March 18, 2021
Ian J. N. Harrison Architect
220 Newport Center Drive, Suite 11-342
Newport Beach, CA 92660
BULKHEAD CONDITIONS REPORT
Daniel Kruse; Applicant
630 Via Lido Nord
City of Newport Beach, County of Orange
PMA Job #34420
Dear Mr. Harrison,
PMA Consulting, Inc. is pleased to provide this report in accordance with Section
21.30.15.E.3 of City of Newport Beach Municipal Code.
STATEMENT OF THE PREPARER’S QUALIFICATIONS
Plamen Petrov, P.E., the preparer of this report, holds a Master of Science in Structural
Engineering from University of Architecture, Structural Engineering & Geodesy of Sofia, Bulgaria,
and is a Licensed Civil Engineer by the State of California Certificate No. C66947. For the last 21
years of his professional career, he has been actively involved in the design and entitlement of
many Waterfront Developments such as custom homes, seawalls, piers, platforms, floating docks
and marinas. A great number of Bulkhead Condition Reports prepared by him have been reviewed
and accepted/approved by California Coastal Commission.
All the above being said, Plamen Petrov, P.E. shall be considered a qualified preparer for
the Bulkhead Conditions Report on this project.
OBSERVATION
A cursory observation of the existing seawall/bulkhead was conducted by a representative
of our office on March 2, 2021. Observed was the visible/exposed portion of the waterfront face of
the seawall. Due to the site conditions, tie-backs were not accessible, thus not observed.
FINDINGS
The pre-cast jetted-in concrete panels and cast-in-place concrete coping of the seawall were
found in generally good condition, without noticeable evidence of distress. Some minor cracks
were observed, which is a typical condition for many of the seawalls of this vintage in the area.
PA2021-069
CONCLUSION
Based on our site observation, we conclude that the existing seawall is required to protect
the proposed principal structure on the lot. To be able to do so, the seawall shall be
repaired/reinforced/raised as reflected on the enclosed Drawings SW-0 thru SW-2. Once the
seawall is reinforced in accordance with the enclosed drawings, no repair or replacement of the
seawall shall be anticipated in the next 75. If during this period though, the seawall displays any
sign of distress that requires immediate attention, it should be repaired or replaced at that time
accordingly, without seaward encroachment from its current location.
The above conclusion was prepared based on the existing conditions, proposed drawings,
and within the inherent limitations of this study, in accordance with generally acceptable
engineering principles and practices. We make no further warranty, either expressed or implied.
PMA Consulting, Inc. appreciates the opportunity to work with you towards the successful
completion of your project. Should you have any questions regarding this report, please give us a
call.
Respectfully submitted,
Plamen Petrov, P.E.
Principal
Enclosures:
Seawall Drawings SW-0 thru SW-2
PA2021-069
C/J ~ 0
Ill 0 0 'II Ill
0 'ft
:E g <
i!" 0 i :::j -<
I: > 'II
0~1;;18;2021 REINFORCING THE EXISTING SEAWALL
LOCATED AT:
1---34-4-20---, 630 VIA LIDO NORD
DWNER / APPLICANT
DANIEL KRUSE
T.PETROV NEWPORT BEACH, CA 92663 630 VIA LIDO NORD
1---,,-ec-,~-'.P-ET_R_ov+-S-T_R_U_CT_U_R_A_L_G_E_N_E_RA-L-NO_T_E_S_&_V_IC-IN-ITY_M_A_P __ _, NEWPORT BEACH, CA 92663
; ~~~i~~;~i!~ ;~ ~~:~~~~ii g i~~~i~~;g~d ~; µ~~:~:;l;:@
;l;,:, ii!~ ~~i;J !,I~ Z58 ~ ~m m~~ :; ~
~;~~~~~ ~~~
l~~l~~~,l~l ~~h"'~~~;~; ·~ i ~';i"
~~;~~:~~;~~~~~~~~~~ ~;~ ~~~~~~i~~~~l~~~~f!~~~
~1~111!ii~l~!~I!~!~ ~:~ llll~l~~l~;i11~11111~
~ i ~~ I
PMA Coll8ulting, Ine. 8
ConsuhingStruttundEogineen
28161CwtesCt.,LegunaNiguel,CA9'1£,T7
E-~~~~cmn
"
F~ ~~~~§~;~~~~~§;t~~~ i~!~:~:i~
~::~~~~~:~;~!!~~~~:;~~~:ii~~~~
~ Iii ~
;~ ~{~~~~ ~~ ~~~~~~ ri i
·~§ •
~~~~~H~~~~~~~~~ ~~~
~~((~~~I((((~~~~ l~~
!:l~Si;Si;~~"'rSi;Si;Si;Si;Si;c"s;; ~!,1!,1 < ~cP•• ~' <§. ~ :,a
; F~ Pl r! ~~ ~ Pi
~ f!l
en
-I
::D
C:
0
-I
C:
::D
:I> r-
G)
m z m
::D
:I> r-
z
0
-I m en PA2021-069
[Il C ~ I ~ 0 m r m < ~ 0 z
<
(J)
~ .....
