HomeMy WebLinkAboutX2020-1234 - CalcsX2n2o • 1264 10D San Mwflie Dr. TAIT RISING TO THE CHALLENGE Vivante Retaining Wall Calculations Project Site: 850 San Clemente Drive Newport Beach, CA 92660 Developer Nexus Development 1 MacArthur Place, Suite 300 Santa Ana, CA 92707 Prepared by Tait & Associates, Inc. 701 North Parkcenter Drive Santa Ana, CA 92705 (714)560-8200 Engineer: Jacob Vandervis, P.E. Registration No. 46301 June 10th, 2020 No. CIVIL TAI T RISING TO THE CHALLENGE Tait & Associates 701 North Parkcenter Drive Santa Ana, CA 92705 (714)560-8200 RETAINING WALL NOTES GENERAL 1. ALL CONSTRUCTION AND WORKMANSHIP SHALL CONFORM TO THE 2019 CBC. 2. CONTRACTOR MUST CHECK ALL DIMENSIONS, AND SITE CONDITIONS BEFORE STARTING WORK. ARCHITECT/ENGINEER SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES OR POSSIBLE DEFICIENCIES. 1. FOOTING ARE TO BE CARRIED A MINIMUM OF 15" INTO FIRM UNDISTURBED NATURAL SOIL OR APPROVED COMPACTED FILL PER GEOTECHNICAL REPORT. 2. FOOTINGS MAY BE DESIGNED USING AN ALLOWABLE BEARING CAPACITY OF 1,500 PSF BASED ON A MINIMUM WIDTH OF 15 INCHES AND EMBEDMENT DEPTH OF 15 INCHES BELOW THE LOWEST ADJACENT GRADE. THE FOLLOWING FOOTING WIDTHS AND EMBEDMENTS ARE RECOMMENDED FOR THE CORRESPONDING ALLOWABLE BEARING PRESSURE. STATIC BEARING PRESSURE s MINIMUM FOOTING MOTH Inches MINIMUM FOOTING' EMBEDMENT Inches 4,000 12 24 3.500 48 24 3.000 24 24 2.000 18 18 1500 15 15 Refers to minimum Jeplh babes lowest adjacent grads at the 8me of foundation constiuctiion. 3. RELATIVELY NON -EXPANSIVE FILL SHOULD BE USED IN BACKFILLING BEHIND WALLS. DESIGN ALLOWS FOR ONSITE SOILS TO BE USED FOR BACK FILL. ALL RETAINING WALLS SHALL BE ADEQUATELY SHORED DURING THE BACKFILL OPERATION. CONCRETE 1. ALL CONCRETE SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH OF 3,700 PSI AT 28 DAYS. 2. AGGREGATES SHALL BE NATURAL SAND AND ROCK CONFORMING TO ASTM C33. 3. CEMENT SHALL BE PORTLAND CEMENT CONFORMING TO ASTM 6150, TYPE V. 4. THE FOLLOWING MINIMUM CLEAR DISTANCES BETWEEN REINFORCING STEEL AND FACE OF CONCRETE SHALL BE MAINTAINED UNLESS NOTED OTHERWISE: SLAB ON GRADE CENTER OF SLAB CONCRETE BELOW GRADE, FORMED 2" CONCRETE BELOW GRADE, UNFORMED (POURED AGAINST EARTH) 3" CONCRETE EXPOSED TO WEATHER 1 1/2" 5. PROVIDE 3/4" CHAMFERS AT ALL EXPOSED CORNERS. REINFORCING STEEL 1. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 40 FOR SIZES #3 AND #4 AND GRADE 60 FOR SIZES #5 AND LARGER, 2. WELDED FABRIC (MESH) SHALL CONFORM TO THE LATEST REVISED ASTM Al 85. SMOOTH WIRE FABRIC SHALL CONFORM TO ASTM A85, YIELD STRENGTH 60 KSI. 3. ALL BARS IN MASONRY SHALL BE LAPPED A MINIMUM OF 40 BAR DIAMETERS (24" MIN.) AT ALL SPLICES UNLESS NOTED OTHERWISE. 4. ALL BARS IN CONCRETE SHALL BE LAPPED A MINIMUM OF 36 BARS DIAMETERS (24" MIN.) AT ALL SPLICES UNLESS NOTED OTHERWISE. 5. SPLICES OF HORIZONTAL REBAR IN WALLS AND FOOTINGS SHALL BE STAGGERED 48" MINIMUM. 6. ALL BENDING OF REINFORCING STEEL SHALL CONFORM TO THE LATEST EDITION OF THE CBC. Project Name/Number: sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vlvar)te Wall Page: 1 to set these five lines of Information Dsgnr. AG Date: 26 MAY 2020 for your program. Description.... RH = 6' w/Vehicle Loading This Wall in wal RetalnPro(0)1987.2019, Build 11.20.03.31 License: KW -06056246 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Retained Height Wall height above soil Slope Behind Wall Height of Soil over Toe Water height over heel 6.00 it 0.50 it 0.00 6.00 In 0.0 it Surcharge Loads Surcharge Over Heel - 250.0 Psi Used To Resist Sliding & Overturning Surcharge Over Toe 0.0 psi Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load 0.0 lbs Axial Live Load 0.0 lbs Axial Load Eccentricity, = 0.0 in Design Summary -i Wall Stability Ratios Soil Data Allow Soil Bearing = 3,500.0 psi Equivalent Fluid Pressure Method Active Heel Pressure = 55.0 psf/ft Overturning = 1.66 OK ,Passive Pressure 275.0 psf/ft Soil Density, Heel = 110.00 pof Soil Density, Toe = 0.00 pef FootingIlSoil Friction = 0.350 Sail height to Ignore 0 psi OK for passive pressure 6.00 In Lateral Load Applied to Stem Lateral Load 0.0 #/it ...Height to Top = 0.00 it ...Height to Bottom = 0.00 it Load Type - Wind (W) 16.0 psi OK (Service Level) Wind on Exposed Stem = 0.0 psi (Strength Level Lateral Sliding Force = Overturning = 1.66 OK Sliding 1.58 OK Total Bearing Load 4,994 lbs ...resultant sec. 16.32 in Soil Pressure @ Toe 3,414 psi OK Soil Pressure @ Heel = 0 psi OK Allowable 3,500 psf Soil Pressure Less Than Allowable ACI Factored @ Toe 4,779 psf ACI Factored @ Heel = 0 psi Footing Shear @ Toe = 11.5 psi OK Footlng Shear @ Heel = 16.0 psi OK Allowable = 75.0 psi Sliding Caics Strength Level it-#= Lateral Sliding Force = 2,484.4 lbs less 100% Passive Force = - 2,165.6 lbs less 100% Friction Force - - 1,747.7 lbs Added Force Req'd = 0.0 lbs OK ....for 1.5 Stability = 0.0 lbs OK Stem Construction 11_ Design Height Above Ftt it. Wall Matedal Above "Ht" _ Design Method = Thickness = Rebar Size = Rebar Spacing = Rebar Placed at = Design Data Modular Ration' fb/FB + fa/Fa = Total Force @ Section Service Level lbs = Strength Level lbs - Moment .... Actual 78.0 Service Level it -#- Strength Level it-#= Moment..... Allowable it-#= Shear..... Actual = Service Level psi= Strength Level psi= Shear..... Allowable psi= Anet(Masonry) in2- Reber Depth 'd' In= Masonry Data 7.60 2nd Stem OK 3.33 Masonry ASD 8.00 # 5 24.00 Edge 0.314 529.8 620.0 1,970.0 5.8 44.4 91.50 5.25 Footing Width Eccentricity Wali to Fig CL Dist Footing Type Base Above/Below Soil at Back of Wall Poisson's Ratio Stem OK 0.00 Masonry ASD 12.00 # 5 8.00 Edge 0.685 1,740.0 4,230.0 6,167.2 12.5 45.3 139.50 9.00 = 0.00 it 0.00 In 0.00 it Line Load 0.0 it 0.300 fm psi= 1,500 1,500 Fs psi= 32,000 20,000 Vertical component of active lateral soil pressure IS Solid Grouting Yes Yes NOT considered In the calculation of soil bearing Modular Ration' 21.48 21.48 Wall Weight psi = 78.0 124.0 Load Factors Short Tenn Factor = 1.000 1.000 Building Code CBC 2016 ACI Equiv. Solid Thick. In- 7.60 11.60 Dead Load 1.200 Masonry Block Type - Medium Weight Live Load 1.600 Masonry Design Method = ASD Earth, H 1.600 Concrete Data Wind, W 1.000 Pc psi= Seismic, E 1.000 Fy psi= = 0.00 it 0.00 In 0.00 it Line Load 0.0 it 0.300 Project Name/Number : sp8384 wall t Page: 2 Use menu Item Settings > Printing &Title Block pislgnr. AGaOte Wall Date: 26 MAY 2020 to set these five lines of Information Description.... for your program. RH = V wNehicle Loading This Wall In File: k:\drawings\sp\sp8384 - newportbeach\docs\structural calcs\background\sp8384 wal Retainprgq 887.2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2015,ACI.318-14,ACI 530-13 Footing Data Is Toe Width 0.50 it 4.17 oe Heel Factored Pressure = 4,779 0 psf Heel Width Total Footing Width = 4.67 Mu': Upward. = 6,761 789 ft# = 1'479 Footing Thickness = 18.00 in Mu': Downward Mu: Design = 504 ft# Key Width = 12.00 in Actual 1 -Way Shear = 11.53 15.99 psi Key Depth = 24.00 in Allow 1 -Way Shear = 75.00 75.00 psi Key Distance from Toe 0.00 it Toe Reinforcing = # 5 @ 8.00 in fc = 2,500 psi Fy = 60,000 psi Heel Reinforcing = # 5 @ 8.00 In Key Reinforcing - None Spec'd Footing Concrete Density = 150.00 pct 0.0018 Footing Torsion, Tu = 0.00 ft -lbs Min. As % Cover @ Top 2.00 @ Btm: 3.00 in Footing Allow. Torsion, phi Tu 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Heel: #4@ 6.17 in, #5@ 9.56 in, #8@ 13.58 In, #7@ 18.51 in, #8@ 24.38 in, #9@ 30. Key: phiMn - phi'5'lambda'sgrt(fc)'Sm Min footing T&S reinf Area 1.82 in2 Min footing T&S reinf Area per foot 0.39 in2 At If one layer of horizontal bars: If two layers of horizontal bars: #4@ 6.17 in #4@ 12.35 in #5@ 9.57 in #5@ 19.14 in #6@ 13.58 in #6@ 27.16 in Summary of Overturning & Resisting Forces & Moments .....OVERTURNING... RESISTING Foree Distance Moment Force Distance Moment lbs ft ft# Item lbs it ft# Soil Over HL (ab. water tbl) 2,092.2 3.09 6,454.4 HL Act Pres (ab water tbl) 1,546.9 2.50 3,867.2 Soil Over HL (bel. water tbl) 3.09 6,464.4 HL Act Pres (be water tbl) Weirs Table Hydrostatic Force Sloped Soil Over Heel = Buoyant Force = Surcharge Over Heel 792.5 3.09 2,444.9 Surcharge over Heel 937.5 3.75 3,515.6 Adjacent Footing Load = Surcharge Over Toe = Axial Dead Load on Stem = Adjacent Footing Load = • Axial Live Load on Stem = Added Lateral Load = Soil Over Toe = 0.25 Load @ Stem Above Soil = Surcharge Over Toe = = Stem Weight(s) 660.2 0.94 619.0 Earth @ Stem Transitions= 97.9 1.33 130.5 Total = 2,484.4 O.T.M. = 7,382.8 Footing Weight = 1,050.8 2.34 2,453.5 Key Weight = 300.0 0.50 150.0 Reslsting/Overturning Ratio = 1.66 Vert. Component = 12,252.3 Vertical Loads used for Soil Pressure = 4,993.5 Itis Total :--- 4,993.5 lbs R.M.- for overturning •resistance butIsIncluded for soil pressure calculation Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Use menu Item Settings > Printing & Title Block to set these five lines of Information for your program. This Wall in (Deflection due to wall bending not considered) Project Name/Number : sp8384 wall t page: 3 Title VIvante Wall Dale: 26 MAY 2020 Dsgnr: AG Description.... RH = 6' w/Vehicle Loading ch\docs\structural caics\background\sp8384 wal Cantilevered Retaining Wall Code: CBC 2016 ACI 318-14.ACI 530-13 Soil Spring pcing Reaction Modulus 0.132 in Horizontal Dell @ Top of Wall (approximate only) The above calculation is not valid if the heel soil] bearingressure exceeds that of the toe because the wall would then tend to rotate into the retained soil. Project Name/Number : sp8384 wall t Use menu Item settings > Printing B,Title Block Title Viva lte Wall Page: 4 to set these five lines of Information Dsgnr. AG Date: 26 MAY 2020 for your program. Description.... RH - 6' wNehicle Loading This Wall In File: k:\draw1ngs\sp\sp8384 - newport beach\docs\structural caics\background\sp8384 wal RetenPrO 0)1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI318-14,ACI530-13 ........ VWAgngRIAK 8- W? "n5@ 24" solid Grout 12" w/ #6@ 8" Solid Grout 1r5@8.in @Toe rr5@8' @ Heel L I M Project Name/Number : sp8384 wall t Page: 1 Title Vlvat)te Wall Date: 8 JUN 2020 Use menu Item Settings > Printing & Title Block Dsgnr: AG to set these five lines of Information Description.._ for your program. RH - 8.33' tructural This Wall is File: -2019.. Suit 11.sp8384 • newport beacCant leveredaRetaining dWall 4 coal Code: CBC 2016,ACI 316-14,ACI 530-13 oe.� n role 7887.2079, Bull 11.20. 3.37 Retained Height = 8.33 it Wall height above soil 0.33 it Slope Behind Wall = 0.00 Height of Soil over Toe = 12.00 In Water height over heel - 0.0 It 0.0 psf Stem Huai von.. 0.0 Itis Axial Live Load = 0.0 in Axial Load Eccentricity = Design Summary 1 Wall Stability Ratios Overturning Sliding Total Beadng Load ...resultant ecc. 1.85 OK 1.52 OK 10.471 lbs 21.86 1n Allow Soil Bearing - 4,655.0 psf 4,493 psf OK fbIFB +falFa Equivalent Fluid Pressure Method ' Soil Pressure @ Heel = Active Heel Pressure - 55.0 psf/ft Total Force @ Section Wind, W Passive Pressure 275.0 psflft Allowable = 4,655 psf Soil Density, Heel 110.00 pof Ibs= 13.00 Soil Density, Toe 0.00 pcf Allowable Strength Level FootingljSoll Friction 0.350 20,000 ACI Factored @ Toe = Soil height to Ignore 6.00 in Moment.... Actual it-#= for passive pressure ACI Factored @ Heel = 21.48 Lateral Load Applied to Stem Adjacent Footing Load 164.0 Footing Shear @ Toe = ' Shear Heel Adjacent Footing Load o.o lbs 0.0 #Ift Lateral Load 0.00 v Footing Width _ 0.00 ft g,00 In ...Height to Top = 0.00 ft Eccentricity - 0.00 it ...Height to Bottom Wall to Ftg CL Dist Load Type = Seismic (E) Footing Type Line Load (Service Level) Base Above/Below Soil = 0.0 it Wind on Exposed Stem = 0.0 psf at Back of Wall = 0.300 (Strength Level) left-to-right toward retention side. Poisson's Ratio Wind acts 2nd Bottom Stem Construction Stem OK Stem OK Design Height Above Fig ft= 4.00 0.00 Wall Material Above 'Ht" = Masonry Masonry Design Method SASD 12.00 16.00 Thickness __ # 6 # 6 Rebar Size 24.00 8.00 Rebar Spacing ` Edge Edge Rebar Placed at Design Data 0760 0.871 Soil Pressure @ Toe = 4,493 psf OK fbIFB +falFa 4,641.1 Itis ' Soil Pressure @ Heel = 0 psf OK Total Force @ Section Wind, W 1,231.3 3,284.5 Allowable = 4,655 psf Service Level Ibs= 13.00 Soil Pressure Less Than Allowable Strength Level lbs = 20,000 ACI Factored @ Toe = 6,291 psf 0 psf Moment.... Actual it-#= 2,294.7 11,032.9 ACI Factored @ Heel = 21.48 Service Level 124.0 164.0 Footing Shear @ Toe = ' Shear Heel 0.0 psi OK 12.8 psi OK Strength Level nt Allowable it-#= ft-#= 3,019.2 12,655.3 Footing Allowable ` 75.0 psi Sliding Calcs Lateral Sliding Force = 4,641.1 Itis less 100% Passive Force = - = 3,403.1 lbs 3,664.7 lbs less 100% Friction Force - 1.600 Added Force Req'd = 0.0 lbs Or, ....for 1.5 Stability = 0.0 Ilia OK Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Load Factors Building Code CBC 2016,ACI Dead Load 1,200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 Mome ..... Shear..... Actual Service Level Strength Level Shear..... Allowable Anel (Masonry) Rebar Depth 'd' Masonry Data fm Fs Solid Grouting Modular Ration' Wall Weight Short Term Factor Equiv. Solid Thick. Masonry Block Type Masonry Design Method Concrete Data fc Fy PSI = 8.8 17.5 PSI = psi= 44.8 45.8 Int = 139.50 187.50 In= 9.00 13.00 psi= 1,500 1,500 psi= 20,000 20,000 = Yes Yes = 21.48 21.48 Pa= 124.0 164.0 = 1.000 1.000 In=11.60 15.60 = Medium Weight - ASD psi = psi = Project NamelNumber: sp8384 wall t Page: 2 Use menu item Settings > Printing & Title Block Title AG Ote Wall Date: 8 JUN 2020 to set these five lines of Information Description.... for your program. RH = 8.33' This Wall in File: k:\drawings\sp\sp8384 - newport.beach\docs\structural caics\background\sp8384 wal RetainPro(e)1997.2019, Buil 1.20.93.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Toe Width Heel Width = U.V. r' = 6.75 _ -- Factored Pressure c 6,291 0 0 psi 8,286 ft-# Total Footing Width 6.75 Mu': Upward Mu': Downward 0 32,753 ft-# Footing Thickness 24.00 In c Mu: Design 0 24,467 ft-# Key Width 12.00 In Actual l -Way Shear '= 0.00 12.78 psi Key Depth = 24.00 In Allow 1 -Way Shear = 0.00 75.00 psi Key Distance from Toe = 0.00 It Toe Reinforcing = # 6 oily 8.00 in fc = 2,500 psi Fy = 60,000 psi Heel Reinforcing = # 6 @ 8.00 In Key Reinforcing - None S=ec'd Footing Concrete Density = 150.00 pcf - 0.0018 Footing Torsion, Tu 0.00 ft -lbs Min. As % Cover @ Top 2.00 @ Stm: 3.00 in Footing Allow. Torsion, phi Tu 0.00 ft -lbs Surcharge over Heel = 1,704.9 5.17 8,808.6 if torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn= phi'5'lambda'sgr9fc)'Sm Heel: #4@ 4.62 in, AS@ 7.17 in, #8@ 10.18 in, #7@ 13.88 In, #8@ 18.28 In, #9@ 23. Key: phiMn = phl'5'lambda'sgrt(fc)'Sm Min footing T&S relnf Area 3.50 in2 Min footing T&S reinf Area per foot 0.52 in2 At If one layer of horizontal bars: If two layers of horizontal bars: #4@ 4.631n #4@ 9.26 in #5@ 7.18 in #5@ 14.35 in #6@ 10.19 in #6@ 20.37 in _ .....OVERTURNING..... Force Distance 'Moment M " --- s """ D Force Distance ft Mo ment ft - # Item lbs ft ft-# lbs Soil Over HL (ab. water tbl) 4,965.1 4.04 20,067.2 HL Act Pre s (ab water tbl) 2,936.2 3.44 10,113.2 Soil Over HL (bel. water tbl) 4.04 20,067.2 HL Act Pres (be water IN Weirs Table Hydrostatic Force Sloped Soil Over Heel = Buoyant Force = Surcharge Over Heel 1,787.5 4.04 7,224.5 Surcharge over Heel = 1,704.9 5.17 8,808.6 Adjacent Footing Load = Surcharge Over Toe Axial Dead Load on Stem= Adjacent Footing Load • Axial Live Load on Stem = Added Lateral Load = Soil Over Toe = Load @ Stem Above Soil = Surcharge Over Toe = Stem Weight(s) = 1,234.2 0.59 726.4 Earth @ Stem Transitions= 158.9 1.17 185.4 Total = 4,641.1 O.T.M. = 18,921.8 Footing Weight = 2,025.0 3.38 6,834.4 Key Weight = 300.0 0.50 150.0 Resistingloverturning Ratio = = 10,470.7 1.86 lbs Vert. Component = Total = 10,470.7 lbs R.M.= 35,187.8 Vertical Loads used for Soil Pressure • for overturning resistance, but Is Included for soil pressure calculationd Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. use menu Item Settings> Printing & Title Block to set these five lines of Information for your program. This Wall in File: k-.