Loading...
HomeMy WebLinkAboutX2019-0912 - MiscOFACCEFTANCE Enforcement Agency Use: Checked by/Date 100 Bayv;ew Cr of OUTDOOR LIGHTING ACCEPTANCE TESTS NA7.8.1 and NA7.8.2 Motion Sensor: A. Construction Inspection 1. Motion Sensor Construction Inspection r Motion sensor has been located to minimize false signals. r Sensor is not triggered by motion outside of controlled area. r Desired motion sensor coverage is not blocked by obstruction that could adversely affect performance. B. Functional testing 1. Simulate motion in area under lights controlled by the motion sensor. Verify and document the following: r Status indicator operates correctly. r Lights controlled by motion sensors turn on immediately upon entry into the area lit by the controlled lights near the motion sensor. r Signal sensitivity is adequate to achieve desired control. 2. Simulate no motion in area with lighting controlled by the sensor. Verify and document the following: r Lights controlled by the sensor reduce light output within a maximum of 20 minutes from the start of an unoccupied condition. r The sensor does not trigger a false "on" from movement outside of the controlled area. r Signal sensitivity is adequate to achieve desired control. NA7.8.3 and NA7.8.4 Photocontrol: C. Construction Inspection 1. Verify and document the following: r The photocontrol is installed. D. Functional testing - This is page of ACCEPTANCE 92660 2of5 1. Verify and document the following: Pr During daytime simulation, all controlled outdoor lights are turned off. r During nighttime simulation, all controlled outdoor lights are turned on. NA7.8.5 and NA7.8.6 Astronomical Time -Switch Control: E. Construction Inspection 1. Prior to Functional Testing, confirm and document the following: r Verify the astronomical time -switch control is installed. r Verify the astronomical time -switch control is programmed with acceptable ON schedule and OFF schedule. r Demonstrate and document for the time switch programming including ON schedule and OFF schedule, for weekday, weekend, and holidays (if applicable). r Verify the correct time and date are properly set in the control. F. Functional Testing 1. Outdoor Lighting Daytime Shut-off Controls r During daytime simulation, all controlled outdoor lights are turned off. r During nighttime simulation, all controlled outdoor lights are turned on in accordance with the astronomical schedule. During nighttime simulation, all controlled outdoor lights are turned off in r accordance with the programmed schedule. NA7.8.7 and NA7.8.8 Part -Night Outdoor Lighting Control: G. Construction Inspection 1. Prior to Functional Testing for time based control type, confirm and document the following: Verify the part -night outdoor lighting control is installed. Verify the control is programmed with acceptable schedules. r Demonstrate and document for the lighting control programming including both ON schedule and OFF schedule, for weekday, weekend, and holidays (if applicable). Verify the correct time and date is properly set in the control. 2. Prior to Functional Testing for occupancy -based control type, verify and document the following: This is page 2of5 Step 2: Simulate no occupancy in areas with lighting controlled by the sensor. r Lights controlled by the sensor are off or reduces light output within a maximum of 20 minutes from the start of an unoccupied condition. r The sensor does not trigger a false "on" from movement outside of the controlled area. r Signal sensitivity is adequate to achieve desired control. r Sensor has been located to minimize false signals. I. Construction Inspection r Sensor is not triggered by motion outside of adjacent area. r Desired sensor coverage is not blocked by obstructions that could adversely affect r performance. H. Functional Testing 1. For time -based control type, verify and document the following: W During daytime simulation, all controlled outdoor lights are turned off. r During nighttime simulation, all controlled outdoor lights are turned on in accordance Pr with the ON schedule. During nighttime simulation, all controlled outdoor lights are turned off or reduced in W light level in accordance with the OFF schedule. 2. For occupancy -based control type, verify and document the following: Step 1: Simulate motion in area under lights controlled by the sensor. r Status indicator operates correctly. Lights controlled by sensors turn on immediately upon entry into the area lit by the r controlled lights near the motion sensor. r Signal sensitivity is adequate to achieve desired control. Step 2: Simulate no occupancy in areas with lighting controlled by the sensor. r Lights controlled by the sensor are off or reduces light output within a maximum of 20 minutes from the start of an unoccupied condition. r The sensor does not trigger a false "on" from movement outside of the controlled area. r Signal sensitivity is adequate to achieve desired control. 3of5 NA7.8.9 and NA7.8.10 Automatic Scheduling Control: I. Construction Inspection 1. Prior to Functional Testing, confirm and document the following: r Verify the automatic scheduling control is installed. r Verify the control is programmed with acceptable schedules. Demonstrate and document for the lighting control programming including both ON r schedule and OFF schedule, for weekday, weekend, and holidays (if applicable), This is page 3of5 r Verify the correct time and date is properly set in the control. 