I
i
8 ;i~ ~I" ! ~j~ 8./g
~ !I~ ijg f,i z ~i~ ~ ;r
!",--., :j~ :1;
F''< ~i •1•
.,
~I~ l ao "• i
0
z m :E ..,
0 :D -I
m ,.
<
OWNER/APPLICANT
~8
iii~ !~ '\~
I I
I
I
I I I I I
-----------N29"'filvif"E~-
--------~-
I ----~ --l lil
ii iij iii! iii j r,111
::1 ·-P-I ' ! 'I n ,. ' ' I , i I!: h!il i !I ' I :p1! I ! Ii!!: j I! '111 ~ii hi II 111'
'' E ii
!! ; fl~
! i 11 i i 1 .! ~ ' I i
j
' I
03;1 s/2021 REINFORCING THE EXISTING SEAWALL
LOCATED AT:
1-----34-4-20---, 630 VIA LIDO NORD
DANIEL KRUSE PMA C:o-ulting, In-,.
l---~-ee-,:-:-ET_R_ov-+-N_E_WP_O_R_T_B_E_A_C_H,_C_A_9_2_66_3 ________ _, ~~o;;~~~~E:6~~ CA 92663
P.PETROV SITE PLAN & ELEVATION
ConsultingSuucw....JE.nginoers
28161CasitMCt.,Laguru,Nigud,CA9'l677
F,M,,il~~~~rom
< ;; .. 6 0
z 0 :D 0 PA2021-069
(3) EPO~'I' COATED CONT#BEAFACE
f4 EPOXY COATED TIE TYP
j
NOlE: 8
(2) EPO~'I' COATED f5 EA
ttlHiJ~-~;DLONG @ EAOl
FOR INFORI.IATION NOT SHOWN,SEEDETAILffi.
DEADMEN ELEVATION
HEAT SHRINK SLEEVE CENTEREDOVERCOUPl.£R
(") ~1~:tiTE CGuR?~N~~r ON
f0M~L!A1i;F~~Er~~eNrJL~Efil{~~~ BARE ENDS OF
2. CONNECT Tl1E TWO BAR ENDS 'MTH THE COUPLER, EACH END SHALL BE SCREWED INTO THE COIJPl.£R HALF Tl1E LENGT11 OF Tl1ECOIJPLER :: I~l]tiHE.~iif~~~&!!~ ... :DA:::U R
HE,.,TUNTIL SLEEVE ISFllLL'l'RECO\IERED
DCP COUPLER DETAIL
R --._1/~1
111=1~=~
Tt?ICAL SECTION
SANDBAG VELOCITY REDUCER DETAIL
VELOCITY REDUCER DETAIL
TIIO RO~ OF SANOBAGS THR££ BAGS HIGH
L
NE ROW OF
SANDBAGS TWO BAGS HIGH
TO£ OF SLOP£ PROTECTION DETAIL
= Tl,ISDETAILSHALLAPPLYATTI,E ENTIREPERlt.lETEROFANYEXCAVATED t.lATERIAL PILED UPATTI,EPRO-ECTSITEIN COMPIJANCE'MTI,ITEM 6 UNDER"EROSIONCONTROL NOTES"ON SHEETS-0
ANCHORPLATE1"•9""9"
W/ANCHOR NUT BEHIND
wRTEPi~~r~r #4EPOX'l'COATED
TIES@ 16" 0.C. NOTE:
;;:;;;FORMATION NOT SHOWN, SEE DETAILS@ &@ .
