PA2021-118
FINISHES:
FLOOR COVERING:
Type 1:1/8" V.C.T. Tile to be 50% OFFSET.
Location: (RESTROOMS ONLY)
Color to be: (FORTRESS WHITE)
Type 2:26 oz. carpet.
Location: (REMAINDER)
Color to be: (RITZ BLITS 66764)
BASE:
Cove Base 1 :4" Vinyl cove.
Location: (THRU-OUT)
Color to be: (BROWN 47)
WALLS:
Covering 1:1/2" VINYL TACKBOARD (CHATFIELD CLARKE GROUP 1 TYPE 1)
over 1/2" raw gypsum. VCG only on Corridor 105 side and Office 106 side of walls.
Location: (CLASSROOMS ONLY) - see hatch
Covering height: 8'
Color to be: (SNOWBANK).
Covering 2:1/2" vinyl covered gypsum
Location: (REMAINDER)
Covering height: 8'
Color to be: (TIKI GRASS CHALK).
Covering 3:Standard FRP panels (per code)
Location: (Restrooms)
Covering height: 4'
Color: (White)
TRIM:
Wall Trim 1:Vinyl Covered batt strips at all tackboard seams (Classrooms only)
Color to be: (SNOWBANK)
Wall Trim 2:Vinyl Covered trim
Color to be: (To match VCG)
CEILING:
Type 1:2'x4' HEAVY DUTY T-Grid w/ Struts & wires
(Armstrong Tile #769A or Equal)
Height: 7'-10"
Installed at factory, held back at module lines.
Completion of ceiling installation on-site by others; not in PMI's scope.
EXTERIOR
Siding body:Color: (BEHR BENNINGTON GRAY) 8' sheets
Hood:Color: (BEHR MIDSUMMER NIGHT)
Corner trim:Color: (BEHR MIDSUMMER NIGHT)
Door & window trim: Color: (BEHR MIDSUMMER NIGHT)
Bottom horizontal trim: Color: (BEHR MIDSUMMER NIGHT)
Intermediate horizontal trim: Color: (BEHR MIDSUMMER NIGHT) separates hood & body
Top horizontal trim:Color: (BEHR MIDSUMMER NIGHT)
Module line trim:Color: (Match hood above intermediate horizontal trim & match body below)
All paint to be:COLOR MATCH WITH GLIDDEN (Satin Finish)
INTERIOR WALL CONSTRUCTION:
Framing: Stud:2X4 #2 HF equal or better @ 16" O.C.
Top plate: Single 2X4 #2 HF equal or better (Double as needed)
Bottom plate: Single 2X4 #2 HF or better bottom plate
Stud length: 92-5/8" (Ceiling Ht.)
Insulation: R-11 unfaced battens (at Classroom walls only - see hatch) (Ceiling Ht.)
Additional Interior Wall Items Included in Quoted Price:
Item 1: Full height walls (to rafters) between classrooms only for sound control.
Item 2: See Post Detail 4/2 for Post #3.
FRAME / CHASSIS:
Frame Type: Basement (CH2)
Quantity:(3) EA
Size:11'-8" X 60'-0"
Type:Outrigger @ 96" O.C.
Crossmember @ 96" O.C.
Module line Clips @ 96" O.C.
Main Rails @ 99 1/2" O.C.
Beam Size: 12" Jr. I-beam
Axles:
Module 1: Qty: Five 6000# rated with (All) brake
Offset: 4" (Toward sidewall) See Detail 1/1
Module 2: Qty: Quad 6000# rated with (All) brake
Offset: None
Module 3: Qty: Quad 6000# rated with (All) brake
Offset: 4" (Toward sidewall) See Detail 1/1
Hitch:Detachable with Standard Hitch
Tires:8x14.5 14 ply rated
Additional Frame / Chassis Items Included in Quoted Price:
Item 1: None
FLOOR CONSTRUCTION:
Floor Joist:2X8 #2 HF equal or better
Joist Length: 133-7/8"
Joist Spacing: 16" O.C.
Floor: Single layer 3/4" T&G Plywood.
Insulation:R-19 unfaced fiberglass batt
Bottom: Reinforced Plastic
Additional Floor Items Included in Quoted Price:
Item 1:N/A
EXTERIOR WALL CONSTRUCTION:
Framing:Stud:2X4 #2 HF equal or better @ 16" O.C.
Top Plate: Double 2X4 #2 HF equal or better
Bottom Plate: Single 2X4 #2 HF or better
Header: (2) 2x4 header with (1) 1/2" shim at all exterior openings (UNO)
Insulation: R-13 Kraft back fiberglass batt
Siding Type: 3/8" LP Smart-panel vertical siding (8" grooves) with barricade wrap underlayment.
Sidewall Height: See cross section for heights
ROOF CONSTRUCTION:
Roof Type: Complex
Roof Slope: 1/4 in 12
Rafter size: 2X8 #2 HF equal or better
(Roof diaphragm chord strap 'ST2215' at rafters installed on-site, see 5/2)
Rafter Length: MOD 1 & 3: 135 1/2"
MOD 2: 134"
Spacing:16". O.C.