7. Functional Testing 1, Verify and document the following: Fr During daytime simulation, all controlled outdoor lights are turned off. r During nighttime simulation, all controlled outdoor lights are turned on in accordance with the ON schedule. r During nighttime simulation, all controlled outdoor lights are turned off in accordance with the OFF schedule. This is page 4 of 5 ACCEPTANCE DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Company Name Name lames Adair Daugherty Address 1239 N. TUSTIN AVE City Zip Code 9280] CEA/ATT Certification Identification (if TC -A217227 applicable) Date of Signature: Phone Author Signature Ironwood Electric, Inc ANAHEIM (714)630-2350 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The Information provided on this Certificate of Acceptance is true and correct. 2. I am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). 3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permits) issued for the building. Field Technician Name Company Name James Adam Daugherty Ironwood Electric, Inc Address: City 1239 N. TUSTIN AVE ANAHEIM Zip Code Phone 92807 (714)630-2350 ATT Certification Position with Company Identification TC A217227 (Title) LIGHTING CONTROLS TECH Field Technician Signature Date of Signature: 12/09/2019 RESPONSIBLE PERSON'S DECLARATION STATEMENT 1 certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated In the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. 5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. 1 understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance lames Adam Daugherty Company Name Ironwood Electric, Inc Person Name 9 y Address: City 1239 N. TUSTIN AVE ANAHEIM Zip Code 92007 Phone (714)630-2350 CSLB License C-10 61]971 Pool) with Company (Title) LIGHTING CONTROLS TECH Responsible Acceptance Person Signature Date of Signature: 12/09/2019 This is page 5 of 5 General Information Building Type: F Nonresidential r High -Rise Res (Common Area) r Hotel/Motel (Common Area) Phase of Construction: r New Construction r Addition r Alteration r Unconditioned Scope of Responsibility Enter the date of approval by enforcement agency of the Certificate of Compliance that provides the specifications for the energy efficiency measures for the scope of responsibility for this Installation Certificate. Date: 6/5/2019 12:00:00 AM This is page 1 of 2 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Acceptance document is accurate and complete. Documentation Author Company Name Name lames Adam Daugherty Address City 1239 N. TUSTIN AVE Zip Code 9280] CEA/ATT Certification Identific applicat Date of Ironwood Electric, Inc ANAHEIM Phone (714)630-2350 __ ,_,____ Author Signature RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA]. 4. I have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. 5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable Inspections. I understand that a signed copy of this Certificate of Acceptance Is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Company Name Person Name lames Adam Daugherty Ironwood Electric, Inc Address: 1239 N. TUSTIN AVE City ANAHEIM Zip Code 92807 Phone (714)630-2350 CSLB License C-10 61]9]1 Position with Company (Title) LIGHTING CONTROLS TECH Responsible Acceptance Person Signature Date of Signature: 12/09/2019 This is page 2 of 2 OUTDOOR LIGHTING CERTIFICATE OF INSTALLATION NRCI_LTO _01_E 100 BAYVIEW Orange General Information Building Type: F Nonresidential Phase of Construction: r New Construction r Addition i7 Alteration Scope of Responsibility Enter the date of approval by enforcement agency of the Certificate of Compliance that provides the specifications for the energy efficiency measures for the scope of responsibility for this Installation Certificate. Date: 6/5/2019 12:00:00 AM In the table below, identify all construction documents that show that the outdoor lighting and controls were installed as it was proposed in the Certificates of Compliance. Document Title or Description TITLE 24 ENVELOPE FORMS Applicable Sheets or Pages, Tables, Schedules, etc. ENV -001 Date Approved 6/5/2019 12:00:00 By the Enforcement Agency AM TITLE 24 COMPLIANCE E002.01 6/5/2019 12:00:00 AM LIGHTING CONTROL DETAILS E005.01 6/5/2019 12:00:00 AM LIGHTING PLAN E003.01 6/5/2019 12:00:00 AM This is page 1 of 2 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Acceptance document is accurate and complete. Documentation Author Company Name Name lames Adam Daugherty Address Zip Code CEA/ATT Certification Identification (if applicable) 1239 N. TUSTIN AVE 9280] TC -A217227 City Phone Author Signature Ironwood Electric, Inc ANAHEIM (714)630-2350 Date of Signature: 12/09/2019 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided an this Certificate of Acceptance. 2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA]. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation Identified on this Certificate of Acceptance has been completed and is posted or made available with the building permits) issued for the building. 