HOAG MEMORIAL HOSPITAL PRESBYTERIAN
HOAG CANCER CENTER
MOBILE TOMOTHERAPY INSTALLATION
NEWPORT BEACH, CA
MHP JOB#: 100160-00-1
INDEX OF STRUCTURAL CALCULATIONS
SHEET# ITEM
INDEX (THIS SHEET)
Al SEISMIC FACTORS FOR ANCHORAGE
B1-B5 ANCHORAGE OF MOBILE TOMOTHERAPY
OCTOBER 5, 2010
DESCRIPTION:
Project consists of providing anchorage a mobile tomotherapy (wt. =123,000#).
ENFORCEMENT CODE: 2007 CBC.
NH a
Subject HOAG Oncology
Sheet No. Al
Mobile TomoTherapy MHP Job # 100160-00-1
STRUCTURAL ENGINEERS
SEISMIC FACTORS FOR EQUIPMENT ANCHORAGE
Date Sep-00
By sl
Site;
One Hoag Drive, Newport Beach CA 92658-6100
Enforcement Code: 2007 CBC
Location:
SOG
Seismic Design Force Factors
apt
Rp'
Ip
z
h
amp factor
response mod factor
importance
factor
height of
attach point
average
roof height
1
1
2.5
1 -
0
7-05, Tabte 13.6-1
Coordinates
Soil Class.
Ss'
S7`
Fa*
Fv'
SDS
Latitude
Longitude
2007 CBC, Tab.
1613.5.3 (1).
(2)
(2l3*Fa`Ss)
33.62229
-117.92995
D
1.831
0.686
1.00
I 1.50
1.22
*from JAVA Ground Motion Parameter Calculator
Seismic Design Force for Equipment Anchorage
0.4a Sac W zl
r - R "I 1 + 2 �-1=
111 111
f 4,
F ,, (max) = I . 6 S ar l ,, IF r =
11,,(min) = 0.3Snc l,,W,I =
0.20 Wo
(ASCE 7-05, Equation 13.3-1)
1.95 Nip (ASCE 7-05, Equation 13.3-2)
0.37 Wo (ASCE 7-05, Equation 13.3-3)
Fp(Govern)= 0.37 WR
Working Stress= 0.26 Wo (0.7 X Fp) (ASCE 7-05, 13.1.7)
Anchorage to Masonry or Concrete? (YIN) Y
When anchoring equipment to masonry or concrete, anchors shall be proportioned to carry the least of:
a. 1.3 times the force in the component and its support due to the prescribed forces.
b. The maximum force that can be transferred to the anchor by the component and its supports.
(ASCE 7-05, 13.4.2)
WORKING STRESS DESIGN
Basic Seismic Anchorage Factor
Fp=
0.26 W„
Seismic Anchorage Factor for Anchorage to Concrete or Masonry
Fp=
0.33 W ,
ULTIMATE STRENGTH DESIGN
Basic Seismic Anchorage Factor
Fp=
0.37 Wo
Seismic Anchorage Factor for Anchorage to Concrete or Masonry
Fp=
0.48 WI,
H:12010\100160tengineeringlMobile Tomotherapy1100160001.seismic factors.xls
9/29/2010
N
STRUCTURAL ENGINEERS
By:
Date:
SL
Sep-10
EQUIPMENT: Mobile Tomo (Use 6 tie downs only)
wt.= 123000 #
Fp= 0.48 W
Fp= 59040.00 #
Sds= 1.22
h= 162 in.
h1= 86.00 in.
d= 206 in. (min)
anch./side= 3
#anch.= 6 F
TA'xhI O.9xWp0.2xSrxyxWp_
(max ) = (#anch/side) xd #anch. #anch
T(max)= -5232.08 #/side NO UPLIFT
T(max, use)= 0.00 #/side
V (max ) = F
(# anch .)
V(max)= 9840.00 #/bolt
Sheet No. Bk
Job No. 090357-00-1
h1
SEE NEXT SHEET FOR ANCHOR CHECK
TRUCTURAI E.N61NEE
4500 E: Pactt Coast Hwy, Suite 100.tong Beach, CA 90804 562.9135.3200 P 56298
www_hilti.us
Company;
Specifier:
Address:
Phone I Fax:
E-Mail:
MHP, Inc.
PROFIS Anchor 2.0.9
Page: 1
Project: HOAG: Mobile Tomo
Sub -Project I Pos. No.:
Date:
9/29/2010
Specifiers comments: Post Installed Anchors
Input data
Anchor type and diameter: HSL-3, M24
Effective embedment depth: he, = 5.906 in.