Mate Beam: Multi-layer plywood
Height:20" to 27 1/2" to 20"
Length: 60'
No. of Layers: 3
No. of Beams: 4
Insulation: R-19 unfaced fiberglass batt with support netting
Sheathing: 1/2" 24/0 Sheathing
Roofing:45 mil single ply EPDM over 1/2" Gypsum
Color: White
Additional Roof Items Included in Quoted Price:
Item 1: N/A
EXTERIOR/INTERIOR DOORS:(SEE DOOR SCHEDULE)
WINDOWS:(SEE WINDOW SCHEDULE)
CLOSEUP:
Type:Medium
Notes:Module WILL NOT exceed 12'-0" (Except door hardware)
APPLIANCES:
None provided
ACCESSORIES:
None provided
SKIRTING:
None provided VARIESGRADE
FLOOR JOIST
ML
EXTERIOR WALL
(SIDEWALL)
MAIN RAIL
(I-BEAM)
24 1/4"99 1/2"16 1/4"
11'-8" FLOOR WIDTH
OUTRIGGER
OUTRIGGER
TYPICAL OFFSET TOWARDS SIDEWALL
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH CLASSROOM
36 X 60
PMI-4943-3660
DRAWING INDEX
SHEET 1: SPECIFICATIONS AND CONDITIONS
SHEET 2: FLOOR PLAN, STRUCTURAL LEGEND, DOOR, WINDOW, PLUMBING SCHEDULES, PLUMBING FIXTURE DETAILS
SHEET 3: ELECTRICAL PLAN, ELECTRICAL SCHEDULE, ELECTRICAL CALCS AND ELECTRICAL NOTES
SHEET 4: REFLECTED CEILING PLAN, DETAILS, PLUMBING SCHEMATICS
SHEET 5: HVAC PLAN, HVAC SCHEDULE
SHEET 6: EXTERIOR ELEVATIONS, BUILDING CROSS-SECTION
"PLEASE REVIEW DRAWINGS AND SPECIFICATIONS
CAREFULLY. WHILE EVERY EFFORT IS MADE TO
ASSURE THE DRAWINGS REFLECT THE
EXPECTATIONS AND QUOTATION, THE FINAL
CONSTRUCTION WILL BE BASED SOLELY ON THE
SPECIFICATIONS AND DRAWINGS APPROVED."
APPROVED
APPROVED EXCEPT AS NOTED
REVISE AND RESUBMIT
BY:DATE:
DATA PLATE AND STATE DECAL TO BE LOCATED ON
LOWER RIGHT HAND CORNER OF THE ENDWALL
OPPOSITE THE HITCH END OF THE MODULE.
SPRINKLERS REQUIRED. NO
INSTALLED AT.N/A
CONTRACTED BY.N/A
INSTALLED BY.N/A
SPECIAL CONDITIONS AND OR
LIMITATIONS:
IDENTIFICATION:
NOTES:
1
1. SITE PLAN NOT AVAILABLE AT THIS TIME. BUILDING
DESIGNED TO HAVE FIRE SEPARATION DISTANCE
GREATER THAN 10 FT. TO PROPERTY LINES AS PER
LOCAL BUILDING DEPARTMENT REQUIREMENTS.
2. THIS PLAN MAY BE REVERSED AND/OR MIRRORED.
3. SEE STRUCTURAL PACKAGE FOR ALL STRUCTURAL
STANDARDS AND DETAILS.
4. COMPLIANCE WITH HCD IGNITION RESISTANT
CONSTRUCTION SYSTEM REQUIREMENTS?
(CBC CHAPTER 7A) NO .
5.TO BE INSTALLED ON A PERMANENT FOUNDATION? NO .
6. THIS BUILDING IS DESIGNED TO COMPLY WITH THE
COMMERCIAL MODULAR REQUIREMENTS OF
CALIFORNIA CODE OF REGULATIONS TITLE 25.
MANUFACTURER:
DESIGN CRITERIA / LOADS:
NOT INCLUDED IN SCOPE OF WORK:
1. PORCHES, STEPS, AND RAMPS TO BE SUPPLIED AND
INSTALLED BY OTHERS IN ACCORDANCE WITH THE
LOCAL BUILDING DEPARTMENT
2. PORTABLE FIRE EXTINGUISHERS TO BE SUPPLIED AND
INSTALLED ON SITE BY OWNER IN ACCORDANCE WITH
LOCAL BUILDING DEPARTMENT
3. ACCESSIBLE DRINKING FOUNTAIN TO BE PROVIDED
ON SITE BY OWNER LOCATED WITHIN 500 FEET ON AN
ACCESSIBLE ROUTE
4. ADDITIONAL HANDICAP TOILET FACILITIES PROVIDED
IN ADJACENT BUILDING ON THE SAME PROPERTY
LOCATED WITHIN 500 FEET ON AN ACCESSIBLE ROUTE
5. SERVICE SINK PROVIDED IN ADJACENT BUILDING ON
THE SAME PROPERTY
6. ANY REQUIRED FIRE/SMOKE DETECTION AND/OR
SUPPRESSION TO BE INSTALLED BY OTHERS ON SITE
IN ACCORDANCE WITH THE LOCAL BUILDING
DEPARTMENT
7. THE BUILDING OWNER IS RESPONSIBLE FOR THE
DEVELOPMENT & DESIGN OF ALL SITE REQUIRED
ACCESSIBILITY ELEMENTS. THESE ELEMENTS ARE
NOT INCLUDED IN THE SCOPE OF THIS DESIGN.
SUBMITTALS ARE REQUIRED BY OWNER THROUGH
THEIR DESIGN PROFESSIONAL
CA: 2019 CBC, 2019 CPC, 2019 CMC, 2019 CEC,
2019 CA Energy, & 2019 CBC Chapter 11B Accessibility
NO OF MODULES.3
BUILDING SQ.FT.2100
TYPE OF CONSTRUCTION. VB
OCCUPANCY USE GROUP. E (Ages 5 thru 8)
OCCUPANCY LOAD.75 (Classrooms)
4 (Remainder)
79 Total
FLOOR LIVE LOAD.50 psf. (2000 lb concentrated)
(100 psf. @ corridor)
ROOF LIVE LOAD.20 psf.
ROOF DEAD LOAD.10 psf.
ROOF SNOW LOAD.20 psf.
WIND LOAD.
OCCUPANCY/RISK CATG. II
SEISMIC
PERMISSIBLE GAS TYPE. N/A
CLIMATE ZONE.6
NAME AND DATE OF CODES;
Ss=3.730, S1=1.389
Site Class 'D'
Design Category 'E'
MANUFACTURER & ADDRESS PHOENIX MODULAR
5301 W. MADISON ST.
(SEE WEBSITE FOR PHOENIX, AZ. 85043
WARRANTY INFORMATION)PHOENIXMODULAR.COM
STATE REQUIRED INFORMATION ON USE AND
LOCATION OF FACTORY-BUILT BUILDING
1. PROPOSED ADDRESS
2. EXPLANATION OF
AND/OR LOCATION OF UNIT.
BUILDING USE.
3. SET TYPE
ASSUMED F.F. TO BE 4" A.F.G.