\drawings\sp\sp8384 - newport b, 12" W1 n6@ 24" Solid Grout 16" uv! #6@:8" Solid Grout #6@8- @ Heel Project Name/Number: sp8384 wall t page: 4 Title Vivagte Wall Date: 8 JUN 2020 Dsgnr. AG Description.... RH - 8.33' h\docs\structural talcs\background\sp8384 wal Cantilevered Retaining Wali Code: CBC 2016,ACI 318-14,ACI 530-13 use menu Item Settings > Printing & Title Block to set these five lines of Information for your program. This W211 in Retained Height = 2.60 ft Wall height above soil = 0.50 ft Slope Behind Wall = 2.00 Height of Soil over Toe = 6.00 In Water height over heel = 0.0 ft u.0 & Overtumii 0.0 Used Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Design Summary 1 Wall Stability Ratios Overturning Sliding Total Bearing Load ...resultant ecc. 1.73 OK 2.48 OK 1,025 lbs 7.26 in Project Name/Number: spB384wall t 1 Title Viva1)te Wall Type 2 Date: Page: 2 JUN 2020 Dsgnr. JW Soil Pressure Less Than Allowable ACI Factored @ Toe = Description.... ACI Factored @ Heel = 0 psi Wall Type 2 - RH=2.5' 0.0 psi O Footing Shear @ Heel = talcs\background\sp8384 wal Allowable = 75.0 psi each\docs\structural Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 -------------- Soil Data 477.4 lbs less 100% Passive Force - - Allow Soil Searing = 2,000.0 psi less 100% Friction Force - - 358.6 lbs 6.631 Equivalent Fluid Pressure Method = = Yes 21 AS Active Heel Pressure = 55.0 psf/ft = o tis Passive Pressure 275.0 psflft NOT Soil Density, Heel 110.00 pcf lbs= 171.9 Soil Density, Toe 0.00 pcf lbs - Short Term Factor Moment .... Actual FootingIlSoil Friction 0.350 Load Factors BuildingdingCode Service Level it-#= Soil height to Ignore 6.00 in = Strength Level ft-#= 1.200 for passive pressure = 1,028.8 Shear..... Actual Lateral Load Applied to Stem Adjacent Footing Load Service Level Lateral Load = 0.0 #/ft Adjacent Footing Load = Footing Width 0.0 0.00 ft s ...Height to Top = 0.00 ft 0.00 It Eccentricity 0.00 in ...Height to Bottom = Wall to Ftg CL Dist0.00 It Load Type = Wind (W) Footing Type Square Footing (Service Level) Base AbovelBelow Soil = 0.0 it Wind on Exposed Stem = 0.0 psi at Back of Wall = 0.300 (Strength Level) Poisson's Ratio Soil Pressure @ Toe 11729 psi OK Soil Pressure @ Heel = o psi O Allowable = 2,000 psi Soil Pressure Less Than Allowable ACI Factored @ Toe = 2'421 psi ACI Factored @ Heel = 0 psi Footing Shear 0 Toe = 0.0 psi O Footing Shear @ Heel = 4.1 psi O Allowable = 75.0 psi Sliding Calcs = Lateral Sliding Force = 477.4 lbs less 100% Passive Force - - 825.0 lbs less 100% Friction Force - - 358.6 lbs Stem Construction K K K Bottom Anet (Masonry) 'd' In2- In = Stem OK Design Height Above Ftp ft= 0.00 Wall Material Above "Ht" _ Masonry Design Method = SD Thickness = 8.00 Rebar Size = # 4 Rebar Spacing = 24.00 Rebar Placed at = 6.631 Design Data = = Yes 21 AS fib/FB +fa/Fa = o tis Total Force @ Section NOT Service Level lbs= 171.9 Strength Level lbs - Short Term Factor Moment .... Actual 1.000 Load Factors BuildingdingCode Service Level it-#= 143.2 Strength Level ft-#= 1.200 Moment..... Allowable = 1,028.8 Shear..... Actual Masonry Design Method = ASD Service Level psi = 1.9 Strength Level psi = Wind, W Shear..... Allowable psi= - 44.3 91 50 Added Force Req'd = 0.0 lbs OK Anet (Masonry) 'd' In2- In = 6.53 t.5 Stability = 0.0 lbs OK Rebar Depth ....for Masonry Data I'm psi= 1,500 Fs psi= 20,000 Vertical component of active lateral soil pressure IS Solid Grouting = = Yes 21 AS considered in the calculation of soil bearing Modular Ration' 78.0 NOT Wall Weight psi = Short Term Factor = 1.000 Load Factors BuildingdingCode CBC 2016,ACI Equiv. Solid Thick. In= - 7.80 Medium Weight Dead Load 1.200 Masonry Block Type Live Load 1.600 Masonry Design Method = ASD Earth, H 1.600 Concrete Data Wind, W 1.000 1.000 fc Fy psi si= Seismic, E Use menu Item Settings> Printing & Title Block to set these five lines of Information for your program. This Wall in Footing Data Toe Width = 0.00 it Heel Width = 2.00 2.00 Total Fooling Width = 94@ 18.52 in #5@ 28.701n Footing Thickness = 12.00 in Key Width = = 6.00 in 12.001n Key Depth Key Distance from Toe = 0.008 fc = 2,500 psi Fy = 60,000 psi 150.00 pcf Footing Concrete Density = Min. r °h 0.2.00 @ Btm.0018 3 00 in Cover @Top Item lbs HL Act Pres (ab water tbl) 477.4 HL Act Pres (be water IN) Hydrostatic Force Buoyant Force = Surcharge over Heel = Surcharge Over Toe = Adjacent Footing Load = Added Lateral Load = Load @ Stem Above Soil Project Name/Number; sp8384 wall t Page: 2 Title Vivapte Wall Type 2 Date: 2 JUN 2020 Dsgnr: JVV Description.... Wail Type 2 - RH=2.5' :h\docs\structuml talcs\background\sp8384 wal Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Fnntina Desiqn Results 1.17 Factored Pressure = 2,4211 47 ft-# sf Mir: Upward = 0 629 ft-# Mu': Downward = 0 581 ft-# Mu: Design = Allow1-Wly ShearShear 0.00 4.07 4000 75.00 psi si Toe Reinforcing None Speed Heel Reinforcing # 4 @ 8.00 In Key Reinforcing = None Speed Fooling Torsion, Tu 0.00 ft -lbs Footing Allow. Torsion, phi Tu. 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn= phi'5'lambda'sgrt(fc)'Sm Heel: iM9.26 n = pIn, #�r5014.35 In, cSm@20.37 in, #7@ 27.77 In, #8@ 36.57 In, #9@ 46 Keeph Min footing T&S reinf Area Min footing T&S reinf Area per foot 0.52 int 0.26 Int At If one layer of horizontal bars: If two layers of horizontal bars: #4@ 9.26 in 94@ 18.52 in #5@ 28.701n #5@ 14.35 in #6@ 20.37 in 96@ 40.74 in ft-# 663.1 Total = 477.4 O.T.M. = 557.0 1.73 Vertical Loads used for Ratio 1,024.6 lbs Vertical Loads used for Soil Pressure = Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered In the calculation of Overturning Resistance. Forcer Distance Moment lbs ft Soil Over HL (ab. water tbl) 366.7 1.33 488.9 488.9 Soil Over HL (bel. water tbl) 1 33 Wave Table 48.9 1.56 76 0 Sloped. Soil Over Heel = Surcharge Over Heel = Adjacent Footing Load = Axial Dead Load on Stem = Axial Live Load on Stem - Soil Over Toe = Surcharge Over Toe = 234 0 0.33 78.0 Stem Weight(s) Earth @ Stem Transitions= 300.0 1.00 300.0 Footing Weight = = 75.0 0.25 18.8 Key Weight Vert. Component = Total= 1,024.6 lbs R.M? g61 7 Y for overturning Axial istaince, but Is Included f r soolpressuteycalculationd Protect NamelNumber : sp8384 wall t Page: 3 Title VivaOte Wall Type 2 Date: 2 JUN 2020 Use menu Item Settings > Printing &Title Block Dsgnr: JWDescription.... to set these five Tines of Information Wall Type 2 - RH4.5' for your program. This Wall In File:k:\drawings\sp\sp8384-newportbeacCanfllBVeredRetan'n9dtwall4wal Code: CBC 2016,AC1318-14,ACI530-13 ... �oaa2919. 6ulld 71.20.0 .31 �t ■ HoMMMMM rizontal Deflectlon at To of Wall due to settlement of soil (Deflection due to well bending not considered) 250.0 pci Soil Spdng Reaction Modulus 0 072 in Horizontal Deft @Top of Wall (appro)imate only) --, —ii nandna oressure ex_ceeds�nat1 The above caicmaum - ,.- �--- because the wall would thentend to rotate into the retained soil. Use menu Item Settings> Printing & Title Block to set these five lines of Information for your program. This Wall in File: k:\drawings\sp\sp8384 - newport b 8"w/ #4@ 24" Solid Grout Project Name/Number : sp8384 wall t Page: 4 Title Vivagte Wall Type 2 Date: 2 JUN 2020 Dsgnr. JVV Description.... Wall Type 2-111-1=2.5 - h\docs\structural calcs\background\s38384 wal Cantiievered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 2 T-0" Project NamelNumber : sp8384 wall t page: 1 I' Title Viv nits Wall Type 2 Date: 2 JUN 2020 > Printing &Title Block Item SettirigsDsgnr. JVV Use menu to set these five lines of Information Description.... Wall Type 2 - RH=3.5' for your program. - newport beach\docs\structuml talcs\b 9round\sp8384 wal 2016,AC1318-14,AC1530-13 Is Wall In File: k:\drawings\sp\sp8384 Th7.2-0-0351 ai nin Wall e red Ret 9 Cade: CBC .Cantilevered ,eta nPro c)1967-2019, BulidCant License: KW -06056246 To: WEI DELLGAYER 11Bo11 11 License 1 l l Data Criteria Soil Bearing 2,000.0 psf = 3.50 it Retained Height Equivalent Equivalent Fluid Pressure Method 55.0 psflft Eq - - 0.50 ft Wall height above Boll - active Heel Pressure - Slope Behind Wall 2.006.00 = = 275.0 psflft Height of Soil over Toe = in passive Pressure = 110.00 pcf Water height over heel = 0.0 ft Soil Density, Heel = 0.00 pcf------�. Soil Density, Toe _ 0.350 FoolingllSoil Friction - Soil height to Ignore_ 6,0o In for passive pressure - Adjacent Footing Load Lateral Load Applied to Stem Adjacent Footing Load 0.01bs ft SUroharge Loads 0.0 = 0.0 #/n a psf Lateral Load _ 0.00 ft 0.00 Footing Width 0.00 in Surcharge Over Heel = ,,,Height Top - 0.00 ft Used To Resist Sliding & overturning .,,Height to Bottom ` ` Eccentricity _ 0.00 n W all to Fig CL Dist Square Footing Surcharge Over Toe used for Sliding & Overturning Load Type Wind (W) (Service Level) Footing Type Base Above/Below Soil = 0.0 n A7(iel Load Applied to Stem Exposed Stem 0.0 psi at Back of Wall = 0.300 Ratio = 0.0 lbs Wind on Axial Dead Load 0.0 lbs (Strength Level) Poisson's Axial Live Load ` 0.0 in Bottom Axial Load Eccentricity = StemConstruetion OK Design Summary Stem Design Height Above Ftg n= 0.00 Wall Material Above'Ht" = Masonry ASD Wall stability Ratios == 2.10 OK Design Method = 8,00 Overturning 1.68 OK Thickness = # 4 Sliding Rebar Size = 24.00 Total Bearing Load ` ` 1,885 lbs Reber Spacing = 8.75 in Rebar Placed at 6,631 ...resultant ecc. Design Data = 0.382 Soil Pressure @Toe 1,631 psi OK iblFB+fall a 0 psi OK Total Force @ Section Soil Pressure Heel = 2,000 psi Service Level lbs = 336.9 Allowable Strength Level lbs = soil Pressure Less Than Allowable ACI Factored Toe Moment...Actual 0 psi Service Level ft-# = 393.0 ACI Factored Heel _ C 0.0 psi OK Strength Level ft-# ` Footing Shear @ Toe Shear @ Heel 3.O psi OK= Moment.....Allowable 1.028.8 Footing Allowable - 75.0 psi Shear ..... Actual 3.7 Sliding Calcs Sliding Force = 883.1 lbs Service Level Psi= Strength Level psi _ Lateral less 100% passive Force = - 825.0 lbs 659 8lbs Shear..... Allowable p 44.6 g1.50 less 100% Friction Force = - in2= 0.0 lbs OK Ane t(Masonry) in- 6.63 Added Force Req'd ` 0.0 lbs OK Rebar Depth 'd' ....for 1.5 Stability ` Masonry Data psi= 1,500 fm psi= 20,000 Fs = Yes Solid Grouting _ of active lateral soil pressure IS Modular Ratio'n' 21 4S 78 0 Vertical component NOT considered in the calculation psf _ of soil bearing Wall Weight = 1.000 Short Tenn Factorin = 7.60 Load Factors CBC 2016,ACI Equiv. Solid Thick. = Building Code Masonry Block Type Medium Weight Dead Load 1,200 = 1.600 Masonry Design Method ASD Live Load 1.600 Concrete Data psi = Earth,H 1.000 fc psi= Wind,W 1.000 Fy Seismic, E Use menu Item Settings > Printing E, Title Block to set these ofive lines of Information for your p 9r Total Footing Width Footing Thickness Key Width Key Depth Key Distance from Toe z 12.00 In 6.00 In 12.001n s 0.00 it 2,500 Psi Fy_` 60,000 psi 150.00 pcf Fcooting concrete Density - 0.0018 Min. As % 2.00 @ Btm . 3.00 in cover @ Top Force lbs Items HL Act Pres (ab water tbl) 883.1 HL Act Pres (be water tbl) Hydrostatic Force Buoyant Force Surcharge over Heel ` Surcharge Over Toe Adjacent Footing Load Added Lateral Load Load @ Stem Above Soil c Project Name/Number: sp8384 wall t page: 2 Title VlvaOte Wall Type 2 Date: 2 JUN 2020 Dsgnr: JVV Description.... Wall Type 2 • RH=3.5' Factoreerroso��� Mu' : upward _ 0 g Mu' : Downward _ 0 Mu: Design Actual 1 -Way Shear 0.00 = 40.00 Allow 1 -Way Shear None Spec'd= = Toe Reinforcing # 4 @ 8,00 in Heel Reinforcing = None Spec'd Key Reinforcing = Footing Torsion, Tu hi Tu = Allow Torsion, p 7. , I318-14,AC153043 HHei 0 psi 733 it-# 2,307 it-# 1,574 it-# 2.99 psi 75.00 PSI 0.00 ft -lbs 0.00 it -lbs Footing provide if torsion exceeds allowable, p supplemental design for footing torsion. Other Acceptablen-hI'5laMbda'sgrt(i )Sm 20 37 in, #7@ 27.77 ^ @ 36.57 in, #9@ 46 Toe: phiMn P 14.35 in, #6@ Heel: #4@ 9.251n. #5@ Key: phiMn - phi'5'lambda'sgrt(fc)'Sm Int Min fooling T&S reinf Area Min footing T&s reinf Area per toot If one layer of horizontal bare: #4@ 9.26 in #5@ 14.35 in #6@ 20.371n - 1.50 1,668.0 O.T.M. _� 1 4 Total 1183.1 2.10 Resistingloverturning Ratio J 885,1 lbs Vertical Loads used for Soll Pressure = 0.78 0:26 In2 Rt If two layers of horizontal bars: #40 18.521n #5@ 28.70 in #6@ 40.741n Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active IaResistancressure IS NOT considered in Resistance. the calculation of Overturning ,....RESIST IN...... Distance Moment Force it tt# lbs J.83 1,646.9 Soil Over HL (ab. water tbl) 696'3 1.83 1,646.9 Soil Over HL (bel. water tbl) Weirs Table 149.7 2.22 332.7 Sloped Sil over rHeeel Surcharge Over Adjacent Footing Load ` Axial Dead Load on Stem = • Axial Live Load on Stem L Soil Over Toe 104.0 Surcharge Over Toe 312.0 0.33 Stem Welght(s) - Earth @ Stem Transitions= 450.0 1.50 675.0 Footing Weigh' = 75.0 0.25 18.8 Key Weight _ Vert. component2.777.4 Total = lbs R.M. for overturning • Axial live load NO includ for toiltpress llaysa Culatlon. resistance, Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active IaResistancressure IS NOT considered in Resistance. the calculation of Overturning page; 3 Protect Vlvap/e W l 384 wall t TYPe 2Date: 2 JUN 2020 Title > Printing & Title Block Dsgnr. JVV Use menu Item Settings Description.... RH-3 5' to sett these 9r m nes of Information Wall Type 2' for y Code: CBC 2016,ACI 316-14,AC1530-13 83gq • newpon beachWocs\structural talcs\backgnnd�a'I4 wal \s Retaining win s\sp P Reta File: k:\dra 9 levered all In ,3t anti This W 11.20.03 C Beta n ro c) 7967.20 9, u 1 License 1KW-06066246 ENDELL GAYER nseT : o Liee ,..__.,-nr of still_ . Horizontal �� nOtconsidered) (Deflection due to wall bending 250.0 pci soil spring Reaction Modulus P 0.060 In To of Wall (approximate only) ressure excl Horizontal Dell (� heel soil bear'' The above calculation is not valid If the because the wall would then tend to rotate into the retained soil. Use menu item Settings> Printing & Title Block to set these program nes of Information for your This Wall in 3 Wf #4@ 24 Solid Grout 4M@8" @ Heel Project Name/Number : sp8384 wall t page: 4 Title Vlvante Wall Type 2 Date: 2 JUN 2020 Dsgnr: JVV Description.... Wail TYPO 2' RH=3.5' h\docs st ucturel talcs\background\sp8384 wal Code: CBC 20161ACI 318-14,ACI 530-13 Cantilevered Retaining Wall TA' RISING TO THE CHALLENGE Vivante Retaining Wall Calculations Project Site: 850 San Clemente Drive Newport Beach, CA 92660 Developer Nexus Development 1 MacArthur Place, Suite 300 Santa Ana, CA 92707 Prepared by Tait & Associates, Inc. 701 North Parkcenter Drive Santa Ana, CA 92705 (714)560-8200 Engineer: Jacob Vandervis, P.E. Registration No. 46301 May 20th, 2020 TAI T HIEING TO THE CHALLENGE Tait & Associates 701 North Parkcenter Drive Santa Ana, CA 92705 (714) 560-8200 RETAINING WALL NOTES GENERAL 1. ALL CONSTRUCTION AND WORKMANSHIP SHALL CONFORM TO THE 2019 CB . ARCHITECT/ENGIN ER SHECK ALL HALL E NOTIFIEDIMMEDIATANDELYSITE ELY OFNANY DISCREPANCIES ORDITIONS BEFORE TPOSS OLE DEFICIENCIES. FOUND TIS D A MINIMUM OF 15" INTO FIRM UNDISTURBED NATURAL SOIL OR 1. FOOTING ARE TO BE CABBIE iFF OG NL DW IN APPROVED COMPACTED FILL PER GEOTECHNICAL REPORT•_ A MINIMUMS WIDTH OF 15IINCHIiS AND EMBEDLMENTDEPTH OF 15 INCHES BELOOW THE LOWESTD ON ADJACENT GRAD p•ONDINGLALLOWABLOE BTEARING PRESSURE.SEDMENTS ARE RECOMMENDED FOR THECORRE ' He . to minimum depth below lowest adjacent grade at the Uma 01 mond­" w••------ - ULD BE IN BACKFILLING BEHIN WALLS. 3.OITE Oi TO BE USED FOR BACK FILL ALL RETAINING WALLS SHALL B ALLOWS R ONSDESIG ADEQUATELY SHORED DURING THE BACKFILL OPERATION. CONCRETE_SIVE STRENGTH OF 3,700 2. AGGREGATES SHALL BE NATURAL SANAND O RICK CONFORMING TO ASTM C33. AT 28 DAYS. 3. CEMENT SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C-150, TYPE V. MINIMUM 4. THE FOLLOWING M CLEAR DISTANCES BETWEEN REINFORCING STEEL AND FACE OF CONCRETE SHALL BE MAINTAINED UNLESS NOTED OTHERWISE: CENTER OF SLAB SLAB ON GRADE 2 CONCRETE BELOW GRADE, FORMED 3^ CONCRETE BELOW GRADE, UNFORMED (POURED AGAINST EARTH) 1 1/2" CONCRETE EXPOSED TO WEATHER 5. PROVIDE 3/4" CHAMFERS AT ALL EXPOSED CORNERS. REINFORCING STEEL 1. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 40 FOR SIZES #3 AND #4 AND GRAD 60 FOR SIZES #5 AND LARGER. 2, WELDED FABRIC (MESH) SHALL CONFORM TO THE LATEST REVISED ASTM AI85. SMOOTH WIRE FABRIC SHALL CONFORM TO ASTM A85, YIELD STRENGTH 60 KSI. 3. ALL BARS IN MASONRY SHALL BE LAPPED A MINIMUM OF 40 BAR DIAMETERS (24" MIN.) AT ALL SPLICES UNLESS NOTED OTHERWISE. 4. ALL BARS IN CONCRETE SHALL BE LAPPED A MINIMUM OF 36 BARS DIAMETERS (24" MIN-) AT ALL SPLICES UNLESS NOTED OTHERWISE. 5. SPLICES OF HORIZONTAL REBAR IN WALLS AND FOOTINGS SHALL BE STAGGERED 48" MINIM 6 ALL BENDING OF REINFORCING STEEL SHALL CONFORM TO THE LATEST EDITION OF THE CBC. tuse menu item Stngs � Printing o set these five lines of information Title Block for your program. This Wall in File: Retained Height Wall height above soil Slope Behind Wall Height of Soil over Toe Water height over heel = 6.00 It 0.50 It = 0.00 6.00 in 0.0 It Surcharge Loads Surcharge Over Heel - 250.0 psf Used To Resist Sliding & Overturning - Surcharge Over Toe 0.0 psf - Used for Sliding & Overturning Axial Load Applied to Stem 0.0 lbs Axial Dead Load - 0.0 lbs Axial Live Load = 0.0 in Axial Load Eccentricity =� Design Summary H_rhtriocs\structural Project Name/Number : sp8384 wall t Title Vivagte Wall Dsgnr: AG Description.... RH = 6' wNehicle Loading Cantilevered Retaining Wail Soil Data Allowsoil Equivalent Fluid Pressure Active Heel Pressure Wall Stability Ratios = 1.66 OK Overturning 1.58 OK _ Sliding to Bottom - Total Bearing Load - 4, 994 lbs = 16.32 in ...resultant ecc. Wind on Exposed Stem = Passive Pressure Soil Density, Heel Soil Density, Toe FootingllSoil Friction Soil height to ignore for passive pressure Page: 1 Date: 26 MAY 2020 wal Code: CBC 2016,ACI 316-14,ACI 530-13 - 1'V .v y-- ethod 55.0 psf/ft 275.0 psf/ft 110.00 pcf 0.00 pcf 0.350 6.00 in Lateral Load Applied toStem - Lateral Load = o.o #/ft 0,00 ft ...Height to Top _ 0.00 It to Bottom - 0 psf ...Height Load TYPO = Wind (ServiceLevel) Wind on Exposed Stem = 0.0 psf (Strength Level) 75.0 psi Soil Pressure @ Toe - 3,414 psf O 0 psf O = Soil Pressure @ Heel - 3,500 psf Allowable Soil Pressure Less Than Allowable - 4,779 psf ACI Factored @ Toe _ 0 psf ACI Factored @ Heel _ 11.5 psi O Footing Shear @ Toe - Shear @ Heel 16.0 psi O Footing _ 75.0 psi Allowable - at Back of Wall = Sliding Calcs Lateral Sliding Force = = 2,484,4 lbs 2,165.61bs less 100% Passive Force = 1 747 7 lbs less 100% Friction Force _ 0.0 lbs Added Force Req'd _ 0.0 lbs ....for 1.5 Stability - Rebar Spacing Adjacentoo Int g Load 2nd Bottom - Adjacent Footing Load _ 0.0 lbs 0.00 ft Footing Width _ 0.00 in Eccentricity __ 0.00 ft Wall to Ftg CL Dist Line Load Footing Type ASD Base Above/Below Soil = 0.0 ft at Back of Wall = 0.300 Poissons Ratio = K 2nd Bottom $t em Construction Stem OK Stem OK Design Height Above Ftc ft 3.33 0.00 Masonry Wall Material Above "Ht" _ _ Masonry ASD Design Method _ ASD 8.00 12.00 Thickness = # 5 # 5 Rebar Size = 24.00 8.00 Rebar Spacing _ - Edge Edge Rebar Placed at Design Data _ 0.314 0.685 fb/FB+fa/Fa - K Total Force @ Section 529.8 1,740.0 Service Level lbs= Strength Level Ibis = Moment.... Actual ft-#= 620.0 4,230.0 Service Level K Strength Level ft-#= 6,167.2 K Moment..... Allowable ft-#= 1,970.0 Shear..... Actual 5.8 12.5 Service Level psi = Strength Level psi = 45.3 Shear ..... Allowable psi 44.4 91.50 139.50 OK Anet(Masonry) int= 5.25 9.00 OI( Rebar Depth 'd' n = MasonryData 1,500 1,500 I'm psi= 32,000 20,000 Fs psi= = Yes Yes I'd Grouting 2148 So i - 21.46 Vertical component of active lateral soil pressure IS Modular Ration' psf _ 78.0 1240 NOT considered in the calculation of soil bearing Wall Weight = 1.000 1.000 Short Term Factor 760 11.60 Equiv. Solid Thick. in= Load Factors CBC 2016,ACI = Medium Weight Building Code 1.200 Masonry Block Type = ASD Dead Load 1.600 Masonry Design Method Live Load 1.600 concrete Data psi= Earth,H 1.000 fc psi = Wind, W 1.000 Fy Seismic, E Project Name/Number : sp8384 wall t Page: 2 i Title vivante Wall Date: 26 MAY 2020 Use menu item Settings Printing &Title Block Dsgnr: AG information Description.... to set these five lines of RH = 6' wNehicle Loading for your program. ral Code: CBC 2016,ACI 318-14,A01530-13 This Wall in File: k:\drawings\sp\sp8384- newpor[beacCantlit@VBred iRetainingdWall 4wal Build 11.20.03.31 Footing Data Moment Ift 0.50 It Toe Width _ 4.17 Heel Width _ 4.67 Total Footing Width 2,444.9 _ Footing Thickness - 16.00 in = 12.00 in Key Width = 24.00 in Key Depth _ 0.00 ft Key Distance from Toe - 2,500 psi Fy = 60,000 psi fc = 150.00 pcf Footing Concrete Density =_ 6.0018 Min. As % 2.00 cover @ Top @ Stm= 3.00 in Footig pesign Results � Ree HH=eI - 4 779 0 psi Factored Pressure _ 6,761 789 ft-# Mu' : Upward _ 1,008 8,504 it-# Mu' : Downward _ 479 7,716 ft-# Mu: Design 11.53 15.99 psi Actual 1 -Way Shear = 75.00 75.00 psi Allow 1 -Way Shear _ # 5 @SAO in Toe Reinforcing = Heel Reinforcing = None S # 5 @ 6,n 00 00 i Key Reinforcing = 0.00 ft -lbs Footing Torsion, Tu hi Tu = 0.00 ft -lbs Footing Allow. Torsion, p rovide If torsion exceeds allowable, p supplemental design for footing torsion. Other Acceptable Sizes & Spacings 18.51 in, #8@ 24.38 in, #9@ 30. Toe: #4@ 6.17 in, #5@ 9.56 in, #6@ 13.58 in, #7@ 18.61 in, #8@ 24.38 in, #9@ 30. Heel: #4@ 6.17 in, #5@ 9.56 in, #6@ 13.58 in, #7@ Key: phiMn -- phi'5'lambda'sgrt(fc)'Sm 1.62 int Min footing T&S re of Area per foot 0.39 m2 A Min footing If two layers of horizontal bars: If one layer of horizontal bars: #4@ 12.35 in #4@ 6.17 in #5@ 19.14 in #5@ 9.57 in #6@ 27.16 in #6@ 13.58 in Force Ulsranw " ft-# lbs ft item HL Act Pres (ab water tbl) 1,546.9 HL Act Pres (be water tbl) Hydrostatic Force Buoyant Force_ g37.5 Surcharge over Heel - Surcharge Over Toe Adjacent Footing Load - Added Lateral Load Load @ Stem Above Soil = 2.50 3,867.2 3.75 3,515.6 Total - O.T.M. = 2837 - 1.66 ResistinglOverturning Ratio 4 g93.5 lbs Vertical Loads used for Soil Pressure = Soil Over HL (ab. water tbl) Soil Over HL (bel. water tbl) Watre Table Sloped Soil Over Heel = Surcharge Over Heel = Adjacent Footing Load = Axial Dead Load on Stem = • Axial Live Load on Stem = Soil Over Toe Surcharge Over Toe Stem Weight(s) - Earth @ Stem Transitions= Footing Weight Wei ht Vertical calculation of Sliding p,nent of active lateral oil pressure IS NOT considered in the Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Force lbs 2,092.2 792.5 tance Moment Ift ft-# 3.09 6,454.4 3.09 6,454.4 3.09 2,444.9 0.25 150.0 0.2 66.g 0.94 619.0 977. 