HomeMy WebLinkAboutS2018-0147 - Misc30/009
CHRISTOPHER JEAN & ASSOCIATES, INC.
ACOUSTICAL CONSUL.'I'ING SERVICES
S)018 - ()1147
309 Via / ,Jo Soul
January 24, 2020
MR. THOMAS THOMAS
INFINITY POOL, & SPA, INC.
840 West 19th Street
Costa Mesa, California 92627
Business License: #BT30044674
SUBJECT: RESULTS OF ACOUSTICAL CERTIFICATION MEASUREMENT
FOR 301 VIA LIDO SOUD -- CITY OF NEWPORT BEACH
Dear Mr. Thomas:
We are pleased to inform you that the pool equipment installation located at 301 Via Lido
Soud in the City of Newport Beach complies with the City's 55 dBA noise limit. No additional
noise mitigation is necessary.
The installation was measured on Friday, January 24, 2020, using a Larson Davis Model
700 Type 2 Sound Level Meter. The installation was observed to consist of a single Jandy VS
Plus pump, a single Jandy Water Feature pump and a Mastertemp 400 heater unit, all located in a
mechanical closet. The measurement microphone was placed at the top of the nearest property
line wall directly opposite the mechanical closet. The measurement reported a level of 51 dBA
with both pumps and the heater unit operating simultaneously. This level complies the City's 55
dBA noise limit.
Thank you, and if there are any questions, please do not hesitate to call.
Clitrstophcr;Jea' a
President
P. �O. BOX 2325 • FULLERTON, CALIFORNIA 92837
"� PHONE: 714-805-0115 i
Continuous Inspection di Materials Testing
vrr®ssv®-
SLTTH ST
Inspection & Testing, 11ic. 841 Commercial Way, La Habra, CA 90631-6168
(562)941-2990 ° (714)526-8441
t
FAX (562)946-0026
FIELD DATA ON TEST SPECIMENS
-- ASTM C31, C138, C143, C172, C173, C231, C1064 ---
CONCRETE: MORTAR: SHOTCRETE: X CORES: GUNITE:
ADDRESS: 301 VIA LIDO SOLID, NEWPORT BEACH JOB #: DATE: 05/1612019
JOB NAME: FEUERSTEIN PERMIT #: S2018-0147ISSUED BY:
ARCHITECT: ENGINEER: FERRELL
CONTRACTOR: INFINITY POOLS SUB: GOLD COAST SHOTCRETE
LOCATION IN STRUCTURE: FLOOR OF THE POOL
TRACT: PHASE: LOT #:
CONCRETE SUPPLIER: NATIONAL RDY MX PLANT: MIX#: 7 1/2 1
TYPE OF CEMENT:'V ADMIXTURE: TICKET #: 308955
SLUMP: 0.00 in. WATER ADDED: 0 gal. AIR TEMP: 0 F
CONCRETE TEMP:: MIXING TIME: TIME CAST: 12:00
DATE CAST: 04/15/2019 RECEIVED AT LAB: 04/25/2019
SPECIMENS MADE BY: KELLY LUIZ SPECIFIED PSI @ 28 Days: 4500
LAB #: 140813 CLIENT: RICHARD LUIZ
TESTING INFORMATION:
SAMPLE IDENTIFICATION:
1822775
1822776
1822777
AGE DAYS:
28
28
28
DATE TEST:
05/13/2019
05/13/2019
05/13/2019
SIZE (in.): Height X Diameter
8.000 X4.005
8.000 X 4.005
8.000 X 4.000
AREA (in.A2):
12.60'
12.60
12.57
CRUSH LOAD (ibs.):
74570
73540
72540
COMPRESSIVE STRENGTH (psi.):
5920
5840
5770
HEIGHT -DIAMETER RATIO:
CORRECTION FACTOR:
CORRECTED STRENGTH (psi.):
BREAK TYPE:
IV
IV'
V
C.T.M. USED:
Forney96
Forney96
Forney96
REMARKS:
ASTM C39, C174, 0192, 'C470, C617, C42
COMPLIES: X DOES NOT COMPLY: FOR INFORMATION:
THIS REPORT SHALL NOT BE REPRODUCED, EXCEPT IN FULL, WITHOUT THE APPROVAL OF SOUTHWEST INSPECTION AND TESTING, INC.
SAMPLES CAST BY OTHERS: RESPECTFULLY SUBMITTED
NOTICE:Thesetest results . are from samples cast by inspectors SOUTHWEST INSPECTION AND TESTING
or technicians not employed: by our fine. They were
eitherdelivered to our laboratory or,picked up by our
driver. We will accept no responsibility forthe inspection
made on the jobsite by the inspector, furthermore we ZAFAR AHME
do not take responsibility for any information on this PRINCIPAL E ER
report other than the strength: as tested .and reported.
ASTM C39 BREAKS: 1=CONE - 11=CONE AND SPLIT - III=COLUMNAR - iV=SHEAR - V=SIDEFRACTURES - VI=POINTED
Report of Special Inspection
Project Name & Addresst '.
Inspection Type(s) "ib"a
Inspection Date(s) It " IJ'- l q ( ) Periodic
[ Y ) Continuous
List Tests Made:
Total Inspection Time Each Day:
List Items Requiring Correction, include uncorrected items previously listed
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Department
approved design drawings, specifications and applicable workmanship provisions of the U.B.C.
except as noted above.