CLASSROOMS
NEWPORT BEACH, CA 92633
1541 MONROVIA AVE.
PAD/PIER PIT SET
2019 CBC - 115 MPH, EXP. C
SITE INSTALLED FIRE ALARM
RED TAG:
R. MARK STEELE, P.E.
CORPORATE ENGINEER
SUNBELT MODULAR, INC
5301 W. MADISON ST.
PHOENIX, AZ. 85043
(602) 327-47695301 W. MADISON ST. - PHOENIX, AZ 85043PH 602-447-6460 FAX 602-447-6476SUNBELT MODULAR, INC. AMTEX I INDICOM I PHOENIX I M.R. STEELTHESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
6
OF
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH
CLASSROOM
STATES:
CALIFORNIA
SERIAL NUMBERS:
PMI-4943-3660
DRAWN BY:
RH / KT
PLOT DATE:
5/13/2021
REV # / DATE:
01 04/20/2021 PR# 4 & 5
02 04/21/2021 PR# 8
03 04/27/2021 PR# 9
----
----
----
----
----
----PHOENIXMODULARFINAL RELEASE
5/13/2021
PRODUCTION SET
1 AXLE OFFSET
3/8" = 1'-0"
PA2021-118
HVAC3 ton 5KwMODULE ( )1MODULE ( )2MODULE ( )3HC
9'-8 1/2"
7'-10"
60'-0"6'-4 1/2"CH
7'-4"
CH
24'-5"
21'-1 1/4"21'-1 1/4"15'-0"35'-0"11'-8"11'-8"11'-8"0203
040404
02 02
011011011A11
47'-3"
1A1
26'-0"
1 A
1'-10"
A 1 11
A
1
7'-0"53'-10"
1
1
1
1
1
A6'-6"1
1
1
1
1
1
10"
10"
1
1
1
1
1
1
1
1
1
1
1
HVAC3 ton 5KwHVAC3 ton 5KwPANEL A
PANEL B
PANEL C10'-11"5'-0"34'-3"22'-11 1/2"1
1
1
1 2 2
2
3 S30S70485 SF
CLASSROOM
CARPET
101
485 SF
CLASSROOM
CARPET
102
587 SF
CLASSROOM
CARPET
103
86 SF
OFFICE
CARPET
104
120 SF
CORRIDOR
CARPET
105
62 SF
BOYS
RESTROOM
V.C.T.
107
47 SF
GIRLS
RESTROOM
V.C.T.
108
47 SF
UNISEX
RESTROOM
V.C.T.
109
7'-4"
CH
30'-6"
16'-8 3/4" SPAN21'-6 3/4" SPAN21'-8 1/2" SPAN 3'-8 1/2"22'-11 1/2"7'-0"
2'-0"
17'-3 1/2"
11
38'-10 1/4"5'-5 1/2"B B B
28'-0"35'-8 1/2"46'-6"
1 1 1111
DOORS:
Qty NO.Type Jamb Wall Thickness Glazing Size Rough Opening U-Factor Color Closer Deadbolt Hardware Fire Rating Keying Notes
3
3
1
3
01
02
03
04
STEEL, INSULATED 18 GA.
PREFINISHED WOOD
HOLLOW CORE
PREFINISHED WOOD
HOLLOW CORE
PREFINISHED WOOD
HOLLOW CORE
TELL 16 GA.
BRONZE
TIMELY METAL
JAMB
BROWNTONE
TIMELY METAL
JAMB
BROWNTONE
TIMELY METAL
JAMB
BROWNTONE
4 7/8"
5"
4 1/2"
4 1/2"
24" X 60" FRENCH 15 LITE
KIT, DUAL GLAZED
NONE
NONE
NONE
3/0X6/8
3/0X6/8
3/0X6/8
3/0X6/8
38" x 81"
37 1/2" x 81 1/4"
37 1/2" x 81 1/4"
37 1/2" x 81 1/4"
0.31
N/A
N/A
N/A
BEHR MIDSUMMER NIGHT
(SAME BOTH SIDES)
LEGACY OAK
LEGACY OAK
LEGACY OAK
HYDRAULIC
NONE
NONE
NONE
NONE
NONE
NONE
NONE
CLASSROOM LOCK,
GRADE 2
PASSAGE LEVER, TELL
GRADE 2
KEYED LEVER, GRADE 2
(WITH SHIMS)
PRIVACY LEVER, TELL
GRADE 2 (WITH SHIMS)
NONE
NONE
NONE
NONE
ALIKE
N/A
SEPERATE
N/A
DRIP CAP, (2) STD & (1) NRP HINGES,
WEATHERSTRIPPING, THRESHOLD, &
DOOR SWEEP.
HINGES & WALL MOUNT STOPS
HINGES & WALL MOUNT STOPS
HINGES & WALL MOUNT STOPS
WINDOWS:
Qty NO.Type Glazing Size Rough Opening U-Factor SHGC Mini-Blind Notes
6
3
A
B
PARAMOUNT VINYL
SERIES (WHITE)
HORIZONTAL
SLIDER
WHITE VINYL
HORIZONTAL
SLIDER
CLEAR, DUAL
GLAZED, 16 LITE
FRENCH GRID
CLEAR, DUAL
GLAZED, LOW-E
4/0X3/0
3/0X1/6
48" x 36"
36" x 18"
0.31
0.31
0.20
0.22
NONE
NONE
HEADER AT 81" AFF
HEADER AT 81" AFF
6"
36" MIN.20" TO 25"12" TO 15"20" TO 25"12" TO 15"14" TO 17"42"1'-0"
MAX
HANDICAPPED WATER
CLOSET FRONT VIEW
(CHILD HT. / AGES: 5 - 8)
HANDICAPPED WATER
CLOSET SIDE VIEW
(CHILD HT. / AGES: 5 - 8)
34" TO 36"18" MIN.21" TO 30"18" MIN.21" TO 30"24" TO 42"1-1/2"MINHATCHING LEGEND:
2x4 WALLS (92 5/8" STUDS) w/ R-11 UNFACED
CEILING HEIGHT INSULATION. CEILING
HEIGHT 1/2" TACKBOARD OVER 1/2" RAW
GYPSUM. SEAMS COVERED WITH VINYL
COVERED BATTS.