5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be Included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance James Adam Daugherty Company Name Person Name 9 y Ironwood Electiiq Inc Address: City 1239 N. TUSTIN AVE ANAHEIM Zip Code Phone 92802 (714)630-2350 CSLB License Position with Company C-10 61]9]1 (Title) LIGHTING CONTROLS TECH Responsible Acceptance Person Signature Date of This is page 2 of 2 Diamond Creek Vineyards 1500 Diamond Mountain Road Calistoga, CA 94515 Bill To Newport Pacific Club Timothy Parkhouse Invoice Date Shipped Invoice # 10/26/2019 10/26/2019 20579 Ship To Tasting Fee P.O. # S.O. # CLASS ID REP TERMS Shipped Via FOB CUST ID 15298 INDV PR Prepaid Tasted @ DCV Winery Item Code Description Quantity U/M Ordered Backord... Prev. In... Price Ea... Amount Tasting Fee Tasting Fee 14 14 0 116.00929 1,624.13T Subtotal $1,624.13 Sales Tax (7.75°/x) $125.87 Total $1,750.00 Payments/Credits -$1,750.00 Balance Due $0.00 707.942.6926 Tel info@diamondcreekvineyards.com 707.942.6936 Fax Enforcement Agency Use: Checked by/Date LIGHTING CONTROL ACCEPTANCE DOCUMENT Automatic Shut-off Controls: Automatic Time Switch Control and Occupant Sensor Intent: Lights are turned off or set to a lower level when not needed per Section 110.9(a) & 130.1(c). A. Construction Inspection Fill out Section A to cover spaces 1 through 3 that are functionally tested under Section B. Instruments needed to perform tests include, but are not limited to: hand-held amperage meter, power meter, or light meter 1: Automatic Time Switch Controls Construction Inspection—confirm for all listed in Section B a. All automatic time switch controls are programmed for (check all): r Weekdays r Weekend P' Holidays b. Document for the owner automatic time switch programming (check all): W Weekday settings r Weekend settings r Holidays settings r y g Set-up settings F Preference program setting r Verify the correct time and date is properly set in the time switch r Verify the battery is installed and energized P Override time limit is no more than 2 hours F Occupant Sensors and Automatic Time Switch Controls have been certified to the Energy Commission in accordance with the applicable provision in Section 110.9 of the Standards, and model numbers for all such controls are listed on the Commission database as Certified Appliance and Control Devices 2. Occupancy Sensor Construction Inspection—confirm for all listed in Section B W Occupancy sensors are not located within 4 feet of any HVAC diffuser r Ultrasonic occupancy sensors do not emit audible sound 5 feet from source This is page 1 of 10 IP.I.t Nerve: 1W BAYVIEW IlEoforcemwt Agency:= OF NEWPORT BEACH IlPemut Number:X201M912 ____1 B. Functional Testing of Lighting Controls For every space in the building, conduct functional tests 1 through 5 below if applicable. If there are several geometrically similar spaces that use the same lighting controls, test only one space and list in the cells below which "untested spaces" are represented by that tested space. EXCEPTION: For buildings with up to seven (7) occupancy sensors, all occupancy sensors shall be tested. (NA7.6.2.3) Representative Spaces Selected Tested space/room name: SOUTH ELEVATOR LOBBY Space Type (office, corridor, etc) ELEVATOR LOBBY Untested areas/rooms Confirm compliance for all control system types (1-5) present in each space: 1. Automatic Time Switch Controls Step 1: Simulate occupied condition a. All lights can be turned on and off by their respective area control switch r b. Verify the switch only operates lighting in the ceiling -height partitioned area in which the switch is located, r Step 2: Simulate unoccupied condition a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may remain on per Section 130.1(c)1 and 130.1(a)1. J. Manual override switch controls only the lights in the selected ceiling height partitioned space where the override switch is located and the lights remain on no longer than 2 hours (unless serving public areas and override switch is captive key type). Step 3: System returned to initial operating conditions r 2. Occupancy Sensors Step 1: Simulate an unoccupied condition a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes from start of an unoccupied condition per Standard Section 110.9(b) r b.The occupant sensor does not trigger a false 'on' from movement in an area r adjacent to the controlled space or from HVAC operation. Step 2: Simulate an occupied condition a. Status indicator or annunciator operates correctly r b. Lights controlled by occupancy sensors turn on immediately upon an occupied condition OR sensor indicates space is 'occupied' and lights may be turned on r manually This is page 2 of 10 Step 3: System returned to initial operating conditions r- 3. 3. Partial Off Occupancy Sensor Step 1: Simulate an unoccupied condition a. Lights go to partial off state within a maximum of 20 minutes from start of an unoccupied condition per Standard Section I10.9(a) r b. The occupant sensor does not trigger a false 'on' from movement in an area adjacent to the controlled space or from HVAC operation. For library book stacks or warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in Jr the aisle or stack. c. In the partial off state, lighting shall consume no more than 500% of installed lighting power, or: No more than 60% of installed lighting power for metal halide or high pressure sodium lighting in warehouses. No more than 60% of installed lighting power for corridors and stairwells in which the installed lighting power is 80% or less of the value allowed under the Area Category Method. Light level may be used as a proxy for lighting power when measurements are taken r Step 2: Simulate an occupied condition The occupant sensing controls shall turn lights fully ON in each separately controlled r areas, Immediately upon an occupied condition 4. Partial On Occupancy Sensors Step 1. -Simulate