Material: • 8.8
Evaluation Service Report::. ESR 1545
Issued I Valid: B/1/2005 I -
Proof: design method ACI 318 / AC 193
Stand-off installation: e, = 0.000 in. (no stand -oft); t = 0.500 in.
Anchor plate: I, x ly x t = 17.000 x 17.000 x 0.500 in. (Recommended plate thickness: not calculated)
Profile no profile
Base material: cracked concrete , 2500. f: = 2500 psi; h = 12.000 in.
Reinforcement: condition B; no supplemental splitting reinforcement present
edge reinforcement none or < No. 4 bar
Geometry [in.] Loading [lb, in. Ib]
Governing loads
N = 19680
Mi 0.000
Y
n.poo )
oo '.__ I
_ 3 4' c i
I _.._ice_
f2.0001
Proof t Utilization (Governing Cases)
V, = 19680
My= 0.000
Eccentricity (structural section) tin.)
e, = 0.000 V, = 0
e,. = 0.000 M, = 0.000
Design values [lb] Utilization I%)
Loading Proof Load Capacity Nip, Status
Tension Concrete Breakout Strength 19680 — 23605 83 / - OK
Shear Pryout Strength 19680 50843 - / 39 OK
Loading pa II 5 Utilization p,,,.[%] Status
Combined tension and shear 0.834
loads
0.387 5/3 94 OK
Warnings
• Please consider all details and hints/wamings given in the detailed report!
Fastening meets the design criteria!
Input data and results must be checked for agreement wiib the existing conditions and for plausibdilyl
PROFIS Mcbor (c 12003-20091a4 AG. FL-9494 Schaan Rilll is a registered Trademark of HIIIiAG Selman
www.hiltl.us
PROFIS Anchor 2.0.9
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MHP, Inc.
Page:
Project:
Sub -Project I Pos. No.:
Date:
1
HOAG: Mobile Tomo
9/29/2010
Specifier's comments:
Cast in Place Anchors
Input data
Anchor type and diameter:
Effective embedment depth:
Material:
Proof:
Stand-off installation:
Anchor plate:
Profile
Base material:
Reinforcement:
Geometry [in.]
Hex Head ASTM F 1554 GR. 55, 1
h•, = 4.724 in.
ASTM F 1554
design method ACI 318 / CIP
e, = 0.000 in. (no stand -oft); t = 0.500 in.
1, x I, x t = 17.000 x 17.000 x 0.500 in. (Recommended plate thickness: not calculated)
no profile
cracked concrete , 2500, f, = 2500 psi; h = 12.000 In.
condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
y
i
17.000
3 i
ll
1 13.000�`/
Proof I Utilization (Governing Cases)
Loading
Loading [lb, in: lb]
Governing loads
N = 19880
Mx= 0D00
V. = 19680
kh. = 0.000
Eccentricity (structural section) (in.]
e,=0.000 V,=0
ey = 0.030 M;; = 0.000
Design values (lb]
Proof Load Capacity
Utilization [%]
p„/IL,
Statu
Tension
Shear
Loading
Concrete Breakout Strength 19680 23780
Pryoul Strength 19680
83/-
47559 -/41
N S
Utilization p„,,.[°A]
OK
OK
Status
Combined tension and shear
loads
0.828 0.414 5l3 96
Warnings
• Please consider all details and hints/warnings given in the detailed report!
Fastening meets the design criteria!
OK
Input data and resultsmust be checked for agreement with the erdsttng condtions and for plausbaky!
PROMS Anchor t c) 2003.2009 Milli AG. FL-9494 Schaan Hint is a registered Trademark of Hint AG, Schwan
NH
STRUCTURAL ENGINEERS
By:
Date:
SL
Jan-10
FOOTING UNDER MOBILE TOMO
wt(equip:)= - 123000 #
Fp= 0.48 Wp
Fp= 59040 #
Sds= 1.22
Fv=0.2'Sds'Wp= 30012.00 #
footing depth= 1.00 ft.
footing width= 60.00 ft.
footing length= 22.00 ft.
wt(conc.)= 198000 #
P= wt. (total)=wt(eq uip)+Fp/3+wt(conc.)
P=wt(total)= 351012.00 #
CG= 7.17 ft.
M(OT)= 482356.80 #-ft.
M(res)= 10530360.00 #-ft.
FS=M(OT) / M(res)= 21.83 STABILITY OKAY
e(equivalent)=M(OT)/wt(total)= - 1.37 ft.
L/6= 10.00 ft
trap or triangular? trap. soil profile
IF TRIANGULAR...
d=3(width/2-e(equivalent))= N/A ft.
q=2P/dW= N/A psf
IF TRAPEZOIDAL...