2x4 EXTERIOR WALLS w/ CEILING HEIGHT 1/2"
TACKBOARD OVER 1/2" RAW GYPSUM. SEAMS
COVERED WITH VINYL COVERED BATTS.
2x4 WALLS (FULL HEIGHT) w/ FULL HEIGHT
R-11 UNFACED INSULATION. CEILING HEIGHT
1/2" TACKBOARD (CLASSROOM SIDE) OVER
1/2" RAW GYPSUM. SEAMS COVERED WITH
VINYL COVERED BATTS. 1/2" RAW GYPSUM
REMAINDER WAY TO RAFTERS ON BOTH
SIDES OF WALL. CEILING HEIGHT1/2" VCG
(RAW GYP. ABOVE) ON NON-CLASSROOM
SIDE ONLY. SEE FLOOR PLAN.
STRUCTURAL LEGEND
Symbol Description Qty
**ALL INTERIOR DIMENSIONS ARE FROM FINISH TO FINISH
& ALL EXTRIOR DIMENSIONS ARE FROM STUD TO STUD**
X
X
1
2
3
SHEARWALL TAG
(SEE STRUCTURAL PACKAGE FOR
DESCRIPTION, SEE SHEET 24)
HOLD DOWN TAG
(SEE STRUCTURAL PACKAGE FOR
DESCRIPTION, SEE SHEET 24)
DIAPHRAGM CHORD TIE SIMPSON 'ST2215'
(SEE DETAIL 5/2)
(3) 2X4 HF #2 POST ON EACH SIDE OF
MOD-LINE W/ BLOCKING UNDER POST (TYP.
#3 HOLDOWN STRAP @ TOP & BOTTOM)
(3) 2x4 HF #2 POST ON EACH SIDE OF
MOD-LINE W/ BLOCKING UNDER POST (TYP.
#3 HOLDOWN STRAP @ TOP & BOTTOM)
(3) 2x4 HF #2 POST ON CLASSROOM SIDE
AND (4) 2x4 HF #2 POST ON CORRIDOR
SIDE OF MOD-LINE (SEE DETAIL 4/2) W/
BLOCKING UNDER POST (TYP. #3
HOLDOWN STRAP @ TOP & BOTTOM)
TYP @ 4
LOCATIONS
TYP @ 40
LOCATIONS
TYP @ 4
LOCATIONS
TYP @ 4
LOCATIONS
TYP @ 3
LOCATIONS
TYP @ 1
LOCATIONS
PLUMBING:
Symbol Type Qty Note Description
CHHC
S30
S70
Water Closet
Urinal
Grab Bars
Paper
Holder
Lavatory
Mirror
Water
Heater
Water
Heater
Water
Hammer
In-line
Strainer
Supply
DWV
System
R.R. Sign
R.R. Sign
R.R. Sign
Partition(s)
3
1
3
3
3
3
1
1
2
1
1
1
1
1
1
1
AS2599001.20
Low Flow
AS6047.121.002
Flush Valve w/
Ferguson F-182
Outside Stem
AS500g.055.020
Seat
Low Flow
Low Flow
Mixing Valves
Chronomite:
S30LLMB120V or
equal
Chronomite:
S70WMD240V or
equal
1"
2"
Copper Inlet
Door Mtd
Door Mtd
Door Mtd
Color to be:
(532 LATTE)
Floor mtd. ADA elongated child height with flush
valve and shut off valve / flush handle to be on
open side of r.r. (Factory standard) See Fixture
Details 2/2 for mounting heights.
Wall hung white vitreous with commercial grade
flush valve w/ rim at 15" a.f.f. (Factory standard)
Set(s) with (1) each 42", 36" horizontal, and 18"
vertical
Single roll wall mount toilet paper holder mtd.
ADA height (Factory standard)
19" X 17" White vitreous wall hung with ADA
handles and shut off valves mounted at child
height. (Factory standard) See Fixture Details 3/2
for mounting heights.
24"x36" w/ clips mtd. 38" to bottom edge (Factory
standard)
Insta-Hot Chronomite S-30 (Electric - 120V)
Insta-Hot Chronomite S-70 (Electric - 240V)
Water hammer arrestor
Strainer at supply entrance
Type M copper or Pex
ABS Schedule 40 (Manifold is by others)
Unisex ADA restroom sign w/ braille mtd. 59"
a.f.f. to center
Women's ADA restroom sign w/ braille mtd. 59"
a.f.f. to center
Men's ADA restroom sign w/ braille mtd. 59" a.f.f.
to center
18" Prefinished metal urinal partition(s).
TOP TRIM (SHIP LOOSE
& SITE INSTALLED
OVER TENSION TIE)
TENSION TIE (SHIP LOOSE
& SITE INSTALL)
4" L.P. TRIM (SHIP LOOSE
& SITE INSTALLED)
J-RAIL
(FACTORY
INSTALLED)MODULELINE6" L.P. TRIM
(FACTORY
INSTALLED)
1'-6"1'-6"
J-RAIL (SHIP LOOSE
& SITE INSTALLED
OVER TRIM)
WALL FINISH
VALUE
(LBS)STRAP TYPE FASTENERS
SIMPSON 'ST2215'(20) 10d NAILS
(0.148"Ø x 1-1/2")1580#
LAV CLEARANCES
(ALL RESTROOMS)34" TO 37"17" MIN
FIXTURE
DEPTH
6" MAX
TOE CLEARANCE9" MIN26" MIN31" MAX24" MIN8"
KNEE CLEARANCE
CLEAR FLOOR SPACE
AT LAVATORIES
(ALL RESTROOMS)30" MIN.17" MIN.
19"
MAX.48" MAX.
5"
CLEAR
FLOOR
SPACE
HANDI GUARD ON
ALL EXPOSED PIPESMIRROR
MOD LINE
2x STUD
EA. SIDE
3-STUD COLUMN
WALL
FINISH
(TYP)
WALL
FINISH
(TYP)
2-STUD COLUMN
1 FLOOR PLAN
1/4"=1'-0" SQUARE FOOTAGE - 2100 S.F.