COIJPLERPER ICCESR-JJ67 SPECIAL INSPECTION IS REQUIRED
CROIJT SI..EEVE (")
2 LAYERS OF MOI.DABLE DENSO TAPE OVERBAREBARANDCOUPL£R
SPACEBETWEEN COIJPLER ANDBAR TOBECOMPL£TEL'l'F1LL£D 'Mll1 CORROSION INHIBITING GREASE
PREPARATION EQR Fifi 0 CIJT BARS·
1. CUT CORROSION PROTECTION AND THREAD BAR 'MTH AN
ABR,.,SI\IE SAW (DO NOT USE" TORCH)
2. g:~~U~J:~~1Nf rlF± J'1~) Ji:~u\~ TED AND CEMENT
CRLRS082134 STANDOFF FITTlNC:S WITl-1 CAP J16 GRADE
STAINLESS STEEL W/ ~r~~iZi~ ri1~tEA ~ ·• STANDOFF FITTlNG 5" l,IIN EMBED TYP(ICC
ESR-1917)
(J COUPLES PER
PANELT'l'P)
B
G
~il~~N~ PANEL -~-------,
= CARESHALL BEEXERCISEDBYTl-lECONTRACTOR
[~~1fL~l t:E z~l~~Ni:~;tHr:;R:~:~.
TOE OF SLOPE PROTECTION R I SECTION AT STEM WALL & GUARDRAIL
~2L~o:cGJ~~RAIL
SEEDETAIL(T') ,
FIJTURE T.O.W ELEV-+TT:7Q"NAV[)88---
"!,Q,_JN)~Ll,_F.S ... _:t-~0~± __
NAVD88•+12.68'±MLLW•E.S.
AVERAGE T.O. fil COPING ,.
l
e, +11.00'± NAVD88•+11.18'± MLLW
~§
!
.• ! I (E) CONC PANEL TYP --------j
:;$;:
TYPICAL SECTION
~z:~t:i~~L OTiP
~~~iif;:~t'I'
ESR-J269
COREDRILL (E)
~~~~gRr~NN. ~~~ ~:n~~G,
'MT!-IBONDING
...CENT AND FILL
~zl~l~K~T
T
~r!:~~:f~~ TO ACCOMMODATE SEA LEVEL RISE
~~Ri~ACT'I'~
RECOI.IMENDED
INSTALlATIONOFFILTER CLOT}jATPANELJOINTS PER NOTES ON SHEET S-0,0RSEALPANEL
~~~t~IB}~/ACE
FlNISH PER ARCHT
-r+,-m(<)aco,
I I W"LL. CONG I I SLAB & FTG
CONCDECK I ~~~ATE
W/#4@12" o.c, .I I PERMIT
EA WA'!' I I """"""'""' '~j-L _____________ t_ T.O. SLAB ELEV-+12.8J'NAVD88
~t' ,, ~ ~------------~ ..,._'---..,J ~(N)f4•1'-0"LG ~ : :0~~;1-Ji\owELS L ____ _j 4" EMBED _,.
~~~~\-~~~~, -:::::::::::::::::::::::::..,:::::::::,::::,·~
7 I
I I J---'
(E) TIE-BACK
& DEADMAN, WHERE OCCUR,
TOREMAINTYP
.• -~
FOR(N)CONT ~:\fEfu________;
.wm:' IN CASE IF PROPOSED BUILDING FOOTINGS INTERFERE
'MTl-lTl-lEllE-BACKS,DEEPEN FOOTINGSPER
~~ugri~iE E~~~~~1t~o~~,l~~t~s R~g~l~~l~JJ 2" CUARDISTANCEAROUNDTIE-BACKS.
K
I Cf)
(!) z f'=
OJ/ .: = ~ .. ~ wi i~.J .5 j'.~. iHU ■ }d!~
.: 'J!j ~ J~ " I ~ •
w Cf) :,
~
...J w ~
m <
0 "· o::i: ~~ 0 a> g f--' °' so ~i "'z
~ ~ ~1--------i-l-711ra~I~ ~
~ .. ~5
u V
~ ~ ~~ o::: Cl 01--
0 w :loc i"' LL.~$ 0 ~ ~ (.) > ~ ;': ~ g ~~ ~
01 >
N 0 ~ ~
,e' I
SW-2
PA2021-069