1.33 130.5 1,050.8 2.34 2,453.5 300.0 0.50 150.0 Key Wei- ht component1- Tota .M lbs R.= * Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation. Project Name/Number: sp8384 wall t page : 3 Title Vivarlte Wall Date: 26 MAY 2020 Use menu item Settings > Printing & Title Block Dsgnr: AG .. to set these five lines of information Description.. RH = W wNehicle Loading for your program. This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structur al calcs\background\sp8384 wal Pro c 1987 019, Build 11.20.03.31 Cantilevered Retaining Wail code: c13c201s,Acl31a-1a,Acl53o-13 Retaln ( ) License : KIN 06056245 i.e„�a TO: WENDELL GAYER _ t �, In flection at To of Wall due to settlement of soil (Deflection due to wall bending not considered) 250.0 Pc! Soil Spring Reaction Modulus 0.132 in Horizontal Dsfl @ Top of Wall (approximate only) .... _ _ —, —a h.nrina oressure exceeds r rhe above caicuiauom, ^�• •--- because the wall would then tend to rotate into the retained soil. i, I Project NamelNumber : sp8384 wall t page: 4 Title Vivante Wall Date: 26 MAY 2020 s > Printing & Title Block Dsgnr. AG Use menu item Setting Description.... to set these five lines of information RH = 6• wNehicle Loading for your program. j ort beach\docs\structural calcs\background\sp8384 wal Code: CBC 2016,ACI 318-14,ACI 530-13 This Wall i( File: 2019,, ingdsp\sp8384-new p Cantilevered Retaining Wali RetainPro (c) 7987-2018, Build 17.20.03.31 License : KW -06056245 License To: WENDELL GAYER Solid Grout 12" WI #5@ $,,. Solid Grout 6"� #5@S.in c@c Toe #5@8- @ Heel I A Use menu item Settings > Printing & Title Block to set these five lines of information for your program. This Wall in File: Criteria Retained Height 8.33 it _ Wall height above soil _ 0.50 ft Slope Behind Wall 0.00 _ Height of Soil over Toe - 12.00 in Water height over heel = 0.0 ft Project Name/Number : sp8384 wall t Title Vivante Wall Dsgnr. AG Description.... RH = 8.33' wlAdditional Screen Wall beach\docs\structural calcs\bacKgrow,�­=--- Cantilevered Retaining Wall S 11 o 11 i 11 l Data = Allow Soil Bearing 4,655.0 psf Equivalent Fluid Pressure Method 35.0 psf/ft Active Heel Pressure page: 1 Data: 20 MAY 2020 wal Code: CBC 2016,ACI 318-14,ACI 530=13 0.0 lbs Axial Dead Load _ 0,0 lbs Axial Live Load - 0.0 in Axial Load Eccentricity = Earth Pressure Seismic Load Method : Triangular Load at bottom of Triangular Distribution ...... (Strength) Design Summa Wall Stability Ratios = = 275.0 psflft Passive Pressure _ 110.00 pcf Soil Density, Heel _ 0,00 pcf Soil Density, Toe = 0.350 FootingilSoil Friction ...He Height to Bottom Soil height to ignore = 6.00 in for passive pressure Seismic (E) Used for Sliding &Overturning t Stem 0.0 lbs Axial Dead Load _ 0,0 lbs Axial Live Load - 0.0 in Axial Load Eccentricity = Earth Pressure Seismic Load Method : Triangular Load at bottom of Triangular Distribution ...... (Strength) Design Summa Wall Stability Ratios = Lateral Load Applied o Surcharge Loads = 0.0 #Ift Surcharge Over Heel = 330.0 psf & Overtur0 Lateral Load = ,..Hei ht to Top = 0.00 ft 0.00 ft used To Resist Sliding 0 Pal ...He Height to Bottom 10.3 psi Surcharge Over Toe - = Seismic (E) Used for Sliding &Overturning Load Type (Service Level) Axial Load Applied to Stemii� d stem 0.0 psf 0.0 lbs Axial Dead Load _ 0,0 lbs Axial Live Load - 0.0 in Axial Load Eccentricity = Earth Pressure Seismic Load Method : Triangular Load at bottom of Triangular Distribution ...... (Strength) Design Summa Wall Stability Ratios = 2.44 OK Overturning _ 1.76 OK Sliding ACI Factored @ Toe _ - Total Bearing Load 8,882 lbs = 14.92 in ...resultant ecc. - Wind on Expose = (Strength Level) Wind acts left-to-right toward retention side. - Soil Pressure @ 3,370 psf O 0 psf O Heel = Soil Pressure @ _ 4,655 psf Allowable Soil Pressure Less Than Allowable - 4,718 psf ACI Factored @ Toe _ 0 psf ACI Factored @ Heel _ 0.0 psi O Footing Shear @ To - Shear @ 10.3 psi Footing _ - 75.0 psi Allowable ASD 12.00 Sliding Calcs Lateral Sliding Force = = 2,793.3 lbs 1 815.0 lbs less 66 % Passive Force 100% Friction Force = _ 308.6 lbs ,1 less 0 0 lbs Added Force Req'd _ 0.0 lbs ....for 1.5 Stability - Rebar Spacing Cnntina Load Footing Width Eccentricity Wall to Ftg CL Dist Footing Type Base Above/Below Soil at Back of Wall Poisson's Ratio Total Strength -Level Seismic Load.... . = 20.000 psf Total Service -Level Seismic Load.... . 0.00 ft 0.00 in 0.00 ft Line Load rrn 0.300 98.330 lbs = 68.831 lbs O IK 2nd Bottom Stem Construction Stem OK Stem OK Height Above Ftp ft= 4A0 0.00 Design Wall Material Above "HY' = Masonry Masonry ASD Design Method = ASD 12.00 16.00 Thickness = # 5 # 5 Rebar Size = 16.00 8.00 Rebar Spacing _ Edge Edge Rebar Placed at Design Data _ 9.467 0.795 K fb/FB+fa/Fa - K Total Force @ Section 802.6 2,160.8 Service Level lbs = Strength Level lbs = Moment.... Actual ft #= 1,487.8 7,217.1 Service Level K Strength Level 3,183.7 9,069.1 Moment..... Allowable ft-#= Shear..... Actual 5.8 11.5 Service Level psi - Strength Level psi = 44.9 45.8 Shear..... Allowable psi 139.50 187.50 OK Anet(Masonry) in2- 9.00 13.00 OK Rebar Depth 'd' In= Masonry Data 1,500 1,500 Fm psi= psi= 20,000 20,000 Fs tin - - Yes Yes 2148 of active lateral soil pressure IS Solid Gr9U g Modular Ration' = 21.48 . 164.0 Vertical component NOT considered in the calculation of soil bearing Wall Weight ps f- 124.0 = 1.000 1.000 Short Term Factor 11.60 15.60 Load Factors CBC 2016,ACI Equiv. Solid Thick. in - = Medium Weight Building Code Dead Load 1.200 Masonry Block Type Design Method = ASD Live Load 1.600 1.600 Masonry Concrete Data psi= Gadh. H . ,,,,,. Fc Project Name/Number :sp8384 wall t page: 2Date: 20 MAY 2020 Title Vivante Wali > Printing & Title Block Dsgnr: AG Use menu item Settings Description.... RH = 8.33' w/Additional Screen Wali to set these five lines of information for your program. ort beach\docs\structural talcs\background\sp8384 wal Code: CBC 2016,AC1 318-14,ACI 530-13 Cantilevered Retaining Wall This Wall in File: k:\drawings\sp\sp8384 - newp ..,..,o R ..Id 11.20.03.31 Footing Data Force"`^•.__ It _ 0.00 It Toe Width= 6.00 Heel Width = 6.00 Total Footing Width 18.00 in Footing Thickness - = 12.00 in Key Width = 24.00 in Key Depth = 0.00 it Key Distance from Toe 60,000 psi 2,500 psi Fy 150.00 pcf fc = Footing concrete Density _ 0,0018 Min. As % 2 00 @ Btm. 3.00 in Cover @ Top Surcharge over Heel _ �n Results Footing tl�el T29 0 psf Factored Pressure 4'71 = 8 9, 109 ft -#,6 = 19 ft-# Mu' :Upward 0 23= Mu' : Downward 0 14,510 ft-#_ Mu: Design 0.00 10.31 psi Actual 1 -Way Shear _ 0.00 75.00 psi Allow 1 -Way Shear _ # 5 @ 8.00 in Toe Reinforcing = # 5 @ 8.00 in Heel Reinforcing- # 5 @ 14.35 in Key Reinforcing = 0.00 ft -lbs Footing Torsion, Tu hi Tu 0.00 ft -lbs Footing Allow. Torsion, p rovide If torsion exceeds allowable, p lemental design for footing torsion. Supp cm Other Acceptable Sizes da sgrt(fc)'Sm 18.51 in, PEI gs #8@ 24.38 in, #9@ 30. Toe: phWn - ph'g,56 m, #6@ 13.58 in, #7@ 18 in Key:. #4@60 m, #5@@ 5.5 in, #6@ 18 in, #7@ 18 in, #8@ 3 int Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars: #4@ 6.17 in #5@ 9.57 in #6@ 13.58 in 2.3 0.39 int A If two layers of horizontal bars: #4@ 12.35 in #5@ 19.14 in #6@ 27.16 in Soil Over HL (ab. water tbl) Soil Over HL (bel. water tbl) Watre Table Sloped Soil Over Heel _ Surcharge Over Heel Adjacent Footing Load - Axial Dead Load on Stem = Axial Live Load on Stem Soil Over Toe Surcharge Over Toe Stem Welght(s) Earth @ Stem Transitions= Footing Weight If seismic is included, the OTM and sliding ratios may be 1.1 per section 1807.2.3 of IBC. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vedical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Force Itis 4,277.6 1,540.0 tan"e tante Force"`^•.__ It ft-tt ft-# - Itis 15,684.6 Items 1,692'0 328 5,545.9 HL Act Pres (ab water tbl) 150.0 Act Pres (be water tbl) 0.50 HL Hydrostatic Force_ 5,076.1 Buoyant Force = 1,032.5 4.92 Surcharge over Heel _ Surcharge Over Toe Load = Adjacent Footing _ Added Lateral Load - Load @ Stem Above Soil = 68.8 3.28 225.6 Seismic Earth Load = gO.T.M. _- Total - = 2.44 ResistinglOverturning Ratio 8,881.8 used for Soil Pressure = Ibs Vertical Loads 2.3 0.39 int A If two layers of horizontal bars: #4@ 12.35 in #5@ 19.14 in #6@ 27.16 in Soil Over HL (ab. water tbl) Soil Over HL (bel. water tbl) Watre Table Sloped Soil Over Heel _ Surcharge Over Heel Adjacent Footing Load - Axial Dead Load on Stem = Axial Live Load on Stem Soil Over Toe Surcharge Over Toe Stem Welght(s) Earth @ Stem Transitions= Footing Weight If seismic is included, the OTM and sliding ratios may be 1.1 per section 1807.2.3 of IBC. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vedical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Force Itis 4,277.6 1,540.0 tan"e tante Moment 737.0 ft-# - 3.67 15,684.6 3.67 15,684.6 3.67 5,646.7 Key Weight Component 2 Vert. Comp 6,463.6 Total = 8,881.8 lbs R.MP • Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation. 0.59 737.0 1,255.3 1 17 185.4 158.9 3.00 4,050.0 1,350.0 150.0 300.0 0.50 Key Weight Component 2 Vert. Comp 6,463.6 Total = 8,881.8 lbs R.MP • Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation. Project tdameWall Date: 20 MAY 2020 : sp8384 wall Page: 3 Title Vivar+te te Wall > Printing & Title Block Dsgnr: AG Use menu item Settings Description.... RH = 8.33' wlAdditional Screen Wall to at these five lines of information for your program. Code: CBC 2016,ACI 318-14,ACI 530-13 s\s \s 8384 - neWPOrt beach\docs\structural talcs\background\a'i 4 wa This Wall in File: k\drawingA 1p_2o.oa.a1 Cantilevered Retaining J. t of Wall due to settlement of soil Horizontal Deflection at To not considered) (Deflection due to wall bending 250.0 pci Soil Spring Reaction Modulus To of Wall (appro)imate only) Horizontal DO@ P the above calculation is not valid if the heel soil t because the wall would then tend to rotate into the retained soil. 0.138 in Project NamelNumber :sp8384 wall t Page: 4 Title vivante Wall Date: 20 MAY 2020 Dsgnr: AG Use menu item Settings > Printing &Title Block Description.... Wall to set these five lines of information RFI = 83T wlpdditional Screen for your program. p 8384 - newport beach\docs\structural calcs\background\sp8384 wal Code: CBC 2016,ACI 318-14,ACI 530-13 This Wall in File: k:\drawings\s \sp Cantilevered Retaining Wall RetainPro (c) 7887.2018, Build 11.20.03.37 License : KW -06056245 License To : WENDELL GAYER 127 WI #5@ 18" Solid Grout. wwi.85@ 8' Solid Grout #5@14.35in @ Center On Key #5@8" @ Heel Use menu item Settings > Printing & Title Block to set these five lines of information for your program. This Wall in File: Criteria - nnwnnrt beach\docs\structural Retained Height = 2.50 ft Wall height above soil = 0.50 ft Slope Behind Wall = 2.00 Height of Soil over Toe = 6.00 in Water height over heel = 0.0 It Surcharge Loads Surcharge Over Heel = 0.0 psf Used To Resist Sliding & overturning Surcharge Over Toe = 0.0 Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Design Summary Wall Stability Ratios _ 1.92 OK Overturning - Sliding = 2.67 OK Project Name/Number : sp8384 wail t Title vivante Wall Type 2 Dsgnr: JW Description.... Wall Type 2 - RH=2.5' ,i-Xha ,Mrnnnd\so8384 wal Cantilevered Retaining Wall Page: 1 Date: 20 MAY 2020 Code: CBC 2016,ACI 318-14,ACI 530-13 Soil Data Lateral Load = = 0.0 #/ft 0.00 ft ...Height to Top ...Height to Bottom = 0.00 ft Allow Soil Bearing = 2,000.0 psf Pressure Method Wind (W) 0. psf OK Equivalent Fluid Wind on Exposed Stem = 0.0 psf (Strength Level) 1'508 psf Active Heel Pressure 55.0 psf/ft = p Footing Shear @ Toe = 4.2 psi O Footing Shear @ Heel = 3.2 psi O Allowable = 75.0 psi %` 24.00 Passive Pressure = 275.0 psf/ft less 100% Passive Force = - 825.0 lbs less 100% Friction Force = - Soil Density, Heel = 110.00 pcf;. 0.0 lbs O ....for 1.5 Stability = 0.0 lbs O Soil Density, Toe = 0.00 pcf �--� lbs= 171.9 FoofingIISoil Friction = 0.350 '.. Moment.... Actual Seismic, E 1.000 Soil height to ignore _ 6.00 in ft-#= 143.2 Strength Level for passive pressure - Moment..... Allowable - 808.1 Lateral Load Applied to Stem Lateral Load = = 0.0 #/ft 0.00 ft ...Height to Top ...Height to Bottom = 0.00 ft Load Type = Wind (W) 0. psf OK (Service Level) Wind on Exposed Stem = 0.0 psf (Strength Level) 1'508 psf Total Bearing Load - = 857 be ...resultant ecc. = 5.63 in Soil Pressure @ Toe = 1,077 psi OK Soil Pressure @ Heel = 0. psf OK Allowable = 2,000 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = 1'508 psf ACI Factored @ Heel = 0 psf Footing Shear @ Toe = 4.2 psi O Footing Shear @ Heel = 3.2 psi O Allowable = 75.0 psi Sliding Calcs 24.00 Lateral Sliding Force = 421.9 lbs less 100% Passive Force = - 825.0 lbs less 100% Friction Force = - 300.0 lbs Added Force Req'd = 0.0 lbs O ....for 1.5 Stability = 0.0 lbs O Adjacent Footing Load Adjacent Footing Load = -- 0.0 lbs Footing Width = 0.00 ft Eccentricity = 0.00 in Wall to Ftg CL Dist = 0.00 ft Footing Type Square Footing Base Above/Below Soil = 0,0 ft at Back of Wall Modular Ration' Poisson's Ratio = 0.300 Stem Construction K K K Bottom psi= 1,500 Stem OK Design Height Above Ftc ft = 0.00 Wall Material Above "Ht" = MasonryASD Design Method - Modular Ration' Thickness = 8.00 Rebar Size = # 4 Rebar Spacing = 24.00 Rebar Placed at = Edge Design Data 7.60 Medium Weight Dead Load 1.200 fb/FB+fa/Fa - - U n7 Total Force @ Section = ASD Earth, H 1.600 Service Level lbs= 171.9 Strength Level lbs = psi= psi = Moment.... Actual Seismic, E 1.000 Fy Service Level ft-#= 143.2 Strength Level ft-#= Moment..... Allowable - 808.1 Shear..... Actual Service Level psi = 1.9 Strength Level psi = Shear..... Allowable psi = 44.3 Anet(Masonry) in2= 91.50 K Rebar Depth 'd' in = 5.25 Masonry Data fm psi= 1,500 Fs psi= 20,000 Vertical component of active lateral soil pressure IS Solid Grouting = = Yes 21.48 NOT considered in the calculation of soil bearing Modular Ration' = 78.0 Wall Weight psf Short Term Factor = 1.000 Load Factors Building Code CBC 2016,AC1 Equiv. Solid Thick. in= = 7.60 Medium Weight Dead Load 1.200 Masonry Block Type Live Load 1.600 Masonry Design Method = ASD Earth, H 1.600 Concrete Data Wind, W 1.000 fc psi= psi = Seismic, E 1.000 Fy i Project Name/Number : sp8384 wall t Page : 2It Title Vivarlte Wall Type 2 Date: 20 MAY 2020 I' Use menu item Settings > Printing &Title Block Dsgnr: JVVDescription.... ' to set these five lines of information Wall Type... RH=2.5 for your program. i i This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural talcs\background\sp8384 wal Code: CBC 2018,ACI 318-14,ACI 530-13 1987.2019, Build 11.20.03.31 Cantilevered Retaining Wall ens, : nv.-------- :ense To : WENDELL GAY Footing Design Results Footing Data roe Heel - Toe Widfh _ 0.50 ft 1.50 - 1,508 0 psf Factored Pressure _ 2 025 12 ft-# Heel Width _ 2 00 Mu' : Upward _ 615 264 ft-# Total Footing Width Mu': Downward 118 252 ft-# _ Footing Thickness - 12.00 in = Mu: Design 4 18 3.18 psi = Key Width 6.00 in 12.00 in Actual 1 -Way Shear = 40.00 75.00 psi Allow 1 -Way Shear = _ Key Depth _ Distance from Toe - 0.50 ft Toe Reinforcing = None Spedd = # 4 @ 8.00 in Key fc = 2,500 psi Fy = 60,000 psi Heel Reinforcing Key Reinforcing = None Spec'd 0.00 ft -lbs = Footing Concrete Density 150.00 pcf 0.0018 FootinTorsion, Tu = 0.00 ft -lbs _ Min. As % Btm = 3.00 in Cover @ Top 2.00 @ FootingAllow. Torsion, p hi Tu allowable, provide If torsion exceeds design for footing torsion. supplemental Other Acceptable Sizes & Spacings Toe: phiMn = phi'5'lambda'sgrt(fc)'Sm 46 25 in, 14.35in, #S@m 20.37 in, #7@ 27.77 in, #8@ 36.57 in, #9@ Heel: #4@ n Key: p #a@ 0.52 int Min footing T&S reinf Area 26 int At footing T&S reinf Area per foot of horizontal bars: If two layers If one layer of horizontal bars: #4@ 18.52 in #4@ 9.26 in #5@ 28.70 in #5@ 14.35 in #6@ 40,74 in #6@ 20.37 in of Overturnin & Resistin Forces & Moments .....RESISTING..... Distance M Summa Force n #nt .,...OVERTURNING..... lbs ft nt Moment Force Distance lbs p49.2 1.58 362.6 Item Soil Over HL (ab. water IN) 1.58 362.8 HL Act Pres (ab water tbl 421.9 1.17 550.6 Soil Over HL (bel. water tbl) HL Act Pres (be water IN) Watre Table 32.9 = 19.1 1.72 Sloped Soil Over Heel Hydrostatic Force = Surcharge Over Heel _ Buoyant Force Adjacent Footing Load - Surcharge over Heel = Axial Dead Load on Stem = Surcharge Over Toe = = • Axial Live Load on Stem 0.25 Adjacent Footing Load - _ Soil Over Toe Added Lateral Load - Surcharge Over Toe = 195.0 0.83 Load @Stem Above Soil =_ 234.0 Stem Weight(s) _ Earth @ Stem Transitions= 1.00 300.0 - 300.0 - 421.9 O.T.M. = 492.2 Footing Weight 56.3 = 75.0 0.75 Total = Key Weight = 1 92 Vert. Component = 74g 0 857.3 lbs R.M.