an occupied condition. Verify partial on operation. a. Immediately upon an occupied condition, the first stage activates between 50 to r 700/. of the lighting automatically. b. After the first stage occurs, manual switches allow an occupant to activate the alternate set of lights, activate 100% of the lighting power, and manually deactivate all of the lights. r Step 2. Simulate an unoccupied condition a. Both stages (automatic on and manual on) lights turn off within a maximum of 20 r minutes from start of an unoccupied condition per Standard Section 110.9(a) b. The occupant sensor does not trigger a false 'on' from movement in an area adjacent to the controlled space or from HVAC operation. r This is page 3 of 10 5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than 250 ft , to Qualify for a Power Adjustment Factor (PAF) Step 0: First, complete Functional Test 2 (above) for each controlled zone. Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2. a. Area served by controlled lighting ft2 b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2). c. Enter PAF claimed for occupant sensor control in this space from the Certificate of Compliance. d. The PAF corresponding to the controlled area (line b), is greater than or equal to r the PAF claimed in the compliance documentation (line c). e. Sensors shall not trigger in response to movement in adjacent walkways or workspaces r f. All steps are conducted in Functional Test 2 'Occupancy Sensor (On Off Control)' r and all answers are Yes. This is page 4 of 10 OFACCEFIANCE C. Testing Results 1. Automatic Time Switch Controls (all answers must be Yes), r 2. Occupancy Sensor (On Off Control) (all answers must be Yes). r- 3. 3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library book stacks, corridors, stairwells in nonresidential buildings must also be r accompanied by passing Test 1 or Test 2. 4. Partial On Occupant Sensor for PAF (all answers must be Yes). r- 5. 5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must r pass Test 2. Representative Spaces Selected Tested space/room name: NORTH ELEVATOR LOBBY Space Type (office, corridor, etc) ELEVATOR LOBBY Untested areas/rooms Confirm compliance for all control system types (1-5) present in each space: 1. Automatic Time Switch Controls Step 1: Simulate occupied condition a. All lights can be turned on and off by their respective area control switch 7 b. Verify the switch only operates lighting in the ceiling -height partitioned area in which the switch is located. r Step 2: Simulate unoccupied condition a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may remain on per Section 130.1(c)1 and 130.1(a)1. b. Manual override switch controls only the lights in the selected ceiling height partitioned space where the override switch is located and the lights remain on no longer than 2 hours (unless serving public areas and override switch is captive key type). r Step 3: System returned to initial operating conditions r 2. Occupancy Sensors Step 1: Simulate an unoccupied condition This is page 5 of 10 b. The occupant sensor does not trigger a false 'on' from movement in an area r adjacent to the controlled space or from HVAC operation. Step 2: Simulate an occupied condition a. Status indicator or annunciator operates correctly r b. Lights controlled by occupancy sensors turn on immediately upon an occupied condition OR sensor indicates space is 'occupied' and lights may be turned on r manually Step 3: System returned to initial operating conditions r- 3. 3. Partial Off Occupancy Sensor Step 1: Simulate an unoccupied condition a. Lights go to partial off state within a maximum of 20 minutes from start of an unoccupied condition per Standard Section 110.9(a) r b. The occupant sensor does not trigger a false 'on' from movement in an area adjacent to the controlled space or from HVAC operation. For library book stacks or warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in r the aisle or stack. c. In the partial off state, lighting shall consume no more than 50% of installed lighting power, or: No more than 60% of installed lighting power for metal halide or high pressure sodium lighting in warehouses. No more than 60% of installed lighting power for corridors and stairwells in which the installed lighting power is 80% or less of the value allowed under the Area Category Method. Light level may be used as a proxy for lighting power when measurements are taken r Step 2: Simulate an occupied condition The occupant sensing controls shall turn lights fully ON in each separately controlled r areas, Immediately upon an occupied condition 4. Partial On Occupancy Sensors Step 1. -Simulate an occupied condition. Verify partial on operation. a. Immediately upon an occupied condition, the first stage activates between 50 to r 70% of the lighting automatically. b. After the first stage occurs, manual switches allow an occupant to activate the alternate set of lights, activate 100% of the lighting power, and manually deactivate all of the lights. r This is page 6 of 10 Step 2. Simulate an unoccupied condition a. Both stages (automatic on and manual on) lights turn off within a maximum of 20 r minutes from start of an unoccupied condition per Standard Section 110.9(a) b. The occupant sensor does not trigger a false 'on' from movement in an area r adjacent to the controlled space or from HVAC operation. This is page 7 of 10 5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than 250 ft , to Qualify for a Power Adjustment Factor (PAF) Step 0: First, complete Functional Test 2 (above) for each controlled zone. Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2. a. Area served by controlled lighting ft2 b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2). c. Enter PAF claimed for occupant sensor control in this space from the Certificate of Compliance. d, The PAF corresponding to the controlled area (line b), is greater than or equal to r the PAF claimed in the compliance documentation (line c). e. Sensors shall not trigger in response to movement in adjacent walkways or workspaces r f. All steps are conducted in Functional Test 2 'Occupancy Sensor (On Off Control)' r and all answers are Yes. This is page 8 of 10 C. Testing Results 1. Automatic Time Switch Controls (all answers must be Yes). 2. Occupancy Sensor (On Off Control) (all answers must be Yes). r 3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library book stacks, corridors, stairwells in nonresidential buildings must also be r accompanied by passing Test 1 or Test 2. 4. Partial On Occupant Sensor for PAF (all answers must be Yes). r 5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must r pass Test 2. D. Evaluation : P' PASS: All applicable Construction Inspection responses are complete and all applicable Equipment Testing Requirements responses are positive. This is page 9 of 10 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Company Name Name James Adam Daugherty Address 1239 N. TUSTIN AVE City Zip Code 92807 CEA/ATT Certification Identification (if TC -A21]22] applicable) Date of Signature: Phone Author Signature Ironwood Electric, Inc ANAHEIM (714)630-2350 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The Information provided on this Certificate of Acceptance is true and correct. 2. I am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Tech n i cl a n). 3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA]. 4. I have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permit(s) issued for the building. Field Technician Name Company Name James Adam Daugherty Ironwood Electric, Inc Address: 1239 N. TUSTIN AVE City ANAHEIM Zip Code 92807 Phone (714)630-2350 ATT Certification TC -A217227 Position with Company LIGHTING CONTROLS TECH Identification (Title) Field Technician Signature Date of Signature: 12/09/2019 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Tednician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or Installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation Identified on this Certificate of Acceptance complies with the acceptance requirements indicated In the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA]. 4. I have confirmed that the Certificate(s) of Installation for the construction or Installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued fol'the building. 5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance James Adam Daugherty Company Name Ironwood Electric, Inc Person Name 9 y Address.: 1239 N. TUSTIN AVE City ANAHEIM Zip Code 92807 Phone (714)630-2350 CSLB License C-10 61]9]1 Position with Company (Title) LIGHTING CONTROLS TECH Responsible Acceptance Person Signature Date of Signa e: 12/09/2019 This is page 10 of 10 INDOOR LIGHTING N RCI_LTI_02E 100 BAYVIEW_ Orange General Information Building Type: r Nonresidential r High -Rise Res (Common Area) r Hotel/Motel (Common Area) Phase of Construction: F New Construction r Addition r Alteration r Unconditioned Scope of Responsibility Enter the date of approval by enforcement agency of the Certificate of Compliance that provides the specifications for the energy efficiency measures for the scope of responsibility for this Installation Certificate. Date: 6/5/2019 12:00:00 AM §130.4(b) Before an Energy Management Control System (EMCS), or Lighting Control System can be recognized for compliance with the lighting control requirements in Part 6 of Title 24, the person who is eligible under Division 3 of the Business and Professions Code to accept responsibility for the construction or installation of features, materials, components, or manufactured devices shall sign and submit this Installation Certificate. If any of the requirements in this Installation Certificate fail the Energy Management Control System or Lighting Control System installation requirements, these options for controlling lighting shall not be recognized for compliance with the Building Energy Efficiency Standards. Check all that apply PART 1 What type of Lighting Control System has been installed? r A. Energy Management Control System (EMCS) - Is a computerized control system designed to regulate the energy consumption of a building by controlling the operation of energy consuming systems, such as the heating, ventilation and air conditioning (HVAC), lighting, and water heating systems, and is capable of monitoring environmental and system loads, and adjusting HVAC operations in order to optimize energy usage and respond to demand response signals. F The Energy Management Control System has been installed to function as a lighting control required by Part 6 and functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with Reference Nonresidential Appendix NA7.7.2. r The EMCS has been separately tested for each respective lighting control system for which it is installed to function as. r B. Lighting Control System - Requires two or more components to be installed in the building