A= 1320 8.2
S= 4840.00 ft.3
q=(P/A) +/- M(OT)/S 365.58 psf
and
166.26 psf
Check Reinforcing
wu=(q*1.7)= 621.48 psf
L=overhang= 2.00 ft.
Mu=(wuL2/2)= 1242.97 #-ft/ft
d=(thickness-clr)= 9 in.
f=bd2/12000 0.009
ku=Mu/f= 138.11
au= 2.7
As=Mu/(au'd)= 0.05 in.2
As(min)=0.0016*d'12"/ft= 0.17 in.2
As(req'd)= 0.17 in,2
#5 @ 12" OC
A(#5)= 0.31 in.2
spacing= 12 in. o.c.
As= 0.31 In 2 okay
Fp
166 psf
Sheet No. B5
Job No. 100160-00-1
P=wt(equip)+Fv
footing width
Triangular Soil Profile N/A
Trapezoidal Soil Profile
e e•uiv.)
H.12010\100160\engineeringlMobile Tomotherapy\footing under mobile tomotherapy with reinforcing.xls
C
CG
footing depth
i
366 psf
FI
CITY OF NEWPORT BEACH
BUILDING DEPARTMENT
3300 NEWPORT BLVD.
P.O.BOX 1768, NEWPORT BEACH, CA 92658
(949) 644-3275
HAZARDOUS MATERIALS QUESTIONNAIRE
If the answer to any of the questions below is yes, applicant must contact the Fire Prevention Office, 3300
Newport Boulevard, P.O. Box 1768, Newport Beach, CA 92658-8915. Telephone: (949) 644-3106.
Bust ss Name Contact Person
47-ah� LXIV/p CA1Rtha
Mailing Address City State
%fl' 4ON6 134t1 �,t1' 90867
Site Address City
Telephone
46Z-59S-
Zip
Zip
OeAie. 77,1falef , jnsne/k 9Z66 3
YES NO
1. Will your business activity generate Hazardous Waste in any quantity, in any physical
form (solid, liquid, gas)?
2. ❑Ere -
Will your business at any one time store, use or handle Hazardous Substances in
quantities
qual to or greater than 55 gallons, 500 pounds or 200 cubic feet of compressed gas?
3. ❑ Will your business store, use or handle Carcinogens or Human Reproductive Toxins in
any amount?
4. ❑ Will your business use an existing or install an Underground Storage Tank for
Hazardous Substances or Hazardous Wastes?
5. ❑ [Will your business store, use or handle Acutely Hazardous Materials?
6.
If your business will be handling Acutely Hazardous Materials, will your business be
located within 1,000 feet from the outer boundary of a school?
Briefly describe the nature of the business activity:
Printed Name of Respondent:
I declare
and c
Si
Circle one:
owner
tenant
lessee
agent
engineer
of perjury that to the best of my knowledge and belief the responses made herein are true
South Coast
Air Quality Management District
21865 Copley Drive, Diamond Bar, CA 91765-4182
(909) 396-3529 • http:// www.aqmd.gov
Air Quality Permit Checklist
California Government Code Section 65850.2 prohibits cities from issuing an occupancy permit
to a business without clearance from the local air quality agency. This Checklist will determine
if you need to obtain clearance from the South Coast Air Quality Management District (AQMD).
Company Name:
Property Address:
City:
Contact Person:
Type of Business:
Fax Number:
Applicant (print name): P4V/C
clhn gfi.E2
a .azcltil�cf5
4"t i'Aa Peiv,
f8OPcse. 660e1,1 Zip Code: 9
�,. a4M9 C/ le0/1e—Title: 4e-C4(
Telephone: e-6.95 5444.
c -6f -5%fl e-mail address:
Signature:
Date:
• Will the facility have any of the following equipment? Yes ❑
Charbroiler
Dry cleaning machine
Spray booth
Printing press (screen/lithographic/flexographic)
Internal combustion engine greater than 50 HP (excluding motor vehicles)
Boiler/combustion equipment (greater than 1 million BTU/hr. maximum input)
Abrasive blasting cabinet/room
Baghouse/cartridge-type dust filter/scrubber
Motor fuel storage and dispensing equipment
• Will any of the following operations be performed? Yes
Application of paints or adhesives
Etching, plating, casting, or melting of metals
Molding, extruding, or curing of plastics
Mixing and blending of liquids and/or powders
Storage of acids, solvents, organic liquids, or fuels
Production of fumes, dust, smoke, or strong odors
-04 rI-e s
•cam
8 /a
No
❑ No
If you answered "No" to both questions, this checklist is your clearance from AQMD. If
you answered "Yes" to either question, you must contact AQMD to determine if air quality
permits are required. If permits are needed, AQMD will assist you in submitting permit
application(s) and then provide you with a clearance letter. You can call AQMD at their Small
Business Assistance Office at 1-800-CUT-SMOG (1-800-288-7664).