= ReslstinglOverturning Ratio = Total = 857.3 lbs in total displayed, or used for overturning Vertical Loads used for Soil Pressure * Axial live load NOT included but is included for soil pressure calculation. resistance, Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. project Name/Number: sp8384 wall t page: 3 Title Vivagte Wall Type 2 Date: 20 MAY 2020 & Title Block Dsgnr: JVV to S menu item Setting,Printing Description.... to set these five lines,of of information Wall Type 2 - RH=2.5' for your program. orbeach\docs\structural talcs\background\sp8384 wal Code: C8C 2016,ACI 318-14,ACI 530-13 This Wall in File: k:\drawings\sp\sp8384 - newp Cantilevered Retaining Wall _ -_ 1-1 ins, -2019, sulld 11.20.03.31 t Horizontal Deflection at To of Wall due to settlement of soil (Deflection due to wall bending not considered) 250.0 pci Soil Spring Reaction Modulus 0.045 in Horizontal Deli @ Top of Wall ( app roximate only) ......,_ —a noarina oressure rhe above calculanw i n - - because the wall would then tend to rotate into the retained soil. Use menu item Settings > Printing & Title Block to set these five lines of information for your program. This Wall in File: k:\drawings\sp\sp8384 - newport b Lzn R.wr,Pro c 1987-2019, Build 11.20.03.31 License: KW -08051M reVFR 8" wt k4@ 24". Solid Gfdut. Project Name/Number : sp8384 wall t Page: 4 Title Vivante Wall Type 2 Date: 20 MAY 2020 Dsgnr: JVV Description.... Wall Type 2 - RH=2.5' h\docs\structural calcs\background\sp8384 wal Cantilevered Retaining Wail Code: CBC 2016,ACI 318-14,ACI 530-13 "@8- @ Heel E 6„ T-6` 24, 1Z -F]34' Project Name/Number : sp8384 wall t Page: 1 Use menu item Settings > Printing &Title Block Title vivante Wall Type 2 Date: 20 MAY 2020Dsgnr: JW to set these five lines of information Description.... for your program. Wall Type 2 - RH=3.5' This Wall in File: Criteria Retained Height = 3.50 ft Wall height above soil = 0.50 ft Slope Behind Wall = 2.00 Height of Soil over Toe = 6.00 in Water height over heel = 0.0 ft Surcharge Loads Surcharge Over Heel = 0.0 psf Used To Resist Sliding & Overturning Surcharge Over Toe = 0.0 Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in )ort beach\docs\structural calcs\1background\spa3s4I Cantilevered Retaining Wall Soil Data Allow Soil Bearing = 2,000.0 psf Equivalent Fluid Pressure Method Active Heel Pressure = 55.0 psf/ft Passive Pressure = 275.0 psf/ft Soil Density, Heel = 110.00 pcf Soil Density, Toe = 0.00 pcf FootingIlSoil Friction = 0.350 Soil height to ignore _ 6.00 in for passive pressure - Wall Stability Ratios Overturning = 222 OK Sliding = 1.73 OK Lateral Load Applied to Stem Lateral Load = ...Height to Top = 0.0 #/ft 0.00 ft ...Height to Bottom = 0.00 ft Load Type = Wind (W) 0 psi P O (Service Level) Wind on Exposed Stem = 0.0 psf (Strength Level) 1'696 psf Total Bearing Load = 1,635 lbs ...resultant ecc. = 7.20 in Soil Pressure @ Toe = 1'21psf OK Soil Pressure @ Heel = 0 psi P O Allowable = 2,000 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = 1'696 psf ACI Factored @ Heel = psf Footing Shear @ Toe = 5.3 psi O Footing Shear @ Heel = 4.8 psi OK Allowable = 75.0 psi Sliding Calcs = Lateral Sliding Force = 806.9 Itis less 100% Passive Force = - 825.0 lbs less 100% Friction Force = - 572.3 lbs Code: CBC 2016,ACI 318-14,ACI 530-13 Footing Width Eccentricity Wall to Fig CL Dist Footing Type Base Above/Below Soil at Back of Wall Poisson's Ratio Load 0.00 It 0.00 in 0.00 ft Square Footing 0.0 ft 0.300 Stem Construction K K CBC 2016,ACI Bottom 1.200 Live Load Stem OK Design Height Above Ftc ft= 0.00 Wall Material Above "Hf- = Masonry Design Method = ASD Thickness = 8.00 Rebar Size = # 4 Rebar Spacing = 24.00 Rebar Placed at = Edge Design Data psi = fb/FB+fa/Fa _ - o.4as Total Force @ Section Service Level be = 336.9 Strength Level lbs = Moment.... Actual Service Level ft-#= 393.0 Strength Level ft-#= Added Force Req'd = 0.0 lbs OK ....for 1.5 Stability = 0.0 lbs OK Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Load Factors Building Code CBC 2016,ACI Dead Load 1.200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 Moment..... Allowable Shear..... Actual Service Level Strength Level Shear..... Allowable Anet(Masonry) Rebar Depth 'd' Masonry Data Fm Fs Solid Grouting Modular Ratio'n' Wall Weight Short Term Factor Equiv. Solid Thick. Masonry Block Type Masonry Design Method Concrete Data fc Fy 808.1 psi = 3.7 psi = psi= 44.6 nt= 91.50 in = 5.25 psi= 1,500 psi = 20,000 = Yes = 21.48 psi = 78.0 = 1.000 in = 7.60 = Medium Weight = ASD psi = psi = Project Name/Number : sp8384 wall t Page: 2 Title Vivar)te Wall Type 2 Date: 20 MAY 2020 use menu item Settings > Printing & Title Block Dsgnr: JW to set these five lines of information Description.... for your program. Wall Type 2 - RH=3.5' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetainPro (c)1987.2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 RIISe TO: WENUCLL ue{���. _ , Footing Design Results Footing Data I Toe Heel - Toe Width - = 0.50 ft 2.50 Factored Pressure = 1,695 0 psi 2 386 378 ft-# Heel Width Total Footing Width = 3.00 - Mu' :Upward - 615 1,429 ft-# Mu' : Downward - Footing Thickness - 12.00 in Mu: Design -148 1,051 ft-# 4.82 psi Key Width = 6.00 inActual 1 -Way Shear = 5.29 = 40.00 75.00 psi Key Depth = 12.00 in Allow 1 -Way Shear = None Spedd Key Distance from Toe = 0.50 it Toe Reinforcing Heel Reinforcing = # 4 @ 8.00 in Fc = 2,500 psi FY = 60,000 psi 150.00 pcf Key Reinforcing = None Spedd 0.00 ft -lbs Footing Concrete Density = = 0.0018 = Footing Torsion, Tu 0.00 ft -lbs Min. As % Cover @Top 2.00 @ Btm = 3.00 in Footing Allow. Torsion, phi Tu = allowable, provide If torsion exceeds supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn = phi'5'lambda'sgrt(fc)'Sm #5@ 14.35 in, #6@m 20.37 in, #7@ 27.77 in, #6@ 36.57 in, #9@ 46 Heel: #4@ 92 Phi, Key: p Min footing T&S reinf Area 0.78 in2 0.26 in2 Ift Min footing T&S reinf Area per foot If two layers of horizontal bars: If one layer of horizontal bars: #4@ 9.26 in #4@ 18.52 in #5@ 28.70 in #5@ 14.35 in #6@ 40.74 in #6@ 20.37 in Summa of Ovetturnln & Resisting FOfCeS a MomentsRESISTING Moment .....OVERTURNING Force Dis ince Moment lbs It Force Distance Itis ft ft-# 1,470.5 705.8 2.08 Item Soil Over HL (ab. water tbl) 1,456.8 2.08 1,470.5 HL Act Pres (ab water tbl) 806.9 1.50 Soil Over HL (bel. water tbl) HL Act Pres (be water tbl) Watre Table 220 8 92.4 2.39 Hydrostatic Force Sloped Soil Over Heel = Buoyant Force = Surcharge Over Heel = Surcharge over Heel = Adjacent Footing Load = Surcharge Over Toe = Axial Dead Load on Stem = Adjacent Footing Load = • Axial Live Load on Stem 0.25 Added Lateral Load = _ Soil Over Toe Load @ Stem Above Soil = Surcharge Over Toe _ 312.0 0.83 260.0 = Stem Weight(s) - Earth @ Stem Transitions= 450.0 1.50 675.0 Total = 806.9 O.T.M. = 1,210.3 Footing Weight _ 75.0 075 56.3 Key Weight -_ Resisting/Overturning Ratio 2,22 Vert. Component = 2,682.5 Total = 1,635.3 Itis R.M.= Vertical Loads used for Soil Pressure = 1,635.3 lbs Axial live load NOT included in total displayed, or used for overturning calculation. resistance, but is included for soil pressure Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. i Project Name/Number: sp8384 wall t page: 3 I Title Vivarite Wall Type 2 Date: 20 MAY 2020 Use menu item Settings > Printing & Title Block Dsgnr: JVV to set these five lines of information Wall Type..Description..... RH=3.5' for your program. cs\backgrounsp83 I'll 8 "1 This Wall in File: k:\drawings\sp\sp8384 - n11 I'll beacCan{IleVeredstructural alRetalrllClgd\Wal4 l w, a, 1 11 Code: CBC 2016,ACI 318-14,ACI 530-13 ..._._e.., 1,1087-2019, Bulld 11.20.03. 31 t lt To of Wall due to settlement of s011 Horizontal Defection a (Deflection due to wall bending not considered) 250.0 pci Soil Spring Reaction Modulus 0.045 in Horizontal Defl @ Top of Wall (approximate only) ......._ _ —L —n hoarina pressure exc� � r I -he above caicuiau��, ,� —, •--- - because the wall would then tend to rotate into the retained soil. Project NamelNumber :sp8384 wall t page: 4 Title Vivar)te Wall Type 2 Date: 20 MAY 2020 Use menu item Settings > Printing &Title BlockDsgnr: JVV Description.... to set these five lines of information Wall Type 2 - RH=3.5' for your program. ort beach\docs\structural talcs\background\sp8384 wal Code: CBC 2016,ACI 318- Cantilevered 530-13 This Wall in File: k:\drawings\sp\sp8384 - newP Cantilevered Retaining Wall ...noz�n�4 eulld 11.20.03.31 8" wl44@ 24. Solid cmoi s� #4@8. @ Heel 133'-6" Use menu item Settings > Printing & Title Block to set these five lines of information for your program. This Wall in File: Criteria Retained Height 4.50 ft _ height above soil 50 ft 60 o.60 Wall Slope Behind Wall 2 .00 Height of Soil over Toe = 6.00 in Water height over heel = 0.0 ft Surcharge Loads 0.0 psf Surcharge Over Heel & Overturning Used To Resist Sliding - 0.0 Surcharge Over Toe Used for Sliding & Overturning Axial Load Applied to Stem 0.0 lbs Axial Dead Load - 0.01bs Axial Live Load = 0.0 in Axial Load Eccentricity = Desi n Summary Wall Stability Ratios = Overturning Sliding Total Bearing Load ...resultant ecc. Project Name/Number : SP8384 WALL T Page: 1 20 MAY 2020 Title Vivar)te Wall Data: 1,500 psf Dsgnr: JVV ACI Factored @ Toe _ 546 psf Description.... Wall Type 3 - RH=4.5' 5.3 psi O Footing Shear @ Toe = Shear @ Heel = Beach\Docs\Structural Calcs\Background\SP8384 WAL 316-14,ACI 530-13 Retaining Wall Code: CBC 2016,ACI Cantilevered Sliding Calcs _ 738.0 lbs Soil Data 275.0 lbs less 100% Passive Force = - = 1,500.0 psf Allow Soil Bearing Pressure Method 0.0 lbs Equivalent Fluid 32 0 psf/ft - 0.0 lbs ....for 1.5 Stability = Active Heel Pressure Service Level fc = 275.0 psf/ft K Strength Level Passive Pressure _ 110.00 pcf ttt Seismic, E Soil Density, Heel = 0.00 pcf 808.1 Soil Density, Toe = 0.350 Shear..... Actual Service Level psi = 3.5 Footingll Soil Friction Strength Level psi = Soil height to ignore _ 6.00 in Shear..... Allowable psi for passive pressure - Footing Load Anet(Masonry) Lateral Load App hed to Stem Adjacent Footing Load = o.o lbs = 0.0 #/ft Lateral Load = 0.00 It Adjacent Footing Width Eccentricity - 0.00 ft 0.00 in ...Height to Top _ 0.00 ft to Bottom - Wall to Fig CL Dist = 0.00 ft Line Load ...Height = Wind (W) Load Type (Service Level) Footing Type Base Above/Below Soil = 0.0 ft Wind on Exposed Stem = 0.0 psf at Back of Wall _ poisson's Ratio - 0.300 (Strength Level) Fs = 4.18 OK 1.54 OK 2,452 lbs 2.92 in - 836 psf O Soil Pressure @ Toe _ 390 psf O Soil Pressure @ Heel _ 1,500 psf Allowable Soil Pressure Less Than Allowable1 71 psf ACI Factored @ Toe _ 546 psf ACI Factored @ Heel - 5.3 psi O Footing Shear @ Toe = Shear @ Heel = 2.5 psi Footing - 75.0 psi Allowable - Building Code Sliding Calcs _ 738.0 lbs Lateral Sliding Force - 275.0 lbs less 100% Passive Force = - 868.3 lbs less 100% Friction Force = 0.0 lbs Added Force Req'd = 0.0 lbs ....for 1.5 Stability = Earth, H Stem Construction Bottom Stem OK Design Height Above Ftc ft= 0.00 Wall Material Above "HY' = Masonry Design Method ASD = 6.00 Thickness = # 4 Rebar Size = 24.00 Rebar Spacing = Edge ASD ASD OK= outing Rebar Placed at Solid r Modular Ratl0'n' = 21.46 78.0 Vertical component NOT considered in the calculation Design Data = 0.601 K fb/FB+fa/Fa Short Term Factor 7,60 K Total Force @ Seetion Equiv. Solid Thick. 324.0 Building Code Service Level lbs = =ASD Dead Load Strength Level lbs = Live Load Moment.... Actual ft#= 486.0 Earth, H Service Level fc psi = K Strength Level ft-# _ Seismic, E Moment ..... Allowable 808.1 Shear..... Actual Service Level psi = 3.5 Strength Level psi = Shear..... Allowable psi 44 9 81.50 OK Anet(Masonry) m2- 5.25 OK Rebar Depth 'd' in= Masonry Data psi= 1,500 Fin psi = 20,000 Fs = Yes G of active lateral sail pressure IS Solid r Modular Ratl0'n' = 21.46 78.0 Vertical component NOT considered in the calculation of soil bearing Wall Weight psf _ = 1.000 Short Term Factor 7,60 Load Factors CBC 2016,ACI Equiv. Solid Thick. in - = Medium Weight Building Code 1.200 Masonry Block Type Design Method =ASD Dead Load 1.600 Masonry Live Load 1.600 concrete Data psi = Earth, H 1.000 fc psi = Wind, W 1.000 F Seismic, E • Use menu item Settings > Printing & Title Block to set these five lines of information for your program. This Wall in File: Data Heel Width Total Footing Width Footing Thickness Key Width Key Depth Key Distance from Toe _ 3.25 4.00 12.00 in 12.00 in = 0.00 in 0.50 It = 60,000 p 2,500 psi sl Fy f c 150.00 pcf Footing Concrete Density _ 0.0018 Min. As % 2 00 @ Btm: 3.00 in cover @ Top Force lbs Items HL Act Pres (ab water tbl) 738.0 HL Act Pres (be water tbl) Hydrostatic Force - Buoyant Force Surcharge over Heel Surcharge Over Toe Load = Adjacent Footing _ Added Lateral Load Load @ Stem Above Soil Project Name/Number : SP8384 WALL T Date: �- Title Vivante Wall Dsgnr: JVV Description.... Wall Type 3 - RH=4.5' Beach\Docs\Structural Calcs\BackgroaliP8384 WCode: CBC 2016' ACI 318-14,ACI 530-13 Cantilevered Retaining Footing Design Results 7e Heel 1,171 546 psf Factored Pressure _ 3,820 2,270 ft-# Mu' : upward _ 1, 199 3,332 ft-# Mu' :Downward _218 1,062 ft-# Mu: Design - 5.28 2.53 psi Actual 1 -Way Shear = 40.00 75.00 psi Allow 1 -Way Shear = None Spec 'd Toe Reinforcing = # 4 @ 8.00 in Heel Reinforcing _ # 5 @ 14,60 in Key Reinforcing = 0,00 ft -lbs Footing Torsion, Tu hi Tu = 0.00 ft -lbs Footing Allow. Torsion, p rovide If torsion exceeds allowable, P torsion. supplemental design for footing SPacingS Other Acceptable Sizes 8, #f5'lambda'sgrt(fc)'Sm 27.77 in, #8@ 36.57 in, #9@ 46 Heel: 4@ Toe: #4@ 9.25 in, #5@ 14.35 in, #6@ 20.37 in, #7@ Key: No key defined n2 Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars: #4@ 9.26 in #5@ 14.35 in #6@ 20.37 in - 3 ft-# 1.83 1,670.8 1,353.1 Total = 738.0 O.T.M. _ 4.78 ResistinglOverturning Ratio2 452,3 lbs Vertical Loads used for Soil Pressure - 1.04 0.26 in2 ft If two layers of horizontal bars: #4@ 18.52 in #5@ 28.70 in #6@ 40.74 in Soil Over HL (ab. water tbl) Soil Over HL (bel. water IN Werra Table Sloped Soil Over Heel - Surcharge Over Heel= Adjacent Footing Load Axial Dead Load on Stem = * Axial Live Load on Stem = Soil Over Toe Surcharge Over Toe Stem Weight(s) _ Earth @ Stem Transitions= Footing Weight = Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Force lbs 1,278.8 183.5 390.0 600.0 I" ..... Moment ante ftdk 2.71 3,463.3 2.71 3,463.3 3.14 576.1 0.38 1.08 422.5 2.00 1,200.0 1.00 Key Weight 8 Vert. Component � lbs R.M.= Total = 2' ed, or used for overturning * Axial live load NOT includ for solltpreasulre calculation. resistance, Project NamelNumber :SP8384 WALL T page: 3Date: 20 MAY 2020 i Title Vivante Wall s > printing & Title Block Dsgnr: JVV Use menu item Setting Description.... 4.V Wall Type 3 - RIi= to at these five lines of information for your program. Code: CBC 2016,ACI 318-14,ACI 530-13 s\SP\SP8384 -Newport Beach\Docs\Structural Calcs\Backgroda\iiP8384 WA This Wall in File,.K:\Dna ann 11.20.03.31 Cantilevered Retaining It Horizontal Deflection at To of Wall due to settlement of soi (Deflection due to wall bending not considered) 250.0 PC' Soil Spring Reaction Modulus 0,029 in To of Wall (approximate only) Horizontal Defl @ P ressure exc I'd if the heel soil bearin the above calculation is not va i because the wall would then tend to rotate into the retained soil. Use menu item Settings > Printing & Title Block to set these five lines of information for your program. This Wall in File: 0" w! #1@ 24" Solid Grout Project Name/Number : SP8384 WALL T Title Vivagte Wall Dsgnr: JVV Description.... Wall Type 3 - RH=4.5' Beach\Docs\Structural Cantilevered Retaining Wall Page: 4 Date: 20 MAY 2020 WAL Code: CBC 2016,ACI 318-14,ACI 630-13 „" 4@0- @ Heel 4'-G" 5.0" 0 0 150 � - 210 1#-* TAI T RISING TO THE CHALLENGE Viva me Retaining Wall Calculations Project Site: 850 San Clemente Drive Newport Beach, CA 92660 Developer Nexus Development 1 MacArthur Place, Suite 300 Santa Ana, CA 92707 Prepared by Tait & Associates, Inc. 701 North Parkcenter Drive Santa Ana, CA 92705 (714)560-8200 Engineer: Jacob Vandervis, P.E. Registration No. 46301 May 20th, 2020 TAI T RISING TO THE CHALLENGE Tait & Associates 701 North Parkcenter Drive Santa Ana, CA 92705 (714)560-8200 RETAINING WALL NOTES GENERAL 1. ALL CONSTRUCTION AND WORKMANSHIP SHALL CONFORM TO THE 2019 CBC. 2. CONTRACTOR MUST CHECK ALL DIMENSIONS, AND SITE CONDITIONS BEFORE STARTING WORK. ARCHITECT/ENGINEER SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES OR POSSIBLE DEFICIENCIES. FOUNDATIONS 1. FOOTING ARE TO BE CARRIED A MINIMUM OF 15" INTO FIRM UNDISTURBED NATURAL SOIL OR APPROVED COMPACTED FILL PER GEOTECHNICAL REPORT. 2. FOOTINGS MAY BE DESIGNED USING AN ALLOWABLE BEARING CAPACITY OF 1,500 PSF BASED ON A MINIMUM WIDTH OF 15 INCHES AND EMBEDMENT DEPTH OF 15 INCHES BELOW THE LOWEST ADJACENT GRADE. THE FOLLOWING FOOTING WIDTHS AND EMBEDMENTS ARE RECOMMENDED FOR THE CORRESPONDING ALLOWABLE BEARING PRESSURE. STATIC BEARING nshoon MINIMUM FOOTING MINIMUM FOOTING• PRESSURE WIDTH EMBEDMENT s Inches Inches 4.000 12 24 3,500 48 24 3.000 24 24 2,000 18 18 1,500 15 1 15 d f d Relers to minimum depth below mesl adjacent grade at the 4me of foun a ion w 3. RELATIVELY NON -EXPANSIVE FILL SHOULD BE USED IN BACKFILLING BEHIND WALLS. DESIGN ALLOWS FOR ONSITE SOILS TO BE USED FOR BACK FILL. ALL RETAINING WALLS SHALL BE ADEQUATELY SHORED DURING THE BACKFILL OPERATION. CONCRETE 1. ALL CONCRETE SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH OF 3,700 PSI AT 28 DAYS. 2. AGGREGATES SHALL BE NATURAL SAND AND ROCK CONFORMING TO ASTM C33. 3. CEMENT SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C-150, TYPE V. 4. THE FOLLOWING MINIMUM CLEAR DISTANCES BETWEEN REINFORCING STEEL AND FACE OF CONCRETE SHALL BE MAINTAINED UNLESS NOTED OTHERWISE: CENTER OF SLAB SLAB ON GRADE 2„ CONCRETE BELOW GRADE, FORMED CONCRETE BELOW GRADE, UNFORMED (POURED AGAINST EARTH) 1 1/2" CONCRETE EXPOSED TO WEATHER 5. PROVIDE 3/4" CHAMFERS AT ALL EXPOSED CORNERS. REINFORCING STEEL 1. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 40 FOR SIZES #3 AND #4 AND GRADE 60 FOR SIZES #5 AND LARGER. 2. WELDED FABRIC (MESH) SHALL CONFORM TO THE LATEST REVISED ASTM At 85. SMOOTH WIRE FABRIC SHALL CONFORM TO ASTM A85, YIELD STRENGTH 60 KSI. 3. ALL BARS IN MASONRY SHALL BE LAPPED A MINIMUM OF 40 BAR DIAMETERS (24" MIN.) AT ALL SPLICES UNLESS NOTED OTHERWISE. 