to provide all of the functionality required to make up a fully functional and compliant lighting control. This is page 1 of 5 I� The installed Lighting Control System complies with the requirements checked below; and all components of the system considered together as installed meet all applicable requirements for the application for which they are installed as required in Sections 130.0 through 130.5, Sections 140.6 through 140.8, Section 141.0, and Section 150.0(k). This is page 2 of 5 iumCYAMIAMA r 1. Automatic Daylight Controls meet all requirements for Automatic Daylight Control devices in the Title 20 Appliance Efficiency Regulations, including the following: a. Is capable of reducing the power consumption in response to measured daylight either directly or by sending and receiving signals; J. If the system includes a dimmer, complies with the Dimmer Control device requirements in the Title 20 Appliance Efficiency Regulations. c. Automatically return to its most recent time delay settings within 60 minutes when put in calibration mode; d. Has a set point control that easily distinguishes settings to within 10 percent of full scale adjustment; e. Has a light sensor that has a linear response within 5 percent accuracy over the range of illuminance measured by the light sensor; f. Has a light sensor that is physically separated from where the calibration adjustments are made, or is capable of being calibrated in a manner that the person initiating the calibration is remote from the sensor during calibration to avoid influencing calibration accuracy; and g. Complies with the Title 20 requirements for photo controls if the system contains a photo control component. r 2. Photo Controls meet all requirements for Photo Control devices in the Title 20 Appliance Efficiency Regulations, including the following that it does not have a mechanical device that permits disabling of the control. F G. The EMCS or Lighting Control System functions as a Dimmer and meets all requirements for a Dimmer Control device in the Title 20 Appliance Efficiency Regulations, including the following: 1. Is capable of reducing power consumption by a minimum of 65 percent when the dimmer is at its lowest level; 2. Includes an off position which produces a zero lumen output; and 3. Does not consume more than 1 watt per lighting dimmer switch leg when in the off position. 4. Dimmer controls that can directly control lamps provide electrical outputs to lamps for reduced flicker operation through the dimming range so that the light output has an amplitude modulation of less than 30 percent for frequencies less than 200 Hz without causing premature lamp failure. 5. If designed for use in three way circuits is capable of turning lights off, and to the level set by the dimmer if the lights are off. r H. The EMCS or Lighting Control System meets the following requirements: 1. Is capable of automatically turning off controlled lights in the area no more than 30 minutes after the area has been vacated; 2. Allows all lights to be manually turned off regardless of the status of occupancy; and 3. Has a visible status signal that indicates that the device is operating properly, or that it has failed or malfunctioned. The visible status signal may have an override switch that turns off the signal. 4. All occupant sensing devices that utilize ultrasonic radiation for detection of occupants meet the Ultrasound Maximum Decibel Values in the Title 20 Appliance Efficiency Regulations 5. All occupant sensing devices that utilize microwave radiation for detection of occupants meet the radiation requirements in the Title 20 Appliance Efficiency Regulations 6. Occupant sensing devices incorporating dimming comply with the requirements for dimmer controls in the Title 20 Appliance Efficiency Regulations 7. The EMCS or Lighting Control System functions as one or more of the Occupant Sensing Controls Checked Below: r a. Occupant Sensors meeting all applicable requirements for Occupant Sensor Control devices in the Title 20 Appliance Efficiency Regulations r b. Motion Sensors meeting all applicable requirements for Motion Sensor Controls devices in the Title 20 Appliance Efficiency Regulations, including that motion sensors are rated for outdoor use. r c. Vacancy Sensors meeting all applicable requirements for Vacancy Sensor Controls devices in the Title 20 Appliance Efficiency Regulations, including the following: i. Does not turn on lighting automatically and does not incorporate DIP switches, or other manual means, for conversion between manual and automatic functionality; ii. Has a grace period of no more than 30 seconds and no less than 15 seconds to turn on lighting automatically after the sensor has timed out; and iii. Does not have an override switch that disables the sensor. This is page 3 of 5 OF INSTALLATION r d. Partial -ON Sensors meeting all applicable requirements for partial on sensing devices in the Title 20 Appliance Efficiency Regulations, including the following: i. Has two poles each with automatic -off functionality; ii. Has one pole that is manual -on and does not incorporate DIP switches, or other manual means, for conversion between manual and automatic functionality; and iii. Has one pole that is automatic -on and is not be capable of conversion by the user to manual -on functionality. F e. Partial -OFF Sensors meet all applicable requirements for partial off sensing devices in the Title 20 Appliance