OCCUPANCY LOAD = 100
2
5 ROOF DIAPHRAGM MODLINE CHORD TIE
3/4" = 1'-0"
R. MARK STEELE, P.E.
CORPORATE ENGINEER
SUNBELT MODULAR, INC
5301 W. MADISON ST.
PHOENIX, AZ. 85043
(602) 327-47695301 W. MADISON ST. - PHOENIX, AZ 85043PH 602-447-6460 FAX 602-447-6476SUNBELT MODULAR, INC. AMTEX I INDICOM I PHOENIX I M.R. STEELTHESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
6
OF
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH
CLASSROOM
STATES:
CALIFORNIA
SERIAL NUMBERS:
PMI-4943-3660
DRAWN BY:
RH / KT
PLOT DATE:
5/13/2021
REV # / DATE:
01 04/20/2021 PR# 4 & 5
02 04/21/2021 PR# 8
03 04/27/2021 PR# 9
----
----
----
----
----
----PHOENIXMODULARFINAL RELEASE
5/13/2021
PRODUCTION SET
4 COLUMN DETAIL
1" = 1'-0"
2 FIXTURE DETAILS
1/4" = 1'-0"
3 FIXTURE DETAILS
1/4" = 1'-0"1
1
2
3
3
PA2021-118
GFCI
WR 3B
HVAC2,4C
3 ton 5KwPC 1C MODULE ( )1EXIT
1C
5A
5A
5A
MODULE ( )2MODULE ( )3HC
CH CH
T
T
T
EXIT
1C
EXIT
1B
SHIPPED
LOOSE
PC 1B
SHIPPED
LOOSE
PC 1C
SHIPPED
LOOSE HVAC2,4B
3 ton 5KwHVAC2,4A
3 ton 5KwPANEL A
PANEL B
PANEL C
GFCI
WR 3AS307AS706,8ACH
1A
3DIM 3DIM 3DIM
3 3 3
O O O
O
1B
GFCI
+42"5A
TR
GFCI
+42"5A
TR
GFCI
+42"3A
TR
FA
+46
6C P+46
H+82
P+46
H+82
P+46
H+82
XH
+102
3A
TR
5A
TR
3A
TR
3B
TR
5C
TR
3C
TR
3B
TR
3C
TR
3B
TR
3A
TR
5C
TR
3C
TR
3C
TR
5C
TR
3B
TR 3B
TR
5C
TR
3B
TR
3C
TR
5A
TR
H +82
DIM
6
3A
TR
ELECTRICAL:
Symbol Type Qty Note Description
4K
6K
PC
EXIT
EXIT
EXIT
3
O
DIM
3DIM
OCC
GFCI
WR
TR
TR
GFCI
6
FA
P
H
XH
RE
A/V SDD
T
Elec Service
Elec
Raceway
Elec Panel
Lights
Lights
Lights
Lights
Emerg. Light
Emerg. Light
Exit Sign
Exit Sign
Emerg. Light
Switch
Switch
Switch
Switch
Occupancy
Sensor
Receptacle
Receptacle
Receptacle
Receptacle
J-Box
J-Box
J-Box
J-Box
J-Box
J-Box
Water
Heater
J-Box
Water
Heater
J-Box
J-Box
Audio /
Visual
Indicator
Exhaust
Fan
T-Stat
Device Color
1
1
3
3
10
3
3
3
3
1
1
2
3
4
1
3
4
3
2
21
3
9
1
1
3
4
1
1
1
3
3
3
3
1
12-Space
Leviton LP212-3B
4000 Lumen
6000 Lumen
Westgate:
LSW-30CW-PC or
equal
Topaz:
F-FM11/15/RN/
P/30/WH or equal
Red lens
Red lens
Red lens
Wattstopper:
IOS-DOV or equal
Lutron: DVTV or
equal
Lutron: DVSTV or
equal
Sensor: CI-205 /
Power pack:
BZ-150 or equal
3/4" Conduit
stubbed above
ceiling
Future inlet
Relay: #90370
Air Products (MS
Series):
MS-RA/P/A or
equal
Broan: 671 or
equal
White Rogers:
1F951277
120/240V 60 HZ. single phase
MC Cable/flex
120/240v 1 PH 125 amp panel w/ 125 amp
main breaker. Exterior NEMA 3R mounted
60" a.f.f. to top (Factory standard)
2'x4' Diffused LED recessed lay-in with
dimmable electronic ballast (Factory
standard)
2'x4' Diffused LED recessed lay-in with
dimmable electronic ballast (Factory
standard)
30W LED porch light with photocell mtd. 82"
a.f.f. (Shipped loose)
15W Surface mounted 1100 lumen LED light
Combo dual emergency light/exit sign with
battery backup mtd. 88" a.f.f. (Factory
standard)
Exterior remote head mtd. 90" a.f.f. (Mounted
in octagon box) Shipped loose
Ceiling mount, 120v with battery backup
Wall mount (88" a.f.f.), 120v with battery
backup
Interior double head battery pack mtd. 88"
a.f.f. (Factory standard)
15a/120v 3-Way wall mtd. single toggle w/
cover plate (Factory standard)
20a/120v Wall mtd. occupancy / vacancy
sensor w/ cover plate mtd. 46" a.f.f.
0-10v Wall mtd. dimming w/ cover plate mtd.
46" a.f.f.
0-10v Wall mtd. 3-way dimming w/ cover
plate
Ceiling mounted occupancy sensor w/ power
pack
20a/120v Duplex w/ cover plate mtd. 18" a.f.f.