4. ALL BARS IN CONCRETE SHALL BE LAPPED A MINIMUM OF 36 BARS DIAMETERS (24" MIN.) AT ALL SPLICES UNLESS NOTED OTHERWISE. 5. SPLICES OF HORIZONTAL REBAR IN WALLS AND FOOTINGS SHALL BE STAGGERED 48" MINIMUM. 6. ALL BENDING OF REINFORCING STEEL SHALL CONFORM TO THE LATEST EDITION OF THE CBC. Use menu item Settings> Printing & Title Block to set these five lines of information for your program. This Wall in File: Criteria Retained Height = 6.00 ft Wall height above soil = 0.50 ft Slope Behind Wall = 0.00 Height of Soil over Toe = 6.00 in Water height over heel = 0.0 ft Surcharge Loads Surcharge Over Heel = 250.0 per Used To Resist Sliding & Overturning Surcharge Over Toe = 0.0 psf Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Desi n Summary Wall Stability Ratios Project Name/Number : sp8384 wall t Title Vivante Wall Dsgnr: AG Description.... RH = 6' w/Vehicle Loading )ort beach\docs\structural calcs\background\sp838, Cantilevered Retaining Wall Soil Data Sliding Allow Soil Bearing = 3,500.0 psf Equivalent Fluid Pressure Method Active Heel Pressure = 55.0 psf/ft Passive Pressure = 275.0 psf/ft Soil Density, Heel = 110.00 pcf Soil Density, Toe = 0.00 pcf FootingilSoil Friction = 0.350 Soil height to ignore 75.0 psi for passive pressure = 6.00 in Overturning = 1.66 OK Sliding = 1.58 OK Total Bearing Load = 4,994 lbs ...resultant ecc. = 16.32 in Lateral Load Applied to Stem Lateral Load = 0.0 #/ft ...Height to Top = 0.00 it ...Height to Bottom = 0.00 ft Load Type = Wind (W) 4,779 psf (Service Level) Soil Pressure @ Toe = 3,414 psf OK Soil Pressure @ Heel = 0 psf OK Allowable = 3,500 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = 4,779 psf ACI Factored @ Heel = 0 psf Footing Shear @ Toe = 11.5 psi OK Footing Shear @ Heel = 16.0 psi OK Allowable = 75.0 psi Sliding Coca ASD Lateral Sliding Force = 2,484.4 lbs less 100% Passive Force = - 2,165.6 be less 100% Friction Force = 1,747.7 lbs Added Force Req'd = 0.0 be OK ....for 1.5 Stability = 0.0 lbs OK Vertical component of active lateral soil pressure I NOT considered in the calculation of soil bearing Load Factors 0.00 ft Building Code CBC 2016,ACI Dead Load 1.200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 Wind on Exposed Stem = 0.0 psi (Strength Level) wal Page : 1 Date: 26 MAY 2020 Code: CBC 2016,ACI 318-14,ACI 530-13 Load Footing Width V = 0.00 ft Eccentricity = 0.00 in Wall to Fig CL Dist = 0.00 ft Footing Type Line Load Base Above/Below Soil = 0.0 ft at Back of Wall 0.00 Poisson's Ratio = 0.300 Stem Construction S 2nd Bottom Stem OK Stem OK Design Height Above Ftf ft= 3.33 0.00 Wall Material Above "Hf' = Masonry Masonry Design Method = ASD ASD Thickness = 8.00 12.00 Rebar Size = # 5 # 5 Rebar Spacing = 24.00 8.00 Rebar Placed at = Edge Edge Design Data Ib/FB +fa/Fa = 0.314 0.685 Total Force @ Section Service Level lbs= 529.8 1,740.0 Strength Level lbs = Moment.... Actual Service Level ft-#= 620.0 4,230.0 Strength Level ft-#= Moment..... Allowable ft-#= 1,970.0 6,167.2 Shear..... Actual Service Level psi = 5.8 12.5 Strength Level psi = Shear..... Allowable psi = 44.4 45.3 Anet(Masonry) int= 91.50 139.50 Rebar Depth 'd' in= 5.25 9.00 Masonry Data fm psi= 1,500 1,500 Fs psi= 32,000 20,000 Solid Grouting = Yes Yes Modular Ration' = 21.48 21.48 Wall Weight psi = 78.0 124.0 Short Term Factor = 1.000 1.000 Equiv. Solid Thick. in= 7.60 11.60 Masonry Block Type = Medium Weight Masonry Design Method = ASD Concrete Data fc psi= Fy psi = Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project Name/Number : sp8384 wall t I Use menu item Settings > Printing & Title Block Title Vivagte Wall Page: 2 to set these five lines of information Dsgnr: AG Dale: 26 MAY 2020 for your program. Description.... RH = 6' wNehicle Loading This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetalnPro (c) 1987.2019, Build 11.20.03.31 License: KW -06056245 Cantilevered Retaining Wall Code: CBC 2016,ACI318-14,ACI 530-13 License To: WENDELL GAYER Footing Data Footing Design Results Toe Width = 0.50 ft Toe Heel Heel Width = 4.17 Factored Pressure = 4,779 0 psf Total Footing Width = 4.67 Mu': Upward = 6,761 789 ft-# Footing Thickness = 18.00 in Mu': Downward = 1,008 8,504 ft-# Mu: Design = 479 7,716 ft-# Key Width = 12.00 in Actual 1 -Way Shear = 11.53 15.99 psi Key Depth = 24.00 in Allow 1 -Way Shear = 75.00 75.00 psi Key Distance from Toe = 0.00 ft Toe Reinforcing = #5 @ 8.00 in fc = 2,500 psi Fy = 60,000 psi Heel Reinforcing = # 5 @ 8.00 in Footing Concrete Density = 150.00 pcf Key Reinforcing = None Spec'd Min. As % = 0.0018 Footing Torsion, Tu = 0.00 ft -lbs Cover @ Top 2.00 @ Btm: 3.00 in Footing Allow. Torsion, phi Tu = 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: #4@ 6.17 in, #5@ 9.56 in, #6@ 13.58 in, #7@ 18.51 in, #8@ 24.38 in, #9@ 30. Heel: #4@ 6.17 in, #5@ 9.56 in, #6@ 13.58 in, #7@ 18.51 in, #8@ 24.38 in, #9@ 30. Key: phiMn= phi'5'Iambda'sgrt(fc)'Sm Min footing T&S reinf Area 1.82 int Min footing T&S reinf Area per foot 0.39 int /it If one layer of horizontal bars: If two layers of horizontal bars: #4@ 6.17 in #4@ 12.35 in #5@ 9.57 in #5@ 19.14 in #6@ 13.56 in #6@ 27.16 in Summa of Overturnin & Resistin Forces & Moments ..... OVERTURNING ..........RESISTING..... Force Distance Moment Force Distance Moment Item lbs It ft-# lbs ft ft-# HL Act Pres (ab water tbi) 1,546.9 2.50 3,867.2 Soil Over HL (ab. water tbl) 2,092.2 3.09 6,454.4 HL Act Pres (be water tbl) Soil Over HL (bel. water tbl) 3.09 6,454.4 Hydrostatic Force Watre Table Buoyant Force = Sloped Soil Over Heel = Surcharge over Heel = 937.5 3.75 3,515.6 Surcharge Over Heel = 792.5 3.09 2,444.9 Surcharge Over Toe = Adjacent Footing Load = Adjacent Footing Load = Axial Dead Load on Stem= Added Lateral Load = ' Axial Live Load on Stem = Load @ Stem Above Soil = Soil Over Toe = 0.25 = Surcharge Over Toe = Stem Weight(s) = 660.2 0.94 619.0 Earth @ Stem Transitions= 97.9 1.33 130.5 Total = 2,484.4 O.T.M. = 7,382.8 Footing Weighl = 1,050.8 2.34 2,453.5 Key Weight = 300.0 0.50 150.0 Resisting/Overturning Ratio = 1.66 Vert. Component = Vertical Loads used for Soil Pressure = 4,993.5 lbs Total = 4,993.5 lbs R.M.= 12,252.3 " Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project Name/Number; sp8384 wall t Use menu item Settings > Printing 8 Title Block Title Vivarlte Wall Page: 3 to set these five lines of information Dsgnr: AG Date: 26 MAY 2020 for your program. Description.... RH = 6' w/Vehicle Loading This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetainPro (c) 1987-2019, Build 11.20.03.31 License: KW -06056245 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Tilt Horizontal Deflection at Top of Wall due to settlement of soil (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal DO @ Top of Wall (approximate only) 0.132 in The above calculation is not valid if the heel soil bearina pressure exceeds that of the toe because the wall would then tend to rotate into the retained soil. Use menu item Settings > Printing & Title Block to set these five lines of information for your program. This Wall in File: beach\docs\structural Project Name/Number : sp8384 wall t Title Vivante Wall Dsgnr: AG Description.... RH = 6' wNehicle Loading wal Page: 4 Date: 26 MAY 2020 RetainPro (c) 1987-2019, Build 11.20.03.31 License: KW -06056245 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 11— ... -r... rmcsInc, I nnvco 8- Wt; 5Q 2¢^ Solid Grout 12" W/ #6@ 8" Solid GrDtlt #5@8.in @Toe #5@8- @ Heel 6'-0" 6'-6" Project Name/Number : sp8384 wall t Use menu item Settings > Printing & Title Block Title Vivante Wall Page: 1 to set these five lines of information Dsgnr: AG Date: 20 MAY 2020 for your program. Description.... RH = 8.33' w/Additional Screen Wall This Wall in File: beach\docs\structural wal Retain Pro (c) 1987-2019, Build 11.20.03.31 License: KW -06056245 _ _ _ Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Criteria Retained Height = 8.33 ft Wall height above soil = 0.50 ft Slope Behind Wall = 0.00 Height of Soil over Toe = 12.00 in Water height over heel = 0.0 ft Soil Data Lateral Load Applied to Stem Allow Soil Bearing = 4,655.0 psf Equivalent Fluid Pressure Method Active Heel Pressure = 35.0 psf/ft Passive Pressure = 275.0 psf/ft Soil Density, Heel = 110.00 pcf Soil Density, Toe = 0.00 pcf FdotingilSoil Friction = 0.350 Soil height to ignore = Seismic (E) for passive pressure = 6.00 in Surcharge Loads Lateral Load Applied to Stem Surcharge Over Heel - 330.0 psf Lateral Load = 0.0 #/ft Used To Resist Sliding & Overturning ...Height to Top = 0.00 ft Surcharge Over Toe = 0.0 psf ...Height to Bottom = 0.00 ft Used for Sliding & Overturning Footing Shear @ Toe = 0.0 psi OK Footing Shear @ Heel = Load Type = Seismic (E) Axial Load Applied to Stem Sliding Calcs (Service Level) Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Earth Pressure Seismic Load Method : Triangular Load at bottom of Triangular Distribution ....... (Strength) Desi n Summa Wall Stability Ratios Overturning = 2.44 OK Sliding = 1.76 OK Total Bearing Load = 8,882 lbs ...resultant ecc. = 14.92 in Soil Pressure @ Toe = 3,370 psf OK Soil Pressure @ Heel = 0 psi OK Allowable = 4,655 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = 4,718 psf ACI Factored @ Heel = 0 psi Footing Shear @ Toe = 0.0 psi OK Footing Shear @ Heel = 10.3 psi OK Allowable = 75.0 psi Sliding Calcs Total Force @ Section Lateral Sliding Force = 2,793.3 lbs less 66 % Passive Force = - 1,815.0 lbs less 100% Friction Force = - 3,108.6 lbs Added Force Req'd = 0.0 lbs OK ....for 1.5 Stability = 0.0 lbs OK Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Load Factors Design Height Above Ft£ Building Code CBC 2016,ACI Dead Load 1.200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 Wind on Exposed Stem = 0.0 psf (Strength Level) Wind acts left-to-right toward retention side. Footing Width Eccentricity Wall to Fig CL Dist Footing Type Base Above/Below Soil at Back of Wall Poisson's Ratio Total Strength -Level Seismic Load.... . 20.000 psf Total Service -Level Seismic Load.... . Stem Construction Design Height Above Ft£ R= Wall Material Above "Ht" _ Design Method = Thickness = Rebar Size = Rebar Spacing = Rebar Placed at = Design Data Wall Weight fb/FB+fa/Fa = Total Force @ Section Short Term Factor Service Level lbs = Strength Level lbs= Moment.... Actual 11.60 Service Level ft-#= Strength Level ft-#= Moment..... Allowable ft-#= Shear..... Actual ASD Service Level psi = Strength Level psi = Shear..... Allowable psi = Anet (Masonry) int = Rebar Depth 'd' in= Masonry Data Stem OK Stem OK 4.00 0.00 Masonry Masonry ASD ASD 12.00 16.00 # 5 # 5 16.00 8.00 Edge Edge 0.467 0.795 802.6 2,160.8 1,487.8 7,217.1 3,183.7 9,069.1 5.8 11.5 44.9 45.8 139.50 187.50 9.00 13.00 fm psi= 1,500 1,500 Fs psi = 20,000 20,000 Solid Grouting = Yes Yes Modular Ratio 'n' = 21.48 21.48 Wall Weight psf= 124.0 164.0 Short Term Factor = 1.000 1.000 Equiv. Solid Thick. in = 11.60 15.60 Masonry Block Type = Medium Weight Masonry Design Method = ASD Concrete Data £c psi = Fy psi = Load 0.0 Ib 0.00 it 0.00 in 0.00 it Line Load 0.0 it 0.300 98.330 lbs 68.831 lbs Project Name/Number : sp8384 wall t Use menu item Settings > Printing & Title Block Title Vivante Wall Page: 2 to set these five lines of information Dsgnr: AG Date: 20 MAY 2020 for your program. Description.... RH = 8.33' w/Additional Screen Wall This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 we[ RetalnPro (c) 1987-2019, Build 11.20.03.31 License : Kw -06056248 _ _ _ _ _ Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Footing Data r Footing Design Results Toe Width = 0.00 ft Toe Heel Heel Width = 6.00 Factored Pressure = 4,718 0 psf Total Footing Width = 6.00 Mu': Upward = 0 9,109 ft-# Footing Thickness = 18.00 in Mu': Downward = 0 23,619 ft-# Mu: Design = 0 14,510 ft-# Key Width = 12.00 in Actual 1 -Way Shear = 0.00 10.31 psi Key Depth = 24.00 in Allow 1 -Way Shear = 0.00 75.00 psi Key Distance from Toe = 0.00 it Toe Reinforcing = # 5 @ 8.00 in fc = 2,500 psi Fy = 60,000 psi Heel Reinforcing = # 5 @ 8.00 in Footing Concrete Density = 150.00 pcf Key Reinforcing = # 5 @ 14.35 in Min. As % = 0.0018 Footing Torsion, Tu = 0.00 ft -lbs Cover @ Top 2.00 @ Btm: 3.00 in Footing Allow. Torsion, phi Tu = 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn = phi'S'lambda'sgrt(fc)'Sm Heel: #4@ 6.17 in, #5@ 9.56 in, #6@ 13.58 in, #7@ 18.51 in, #8@ 24.38 in, #9@ 30. Key: #4@ 10 in, #5@ 15.5 in, #6@ 18 in, #7@ 18 in, #8@ 18 in Min footing T&S reinf Area 2.33 int Min footing T&S reinf Area per foot 0.39 int A If one layer of horizontal bars: If two layers of horizontal bars: #4@ 6.17 in #4@ 12.35 in #5@ 9.57 in #5@ 19.14 in #6@ 13.58 in #6@ 27.16 in Item HL Act Pres (ab water tbl) HL Act Pres (be water tbl) Hydrostatic Force Buoyant Force = Surcharge over Heel = Surcharge Over Toe = Adjacent Footing Load = Added Lateral Load = Load @ Stem Above Soil = Seismic Earth Load = Force Distance Moment lbs it ft-# 1,692.0 3.28 5,545.9 1,032.5 4.92 5,076.1 68.8 3.28 225.6 Total = 2,793.3 O.T.M. = 10,847.7 Resisting/Overturning Ratio = 2.44 Vertical Loads used for Soil Pressure = 8,881.8 lbs If seismic is included, the OTM and sliding ratios may be 1.1 per section 1807.2.3 of IBC. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Soil Over HL (ab. watertbl) Soil Over HL (bel. water tbl) Watre Table Sloped Soil Over Heel = Surcharge Over Heel = Adjacent Footing Load = Axial Dead Load on Stem = * Axial Live Load on Stem = Soil Over Toe = Surcharge Over Toe = Stem Weight(s) _ Earth @ Stem Transitions= Footing Weight = Key Weight = Vert. Component = .....RESISTING..... Force Distance Moment lbs ft ft-# 4,277.6 3.67 3.67 1,540.0 3.67 15,684.6 15,684.6 5,646.7 1,255.3 0.59 737.0 158.9 1.17 185.4 1,350.0 3.00 4,050.0 300.0 0.50 150.0 Total = 8,881.8 lbs R.M.= 26,453.6 * Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation. Project Name/Number: spasn4 wall z Page: 3 Use menu item Settings > Printing & Title Block Title Vivante Wall Date: 20 MAY 2020 Dsgnr: AG to set these five lines of information Description.... for your program. RH = 8.33' w/Additional Screen Wall This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetalnPro (c) 1987^2079, Buitd 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Horizontal Deflection at Top of Wall due to settlement of soil (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal DO @ Top of Wall (approximate only) 0.138 in The above calculation is not valid if the heel soil bearing ressure exceeds that of the toe because the wall would then tend to rotate into the retained soil. Project NamelNumber : spbM4 wall r Page: 4 Title Vivante Wall Date: 20 MAY 2020 Use menu item Settings > Printing &Title Block Dsgnr: AG to set these five lines of information Description.... for your program. RH = 8.33' w/Additional Screen Wall This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetalnPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 12"IN/ 45@ 16" Solid Grout 16"w1#5@ 8" Solid Grout ,@5@14.35n @ Center On Key #5@8- @ Heel Project Namemlumoer : Page: 1 Use menu item Settings > Printing &Title Block Title Vivar)te Wall Type 2 Date: 20 MAY 2020Dsgnr: JVV to set these five lines of information Description.... for your program. Wall Type 2 - RH=2.5' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetalnPro (c) 1987.2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Criteria Retained Height = 2.50 ft Wall height above soil = 0.50 ft Slope Behind Wall = 2.00 Height of Soil over Toe = 6.00 in Water height over heel = 0.0 ft Surcharge Loads Surcharge Over Heel = 0.0 psf Used To Resist Sliding & Overturning Surcharge Over Toe = 0.0 Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Design Summary Wall Stability Ratios Overturning = 1.92 OK Sliding = 2.67 OK Soil Data Allow Soil Bearing = 2,000.0 psf Equivalent Fluid Pressure Method Active Heel Pressure 55.0 sf/ft = P Passive Pressure = 275.0 psf/ft Soil Density, Heel = 110.00 pcf Soil Density, Toe = 0.00 pcf FootingllSoil Friction = 0.350 Soil height to ignore _ 6.00 in for passive pressure - Lateral Load Applied to Stem Lateral Load = = 0.0 #/ft 0.00 ft ...Height to TOP ...Height to Bottom = 0.00 ft Load Type = Wind (W) 0 psf O (Service Level) Wind on Exposed Stem = 0.0 psf (Strength Level) 1,508 psf Total Bearing Load = 857 lbs ...resultant ecc. = 5.63 in Soil Pressure @ Toe = 1,077 psf O Soil Pressure @ Heel = 0 psf O Allowable = 2,000 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = 1,508 psf ACI Factored @ Heel = 0 psf Footing Shear @ Toe = 4.2 psi O Footing Shear @ Heel = 3.2 psi OK Allowable = 75.0 psi Sliding Calcs 24.00 Lateral Sliding Force = 421.9 lbs less 100% Passive Force = - 825.0 Ibis less 100% Friction Force = - 300.0 lbs Added Force Req'd = 0.0 lbs O ....for 1.5 Stability = 0.0 lbs O Adjacent Footing Load Adjacent Footing Load = 0.0 lbs Footing Width = 0.00 ft Eccentricity = 0.00 in Wall to Ftg CL Dist = 0.00 ft Footing Type Square Footing Base Above/Below Soil = 0.0 ft at Back of Wall Short Term Factor Poisson's Ratio = 0.300 Stem Construction fb/FB K K Bottom _ 21.48 Stem OK Design Height Above Ftc ft= 0.00 Wall Material Above "Hf' wall Weight MasonryASD Design Method - Short Term Factor Thickness = 8.00 Rebar Size = # 4 Rebar Spacing = 24.00 Rebar Placed at = Edge Design Data ASD Earth, H 1.600 + fa/Fa = 0.177 Total Force @ Section fc psi= psi= Service Level lbs= 171.9 Strength Level lbs = Moment.... Actual Service Level ft-#= 143.2 Strength Level ft-#= Moment ..... Allowable - - 808.1 Shear ..... Actual Service Level psi = 1.9 Strength Level psi = Shear..... Allowable psi= 44.3 K Anet(Masonry) int= 91.50 K Rebar Depth 'd' in= 5.25 Masonry Data fm psi= 1,500 Fs psi= = 20,000 Yes Vertical component of active lateral soil pressure IS Solid Grouting Modular Ratio'n' _ 21.48 NOT considered in the calculation of soil bearing psf = 78.0 wall Weight Short Term Factor = 1.000 Load Factors Building Code CBC 2016,ACI Equiv. Solid Thick. in= = 7.60 Medium Weight Dead Load 1.200 Masonry Block Type Live Load 1.600 Masonry Design Method = ASD Earth, H 1.600 Concrete Data Wind, W 1.000 fc psi= psi= Seismic, E 1.000 Fy Project Name/Number : sp8384 wall [ Page: 2 Use menu item Settings > Printing & Title Block TTiitllgenr iv me Wall Type 2 Date: 20 MAY 2020 to set these five lines of information Description.... for your program. Wall Type 2 - RH=2.5' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural talcs\background\sp8384 wal RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Footing Design Results J Footing Data I Toe Width = = 0.50 ft 1.50 Toe Heel Factored Pressure - 1,508 0 psf Heel Width Total Footing Width = 2.00 Mu': Upward 2,025 12 ft-# 615 264 ft-# Footing Thickness = 12.00 in Mu' : Downward _ Mu: Design - 118 252 ft-# Key Width = 6.00 in Actual 1 -Way Shear = 4.18 3.18 psi Key Depth = 12.00 in Allow 1 -Way Shear = 40.00 75.00 psi Key Distance from Toe = 0.50 It Toe Reinforcing = None Spec'd fc = 21500 psi Fy = 60,000 psi Heel Reinforcing = # 4 @ 8.00 in Key Reinforcing = None Spec'd Footing Concrete Density = 150.00 pcf - 0.00 ft -lbs Footing Torsion, Tu - Min. As % - 0.0018 Cover @ Top 2.00 @ Btm: 3.00 in Footing Allow. Torsion, phi Tu = 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn = phi'5'lambda'sgrt(fc)'Sm 20.37 in, #7@ 27.77 in, #8@ 36.57 in, #9@ 46 Heel: #4@ 9.25 in, #5@ 14.35 in, #6@ Key: phiMn = phi'5'lambda'sgrt(fc)'Sm Min footing T&S reinf Area 0.52 in2 Min footing T&S reinf Area per foot 0.26 in2 Ift If one layer of horizontal bars: If two layers of horizontal bars: #4@ 9.26 in #4@ 18.52 in #5@ 14.35 in #5@ 28.70 in #6@ 20:37 in #6@ 40.74 in Summary of overturning & Resis#M Forces & Moments RESISTING .....OVERTURNING..... ..... Force Distanccee Moment Force Distance Moment lbs ft ft-# Item lbs ft ft-# Soil Over HL (ab. water t 229.2 1.58 362.8 HL Act Pres (ab water tbl) 421.9 1.17 550.8 I) Soil Over HL (bel. water bl) 1.58 362.8 HL Act Pres (be water tbl) Watre Table Hydrostatic Force Sloped Soil Over Heel = 19.1 1.72 32.9 Buoyant Force = Surcharge Over Heel = Surcharge over Heel = Adjacent Footing Load = Surcharge Over Toe = Axial Dead Load on Stem = Adjacent Footing Load = « Axial Live Load on Stem = Added Lateral Load = Soil Over Toe 0.25 Load @ Stem Above Soil = Surcharge Over Toe = = Stem Weight(s) = 234.0 0.83 195.0 Earth @ Stem Transitions= Total = 421.9 O.T.M. = 492.2 Footing Weight = 300.0 1.00 300.0 56.3 Key Weight = 75.0 0.75 ResistinglOverturning Ratio = 1.92 Vert. Component = 857.3 lbs R.M.