HARDWARE ANALYSIS RESULTS
Vertical Load Design Shear
Governing Load Combo
DL
LL
SL
W
E
Total .
; D
68.8lbs
---
---
--
---
68.8lbs .
Lateral Load Design Withdrawal
Governing Load Combo
DL
LL
SL
W
E
Total
p ....
'34.6 lbs
34.6 lbs
Fastener Check
Withdrawal Load
Shear Load
Load Duration Factor
W.
Z'
a
p
W
Z
Cc
=
=
=
=
=
=
=
387.0lbs
145.8 lbs
26.74
2.50 in.
34.6lbs
68.8 lbs
0.90
R
Z'a
R
Z'a
'_
=
_
77.0lbs
166.9lbs
0.461381251
_
<_ 1.05
Fass
June 29, 2021
City of Newport Beach
Project Address: 2542 Circle Drive, Newport Beach CA 92663
Project Name: Marans Residence
Plan check comments received, comments/corrections indicated below:
Gas Meter located in Site Plan and Rigid steel used for exterior conduit updated.
Please do not hesitate to get in touch with me if you have any questions or concerns.
Thank you for your time and consideration,
Aranza Lopez Juarez
PV Design II
e I arlopezjurez@tesla.com
T = 5 L In Testa, Inc.
3500 Deer Creek Road. Palo ,Alto. CA 94304
p +852 3974 0288 f +852 3974 0287
February 18, 2020
RE:
Project/Job #
Project Address:
AHJ
SC Office
To Whom it may concern:
Powerwall Certification Letter
92614856
Marans Residence
2542 Circle Dr
Newport Beach, CA
Newport Beach
Irvine
Version #8.1
Nb. S 5185
Exp 12/31 /20 '� J
STgT oi�C A�.O��Q'
..,
Abelardo
De Vera
The installation manual for the Tesla Powerwall was reviewed for wall mounting considerations. Based on the weight of
the unit and the attachment layout of the mounting bracket, it was determined that the following fasteners should be used:
For mounting to walls with wood studs:
4 -1/4 in. Wood Screws with a minimum embedment of 2.5"
In addition, the wall structure has been verified as sufficient to support the additional load imposed by the Tesla PowerWall
unit.
Sincerely,
Testa Energy
Tesla, Inc.
T = 5 L n
WALL DESIGN AND LOADING SUMMARY
Applicable Codes: IBC/IRC 2018. ASCE 7-16
Member Specs
Wall Height 8.0 ft.
Stud Size 1.5 x 3.5
Stud Spacing 16 in. O.C.
Lumber Type DF Stud
Trib. Roof Loading 10.0 ft
Applied Dead Load, Live Load, Snow Load
PSF (DL adjusted for pitch)
Compression Stress (PSI)
DL, LL, SL
DL
LL
SL
DL
LL
SL
Roof
9.3
20.0
o.0
23.6
50.8
0.0
Ceiling
5.0
12.7
First Floor Wall
8.5
17.3
Second Floor & Ceiling
8.0
40.0
13.5
67.7
Second Floor Wall
8.5
17.3
Total - 84.3 psi ,118.5 psi 0.0.psi
Powerwall Dead Load
Powerwall Dead Load
275.0lbs
No. Stacked PowerWall Units
1
Dead Load per Stud No. Studs 2
137.5 Ibs
Resulting Axial Stress =
'. >26.2 psi
Eccentric Moment Total
1870.3 lbs-in
Moment per Stud No. Studs 2
=
935.2 Ibs-in
152.7psi
Resulting Bending Stress
Applied Wind Load
Wind Speed
100 mph
Risk Category
2C
Exposure Category
0-15 ft.
PowerWall Elevation
Distance of PowerWall(s) to Corner of Building
10.0 ft.
Directionality Factor
0.85
Topographic Factor
1.00
Velocity Pressure Exposure Coefficient
=
0.85
989.5 psi
Resulting Bending Stress
Applied Seismic Load
Component Amplification Factor ah 1.00
Soil Site Class
D
Component Response Modification Factor Rp 2.5
SRA at Short Period Ss
1.383
Component Importance Factor Ip 1.00
SRAat 1s Period Sy
0.492
Component Operating Weight Wp 275.0lbs
Wall Dead Load
8.50 psf
Wall Bending Stress =
157.2.psi
4.8 psi
Battery Axial Stress =
337.8 psi
Battery Bending Stress =
28.2 psi
Eccentric Battery Stress =
WALL ANALYSIS RESULTS
Design Axial Stress
-
Governing Load Combo
DL
LL
SL
W
E
Total
D+.75L+.75W+.75S
110.5 psi
88.9 psi.
Design Bending Stress
Governing Load Combo
DL
LL
SL.
W
E
`. Total -
D+-75L+;75W+.75S
152.7,psi
---
---
`.340.0psi,.
—
493.6psi;
Components & Cladding Bending Stress
-
Governing Load Combo
DL
LL
SL
W
E
Total
D+W
152.7.psi
--
--
5g3.7psi
--- "
746.4psi..
Load Duration Factor
Co =
Repetive Member Factor
C, =
Size Factor: Bending
CF =
Member Check
1.60
1.15
Size Factor: Compression
1.10 CF =
(Cfu= 1.O,CM=1.0,Ct=1.O Ci=1.0,CT=1.O,Cv=1.O,CL71.0,Ke=1,c=0.8)
1.05
Fc =
Fb =
E =
Emi„ =
850.0 psi
700.0 psi
1400000.0 psi
510000.0 psi
Based on NOS Eqn. 3.9-3....
0.700 <=
Based on NOS Eqn. 3.9-4....
0.031 <=
1.05
1.05
Pass
Pass:
Components &Cladding Bending Check
Fs =
F'bl =
746.4 psi
1416.8 psi
Fa
=
F'bl
0.527
<_ 1.05
....
Pass
HARDWARE DESIGN AND LOADING SUMMARY
Fastener Specs -
Fastener Type
1/4 in. Wood Screw
# Top Fasteners
2
Fastener Diameter
0.25 in.
# Bottom Fasteners
2
Fastener Area
0.049 sq.in.
Total Fasteners
4
Vertical Distance Between
27.00 in.
Fasteners
Dead Load Applied to Fasteners -
PowerWall Battery Version V2
PowerWall Battery Weight 275.0lbs
No. Stacked PowerWall Units 1
Eccentricity
Panel Depth
6.10 in.
Wall Finish Depth
1.00 in.
Half Panel Depth
3.05 in.
Total Wall Depth
3.50 in.
Frame Depth
1.00 in.
Half Wall Depth
1.75 in.
Total Eccentricity = 6.80 in.
Eccentricity Moment = 1870.3 lbs-in
T and C Components = 69.3 lbs / fastener row
T per Fastener = ` 34.6 lbs
Shear per Fastener = 68.8 lbs
Wind Suction
Approximate Battery
Wind Load
20.35 psf
Dimensions
Width 29.70 in.
Height 45.30 in.
Surface Area 1345.41 sq. in.
Suction Force = 190.09 lbs
Tension per Lag = 47.52.lbs
Seismic - Vertical and Lateral
Seismic Vertical
50.71 lbs
Moment
344.89 lbs-in
Shear per lag
12.68 lbs
T and C Components
12.8 lbs / fastener row
Seismic Vertical = 50.71 lbs
Seismic Horizontal = 86.21 lbs
Withdrawal per lag = 21.55lbs From Horizontal FP
V per fastener = 12.68 lbs From Vertical FP
T per fastener = 6.39lbs From Vertical FP Eccentricity (top fasteners only)