newport Beach 92660
PLANS.
INSTALLATION CONFORMS TO ACCEPTED PLANS -,� YES ❑ NO
EQUIPMENT USED 15 APPROVED e—YES ❑ NO
IF NO. STATE DEVIATIONS:
HAS THE PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ?c:�i'ES ❑ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT.
IF NO; EXPLAIN
INSTRUCTIONS
----
HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS i?'i'ES ❑ NO
BEEN LEFT ON THE PREMISES.
IF NO, EXPLAIN
SUPPLIES SLOGS. 1601 Avocado Ave.
LOCATION
PIPE TYPES. AND; CLASS C900& Ductile Iron
TYPE JOINT MJ
PIPE CONFORMS TO NFPA 24 STANDARD T -YES ❑ NO
UNDERGROUND
FITTINGS CONFORM TO NFPA.24 STANDARD 7CQ'ES ❑ NO
PIPES
IF NO, EXPLAIN
AND
JOINTS
JOINTS NEEDING ANCHORAGE CLAMPED, STRAPPED OR BLOCKED IN ',O_ YES ❑ NO
ACCORDANCE WITH NEPA 24 STANDARD
IF NO, EXPLAIN
FLUSHING- Flow the required rate until water is clear as indicated by no collection of foreign material in burlap begs at outle
such as hydrants and blow -offs. Flush atflows not less than 400 gpm (1514 Ilmin) for 4 -inch pipe 600 gpm (2271 I/min) for!
inch pipe, 900 gpm (28391/min) for 6 -Inch pipe, 1600 gpm (3786 I/min) for 8 -Inch pipe, 2440 gpm (5678 Itmin) for 10 -inch pip
and 3520 gpm (75701/min)for 12 -inch pipe. When supply cannotproduce: stipulated flow rates, obtain maximum available.
TEST
HYDROSTATIC: Hydrostatic tests shall be made at hot less than 200 psi (13,8 bars)for two hours or 50 psi (3.4 bars) above
DESCRIPTION
static pressure in excess of 150 psi (10.3 bars) for two hours.
LEAKAGE, New pipe fold with rubber gasketed joints. shall, If the workmanship is satisfactory, have little or no leakage at the
joints. The amount of leakage at the joints shall not exceed 2 qts;perhr (1.591/h) per 100 joints Irrespective of pipe diameter.
The leakage shall be distributed over all joints. If such leakage occurs at a few joints the installation shall be considered
unsatisfactory and necessary, repairs made. The amount of allowable leakage specified above may be Increased by 1 fi oz P
In. valve diameter per hour (30 mt125 mm/h) for each metal seated valve Isolating the test section. If dry barrel hydrants are
tested with the main valve open, so the hydrants are under pressure, an additional 5 o7Jmin leakage Is permitted for each
hvdrant
NEW UNDERGROUND PIPING FLUSHED ACCORDING TO NFPA 24 STANDARD `,-YES ❑ NO
BY: (COMPANY) Muir Chase Plumbing
IF NO, EXPLAIN
HOW FLUSHING FLOW WAS OBTAINED THROUGH WHAT TYPE OPENING
FLUSHING
TESTS
E PUBLIC MAIN ❑ TANK OR RESERVOIR ❑ FIRE PUMP ❑ HYDRANT BUTT 9 OPEN P
-
LEAD-INS FLUSHED ACCORDING TO . STANDARD -OYES ❑ NO
BY: (COMPANY) Muir Chasc Plumbing
FN N
HOW FLUSHING FLOW WAS OBTAINED THROUGHWHATTYPE OPENING
E PUBLIC MAIN ❑ TANK OR RESERVOIR ❑ FIRE PUMP ❑ Y CONN TO FLANGE & SPIGOT N OPEN P
S
e,
-r
PE
PE
HYDROSTATIC
ALL NEW UNDERGROUND PIPING HYDROSTATICALLY TESTED AT
TESTS
M PSI FOR u HOURS Yes
TOTAL AMOUNT OF LEAKAGE MEASURED
LEAKAGE
GALS. OVER ++ HOURS
TEST
ALLOWABLE LEAKAGE
GALS. OVER HOURS
NUMBER INSTALLED
TYPE AND MAKE
ALL OPERATE SATISFACTORILI
HYDRANTS
0
❑ YES ❑ NO
WATER CONTROL VALVES LEFT WIDE OPEN
YES ❑ NO
CONTROL
IF NO, STATE REASON
VALVES-
HOSE THREADS OF FIRE DEPARTMENT CONNECTIONS AND HYDRANTS INTERCHANGEABLE
WITH THOSE OF FIRE DEPARTMENT ANSWERING ALARM
YES ❑ NO
DATE LEFT IN SERVICE
REMARKS
10/22/19
NAME OF INSTALLING CONTRACTOR Muir Chase Plumbing
PRIORITY FIRE PROTECTION INC.
TESTS WITNESSED BY AdaM Shade
SIGNATURES
FOR PROPERTY�O NER (�_ „SIGNED)
TITLE Owners Representative
DATE 12/5/19
FOR INST�LLIhiG G �N7RACTOR (SIG(SIGNED)
TITLE Project Manager
DATE12/5/19'
ADDITIONAL EXPLANATIONS AND NOTES