Efficiency Regulations, including the following: i. Has two poles; ii. Has one pole that is manual -on and manual off; and iii. Has one pole that is automatic -on and automatic -off and is not capable of conversion by the user to manual -on only functionality. W f. Occupant Sensing Control systems consist of a combination of single or multi-level Occupant, Motion, or Vacancy Sensor Controls, and all components installed to comply with manual -on requirements are not capable of conversion by the user from manual -on to automatic -on functionality. PART 3 Requirements for which the control is being installed to complied with: Identify all requirements in the Standards for which the EMCS or Lighting Control System is installed to function as and complies with: Check all that are applicable. F A. Section 130.1(a) Area Controls. P B. Section 130.1(b) Multi -Level Lighting Controls W C. Section 130.1 (c) Shut -OFF Controls r D. Section 130.1 (d) Automatic Daylighting Controls. r E. Section 130.1 (e) Demand Responsive Controls. r F. Section 130.5 (d) Circuit Controls for 120 -Volt Receptacles. r G. To qualify for the PAF for a Partial -ON Occupant Sensing Control in TABLE 140.6-A r H. To qualify for the PAF for an occupant sensing control controlling the general lighting in large open plan office areas above workstations, in accordance with TABLE 140.6-A r I. To qualify for the PAF for a Manual Dimming System PAF or a Multiscene Programmable Dimming System PAF in TABLE 140.6-A r J. To qualify for the PAF for a Demand Responsive Control in TABLE 140.6-A r K. To qualify for the PAF for Combined Manual Dimming plus Partial -ON Occupant Sensing Control in TABLE 140.6-A This is page 4 of 5 OF INSTALLATION DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1 certify Chat this Certificate of Acceptance document is accurate and complete. Documentation Author Company Name Name lames Adam Daugherty Address 1239 N. TUSTIN AVE City Zip Code 92807 CEA/ATT Certification Identification (if TC -A21]22] applicable) Date of �iyoamFe. Phone Author Signature Ironwood Electric, Inc ANAHEIM (714)630-2350 12/09/2019 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed tire information provided on this Certificate of Acceptance. 2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or Installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person), 3. The Information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA]. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. S. 1 will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance Is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance lames Adam Daugherty Company Name Ironwood Electric, Inc Person Name 9 Y Address: 1239 N. TUSTIN AVE City ANAHEIM Zip Code 92007 Phone (714)630-2350 CSLB License C-10 617971 (Title) with Company Title) LI6 HTING CONTROLS TECH Responsible Acceptance Person Signature 49AZ � Date of Signature: 12/09/2019 This is page 5 of 5 ENERGY MANAGEMENT CONTROL SYSTEM OR LIGHTING CONTROL SYSTEM CERTIFICATE OF INSTALLATION NRCI_LTO_02_E 100 BAYVIEW Orange General Information of 5 Building Type: F Nonresidential Outdoor Lighting Phase of Construction: r New Construction r Addition P Alteration Scope of Responsibility Enter the date of approval by enforcement agency of the Certificate of Compliance that provides the specifications for the energy efficiency measures for the scope of responsibility for this Installation Certificate. Date: 6/5/2019 12:00:00 AM Requirements in the Standards: §130.4(b) Before an Energy Management Control System (EMCS), or Lighting Control System can be recognized for compliance with the lighting control requirements in Part 6 of Title 24, the person who is eligible under Division 3 of the Business and Professions Code to accept responsibility for the construction or installation of features, materials, components, or manufactured devices shall sign and submit this Installation Certificate. If any of the requirements in this Installation Certificate fail the Energy Management Control System or Lighting Control System installation requirements, these options for controlling lighting shall not be recognized for compliance with the Building Energy Efficiency Standards. Check all that apply PART 1 What type of Lighting Control System has been installed? r A. Energy Management Control System (EMCS) - Is a computerized control system designed to regulate the energy consumption of a building by controlling the operation of energy consuming systems, such as the heating, ventilation and air conditioning (HVAC), lighting, and water heating systems, and is capable of monitoring environmental and system loads, and adjusting HVAC operations in order to optimize energy usage and respond to demand response signals. r The Energy Management Control System has been installed to function as a lighting control required by Part 6 and functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with Reference Nonresidential Appendix NA7.7.2. r The EMCS has been separately tested for each respective lighting control system for which it is installed to function as. F B. Lighting Control System - Requires two or more components to be installed in the building to provide all of the functionality required to make up a fully functional and compliant lighting control. r The installed Lighting Control System complies with the requirements checked below; and all components of the system considered together as installed meet