= 947.0 Vertical Loads used for Soil Pressure = 857.3 lbs Total = or n for overturning «eisncbu"°nudd oiresraculato fsltpsuleycl resistance, but is Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project Name/Number : sp8384 wall t Title Vivapte Wall Type 2 Page: 3 Use menu item Settings> Printing &Title Block Dsgnr: JW Date: 20 MAY 2020 to set these five lines of information Description.... for your program. Well Type 2 - RH=2.5' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural talcs\background\sp8384 wal RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 Tilt Horizontal Deflection at Top of Wall due to settlement of soil (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal DO @ Top of Wall (approximate only) 0.045 in The above calculation is not valid if the heel soil bearing ressure exceeds that of the toe because the wall would then tend to rotate into the retained soil. Project NamelNumver : spo. -o rva , . Page: 4 Use menu item Settings > Printing &Title Block Title Vivante Wall Type 2 Date: 20 MAY 2020 Dsgnr: JW to set these five lines of information Description.... for your program. Wall Type 2 - RH=2.5' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetalnPro(c)1987^2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 8° w( 94@ 24" Solid Grout. 61� 94@8" @ Heel 2 1 I l E.11" T-0' i i i I i 61. 16" I 1.0., 6„ 1: 6„ TitleGy, Vivante Wall Type 2 Date: 20 MAY 2020 Use menu item Settings > Printing & Title Block Dsgnr: JVV to set these five lines of information Description.... for your program. Wall Type 2 - RH=3.5' hoarh\docs\structural This Wall in File_ Criteria = 275.0 psf/ft Retained Height = 3.50 ft Wall height above soil = 0.50 ft Slope Behind Wall = 2.00 Height of Soil over Toe = 6.00 in Water height over heel = 0.0 ft Surcharge Loads Surcharge Over Heel = 0.0 psf Used To Resist Sliding & overturning Surcharge Over Toe - 0.0 Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Design® Wall Stability Ratios_ = 275.0 psf/ft Overturning = 2 22 OK 1.73 OK Sliding = 0.00 pcf Total Bearing Load = 1,635 lbs ...resultant ecc. = 7.20 in .i-xhm ,knrrnmd\sD8384 wal Cantilevered Retaining Wall Soil Data Allow Soil Bearing - 2,000.0 psf Equivalent Fluid Pressure Method 55.0 psf/ft Active Heel Pressure - Passive Pressure = 275.0 psf/ft Soil Density, Heel = 110.00 pcf Soil Density, Toe = 0.00 pcf FootingIlSoil Friction = 0.350 Soil height to ignore_ 6.00 in for passive pressure - Lateral Load Applied to Stem Lateral Load = = 0.0 #/ft 0.00 ft ...Height to Top ...Height to Bottom = 0.00 ft Load Type = Wind (W) (Service Level) Wind on Exposed Stem = 0.0 psf (Strength Level) Base Above/Below Soil Code: CBC 2016,ACI 318-14,ACI 530-13 Adjacent Footing Load Adjacent Footing Load Bottom Footing Width = 0.00 ft Eccentricity = 0.00 in Wall to Ftg CL Dist = 0.00 It Footing Type Square Footing Base Above/Below Soil = 0.0 ft at Back of Wall 24.00 Poisson's Ratio = 0.300 Stem Construction Bottom Soil Pressure @ Heel = Stem OK Design Height Above HE ft= 0.00 Wall Material Above "HF' Masonry Design Method SO Thickness _8. _ # 4 Rebar Size 24.00 Rebar Spacing Sliding Calcs Lateral Sliding Force = PI ed at _ Edge - Soil Pressure @ Toe = 1,211 psf O 0 psf O Soil Pressure @ Heel = fb/FB+fa/Fa Allowable = 2,000 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = = 1,695 psf 0 psf ACI Factored @ Heel Footing Shear @ Toe = 5.3 psi O Footing Shear @ Heel = O Allowable = 75.0 psi Sliding Calcs Lateral Sliding Force = 806.9 lbs less 100% Passive Force = - 825.0 lbs 572.3 lbs less 100% Friction Force = - 393.0 Added Force Req'd = 0.0 lbs O ....for 1.5 Stability = 0.0 lbs Rebar ac Design Data K K OK Solid Grouting Ratio'n' _ fb/FB+fa/Fa _ - a.4as Total Force @ Section 76'0 Service Level lbs= 336.9 Strength Level lbs= in = = Moment.... Actual 1.200 Masonry Block Type Service Level ft-#= 393.0 K Strength Level _ ft-# K Moment..... Allowable Concrete Data 808.1 Shear..... Actual Earth, H 1.000 fe Service Level psi = 3 7 Strength Level psi = Shear.. -Allowable psi = 44'6 K Anet (Masonry) in2 = . 91.50 Rebar Depth 'd' in = 5.25 Masonry Data 1,500 Fm psi= psi = 20,000 Fs = Yes Vertical component of active lateral soil pressure IS Solid Grouting Ratio'n' _ 21.48 NOT considered in the calculation of soil bearing Wall Weight psf = 76'0 Short Term Factor = 1.000 Load Factors 201 Building Code CBC 6,ACI Equiv. Solid Thick. in = = 7.60 Medium Weight 1.200 Masonry Block Type Dead Load 1.600 Masonry Design Method =ASD Live Load 1.600 Concrete Data Earth, H 1.000 fe psi = P Wind, W 1.000 Fy psi= Seismic, E Title Vivante Wall Type 2 Use menu item Settings > Printing & Title Block Dsgnr: JVV to set these five lines of information Description.... for your program. Wall Type 2 - RH=3.5' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wall RetainPro 0)1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Footing Data Toe Width = 0.50 ft Heel Width = 2.50 3.00 Total Footing Width = Footing Thickness = 12.00 in Key Width = 6.00 in Key Depth = 12.00 in Key Distance from Toe = 0.50 ft fc = 2,500 psi Fy = 60,000 psi 150.00 pcf Footing Concrete Density = Min. As % 2 00 Cover @ Top @ Bt 0.0018 in Item HL Act Pres (ab water tbl) HL Act Pres (be water tbl) Hydrostatic Force Buoyant Force = Surcharge over Heel = Surcharge Over Toe = Adjacent Footing Load = Added Lateral Load = Load @ Stem Above Soil = Results Page: z Date: 20 MAY 2020 Code: CBC 2016,ACI 318-14,ACI 530-13 Toe Heel Factored Pressure = 1,695 0 psf Mu,: Upward = 2,386 378 ft-# Mu' : Downward = 615 1,429 ft-# Mu: Design = 148 1,051 ft-# Actual 1 -Way Shear = 5.29 4.82 psi Allow 1 -Way Shear = 40.00 75.00 psi Toe Reinforcing = None Spedd Heel Reinforcing = #4 @ 8.00 in Key Reinforcing = None Spedd - 0.00 ft -lbs Footing Torsion, Tu 0.00 ft -lbs Footing Allow. Torsion, phi Tu = If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn = phi'5'lambda'sgrt(fc)'Sm Heel: #4@ n.2 in, #5@ 14.35 in, #6@ 20.37 in, #7@ 27.77 in, #8@ 36.57 in, #9@ 46 Key: p Min footing T&S reinf Area footing T&S reinf Area per foot 0.78 in2 0.26 ii -2 /it Min If one layer of horizontal bars: If two layers of horizontal bars: #q@ 9.26 in #4@ 18.52 in #5@ 26.70 in #5@ 14.35 in #6@ 20.37 in #6@ 40.74 in Force uisrance lbs ft 806.9 1.50 1,456.8 Total = 806.9 O.T.M. = 1,210.3 ResistinglOverturning Ratio 2.22 Vertical Loads used for Soil Pressure = 1,635.3 Iles Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Force Distance moment lbs ft Soil Over HL (ab. water tbl) 705.8 2.08 1,470.52 1,470.5 Soil Over HL (bel. water tbl) OB Watre Table 92.4 2.39 220.8 Sloped Soil Over Heel = Surcharge Over Heel = Adjacent Footing Load = Axial Dead Load on Stem = * Axial Live Load on Stem = Soil Over Toe - 0 25 Surcharge Over Toe = 312.0 0.83 260.0 Stem Weight(s) _ Earth @ Stem Transitions _ g50.0 1.50 675.0 Footing Weight - = 75.0 0.75 56.3 Key Weight Vert. Component = 1,635.3 lbs RX: 2,682.5 Total= * ed for overturning resisltance, but is iiincluded for sOOtpresSlplrBYcalculation. Title vivapte Wall Type 2 Use menu item settings> Printing &Title Block Dsgnr: JW to set these five lines of information Description.... for your program. Wall Type 2 - RH=3.5' This Wallin File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal RetatnPro (c) 1987.2919, Build 11.20.03.31 Cantilevered Retaining Wall Horizontal Deflection at Top of Wall due to settlement of soil (Deflection due to wall bending not considered) S 'I S ring Reaction Modulus 250.0 pci of p Horizontal DO@Top of Wall (approximate only) 0.045 in The above calculation is not valid if the heel soil bearinct 12ressure exceeds that of the toe because the wall would then tend to rotate into the retained soil. page: s Date: 20 MAY 2020 Code: CBC 2016,ACI 318-14,ACI 530-13 Project name rvu, • r Page Title Vivapte Wall Type 2 Date: 20 MAY 2020 Use menu item Settings> Printing &Title Bloc Dsgnr: JVV to set these five lines of information Description.... for your program. Wall Type 2 - RH=3.5' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 we[ RetainPro (c)1987.2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 8" wf 91@ 24" Solid Grout n4@8" @ Heel ' vrolecr Use menu item Settings > Printing & Title Block Title Vivante Wall Dsgnr: JVV to set these five lines of information Description.... for your program. Wall Type 3 - RH=4.5' Wall in File: K:\Drawings\SP\SP8384 - Newport Beach\Docs\Structural Calcs\Background\SPi This RotainPro(c)1967-2019, Build 11.20.03.31 Cantilevered Retaining Wall License: KW -06056245 License To: WENDELL GAYER ACI Factored @ Heel Thickness $OII Data Criteria Allow Soil Bearing = 1,500.0 psf Retained Height = 4.50 ft Equivalent Fluid Pressure Method Wall height above soil = 0.50 it Active Heel Pressure = 32.0 psf/ft Slope Behind Wall = 2.00 = Height of Soil over Toe = 6.00 in Passive Pressure = 275.0 psf/ft Water height over heel = 0.0 ft Soil Density, Heel = 110.00 pcf 0.0 lbs O Soil Density, Toe = 0.00 pcf 0.0 lbs O Footing1lSoil Friction = 0.350 Total Force @ Section Soil height to ignore _ 6.00 in Building Code for passive pressure - Surcharge Loads Surcharge Over Heel = 0.0 psf Used To Resist Sliding & Overturning Surcharge Over Toe 0.0 - Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Design Su= Wall Stability Ratios _ q 18 OK Overturning 1.54 OK Sliding = Lateral Load Applied to Stem Lateral Load = = 0.0 #/ft 0.00 ft ...Height to Top ...Height to Bottom = 0.00 ft Load Type = Wind (W) 390 psf O (Service Level) Wind on Exposed Stem = 0.0 psf (Strength Level) 1,171 psf 546 psf Total Bearing Load = = 2,452 lbs 2.92 in ...resultant ecc. 0.00 in Soil Pressure @ Toe = 836 psf O Soil Pressure @ Heel = 390 psf O Allowable = 11500 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = = 1,171 psf 546 psf ACI Factored @ Heel Thickness Footing Shear @ Toe = 5.3 psi O Footing Shear @ Heel O _ Allowable - 75.0 psi Sliding Calcs Lateral Sliding Force = 738.0 lbs less 100% Passive Force = - 275.0 lbs less 100% Friction Force = - 858.3 lbs Added Force Req'd = 0.0 lbs O ....for 1.5 Stability = 0.0 lbs O Page: 1 Date: 20 MAY 2020 WAL Code: CBC 2016,ACI 318-14,ACI 530-13 Load _ Footing Width o.00ft _ Eccentricity - 0.00 in Wall to Fig CL Dist = 0.00 ft Footing Type Line Load Base Above/Below Soil = 0.0 ft at Back of Wall Design Method Poisson's Ratio = 0.300 Stem Construction K ft-#= K Bottom fm psi= S[em OK Design Height Above Ftg ft= 0.00 Wall Material Above "Ht" _ Masonry Design Method Solid Grouting _ SD A SD Thickness _ _ # 004 Rebar Size _ 2q.00 Rebar Spacing Wall Weight psi = Rebar Placed at _ - Edge Design Data = 0.667 fb/FB+fa/Fa = Equiv. Solid Thick. Total Force @ Section 7.6 Building Code Service Level lbs = 324.0 Strength Level lbs = 1.600 Moment.... Actual =ASD Service Level 886.0 Strength Level ft-#= Earth, H K Moment..... Allowable - 808.1 Shear..... Actual Wind,W 1.000 1.000 Service Level psi = 3.5 Strength Level psi = Shear..... Allowable psi= 44.9 K Anal (Masonry) in2= 91.50 K Rebar Depth 'd' in= 5.25 Masonry Data ASD ASD fm psi= 1,500 Fs psi= 20,000 active lateral soil pressure IS Solid Grouting _ = = Yes 21.48 Vertical component of in the calculation of soil bearing Modular Ratio'n' 78.0 NOT considered Wall Weight psi = Short Term Factor = 1.000 Load Factors CBC 2016,ACI Equiv. Solid Thick. in = 7.6 Building Code 1.200 Masonry Block Type = Medium Weight Dead Load 1.600 Masonry Design Method =ASD Live Load Earth, H 1.600 Concrete Data psi P - Wind,W 1.000 1.000 fc Fy psi= Seismic, E Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project Name/Number : SP&J64 VVALL I Page: 2 item Settings > Printing &Title Block Title Vivarite Wall Date: 20 MAY 2020Dsgnr: JVV U1se menu to set these five lines of information Description.... for your program. Wall Type 3 - RH=4.5' Wall in File: K:\Drawings\SP\SP8384 - Newport Beach\Docs\Structural Calcs\Background\SP8384 WAL This RetainPro (c)1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 : KW -06066245 e To:WENDELL GAYER i Footing Design Results ting Data - 0.75 ft Toe Width - 325 Toe Heel Factored Pressure = 1,171 546 psf Heel Width - 4 00 Total Footing Width = Mu' :Upward = 3,820 2,270 ft-# = 1,199 3,332 ft-# Footing Thickness = 12.00 in Mu': Downward Mu: Design = 218 1,062 ft-# Key Width = 12.00 in Actual 1 -Way Shear = 5.28 2.53 psi 40.00 75.00 psi Key Depth = 0.00 in Key Distance from Toe = 0.50 ft Allow 1 -Way Shear = Toe Reinforcing = None Spec'd p 60,000 psi fc = 2,500 psi Fy = Heel Reinforcing = # 4 @ 8.00 in Key Reinforcing = # 5 @ 14.60 in Footing Concrete Density = 150.00 pcf Footing Torsion, Tu = 0.00 ft -lbs Min. As % = 0.0018 2.00 @ Btm = 3.00 in Footing Allow. Torsion, phi Tu = 0.00 ft -lbs Cover @ Top if torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn = phi'5'lambda'sgrt(fc)'Sm in, #7@ 27.77 in, #8@ 36.57 in, #9@ 46 Heel: #4@ 925 in, #5@ 14.35 in, #6@ 20.37 Key: No key defined Min footing T&S reinf Area 1.04 int - 0.26 in2 /it Min footing T&S reinf Area per foot If one layer of horizontal bars: If two layers of horizontal bars: #4@ 9.26 in #4@ 18.52 in #5@ 14.35 in #5@ 28.70 in #6@ 20.37 in #6@ 40.74 in Summary of Overturning & Resisting Forces & Moments ,,,,,RESISTING..... .....OVERTURNING..... Force Distance Moment Moment ft Force Distance lbs Item lbs ft Soil Over HL (ab. water tbl) 1,278.8 2:71 HL Act Pres (ab water tbl) 738.0 1.83 1,670.8 3,463.3 Soil Over HL (bel. water tbl) HL Act Pres (be water tbl) Watre Table 576.1 Hydrostatic Force Sloped Soil Over Heel = 183.5 3.14 Buoyant Force = Surcharge Over Heel = Surcharge over Heel = Adjacent Footing Load = Surcharge Over Toe = Axial Dead Load on Stem = Adjacent Footing Load = Axial Live Load on Stem = Added Lateral Load = Soil Over Toe = 0.38 Load @ Stem Above Soil = Surcharge Over Toe = 1.08 422.5 = Stem Weight(s) = 390.0 Earth @ Stem Transitions= 600.0 2.00 1,200.0 Total = 738.0 O.T.M. = 1,353.1 Footing Weight = 1.00 Key Weight = ResistinglOverturning Ratio = 4.18 Vert. Component = 5,661.8 lbs Total = 2,452.3 lbs R.MP Vertical Loads used for Soil Pressure = 2,452.3 * calculation. ed for overturning NOTt soil resistance, buis included for pressure Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project rvanro ,.0 �_• �.,Title Vivante Wall Use menu item Settings > Printing &Title Block Dsgnr: JVV to at these five lines of information Description.... for your program. Wall Type 3 - RH=4.5' This Wall in File: K:\Drawings\SP\SP8384 - Newport Beach\Docs\Structural calcs\Backgroun= RetainPro(c 1987.2019, Build 11.20.03.31 Cantilevered Retaining Wall License: KW -06056245 License To : WENDELL GAYER Tilt Horizontal Deflection at TOP of Wall due to settlement of soil (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal Daft @Top of Wall (approximate only) 0.029 in The above calculation is not valid if the heel soil bearing ressure exceeds that of the toe because the wall would it tend to rotate into the retained soil. Page: 3 Date: 20 MAY 2020 WAL Code: CBC 2016,ACI 318-14,ACI 530-13 vr01ec[ nau,a .., .--• Title vivante Wall Use menu item settings > Printing &Title Block Dsgnr: JW to set these five lines of information Description.... for your program. Wall Type 3 - RH=4.5' This Wall in File: K:\Drawings\SP\SP8384 - Newport Beach\Docs\Structural Calcs\Background\SPS RetalnPro(c)1987.2019, Build 11.20.03.31 Cantilevered Retaining Wall 6" w! k4@ 24" SolidGrout 6"T� #4@6" @ Heel Page: 4 Date: 20 MAY 2020 WAL Code: CBC 2016,ACI 318-14,ACI 530-13 TAIT RISING TO THE CHALLENGE Vivante Retaining Wall Calculations Project Site: 850 San Clemente Drive Newport Beach, CA 92660 Developer Nexus Development 1 MacArthur Place, Suite 300 Santa Ana, CA 92707 Prepared by Tait & Associates, Inc. 701 North Parkcenter Drive Santa Ana, CA 92705 (714)560-8200 BUILDING DIVISION Engineer: Jacob Vandervis, P.E. JUiV 1 c 2020 Registration No. 46301 June 10th, 2020 BY. M•K TAI RISING TO THE CHALLENGE Tait & Associates 701 North Parkcenter Drive Santa Ana, CA 92705 (714)560-8200 RETAINING WALL NOTES GENERAL 1. ALL CONSTRUCTION AND WORKMANSHIP SHALL CONFORM TO THE 2019 CBC. 2. CONTRACTOR MUST CHECK ALL DIMENSIONS, AND SITE CONDITIONS BEFORE STARTING WORK. ARCHITECT/ENGINEER SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES OR POSSIBLE DEFICIENCIES. FOUNDATIONS 1. FOOTING ARE TO BE CARRIED A MINIMUM OF 15" INTO FIRM UNDISTURBED NATURAL SOIL OR APPROVED COMPACTED FILL PER GEOTECHNICAL REPORT. 