HomeMy WebLinkAbout20140707_PRR_Fire Newport Beach Fire Department
Life Safety Services Division
Fire Prevention Department
100 Civic Center Drive
Newport Beach, CA 92658
(949) 644-3107
Planning Commission Project Review
Conditions for Approval
DATE: July 7, 2014
PROJECT LOCATION: 2801 E. Coast Highway
Conditions:
1. The proposed fire pit installation and location must comply with the manufactures specifications,
California Fire Code, and the California Mechanical Code with regard to horizontal and vertical
clearances.
2. A hood fire suppression system must be installed over the cooking areas as required by the California
Fire Code 904.2.1.
3. Fire Sprinklers will be required and must be extended to any additions to the structure.
4. Dumpsters with an individual capacity of 200 gallons or more shall not be stored in buildings or placed
within 5 feet of combustible walls openings or combustible roof eave lines unless the dumpsters are
constructed of noncombustible materials. Exception: Dumpsters in areas protect by an approved
automatic sprinkler system installed throughout in accordance with Sec. 903.3.1.1 or 903.3.1.3 C.F.C.
(Examples of combustible construction: plaster on wood, gypsum board on wood studs, plywood or
other wood sheathing on wood metal studs). C.F.C. Sec. 304.3.4.
5. Egress analysis will need to be reviewed with the plan review process.