all applicable requirements for the application for which they are installed as required in Sections 130.0 through 130.5, Sections 140.6 through 140.8, Section 141.0, and Section 150.0(k). This is page of 5 This is page 2 of 5 r✓ 2. Photo Controls meet all requirements for Photo Control devices in the Title 20 Appliance Efficiency Regulations, including the following that it does not have a mechanical device that permits disabling of the control. r G. The EMCS or Lighting Control System functions as a Dimmer and meets all requirements for a Dimmer Control device in the Title 20 Appliance Efficiency Regulations, including the following: 1. Is capable of reducing power consumption by a minimum of 65 percent when the dimmer is at its lowest level; 2. Includes an off position which produces a zero lumen output; and 3. Does not consume more than 1 watt per lighting dimmer switch leg when in the off position, 4. Dimmer controls that can directly control lamps provide electrical outputs to lamps for reduced flicker operation through the dimming range so that the light output has an amplitude modulation of less than 30 percent for frequencies less than 200 Hz without causing premature lamp failure. 5. If designed for use in three way circuits is capable of turning lights off, and to the level set by the dimmer if the lights are off. r H. The EMCS or Lighting Control System meets the following requirements: 1. Is capable of automatically turning off controlled lights in the area no more than 30 minutes after the area has been vacated; 2. Allows all lights to be manually turned off regardless of the status of occupancy; and 3. Has a visible status signal that indicates that the device is operating properly, or that it has failed or malfunctioned. The visible status signal may have an override switch that turns off the signal. 4. All occupant sensing devices that utilize ultrasonic radiation for detection of occupants meet the Ultrasound Maximum Decibel Values in the Title 20 Appliance Efficiency Regulations 5. All occupant sensing devices that utilize microwave radiation for detection of occupants meet the radiation requirements in the Title 20 Appliance Efficiency Regulations 6. Occupant sensing devices incorporating dimming comply with the requirements for dimmer controls in the Title 20 Appliance Efficiency Regulations 7. The EMCS or Lighting Control System functions as one or more of the Occupant Sensing Controls Checked Below: r a. Motion Sensors meeting all applicable requirements for Motion Sensor Controls devices in the Title 20 Appliance Efficiency Regulations, including that motion sensors are rated for outdoor use. r b. Partial -ON Sensors meeting all applicable requirements for partial on sensing devices in the Title 20 Appliance Efficiency Regulations, including the following: i. Has two poles each with automatic -off functionality; ii. Has one pole that is manual -on and does not incorporate DIP switches, or other manual means, for conversion between manual and automatic functionality; and iii. Has one pole that is automatic -on and is not be capable of conversion by the user to manual -on functionality. r c. Partial -OFF Sensors meet all applicable requirements for partial off sensing devices in the Title 20 Appliance Efficiency Regulations, including the following: i. Has two poles; it. Has one pole that is manual -on and manual off; and iii. Has one pole that is automatic -on and automatic -off and is not capable of conversion by the user to manual -on only functionality. PART 3 Requirements for which the control is being installed to complied with: Identify all requirements in the Standards for which the EMCS or Lighting Control System is installed to function as and complies with: Check all that are applicable r A. Section 130.2(c)1 Photocontrol r B. Section 130.2(c)1 Outdoor astronomical time -switch control r C. Section 130.2 (c)3 Motion Sensor r D. Section 130.2 (c)4A Part -Night Outdoor Lighting Control This is page 3 of 5 This is page 4 of 5 r E. Section 130.2 (c)4B Motion Sensor W F. Section 130.2 (c)5A Part -Night Outdoor Lighting Control r G. Section 130.2 (c)5B Motion Sensor F H. Section 130.2 (c)5C Centralized time -based zone lighting control. This is page 4 of 5 loo DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Acceptance document is accurate and complete. Documentation Author Company Name Name lames Adam Daugherty Address 1239 N. TUSTIN AVE Zip Code 92807 CEA/ATT Certification Identification (if TC -A21]22] applicable) Date of Signature: 12/09/2019 City Phone Author Signature Ironwood Electric, Inc ANAHEIM (714)630-2350 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. 1 am eligible under Division 3 of the Business and Professions Code In the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA]. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or Installation identified on this Certificate of Acceptance has been completed and Is posted or made available with the building permit(s) issued for the building. 5. 1 will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance Is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Company Name Person Name lames Adam Daugherty Ironwood Electric, Inc Address: 1239 N. TUSTIN AVE City ANAHEIM Zip Code 92807 Phone (714)630-2350 CSLB License C-10 61]9]1 Position with Company (Title) LIGHTING CONTROLS TECH Responsible Acceptance Person Signature -J4At Date of Signature: 12/09/2019 This is page 5 of 5