2. FOOTINGS MAY BE DESIGNED USING AN ALLOWABLE BEARING CAPACITY OF 1,500 PSF BASED ON A MINIMUM WIDTH OF 15 INCHES AND EMBEDMENT DEPTH OF 15 INCHES BELOW THE LOWEST ADJACENT GRADE. THE FOLLOWING FOOTING WIDTHS AND EMBEDMENTS ARE RECOMMENDED FOR THE CORRESPONDING ALLOWABLE BEARING PRESSURE. STATIC BEARING PRESSURE a i MINIMUM FOOTING WIDTH iRchea MINIMUM FOOTING' EMBEDMENT inches 4,000 12 24' 3.300 48 24 3.000 24 24 2.000 18 18 1,500 15 15 Kalers to minimum depth babe beast adjacent grade at Na done OE foundation comma 110n. 3. RELATIVELY NON•EXPANSWE FILL SHOULD BE USED IN BACKFILLING, BEHIND WALLS. DESIGN ALLOWS FOR ONSITE SOILS TO BE USED FOR BACK FILL. ALL RETAINING WALLS SHALL BE ADEQUATELY SHORED DURING THE BACKFILL OPERATION. CONCRETE I. ALL CONCRETE SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH OF 3,700 PSI AT 28 DAYS, 2. AGGREGATES SHALL BE NATURAL SAND AND ROCK CONFORMING TO ASTM C33. 3. CEMENT SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C•150, TYPE V. 4. THE FOLLOWING MINIMUM CLEAR DISTANCES BETWEEN REINFORCING STEEL AND FACE OF CONCRETE SHALL BE MAINTAINED UNLESS NOTED OTHERWISE: SLAB ON GRADE CENTER OF SLAB CONCRETE BELOW GRADE, FORMED 2" CONCRETE. BELOW GRADE, UNFORMED (POURED AGAINST EARTH) 3" CONCRETE EXPOSED TO WEATHER 1 1/2" 5. PROVIDE 3/4" CHAMFERS AT ALL EXPOSED CORNERS. REINFORCING STEEL 1. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 40 FOR SIZES #3 AND #4 AND GRADE 60 FOR SIZES #5 AND LARGER. 2. WELDED FABRIC (MESH) SHALL CONFORM TO THE LATEST REVISED ASTM A185. SMOOTH WIRE FABRIC SHALL CONFORM TO ASTM A85, YIELD STRENGTH 60 KSI. 3. ALL BARS IN MASONRY SHALL BE LAPPED A MINIMUM OF 40 BAR DIAMETERS (24" MIN.) AT ALL SPLICES UNLESS. NOTED OTHERWISE. 4. ALL BARS IN CONCRETE SHALL BE LAPPED A MINIMUM OF 36 BARS DIAMETERS (24" MIN.) AT ALL SPLICES UNLESS NOTED OTHERWISE. 5. SPLICES OF HORIZONTAL REBAR IN WALLS AND FOOTINGS SHALL BE STAGGERED 48" MINIMUM. 6. ALL BENDING OF REINFORCING STEEL SHALL CONFORM TO THE LATEST EDITION OF THE CBC. Project Name/Number : sp8384 wall t Use menu Item Settings > Printing &.Title Block Title Vlva )te Wall Page: 1 to set these five lines of Information Dsgnr: AG Date: 26 MAY 2020 for your program. Description.... RH = 6' w/Vehicle Loading This Wall in Retained Height = 6.00 ft Wall height above soll = 0.50 ft Slope Behind Wall 0.00 Height of Soil over Toe 6.00 in Water height over heel 0.0 It Surcharge Loads Surcharge Over Heel - 250.0 psf Used To Resist Sliding & Overturning Surcharge Over Toe 0.0 pat Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 in Design Summary beachldocslstructurai Cantilevered Retaining Wall Soil Data Allow Soil Bearing = 3,500.0 psf Equivalent Fluid Pressure Method Active Heel Pressure = 55.0 psf/ft Passive Pressure = 275.0 psf/ft Soil Density, Heel = 110.00 pcf Soil Density, Toe = 0.00 pcf FootingIlSoil Friction = 0.350 Soil height to ignore 16.321n for passive pressure 6.00 In Lateral Load Applied to Stem Lateral Load 0.0 #/ft ...Height to Top. = 0.00 ft ...Height to Bottom = 0.00 It Load Type Wind (W) 16.321n (Service Level) Wall Stability Ratios 0.00 ft Overturning = 1.66 OK Sliding = 1.58 OK Total Beadng Load 4,994 lbs ...resultant ecc. 16.321n Soil Pressure @ Toe 3,414 psf OK Soil Pressure (g Heel 0 psf OK Allowable = 3,500 psf Soil Pressure Less Than Allowable ACI Factored Q Toe = 4,779 psf ACI Factored Q Heel = 0 psf Footing Shear® Toe 11.5 psi OK Fooling Shear @ Heel - 16.0 psi OK Allowable 75.0 psi Sliding Calcs Lateral Sliding Force = 2,484.4 lbs less 100% Passive Force = • 2,165.6 Itis less 100% Friction Force - • 1,747.7 lbs Added Force Req'd = 0.0 lbs OK ....for 1.5 Stability = 0.0 Itis OK Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Load Factors 0.00 ft Building Code CBC 2016,ACI Dead Load 1.200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 Wind on Exposed Stem = 0.0 psf (Strength Level) Code: CBC 2016,ACI 318.14,ACI 530-13 Footing Width 0.00 ft Eccentricity 0.00 in Wall to Fig CL Dist = 0.00 it Footing Type Line Load Base Above/Below Soil ft= _ at Back of Wall - 0,0 It Poisson's Ratio 0.300 Stem Construction 1,500. 2nd Bottom int= 91.50 139.50 Stem OK Stem OK Desi n Height Above Ft 9 g E ft= 3.33 0.0000 Wall Material Above "Ht" = Masonry Masonry Design Method = ASD ASD Thickness = 8.00 12.00 Rebar Size = # 5 # 5 Rebar Spacing 24.00 8.00 Rebar Placed at Edge Edge Design Data fb/FB+fa/Fa = 0.314 0.685 Total Force @ Section Service Level lbs= 529.8 1,740.0 Strength Level lbs = Moment.... Actual Service Level ft-#= 620.0 4,230.0 Strength Level ft.#= Moment..... Allowable ft-#= 1,970.0 6,167.2 Shear..... Actual Service Level Strength Level Shear..... Allowable Anet (Masonry) Rebar Depth 'd' Masonry Data I'm Fs Solid Grouting Modular Ratio'n' Wall Weight Short Tenn Factor Equiv. Solid Thick. Masonry Block Type Masonry Design Method Concrete Data fc Fy . psi - 5.8 12.5 psi = 1,500. PSI = 44.4 45.3 int= 91.50 139.50 In= 5.25 9.00 psi= 1,500. 1,500 psi= 32,000 20,000 .Yes Yes = 21.48 21.48 psf = 78.0 124.0 = 1.000 1.000 In= 7.60 11.60 - Medium Weight = ASD psi - psi = Project Name/Number: sp8384 wall t Use menu Item Settings> Printing & Title Block Title Vivapte Wall Page: 2 to set these five lines of Information Dsgnr: AG Date: 26 MAY 2020 for your program. Description.... RH = 6' w/Vehicle Loading This Wall In File: k:\drawings\sp\sp8384 - newport beacMdocs\structural calcs\background\sp8384 wal Rets nPro (c)1987.2019, Build 11.20.03.31 License: KW -09059246 Cantilevered Retaining Wall Code: CBC 2015,ACI 318-14,ACI 530-13 11.. T..I�I=�In=II R•V=e roewiom = u.ou it Toe Heel Heel Width = 4.17 Factored Pressure = 4,779 0 psi Total Footing Width = 4.67 Mu': Upward = 6,761 789 ft-# Footing Thickness = 18.00 in Mu': Downward = 1,008 8,504 ft-# Key Width = 12.00 in Mu: Design = 479 7,716 114 Key Depth = 24.00 in Actual 1 -Way Shear = 11.53 15.99 psi Key Distance from Toe 0.00 ft Allow 1 -Way Shear 75.00 75.00 psi Toe Reinforcing = # 5 @ 8.00 in fc = 2,500 psi Fy = 60,000 psi Heel Reinforcing = # 5 @ 8.00 In Footing Concrete Density = 150.00 pcf Key Reinforcing - None Spec'd Min. As % = 0.0018 Footing Torsion, Tu = 0.00 ft -lbs Cover @ Top 2.00 Q Btm: 3.00 in Footing Allow. Torsion, phi Tu 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: #4Q 6.17 in, #5@ 9.56 In, #6@ 13.58 in, #7@ 18.51 In, #8@ 24.38 In, #9@ 30. Heel: #4@ 6.17 In, #5@ 9.56 In, #6@ 13.58 In, #7@ 18.51 in, #8@ 24.38 in, #9@ 30. Key: phiMn = phi'5'lambda'sgrt(fc)'Sm Min footing T&S reinf Area 1.82 int Min footing T&S reinf Area per foot 0.39 tn2 Ift If one layer of horizontal bars: If two layers of horizontal bars: #4@ 6.17 in #4® 12.351n #S@ 9.57 in 05@ 19.141n #6@ 13.58 In #6@ 27.16 in Summary of Overturning & Resisting Forces & Moments .....OVERTURNING..... .....RESISTING..... Force Distance Moment Force Distance Moment Item lbs It ft-# lbs ft ft-# HL Act Pres (ab water tbl) 1,546.9 2.50 3,867.2 Soil Over HL (ab. water tbl) 2,092.2 3.09 6,464.4 HL Act Pres (be water tbl) Soil Over HL (bet. water tbl) 3.09 6,454.4 Hydrostatic Force Watre Table Buoyant Force = Sloped. Soil Over Heel = Surcharge over Heel = 937.5 3.75 3,515.6 Surcharge Over Heel = 792.5 3.09 2,444.9 Surcharge Over Toe = Adjacent Footing Load - Adjacent Footing Load Axial Dead Load on Stem - Added Lateral Load = ' Axial Live Load on Stem = Load @ Stem Above Soil = Soil Over Toe = 0.25 = Surcharge Over Toe = Stem Weight(s) = 660.2 0.94 619.0 Earth @ Stem Transitions= 97.9 1.33 130.5 Total 2,484.4 O.T.M. 7,382.8 Footing Weight 1,050.8 2.34 2,453.5 Key Weight = 300.0 0.50 150.0 Resisting/Overturning Ratio = 1.66 Vert. Component Vertical Loads used for Sall Pressure = 4,993.5 lbs Total = 4,993.5 lbs R.M.= 12,252.3 Axial live load NOT Included in total displayed, or used for overturning resistance, but Is Included for soil pressure calculation. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project Name/Number: sp8384 wall t Use menu Item Settings > Printing 8 Title Block Title Vivapte Wall Page: 3 to set these five lines of information Dsgnr: AG Date: 26 MAY 2020 for your program. Description.... RH = 6' wNehicle Loading This Wall in File: k:\drawingMsp\sp8384 - newport beach\docs\structural talcs\background\sp8384 we[ Licenser.: rW.06066z4's' a°Im, .zo.aa.a, Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 1 lrsna<Tn • WFNr1F1 r r_Avco Horizontal Deflection at Too of Wal( due to settlement of soil (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal Defl @ Top of Wall (approximate only) 0.132 In The above calculation is not valid if the heel soil bearina pressure exceeds that of the toe because the wall would then tend to rotate Into the retained soil Project Name/Number; sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vivapte Wall Page: 4 to set these five lines of Information Dsgnr. AG Date: 26 MAY 2020 for your program. Description.... RH - 6' w/Vehicle Loading This Wall In File: k:ldrawingslsp1sp8384 - newport beachWoeMstructural calcslbackground\sp8384 wal Rota n ro e 1987-2019, Build 11.20.03.31 License: KW -06066246 Cantilevered Retaining Wall Code: CBG 2016,ACI 318-14,ACi 530-13 8" WI#5@ 24" Solid Grant 12" w1 #5@ 6" Solid Grout 6"1- #5@8.in @Toe �5@8" @ Heel F-15" Project Name/Number : sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vlvaift Wall Page: 1 to set these five lines of Information Dsgnr. AG Date: 8 JUN 2020 for your program. Description.... RH = 8.33' This Wall In File: Retained Height = 8.33 it Wall height above soil = 0.33 ft Slope Behind Wall = 0.00 Height of Soil over Toe = 12.00 in Water height over heel = 0.0 ft Surcharge Loads Surcharge Over Heel 330.0 psf Used To Resist Sliding & Overturning Surcharge Over Toe 0.0 psf Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load = 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 In Design Summary Wall Stability Ratios Overturning Sliding Total Bearing Load ...resultant ecc. 1.86 OK 1.52 OK = 10,471 lbs = 21.86 In beachldocs\structural Cantilevered Retaining Wall Soil Data Allow Soil Bearing = 4,655.0 psi Equivalent Fluid Pressure Method Active Heel Pressure = 55.0 psf/ft Passive Pressure = 275.0 psl/ft Soil Density, Heel = '110.00 pd Soil Density, Toe = 0.00 pcf FootingIlSoil Friction = 0.350 Soil height to Ignore 0.00 ft for passive pressure 6.00 In wal Code: CBC 2016,ACI 318-14,ACI 530-13 Lateral Load Applied to Stem Adjacent Footing Load Soll Pressure @ Heel = 0 psi OK Lateral Load = 0.0 #/ft Adjacent Footing LOW = 0.0 lbs ...Height to Top 0.00 It Footing Width = 0.00 ft ...Height to Bottom 0.00 ft Eccentricity = 0.00 In Load Type - Seismic (E) Wall to Fig CL Dist = 0.00 ft (Service Level) Footing Type Line Load Base Above/Below Soil = 0 0 R Wind on Exposed Stem = 0.0 psf at Back of Wall less 100% Friction Force = - (Strength Level) Wind acts left-to-right toward retention side. Poisson's Ratio 0.300 Stem Construction 2nd Bottom 12,655.3 Shear..... Actual Stem OK Stem OK Design Height Above Ft£ ft= 4.00 0.00 8.8 Wall Material Above "Hr = Masonry Masonry psi= Design Method = ASD ASD Shear..... Allowable Thickness = 12.00 16.00 45.8 Rebar Size = # 6 # 6 139.50 Rebar Spacing 24.00 8.00 In= Rebar Placed at = Edge Edge Masonry Data Soil Pressure @ Toe = 4,493 psi OK Soll Pressure @ Heel = 0 psi OK Allowable = 4,655 psf Soil Pressure Less Than Allowable ACI Factored @ Toe = 6,291 psf ACI Factored Q Heel = 0 psf Footing Shear @ Toe 0.0 psi OK Footing Shear @ Heel - 12.6 psi OK Allowable = 75.0 psi Sliding Calcs Lateral Sliding Force = 4,641.1 lbs less 100% Passive Force = - 3,403.1 lbs less 100% Friction Force = - 3,664.7 lbs Added Force Req'd = 0.0 lbs OK ....for 1.5 Stability = 0.0 lbs OK Vertical component of active lateral soil pressure IS NOT considered In the calculation of soil beadng fb/FB+fa/Fa = 0.760 0.871 Total Force @ Section CBC 2016,ACI Equiv. Solid Thick. In = 11.60 15.60 Service Level lbs= 1,231.3 3,284.5 Strength Level lbs= Masonry Design Method = ASD MomenL...Actual 1.600 Concrete Data Service Level ft-#= 2,294.7 11,032.9 Strength Level ft-#= 1.000 Fy Moment ..... Ailowable ft-#= 3,019.2 12,655.3 Shear..... Actual Service Level psi - 8.8 17.5 Strength Level psi= Shear..... Allowable psi= 44.8 45.8 Anet(Masonry) Int= 139.50 187.50 Rebar Depth 'd' In= 9.00 13.00 Masonry Data I'm psi = 1,500 1,500 Fs psi= 20,000 20,000 Solid Grouting = Yes Yes Modular Ratlo'n' = 21.48 21.48 Wall Weight psi = 124.0 164.0 Load Factors Short Term Factor = 1.000 1.000 Building Code CBC 2016,ACI Equiv. Solid Thick. In = 11.60 15.60 Dead Load 1.200 Masonry Block Type = Medium Weight Live Load 1.600 Masonry Design Method = ASD Earth, H 1.600 Concrete Data Wind, W 1.000 rc psi= Seismic,E 1.000 Fy psi= Project Name/Number : sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vivapte Wall Page: 2 to set these five lines of Information Dsgnr: AG Date: 8 JUN 2020 for your program. Description.... RH = 8.33' This Wall In File: k:\drawings\sp\sp8384 - newport beach\docs\stmcturai eases\background\sp8384 we] Rete n ro c 1987.2018, Build 11.20.03.31 License: KW -06058246 Cantilevered Retaining Wali Code: CBC 2016,AC1318-14,ACI 530-13 License To: WENDFLL GAVFR Toe Width = 0.00 ft Heel Width = 6.75 Total Footing Width = 6.75 Footing Thickness = 24.00 in Key Width = 12.00 in Key Depth = 24.00 in Key Distance from Toe 0.00 it fc - 2,500psl Fy = 60,000 psi Footing Concrete Density 150.00 pcf Min. As % = 0.0018 Cover @ Top 2.00 @ Btm = 3.00 in Toe Heel Factored Pressure = 6,291 0 psi Mu': Upward 0 8,286 it-# Mu': Downward 0 32,753 ft-# Mu: Design 0 24,467 ft-# Actual 1 -Way Shear = 0.00 12.78 psi Allow 1 -Way Shear = 0.00 75.00 psi Toe Reinforcing = # 6 @ 8.00 In Heel Reinforcing = # 6 @ 8.00 in Key Reinforcing = None SpeVd Footing Torsion, Tu = 0.00 ft -lbs Footing Allow. Torsion, phi Tu. 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for footing torsion. Other Acceptable Sizes & Spacings Toe: phiMn= phi'5'lambda'sgrt(fc)'Sm Heel: #4@ 4.621n, #5@ 7.17 in, #6@ 10.18 in, #7@ 13.88 in, #8@ 18.28 in, #9@ 23. Key: phlMn = phi'5'lambda'sgrt(fc)'Sm Min footing T&S reinf Area 3.50 in2 Min footing T&S reinf Area per foot 0.52 in2 At If one layer of horizontal bars: If two layers of horizontal bars: #4@ 4.63 in #4@ 9.26 in #5@ 7.18 in #5@ 14.35 in #8@ 10.19 In #6@ 20.37 in Summary of Overturninq & Resistina Forces & Moments Item HL Act Pres (ab water tbl) HL Act Pres (be water tbl) Hydrostatic Force Buoyant Force Surcharge over Heel = Surcharge Over Toe = Adjacent Footing Load = Added Lateral Load = Load @ Stem Above Soil = Force Distance Moment lbs it ft-# 2,936.2 3.44 10,113.2 1,704.9 5.17 8,808.6 Total 4,641.1 O.T.M. = 18,921.8 Reslsting/Overturning Ratio 1.86 Vertical Loads used for Soil Pressure = 10,470.7 lbs Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Soil Over HL (ab. water tbl) Soil Over HL (bet. water tbl) Watre Table Sloped. Soil Over Heel = Surcharge Over Heel = Adjacent Footing Load = Axial Dead Load on Stem = • Axial Live Load on Stem - Soil Over Toe = Surcharge Over Toe = Stem Welght(s) Earth @ Stem Transitions= Footing Weight = Key Weight = Vert. Component = Force Distance Moment lbs it ft-# 4,965.1 4.04 4.04 1,787.5 4.04 20,067.2 20,067.2 7,224.5 1,234.2 0.59 726.4 158.9 1.17 185.4 2,025.0 3.38 6,834.4 300.0 0.50 150.0 Total - 10,470.7 lbs R.M = 35,187.8 Axial live load NOT Included in total displayed, or used for overtuming resistance, but is Included for soil pressure calculation. Project Name/Number : sp8384 wall t Use menu Item Settings > Printing & Title Block - Title Vivaote Wall Page: 3 to set these five lines of information Dsgnr: AG Date: 8 JUN 2020 for your program. Description.... RH = 8.33' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docMstructural talcs\background\sp8384 wal Rata nPro c) 1987-2019, Build 11.20.03.31 Licensed KW -06038246 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,AC1530-13 (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal Deb Q Top of Wall (approximate only) 0.180 In The above calculation is not valid if the heel soil bearinc pressure exceeds that of the toe, because the wall would then tend to rotate into the retained soil. Project Name/Number : sp8384 wall t Use menu Item Settings > Printing 8 Title Block Title Vivapte Wall Page: 4 to set these five lines of Information Dsgnr: AG Date: 8 JUN 2020 for your program. Description.... RH - 8.33' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docs%tmctuml talcs\background\sp8384 wal RetalnProLicense: KW -06056245' Buil 180.03.31 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 License To: WENDELL GAYER 12"w/#6@2C Solid Grout 16" WI #6@ 8" Solid Grout #6@8- @ Heel M 2„ Z-0" M" MW Surcharge Loads Surcharge Over Heel = 0.0 psf Used To Resist Sliding & Overturning Surcharge Over Toe 0.0 Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 In Design Summary Wall Stability Ratios Lateral Load Applied to Stem Lateral Load Project Name/Number : sp8384 wall t Use menu Item Settings a Printing & Title Block Title Vivapte Wall Type 2 Page: 1 to set these five lines of Information Load Type Dsgnr: JVV Date: 2 JUN 2020 for your program. 0 psf OK Description.... 2,000 psi Soil Pressure Less Than Allowable Wall Type 2 - RH=2.6' 2,421 psf This Wall in File: k:1drewingstsp\sp8384 - newport beachWocs\structural caleMbackgroundtsp8384 we] 0 psf RetalnPro (c)19 -2019, Build . 