Signed: P `JI�Lr Lv Date
l
Print Full Name: Registration No, 400 ' COKHLTc
FO.&ht S1-0?; 90
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive I P.O. Box 1768 1 Newport Beach, CA 92658
www.newoortbeachca.00v 1(949)644-3200
SPECIAL INSPECTION REPORT
Project Address: Gray Residence. 301 Via Lido Soud, Newport Beach, CA
Permit Number: S2018-0147
Inspection Type
Inspection Date
Concrete
2/26/19
Periodic
Observed the placement and consolidation of 8 Cubic yards of concrete, mix design RS3001344, supplied by
Robertsons and placed at footing for property line pool wall footing per detail 6/SP-A4. One set of 4 test samples was
taken - ticket # 3619439, slump 5", PSI 3000, concrete temp 50F.
Apollo Inspection Service. Castle Masonry.
Total Inspection Time Each Day:
Date_- --2/26/19__
Hours: + Min
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments;
Other than any noted discrepancies all work was done per approved plans, job site specifications, applicable codes, RFPs and WPS's to the best of my
knowledge and appeared to be in compliance at time of inspection.
Special Inspector Signature:
Date:
2/26/19
Print Full Name:
i Newport Beach Registration No.: .
Peter Gilpin
NB -0381
SpeciallnspectionReport 8-24-15
Continuous Inspection t%, Testing
SOUTH STs s ® AL =1� AL '1W 1W
It lrispectwn & Testirig, 11ic. 441 Commercial Way, La Habra, CA 90631-6168
(562)941-2990 - (714)526-8441
FAX (562)946-0026
FIELD DATA ON TEST SPECIMENS
--- ASTM C31; C138, C143, C172, C173, C231, C1064 ---
CONCRETE: MORTAR: SHOTCRETE: X CORES: GUNITE:
ADDRESS: 301 VIA LIDO SOLID, NEWPORT BEACH JOB #: DATE: 05/16/2019
JOB NAME: FEUERSTEIN PERMIT #: S2018-0147 ISSUED BY:
ARCHITECT': ENGINEER: FERRELL
CONTRACTOR: INFINITY POOLS SUB: GOLD COAST SHOTCRETE
LOCATION IN STRUCTURE: FLOOR OF THE POOL
1822775
TRACT:
PHASE:
LOT M
CONCRETE SUPPLIER: NATIONAL RDY MX
PLANT:
MIX #: 71/2 -1
TYPE OF CEMENT: V
ADMIXTURE:
TICKET M 308955
SLUMP: 0.00 in.
WATER ADDED: 0 gal.
AIR TEMP: 0 F
CONCRETE TEMP:
MIXING TIME:
TIME CAST: 12:00
DATE CAST: 04/15/2019 RECEIVED AT LAB: 04/25/2019
SPECIMENS MADE BY: KELLY LUIZ SPECIFIED PSI @ 28 Days: 4500
LAB #: 140813 CLIENT: RICHARD LUIZ
TESTING INFORMATION
SAMPLE IDENTIFICATION:
1822775
1822776
1822777
AGE DAYS:
28
28
28
DATE TEST:
05/13/2019
0511'3/2019
05/13/2019
SIZE (in.): Height X Diameter
8.000 X 4.005
8.000 X 4.005
8.000 X 4.000
AREA (in.A2):
12.60
12.60
12.57
CRUSH LOAD (lbs.):
74570
73540
72540
COMPRESSIVE STRENGTH (psi.):
5920
5840
5770
HEIGHT -DIAMETER RATIO:
CORRECTION FACTOR:
CORRECTED STRENGTH (psi.):
BREAK TYPE:
1V
IV
V'
C.T.M. USED:
Forney96
Forney96
Forney96
REMARKS:
COMPLIES: X
ASTM C39, C174, C192, C470, 'C617, C42
DOES NOT COMPLY:
FOR INFORMATION:
THIS REPORT SHALL NOT BE REPRODUCED, EXCEPT IN FULL, WITHOUT THE APPROVAL OF SOUTHWEST INSPECTION AND TESTING, INC.
SAMPLES CAST BY OTHERS:
RESPECTFULLY SUBMITTED
NOTICE:These test results are from samples cast by inspectors
SOUTHWEST INSPECTION AND TESTING
or technicians not employed by our firm. They were
either delivered toour laboratory' or picked up by our
driver. We will accept no responsibility forthe inspection
made on the lobsite by the inspector, furthermore we
ZAFAR AHME
do not take responsibility for any information on this
PRINCIPAL
ER
report other than the strength as tested and reported.
ASTM C39 BREAKS: [=CONE - 11=CONEAND.SPLIT -
111=COLUMNAR. - IV=SHEAR' - V=SIDE FRACTURES - VI=POINTED
Report of Special Inspection
Project Name & Address J'eu�14' ' Sol kt�- &,'
inspection Type(s) �
Inspection Date(s) Periodic [ ] Continuous
Total Inspection Time Each Day;
List Items Requiring Correction, include uncorrected items previously listed
Comments: X,"'
To the best of my knowledge, the work inspected was in accordance with the Building Department
approved design drawings, specifications and applicable workmanship provisions of the U.B.C.
except as noted above.
Signed: Date"lam j
Print Full Name: Registration No, if"4 0 - CONCR=TE
FORM S"2i9-