(Factory standard)
20a/120v GFCI 'WR' rated exterior
receptacle with weatherproof in-use cover
mtd. 18" a.f.f. (Factory standard)
20a/120v Tamper resistant duplex w/ cover
plate mtd. 18" a.f.f. (Factory standard)
20a/120v GFCI Tamper resistant duplex w/
cover plate mtd. 42" a.f.f. (Factory standard)
4x4 Empty box w/ sngl. gang mud ring, and
blank cover plate mtd. 18" a.f.f. for future
phone/date (Factory standard)
6x6x6 Empty semi-recessed NEMA-3R box
w/ metal cover and 3/4" conduit stubbed
above ceiling (Factory standard)
20a/120v 4x4 Wired j-box w/ sng gang mud
ring, and cover plate mtd. 46" a.f.f. for future
fire alarm control panel provided by fire alarm
installer (Factory standard)
4X4 Empty J-box w/ sng gang mud ring,
cover plate and 3/4" conduit stubbed above
ceiling mtd. 46" a.f.f. for pull station by alarm
provider (Factory standard)
4X4 Empty J-box w/ extension ring, cover
plate and 3/4" conduit stubbed above ceiling
mtd. 82" a.f.f. for horn / strobe by alarm
provider (Factory standard)
4X4 Empty exterior j-box w/ sng gang mud
ring, cover plate and 3/4" conduit stubbed
thru wall mtd. 102" a.f.f. for horn by alarm
provider (Factory standard)
120v/30a 4x4 Wired box w/ sng gang mud
ring and cover plate for water heater mtd. 18"
a.f.f. (Factory standard)
240v/35a 4x4 Wired box w/ sng gang mud
ring and cover plate for water heater mtd. 18"
a.f.f. (Factory standard)
Relay mountd in 4x4 j-box w/ cover plate
mtd. to rafter / install low voltage wire to
HVAC terminal block (See Details 3/5 & 4/5).
4x4 J-box w/ sng gang mud ring, and face
flush w/ ceiling for Audio/Visual indicator w/
24 AWG wire in flex conduit connected to
smoke duct detector @ HVAC unit (See
Details 3/5 & 4/5).
70 CFM Ceiling mounted / vent thru wall
Programmable T-Stat(s) mtd. 46" a.f.f.
Color to be: (IVORY) / Exterior device(s) and
mansonry boxes with metal cover plate as
applicable
NOTE:
1. ALL A.F.F. DIMENSIONS ARE TO THE CENTER OF THE DEVICE
BOX UNLESS NOTED OTHERWISE (REFER TO SCHEDULE AND
PLANS FOR HEIGHTS).
2. ALL ELECTRICAL ITEMS ARE FACTORY STANDARD UNLESS
NOTED OTHERWISE.
3. BLANK COVERS WILL BE PROVIDED ON J-BOXES UNLESS
NOTED OTHERWISE.
4. ALL EXTERIOR ELECTRICAL DEVICES TO BE WEATHERPROOF.
1 ELECTRICAL PLAN
1/4"=1'-0"
3
R. MARK STEELE, P.E.
CORPORATE ENGINEER
SUNBELT MODULAR, INC
5301 W. MADISON ST.
PHOENIX, AZ. 85043
(602) 327-47695301 W. MADISON ST. - PHOENIX, AZ 85043PH 602-447-6460 FAX 602-447-6476SUNBELT MODULAR, INC. AMTEX I INDICOM I PHOENIX I M.R. STEELTHESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
6
OF
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH
CLASSROOM
STATES:
CALIFORNIA
SERIAL NUMBERS:
PMI-4943-3660
DRAWN BY:
RH / KT
PLOT DATE:
5/13/2021
REV # / DATE:
01 04/20/2021 PR# 4 & 5
02 04/21/2021 PR# 8
03 04/27/2021 PR# 9
----
----
----
----
----
----PHOENIXMODULARFINAL RELEASE
5/13/2021
PRODUCTION SET
1
PA2021-118
HVAC3 ton 5KwPC
6"
8"
10"
8"
10"
12"MODULE ( )1EXIT MODULE ( )2MODULE ( )31'-2"8"1'-1"1'-2"8"1'-4"6"1'-2"8"6"
6"
3'-0 1/2"
3'-0 1/2"
1'-5 3/4"
1'-8"11"1'-8"1'-11 1/2"2'-3"
4K
1A
6K
1B
6K
1B
6K
1B
6K
1B
6K
1C
6K
1C
6K
1C
6K
1C
6K
1C
6K
1C
1A 1A 1A
4K
1A
4K
1A8"
6"6"
T
10"10"
T
10"10"
T
10"
10"
10"
10"
10"
10"
10"
EXIT EXIT
PCPC HVAC3 ton 5KwHVAC3 ton 5KwPANEL A
PANEL B
PANEL C10"10"10"70 CFM
1A
70 CFM
1A
70 CFM
1A
3DIM 3DIM 3DIM
3 3 3
O O O
O
OCC OCC
OCCEXIT1AEXIT1A
OCC
DIM
RE
RE
RE
A/V SDD
A/V SDD
A/V SDD
8"
INDICATES T-GRID
SUSPENDED CEILING
INSTALLED @ FACTORY
INDICATES SUSPENDED
CEILING HOLD-BACK @
MATELINES, TO BE
COMPLETED ON-SITE
BY OTHERS
CEILING LEGEND
PLUMBING
VENT
PREMOLDED
EPDM PIPE BOOT
CLAMPING RING
LAP SEALANT
6" MINLAP
SEALANT
BUTYL TAPE
TAPE PRIMER
ROOF UNDERLAYMENT EPDM
MEMBRANEROOF SHEATHING
LP TRIM
END JOIST OR
DBL RIM JOIST
FLOOR DECKING
WALL STUDS
@ 16" O.C.
LP SIDING
3/4" BOTTOM
PLATE
P.T. FILLER
SAN-T2"2"URINAL
C.O.
V.T.R
3"
LTTY
WASTE & VENT LEGEND
DESCRIPTIONSYM
WASTE DRAIN (FACTORY INSTALLED)
WASTE DRAIN (SUPPLIED & INSTALLED BY OTHERS)
WASTE VENT (FACTORY INSTALLED)
NOTE:
1. ALL PIPE TO BE ABS SCHEDULE 40 & WILL SLOPE 1/4
PER FOOT.
2. PLUMBING MANIFOLD TO BE SUPPLIED & INSTALLED
AT SITE BY OTHERS.
SAN-T2"3"W.C.
SAN-T2"2"LAV.
LTTY
SAN-T2"3"W.C.
LTTY
SAN-T2"2"LAV.
LTTY
LTTY
LTTY
SAN-T2"3"W.C.
SAN-T2"2"LAV.
LTTY HAMMERLAV.1/2"1/2"1"W.C.
2" INLET
G.V.
INLINE
STRAINER
COLD & HOT SCHEMATIC
1. MAX PRESSURE RANGE @ CONNECTION:
2. MAX DEVELOPED LENGTH:
NOTE:
A. PEX HOT / COLD WATER SUPPLY MAY BE INSTALLED
ABOVE CEILING.