0.03.31 Licensed KW -09058246 Cantilevered Retaining Wall Code: CBC 2016,ACI 318.14,ACI 530-13 License To: WENDELL GAYER Allowable 75.0 psi fb/FB + fa/Fa Criteria Retained Height = 2.50 ft Soil Data Allow Soil Bearing 2,000.0 Wall height above soil = 0.50 ft Equivalent Fluid Pressure psf Method Strength Level lbs = Slope Behind Wall = 2.00 Active Heel Pressure 55.0 psf/ft Servide Level Height of Soil over Toe = 6.00 In 143.2 = ft-#= Water height over heel = 0.0 ft Passive Pressure = 275.0 psf/ft Shear..... Actual Soil Density, Heel = 110.00 pef 1.9 Strength Level psi= Soil Density, Toe 0.00 pef psi= 44.3 Anet(Masonry) FoolingIlSoil Friction = 0.350 Rebar Depth 'd' In= 6.63 Soil height to ignore fm psi= for passive pressure = 6.00 in psi= 20,000 Surcharge Loads Surcharge Over Heel = 0.0 psf Used To Resist Sliding & Overturning Surcharge Over Toe 0.0 Used for Sliding & Overturning Axial Load Applied to Stem Axial Dead Load 0.0 lbs Axial Live Load = 0.0 lbs Axial Load Eccentricity = 0.0 In Design Summary Wall Stability Ratios Lateral Load Applied to Stem Lateral Load = 0.0 #/ft ...Height to Top 0.00 ft ...Height to Bottom = 0.00 ft Load Type Wind (W) 1,729 psf OK (Service Level) Overturning = 1.73 OK Sliding = 2.48 OK Total Bearing Load = 1,025 lbs ...resultant sec. = 7.26 in Soil Pressure @ Toe = 1,729 psf OK Soil Pressure @ Heel = 0 psf OK Allowable = 2,000 psi Soil Pressure Less Than Allowable ACI Factored @ Toe = 2,421 psf ACI Factored @ Heel = 0 psf Footing Shear @ Toe = 0.0 psi OK Footing Shear @ Heel = 4.1 psi OK Allowable 75.0 psi Sliding Calcs Lateral Sliding Force = 477.4 lbs less 100% Passive Force = - 825.0 lbs less 100% Fdction Force = - 358.6 lbs Added Force Req'd = 0.0 lbs OK ....for 1.5 Stability = 0.0 lbs OK Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Wind on Exposed Stem = 0.0 psi (Strength Level) Footing Width = 0.00 ft Eccentricity 0.00 In Wall to Fig CL Dist 0.00 It Footing Type Square Footing Base Above/Below Soil 1.200 at Back of Wall _ 0.0 ft - Poisson's Ratio = 0.300 Stem Construction Bottom Design Height Above Ft£ ft= B em OK 0.00 Wall Material Above "Ht" Equiv. Solid Thick. Masonry Design Method 1.200 ASD Thickness = 8.00 Rebar Size = # 4 Rebar Spacing = 24.00 Rebar Placed at = 6.631 Design Data Seismic, E 1.000 fb/FB + fa/Fa psi= 0.139 Total Force @ Section Service Level lbs= 171.9 Strength Level lbs = Moment.... Actual Servide Level ft-#= 143.2 Strength Level ft-#= Moment..... Allowable = 1,028.8 Shear..... Actual Service Level psi = 1.9 Strength Level psi= Shear..... Allowable psi= 44.3 Anet(Masonry) In2- 91.50 Rebar Depth 'd' In= 6.63 Masonry Data fm psi= 1,500 Fs psi= 20,000 Solid Grouting = Yes Modular Ratio'n' = 21.48 Wall Weight psf = 780 Load Factors Short Term Factor = 1.000 Building Code CBC 2016,ACI Equiv. Solid Thick. In = 7.60 Dead Load 1.200 Masonry Block Type - Medium Weight Live Load 1.600 Masonry Design Method = ASD Earth, H 1.600 Concrete Data Wind,W 1.000 fc - psi= Seismic, E 1.000 Fy psi= Project Name/Number : sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vlvapte Wall Type 2 Page: 2 to set these five lines of Information Dsgnr: JVV Date: 2 JUN 2020 for your program. Description.... Wall Type 2 • RH=2.5' This Wall In File: k:\drawings\sp\sp8384 - newport beachldocs\structural caics\background\sp8384 wal Rete nPro (c) 1967-2019, Build 11.20.03.31 Licenae: KW -060562/5„ Cantilevered Retaining Wall Code: CBC 2016,ACI 318.14,ACI 530-13 Footing Data 0.52 Int Toe Width = 0.00 it Heel Width = 2.00 Total Footing Width = 2100 Footing Thickness = 12.00 in Key Width = 6.00 In Key Depth = 12.00 in Key Distance from Toe = 0.00 it fc - 2,500 psi Fy = 60,000 psi Footing Concrete Density = 150.00 pcf Min. As % = 0.0018 Cover @ Top 2.00 @ Btm = 3.00 in Item HL Act Pres (ab water tbl) HL Act Pres (be water tbl) Hydrostatic Force Buoyant Force = Surcharge over Heel. Surcharge Over Toe = Adjacent Footing Load = Added Lateral Load = Load @ Stem Above Soil = Force Diets lbs it 477.4 1.17 Toe Heel Factored Pressure = 2,421 0 psi Mu': Upward = 0 47 it-# Mu': Downward = 0 629 ft-# Mu: Design = 0 581 ft-# Actual 1 -Way Shear 0.00 4.07 psi Allow 1 -Way Shear 40.00 75.00 psi Toe Reinforcing = None Spedd Heel Reinforcing = # 4 @ 8.00 In Key Reinforcing = None Spedd Footing Torsion, Tu = 0.00 ft -lbs Footing Allow. Torsion, phi Tu = 0.00 ft -lbs If torsion exceeds allowable, provide supplemental design for fooling torsion. Other Acceptable Sizes & Spacings Toe: phiMn= phi'5'lambda'sgrt(fc)'Sm Heel: #4@ 9.25 in, #5@ 14.35 In, #6@ 20.37 in, #7@ 27.77 in, #8@ 36.57 In, #9@ 46 Key: phiMn - phi'5'lambda'sgrt(fc)'Sm Min footing T&S reinf Area 0.52 Int Min footing T&S reinf Area per foot 0.26 Int dt If one layer of horizontal bars: If two layers of horizontal bars: #4@ 9.261n #4@ 18.52 in #5@ 14.35 in #5@ 28.701n #8@ 20.37 in #6@ 40.74 In ft-# Total = 477.4 O.T.M. _ Resisting/Overturning Ratio = 1.73 Vertical Loads used for Soil Pressure = 1,024.6 lbs Force Distance Moment lbs K it-# 663.1 Soil Over HL (ab. water tbl) 366.7 1.33 488.9 Soil Over HL (bel.watertbl) 1.33 488.9 Watre Table Sloped. Soil Over Heel = 48.9 1.56 76.0 Surcharge Over Heel = Adjacent Footing Load = Axial Dead Load on Stem = • Axial Live Load on Stem = Soil Over Toe = Surcharge Over Toe = Stem Weight(s) = 234.0 0.33 78.0 Earth @ Stem Transitions= 557.0 Footing Weight = 300.0 1.00 300.0 Key Weight = 75.0 0.25 18.8 Vert. Component Total= 1,024.6 lbs R.M= 961.7 "Axial live load NOT Included in total displayed, or used for overturning resistance, but Is Included for soil pressure calculation. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project NamelNumber : sp8384 wall t Use menu Item Settings > Printing & Title Block Title VivaOte Wall Type 2 Page: 3 to set these five lines of Information Dsgnr: JVV Date: 2 JUN 2020 for your program. Description.... Wali Type 2 - RH=2.6' This Wall in File: k:\drawings\sp\sp8384 - newport beach\docsWructural talcs\background\sp8384 wal Reta n roe 7.20 0, Build 11.20.03.31 License: KW -06066246 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal DO (r0 Top of Wall (approximate only) 0.072 in The above calculation is not valid if the heel soil bearing pressure exceeds that of the toe, because the wall would then tend to rotate into the retained soil. Use menu Item Settings > Printing & Title Block to set these five lines of Information for your program. This Wall in File: k:\drawinos\sD19D8384 - newoort bt Project Name/Number: sp8384 wall t Title Vivayte Wall Type 2 Dsgnr. JVV Description.... Wall Type 2 • RH=2.5' h\docs\structural talcs\background\sp8384 wal Page: 4 Date: 2 JUN 2020 License: KW -06056246 Cantilevered Retaining Wall Cade: CBC 2016,ACI 318-14,ACI 530-13 1 Iennea Tn • w9mrim 1 r Avcc, 8" w/ #4@ 24" Solid Grout #4@8,. @ Heel 2 Project Name/Number: sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vivagte Wall Type 2. to set these five lines of Information Dsgnr: JVV Date: for your program. Description.... Wall Type 2 - RH=3.6' This Wall In File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal Page: 1 2 JUN 2020 RetainPro(a) 1987.2019, u 1 .20.03.31 License: KW -06066245 Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,AC1530-13 License To: WENDELL GAYER Fs Criteria = 20,000 Soil Data j� Allow Soil Bearing 'I Solid Grouting Retained Height 3.50 it = 2,000.0 psf - Modular Ration' Wall height above soil = 0.50 R Equivalent Fluid Pressure Method Wall Weight psf = Active Heel Pressure 55.0 psf/ft Load Factors Slope Behind Wall 2.00 = 1.000 Height of Soil over Toe = 6.00 in = In= Water height over heel = 0.0 It Passive Pressure = .275.0 psf/ft Masonry Block Type = Medium Weight Live Load Soil Density, Heel = 110.00 pcf Masonry Design Method = ASD Earth, H Soil Density, Toe 0.00 pcf Concrete Data FootingIlSoll Friction = 0.350 Wind, W 1.000 Soil height to Ignore psi= Seismic, E for passive pressure = 6.00 In Fv Surcharge Loads i Lateral Load Applied to Stem Adjacent Footing Load Surcharge Over Heel = 0.0 pat Lateral Load = 0.0 f#ft Adjacent Footing Load = 0.0 IDS Used To Resist Sliding & Overturning ...Height to Top 0.00 It Footing Width = 0.00 It Surcharge Over Toe 0.0 ...Height to Bottom = 0.00 ft Eccentricity = 0.00 in Used for Sliding & Overturning Wail to Ft CL Dist Load Type = Wind (W) 9 0.00 ft Arial Load Applied to Stem (Service Level) Footing Type Square Footing Base Above/Below Soil Axial Dead Load = 0.0 IDS = Wind on Exposed Stem = 0.0 psi at Back of Wall 0.0 ft Axial Live Load = Axial Load Eccentricity = 0.0 IDS 0.0 in (Strength Level) Poisson's Ratio = 0.300 Design Summary ' Stem Construction Bottom Stem OK Design Height Above FtF ft= 0.00 Wall Stability Ratios Wall Material Above "Ht" Masonry Overturning = 2.10 OK Design Method ASD Sliding = 1.68 OK Thickness = 8.00 Rebar Size = # 4 Total Bearing Load = 1,885 IDS Rebar Spacing 24.00 ...resultant ecc. = 8.75 in Rebar Placed at 6.631 Soil Pressure @ Toe = 1,631 psi OK Design Data fb/FB +fa/Fa 0.382 Soli Pressure @ Heel = 0 psf OK Allowable = 2,000 pat Total Force @ Section Soil Pressure Less Than Allowable Service Level IDS = 336.9 ACI Factored C Toe = 2,283 psf Strength Level IDS = ACI Factored C Heel = 0 psf MomenL-Actual Footing Shear @ Tee = 0.0 psi OK Service Level ft-#= 393.0 Footing Shear @ Heel - 3.0 psi OK Strength Level ft-# Allowable = 75.0 psi Moment..... Allowable = 1,028.8 Sliding Caics Shear..... Actual Lateral Sliding Force = 883.1 lbs Service Level psi = 3.7 less 100% Passive Force = - 825.0 IDS Strength Level psi = less 100% Friction Force = - 659.8 IDS Shear..... Allowable psi = 44.6 Added Force Req'd = 0.0 IDS OK Anet (Masonry) Int= 91.50 ....for 1.5 Stability = 0.0 lbs OK Rebar Depth 'd' in = 6.63 Masonry Data I'm psi= 1,500 Fs psi= 20,000 Vertical component of active lateral sail pressure IS Solid Grouting = Yes NOT considered in the calculation of soil bearing Modular Ration' = 21.48 Wall Weight psf = 78.0 Load Factors Short Term Factor = 1.000 Building Code CBC 2016,ACI Equiv. Solid Thick. In= 7.60 Dead Load 1.200 Masonry Block Type = Medium Weight Live Load 1.600 Masonry Design Method = ASD Earth, H 1.600 Concrete Data Wind, W 1.000 rc psi= Seismic, E 1.000 Fv nsl = Project Name/Number; sp8384 wall t Use menu Item Settings> Printing & Title Block Title Vivaryte Wall Type 2 Page: 2 to set these five lines of Information Dsgnr: JVV Date: 2 JUN 2020 for your program. Description.... Wall Type 2 - RH=3.5' This Wall In Filer k:\drawings\sp\sp8384 - newport beach\docs\structural talcs\background\sp8384 wal Rata nPro c 1987-2019, Build 11.20.03.31 License: MN -06056246= Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACi 530-13 Footing Data Footing Design Results Toe Width 0.00 it Toe Heel Heel Width 3.00 Factored Pressure 2,283 0 psf Total Footing Width = 3.00 Mu': Upward 0 733 ft-# Footing Thickness = 12.00 In Mu': Downward = 0 2,307 ft-# HL Act Pres (be water tbl) Soil Over HL (bel. water tbl) Mu: Design = 0 1,574 ft# Key Width = Key Depth = 6.00 In 12.00 in Actual 1 -Way Shear = 0.00 2.99 psi Key Distance from Toe 0.00 it Allow 1 -Way Shear = 40.00 75.00 psi Buoyant Force = Toe Reinforcing = None Spedd fc = 2,500 psi Fy = 60,000 psi Heel Reinforcing - # 4 @ 8.00 in Footing Concrete Density 150.00 pcf Key Reinforcing = None Spedd Min. As % = 0.0018 Footing Torsion, Tu = 0.00 ft -lbs Cover @ Top 2.00 @ Btm = 3.00 In Footing Allow. Torsion, phi Tu = 0.00 ft -lbs If torsion exceeds allowable, provide Axial Dead Load on Stem = supplemental design for footing torsion. Added Lateral Load = Other Acceptable Sizes & Spacings Toe: phlMn - phi'&Iambda'sgrt(fcySm Load @ Stem Above Soil = Soil Over Toe = Heel: fkl@ 9.251n, #5@ 14.35 In, #8@ 20.37 in, #7@ 27.77 In, #8@ 36.57 in, #9@ 46 Key: phiMn - phi'5'lambda'sgrt(fc)'Sm Surcharge Over Toe = Min footing T&S relnf Area 0.78 in2 Min footing T&S relnf Area per foot 0.26 in2 At 312.0 0.33 If one layer of horizontal bars: if two layers of horizontal bars: Earth @ Stem Transitions= #4@ 9.261n #40 18.52 in #5@ 14.35 in #5@ 28.70 in Footing Weight = 450.0 #6@ 20.37 in #8@ 40.74 in Force Distance Moment Force Distance Moment Item lbs R ft# lbs It ft-# HL Act Pres (ab water tbl) 883.1 1.50 1,668.0 Soil Over HL (ab. water tbl) 898.3 1.83 1,646.9 HL Act Pres (be water tbl) Soil Over HL (bel. water tbl) 1.83 1,646.9 Hydrostatic Force Watre Table Buoyant Force = Sloped Soil Over Heel = 149.7 2.22 332.7 Surcharge over Heel = Surcharge Over Heel = Surcharge Over Toe Adjacent Footing Load - Adjacent Footing Load = Axial Dead Load on Stem = Added Lateral Load = ' Axial Live Load on Stem - Load @ Stem Above Soil = Soil Over Toe = = Surcharge Over Toe = Stem Weight(s) = 312.0 0.33 104.0 Earth @ Stem Transitions= Total = 883.1 O.T.M. = 1,324.6 Footing Weight = 450.0 1.50 675.0 Key Weight = 75.0 0.25 18.8 ResistinglOverturning Ratio 2.10 Vert. Component - Vertical Loads used for Soil Pressure = 1,885.1 lbs Total = 1,885.1 lbs R.M.= 2,777.4 ' Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance. Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance. Project Name/Number : sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vivante Wall Type 2 Page: 3 to set these five lines of Information Dsgnr: JVV Date: 2 JUN 2020 for your program. Description.... Wall Type 2 - RH=3.5' his Wall in File: k:\drawings\sp\sp8384 - newport beach\docs\structural calcs\background\sp8384 wal 'eta n ro (c)1987• e, Build 11.20.03.31 icense: KW.06066245 Cantilevered Retaining Wall Code: CBC 2016 AC1318-14,ACI 530-13 (Deflection due to wall bending not considered) Soil Spring Reaction Modulus 250.0 pci Horizontal DO @ Top of Wall (approximate only) 0.060 in The above calculation is not valid if the heel soil bearing Pressure exceeds that of the toe, because the wall would then tend to rotate Into the retained soil. Project Name/Number: sp8384 wall t Use menu Item Settings > Printing & Title Block Title Vivagte Wall Type 2 Page: 4 to set these five lines of Information Dsgnr: JVV Date: 2 JUN 2020 for your program. Description.... Wall Type 2 • RH=3.8' This Wall In File: k:\drawings\sp\sp8384 - newportbeach\docs\stmctural talcs\background\sp8384 wal RetainPro (c)1987.2019, Build 11.20.03.31 License: KW -09056249 --__ Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13 8" w/ #i@ 24" Solid Grout 3'-6" 4'-0" I TA 1 T RISING TO THE CHALLENGE VIVANTE NEWPORT CENTER 701 N. P.,k..mG, Drive, Santa Ana, CA 92705 P:]I 4/560/8200 www.tait.<om Retaining Wall Plan Review — Response Letter— Public Works Division Project Name: Vivante Newport Center Project Address: 850 & 856 San Clemente Drive, Newport Beach Plan Checker: David Keely TAIT Project Engineer: Bart J. Mink, PE TAIT Project Manager: Jacob Vandervis, PE Date: June 10, 2020 City of Newport Beach Plan Checkers: Please accept these comment responses and the revised report for your 2nd review of the Retaining Wall Permit #0951-2020 for the above mentioned project. Our responses, in Bold, follow your bulleted and/or numbered comments. RETAINING WALL PERMIT (#0951-2020) PUBLIC WORKS COMMENTS: 1. Note on the Plans "An approved encroachment permit is required for all work activities within the public right-of-way/easement area." (KEEP FOR ALL UNLESS IT'S AN EA, THEN USE #4) Note added to Title Sheet. 2, Note on the Plans "An encroachment agreement is required for all non-standard improvements within the public right of way/easement area. All non-standard improvements shall comply with City Council Policy L-6." Note added to Title Sheet. 3. Show the existing and proposed new easement on the plans. Existing and proposed easements now shown on the plan. 4. The proposed retaining wall 3 is over the new waterline alignment and easement. The wall cannot be over the easement and new water line. Redesign. Retaining Wall has been removed completely. 11 Page ' TAIT RISINO TO TME CX�Ltf X4E PJ14/56018200 www.tait.c m 701 N. Parkcenter Drive, Santo Ana, CA 92705 4. Verify that top of wall elevations on RW sheets match the Civil plans in plan check 1950-2019. See RW1.02 for clarification. TW elevations removed from civil plans to remove redundancy and clutter from the civil plans. 5. Show on details all minimum clearance distances for reinforcement embedded in concrete to scale. Minimum clearance distances now shown. 6. Verify line work for reinforcement in wall construction details. See red marked RW1.03 for clarification. Linework revised. 7. Reference plan check number 1950-2019 where the details reference the Landscape drawings for guardrail attachment. Provide dimensions for continuous top bar placement on the details so that the 2 -inch cores specified for the guardrail post anchorage do not cut or damage the continuous bars at the top of the wall. Note, the continuous bar may need to be moved below the anchorage in the 8 -inch wall. Plan check number now referenced on guardrails. 8. For wall to 8'-4" in height, include the additional 20 psf soil pressure for seismic load per the geotechnical report. Additional seismic load has been applied to the design. See calculations. 9. See red marked plans for additional corrections/clarification. The redline comments have a0 been addressed on the attached revised plans. 10. See red marked calculations for additional corrections/clarification. The redline comments have all been addressed on the attached revised plans. 11. Return all red marked plans and calculations with recheck. The redline comments have all been addressed on the attached revised plans. 21 Page �ITAIT ais�aa •o •xe exuiwae p:71 4156018200 www.tait.com Please let us know if you have any other comments or questions. Respectfully, Bart J. Mink, PE, LEED AP Project Manager TAIT & Associates, Inc. 701 W Parkcente, Drive, Santa Ana, CA 92705 31 Page TAIT arsixo ro 1.L exuaaxee 701 N. %,kce M., Drive, Santa Ana, CA 92705 P:714/560!8200 www.tait.com 5. Seethe Plans for additional redlined comments. The redline comments have all been addressed on the attached revised plans. Please let us know if you have any other comments or questions. Respectfully, Bart J. Mink, PE, LEED AP Project Manager TAIT & Associates, Inc. 21 Page TAIT IEINO Ta TXL CNALLEN4E P:71 4156018200 ww w.talr.com VIVANTE NEWPORT CENTER 701 N. PaAcenter Drive, Santa Ana, CA 92705 Retaining Wall Plan Review— Response Letter— Building Division Project Name: Vivante Newport Center Project Address: 850 & 856 San Clemente Drive, Newport Beach Plan Checker: Melissa Kubischta TAIT Project Engineer: Bart J. Mink, PE TAIT Project Manager: Jacob Vandervis, PE Date: June 10, 2020 City of Newport Beach Plan Checkers: Please accept these comment responses and the revised report for your 2nd review of the Retaining Wall Permit #0951-2020 for the above mentioned project. Our responses, in Bold, follow your bulleted and/or numbered comments. RETAINING WALL PERMIT (#0951-2020) BUILDING COMMENTS: Obtain plan review approval from the following: a. Building Division b. Planning Division C. Grading d. Public Works We are working with each department listed above for such review approvals. 2. Final drawings which will be approved for permit issuance, shall be signed by the respective design professional (electronic signature is acceptable). This correction will remain until the permit is issued. The revised plans attached have been signed/stamped. 3. Soils engineer to review and approve the grading plan, foundation plan, and foundation details to verify that the design is consistent with the geotechnical report recommendations. Soils engineer to stamp these plans with a review stamp asserting compliance with geotechnical report recommendations. This correction will remain until the permit is issued. The revised plans attached have been signed/stamped by the soils engineer. 11 Page