Revised November 2006
Project Description:
Project Address:
Plan Check No.:
Use:
Architect/Engineer:
CITY OF NEWPORT BEACH
BUILDING DEPARTMENT
3300 NEWPORT BLVD.
P.O.BOX 1768, NEWPORT BEACH, CA
(949) 644-3275
TENANT IMPROVEMENT CORRECTIONS
MODULAR BLDG —"MOBILE TOMOTHERAPY"; SITE WORK AND ACCESS RAMP
1 HOAG DR (ADJACENT TO CANCER CENTER)
1873-2010 Date Filed: 10/08/10 No. Stories: 1
MEDICAL Occupancy: B Const. Type: VB
CA ARCHITECTS (DAVID CHARTIER) Phone: 562-595-5666
Owner: HOAG HOSPITAL
(CARY BROOKS)
Checked by: S. KUSIK
1* Check 10/19/10
4th Check*
Phone: 949-764-4496 Submitted Valuation: $120,000
Phone: 949-644-3285 Permit Valuation:
2nd Check 11/04/10 3rd Check
*NOTE: Do not resubmit after the 3`d plan check. Call plan check
engineer for an in -person recheck appointment.
WARNING: PLAN CHECK EXPIRES 180 DAYS AFTER SUBMITTAL.
THIS PLAN CHECK EXPIRES ON: 04/06/2011
Approval of plans and specifications does not permit violation of any section of the Building Code
or other City ordinances or State law.
This plan check is according to 2007 California Building Code.
• Make all corrections listed below.
• DO NOT resubmit after the third check. Call plan check engineer and schedule in -person recheck.
• Return this correction sheet and check prints with corrected plans.
• Indicate how each correction was resolved.
Note: This list is applicable to B/MIA-2 occupancies.
GENERAL
1. Approval is required from: Planning Department
and ontry landing framing plan
Shared\Correction Lists\TICORR 2007 11/04/10 Page 1 of 3
111
building -inspector,
5 Accurately idontify 4he p sed nit.. o.. the .i cinity man (AA 9) 6. All -plea -sheets -and design calculations shall be wet signed by the appropriate design professional.
Electronic signatures, signature stamps or photocopies are not sufficient.
SITE DEVELOPMENT & ACCESSIBLE PARKING
and loading areas. (C1.0, A1.0, A2.0, E2.1, L1.0 & L2.0)
la -The -war -der Ne-packineshall-befaieted-within--eash--existieg-ec-new-aerress-aisleiteadieg-area-with-1-2f
baskgpaun
$250." 112913.1, Fig 11 B 18A, B & C
RAMPS
landing. 11338.5.3 (C1.0)
116 38 & 39
39(b)
ramps. 11336.5.1.1 & Fig 11B 30(b)
Shared\Correction Lists\TICORR 2007 11/04/10 Page 2 of 3
25. Clarify and dimension the handrail installations on the plans. Handrails shall be placed on each side of
each ramp, shall be continuous the full length of the ramp, shall extend a minimum of 12" beyond the
top and bottom of the ramp. The extension may be turned 90° if it creates a hazard or returned
smoothly to wall, floor, or post. 1133B.5.5.1 & Fig 11 B-27(b) &(c)
26. Detail the handrail height above the ramp walk surface. Handrails shall be 34" to 38" above the ramp
surface. Revise the handrail details accordingly; "height above nosing" is not applicable to the ramp
construction.
27. Handrails projecting from a wall shall have a space of 1 ''"A" between the wall and the handrail. Omit the
"min." from the handrail details. 113313.5.5.1, Fig 11 B-36 (4/A3.0)
28. Clarify the surface finish and continuous solid smooth wall surface for each side of the ramp. The ramp
surface shall be bound by a solid uninterrupted wall; or, a guide curb at minimum of 2" in height shall
be provided at each side of the ramp; or, a wheel guide rail shall be provided above the surface of the
ramp. 1133B.5.6.1 & 1133B.5.6.2 (1/A3.0 & 2/A3.0)
29. Provide a 42" minimum guard height above the ramp and landing walk surfaces, where the surface is
greater than 30" above the adjacent grade.
30. Show the light fixtures on the ramp sections. The light fixtures shall not reduce any required clear
areas, widths or landings. (1A3.0 & E2.1)
31. Define the light fixture heights on the ramp sections or installation details.
Shared\Correction Lists\TICORR 2007 11/04/10 Page 3 of 3