30-45 (UPC)
100'1"W.C.
LAV.1/2"1/2"3/4"URINAL
1"W.C.
LAV.1/2"1/2"HAMMER1 REFLECTED CEILING PLAN
1/4"=1'-0"
4
R. MARK STEELE, P.E.
CORPORATE ENGINEER
SUNBELT MODULAR, INC
5301 W. MADISON ST.
PHOENIX, AZ. 85043
(602) 327-47695301 W. MADISON ST. - PHOENIX, AZ 85043PH 602-447-6460 FAX 602-447-6476SUNBELT MODULAR, INC. AMTEX I INDICOM I PHOENIX I M.R. STEELTHESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
6
OF
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH
CLASSROOM
STATES:
CALIFORNIA
SERIAL NUMBERS:
PMI-4943-3660
DRAWN BY:
RH / KT
PLOT DATE:
5/13/2021
REV # / DATE:
01 04/20/2021 PR# 4 & 5
02 04/21/2021 PR# 8
03 04/27/2021 PR# 9
----
----
----
----
----
----PHOENIXMODULARFINAL RELEASE
5/13/2021
PRODUCTION SET
2 PLUMBING VENT
1 1/2"=1'-0" FACTORY INSTALLED
3 WALL FINISH
1 1/2"=1'-0" AT FLOOR
1
PA2021-118
HVAC3 ton 5Kw6"
8"
10"
8"
10"
12"MODULE ( )1MODULE ( )2MODULE ( )3TS-3TS-3TS-322x10
22x10
1'-8"16x1016x1016x10
22x1022x1022x1022x1022x10
8"
6"6"
T
22x1022x1022x1022x10
22x1022x1022x1022x10
22x10
22x10
10"10"
T
10"10"
T
10"
10"
10"
10"
10"
10"
10"
22x1016x1016x1016x10
22x1016x1016x1016x10 5'-8"9'-8"5'-6"9'-6"2'-4"6'-8"HVAC3 ton 5KwHVAC3 ton 5KwPANEL A
PANEL B
PANEL C
70 CFM 70 CFM 70 CFM
29'-0"37'-0"49'-0"
22x10
8"
16x101'-0"HVAC:
Symbol Type Qty Note Description
HVAC Heat Pump
HVAC Unit
Duct
Sleeve
Return Air
Plenum
Fiberglass
Duct
Fiberglass
Duct
Fiberglass
Duct
Fiberglass
Duct
Fiberglass
Duct
Fiberglass
Duct
Supply
Diffusers
Supply
Diffusers
Supply
Diffusers
R/A Grille
R/A Grille
R/A Grille
Duct type
3
3
3
8
2
1
16
1
2
3
2
7
2
6
1
1
CRV - Smoke Duct
Detector - FIRE
ALARM RELAY
6"
8"
10"
8"
10"
12"
3 Ton heat pump with 5KW heat strip 11 EER end
mount unit / Model: W36HB-A05 or equal
(See Details 3/5 and 4/5 for J-box locations and
wiring diagram)
29"x9" To 22"x10" Galvanized sleeve, 16" long
32"x7" Return air plenum w/ 28"x14"x4" tap-in
16"x10"x10'-0" Fiberglass
16"x10"x7'-6" Fiberglass
22"x10"x2'-6" Fiberglass
22"x10"x10'-0" Fiberglass
22"x10"x7'-6" Fiberglass
22"x10"x5'-0" Fiberglass
24" x 24" 4-way throw diffuser with start collar, collar
w/ scoop and damper, and flex (Factory standard)
24" x 24" 4-way throw diffuser with start collar, collar
w/ scoop and damper, and flex (Factory standard)
24" x 24" 4-way throw diffuser with start collar, collar
w/ scoop and damper, and flex (Factory standard)
24" x 24" Perforated lay-in with start collar, collar, and
flex (Factory standard)
24" x 24" Perforated lay-in with start collar, collar, and
flex (Factory standard)
24" x 24" Perforated lay-in with start collar, collar, and
flex (Factory standard)
R-4.2 Fiberglass insulation. Flex duct not to exceed
5'
CEILING MTD.
INDICATOR
LOW VOLTAGE WIRE FROM
ADDED CONTACTS
J-BOX FOR FUTURE
FIRE ALARM
LOW VOLTAGE WIRE FROM
SMOKE DETECTOR TO
INDICATOR
C B/W1
G W2
RT W3
R 1
Y1 2
Y2 3
A 4
D 5
L 6
BLACK / RED TO
CEILING BOX
BLUE / WHITE
TO CEILING BOX
WIRE TO T-STAT
T
R
O
U
B
L
E
A
L
A
R
M
ADDED CONTACTS FOR
SMOKE DETECTION
ALARM
ALL WIRE TO BE #18 AWG (LOW VOLTAGE)
COM
OPEN
COM
OPEN
CONNECT TO
REMAINING BLACK
WIRE FROM T/R
BUTTON
CONNECT TO BLACK
WIRE FROM PILOT
LED & BLACK WIRE
FROM T/R BUTTON
CONNECT TO BLACK
WIRES FROM GREEN
& RED LED
CONNECT TO RED
WIRE FROM ALARM
LED
T-STAT WIRE COMING
FROM THE SMOKE
DETECTOR
WIRING FOR INDOOR
CEILING INDICATOR
1 HVAC PLAN
1/4"=1'-0"
5
R. MARK STEELE, P.E.
CORPORATE ENGINEER
SUNBELT MODULAR, INC
5301 W. MADISON ST.
PHOENIX, AZ. 85043
(602) 327-47695301 W. MADISON ST. - PHOENIX, AZ 85043PH 602-447-6460 FAX 602-447-6476SUNBELT MODULAR, INC. AMTEX I INDICOM I PHOENIX I M.R. STEELTHESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
6
OF
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH
CLASSROOM
STATES:
CALIFORNIA
SERIAL NUMBERS:
PMI-4943-3660
DRAWN BY:
RH / KT
PLOT DATE:
5/13/2021
REV # / DATE:
01 04/20/2021 PR# 4 & 5
02 04/21/2021 PR# 8
03 04/27/2021 PR# 9
----
----
----
----
----
----PHOENIXMODULARFINAL RELEASE
5/13/2021
PRODUCTION SET
3 ADDED WIRE TO BOXES
3/4"=1'-0"4 WIRING DIAGRAM
N.T.S.
1
1
PA2021-118
A
B
D C
14'-3 7/16" SHIPPING HEIGHT
HATCHING DENOTES
SHIPLOOSE TRIM
6x6 INLET BOX (TYP. 1)
PORCH LIGHT (TYP 3)
(3) SHIPPED LOOSE
REMOTE HEAD (TYP 3)
(3) SHIPPED LOOSE
EXHAUST FAN VENT
(TYP 3)
4" SMART TRIM
(DOOR)
4" SMART TRIM
(WINDOW)
2
5
ELEC. PANEL (TYP. 3)WP GFCI RECEP (TYP. 2)
HOOD
6" SMART TRIM
(TOP HORIZONTAL)
BODY
4" SMART TRIM
(INTERMEDIATE HORIZONTAL)
4" SMART TRIM
(CORNER)
8" SMART TRIM
(BOTTOM HORIZONTAL)
4" SMART TRIM
(MOD-LINE)
4" SMART TRIM
(MOD-LINE)
ELEVATION ' '
ELEVATION ' '
ELEVATION ' 'ELEVATION ' '
12"1/4"12"1/4"
12"1/4"12"1/4"7'-10" CEILING HEIGHT3'-0" MAX
60'-0" FLOOR LENGTH 27 1/2"PEAKPLYWOOD BEAM
GRADE2'-10"109" MIN. STUD HT.116 5/16" MAX STUD HT.2
4
3
46 3/4"14'-3 7/16" SHIPPING HEIGHT W/ PLUMBING VENT3/4" T&G PLYWOOD
DECKING
2X8 FLOOR JOISTS
@ 16" O.C.
3/8" LP SMART PANEL
SIDING OVER
BARRICADE WRAP
1/2" VINYL TACK BOARD OVER 1/2" RAW GYP.
ON 2x4 INT. STUDS @ 16" O.C.
SUSPENDED LAY-IN
CEILING @ 7'-10" A.F.F.
R-19 UNFACED
INSULATION
2X8 RAFTERS12"1/4"
R-19 UNFACED BATT
EPDM ROOFING
R-13 KRAFT FACED
INSULATION20" HEEL1/2" VINYL TACK BOARD OVER 1/2" RAW GYP.
ON 2x4 EXT. STUDS @ 16" O.C.20" HEEL12"1/4"
1 BUILDING CROSS-SECTION
1/4"=1'-0"
6
R. MARK STEELE, P.E.
CORPORATE ENGINEER
SUNBELT MODULAR, INC
5301 W. MADISON ST.
PHOENIX, AZ. 85043
(602) 327-47695301 W. MADISON ST. - PHOENIX, AZ 85043PH 602-447-6460 FAX 602-447-6476SUNBELT MODULAR, INC. AMTEX I INDICOM I PHOENIX I M.R. STEELTHESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
6
OF
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH
CLASSROOM
STATES:
CALIFORNIA
SERIAL NUMBERS:
PMI-4943-3660
DRAWN BY:
RH / KT
PLOT DATE:
5/13/2021
REV # / DATE:
01 04/20/2021 PR# 4 & 5
02 04/21/2021 PR# 8
03 04/27/2021 PR# 9
----
----
----
----
----
----PHOENIXMODULARFINAL RELEASE
5/13/2021
PRODUCTION SET
2
1
1
3
PA2021-118
HVAC3 ton 5KwMODULE ( )1MODULE ( )2MODULE ( )3HVAC3 ton 5KwHVAC3 ton 5Kw1'-1 1/2"7'-0"26'-0"51'-6"53'-10"60'-0"11'-8"6'-6"11'-8"11'-8"11'-4 1/2"6'-11"25'-2 1/2"7'-5"15'-1 1/2"6'-5 1/2"11'-0"7'-8 1/2"15'-5"25'-6"
21'-7"34'-11"43'-1 1/2"11'-8"11'-4 1/2"1'-1 1/2"
1'-10"7'-0"
16'-7"
26'-0"17'-3 1/2"
38'-1 3/4"
47'-3"60'-0"
2X6 PLUMBING WALL
16'-7"
38'-10 1/4"5'-7 1/2"5'-1"5'-4 1/2"4'-0 1/2"
28'-0"35'-8 1/2"46'-6"6'-8"6'-2"5'-8"1'-8 1/2"
9'-5"20'-2 1/2"0'1'-4"2'-8"4'5'-4"6'-8"8'9'-4"10'-8"12'13'-4"14'-8"16'17'-4"18'-8"20'21'-4"22'-8"24'25'-4"26'-8"28'29'-4"109109 5/16109 5/8110110 5/16110 5/8111111 5/16111 5/8112112 5/16112 5/8113113 5/16113 5/8114114 5/16114 5/8115115 5/16115 5/8116116 5/161 WALL SET
1/4"=1'-0"
WS
2 BALLOON WALL
1/4"=1'-0"
R. MARK STEELE, P.E.
CORPORATE ENGINEER
SUNBELT MODULAR, INC
5301 W. MADISON ST.
PHOENIX, AZ. 85043
(602) 327-47695301 W. MADISON ST. - PHOENIX, AZ 85043PH 602-447-6460 FAX 602-447-6476SUNBELT MODULAR, INC. AMTEX I INDICOM I PHOENIX I M.R. STEELTHESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
6
OF
DEALER:
MOBILE MODULAR
PROJECT:
NEWPORT BEACH
CLASSROOM
STATES:
CALIFORNIA
SERIAL NUMBERS:
PMI-4943-3660
DRAWN BY:
RH / KT
PLOT DATE:
5/13/2021
REV # / DATE:
01 04/20/2021 PR# 4 & 5
02 04/21/2021 PR# 8
03 04/27/2021 PR# 9
----
----
----
----
----
----PHOENIXMODULARFINAL RELEASE
5/13/2021
PRODUCTION SET
PA2021-118
PA2021-118
PA2021-118
PA2021-118
PA2021-118
PA2021-118
PA2021-118