Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
1949 PORT RAMSGATE PL.
NEWPORT BEACH, CA 92660 BUILDING DIVISION
Job: ARA RESIDENCE
Mar 03 2022
Prepared For:
BY: D.E.A.
ENLIGHTENED SOLAR
2377 S. EL CAMINO REAL, #200
SAN CLEMENTE, CA 92672
(949)690-2606
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16
2 - Wind: 95 MPH, Exposure: C
3 - Wood Species: DF-L No. 1 (SG = 0.5 )
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
cp
No. C70784
_Exp. 0613012023
1-844-PV ELITE I info@yoursolarplans.com
3000 E. Birch Street Suite 2011 Brea CA 92821
2/2/22, 9:37 AM
ITC Hazards by Location
ATC Hazards by Location
Search Information
Address: 1949 Port Ramsgate PI, Newport Beach, CA
92660, USA
Coordinates: 33.6231513,-117.8543578
Elevation: 231 fit
Ti mesta m p: 2022-02-02T17:37:46.596Z
Hazard Type: Wind
ASCE 7-16 ASCE 7-10
MRI10-Year _____..___.___._..._ 66 mph
MRI25-Year -------------------- 71 mph
MRI50-Year __..____---------- 77 mph
MRI100-Year --------
Risk Category l ----
Risk Category II
___ 81 mph
MRI 10-Year ---------------- 72 mph
MRI25-Year --------------- 79 mph
MRI50-Year ___..___------ 85 mph
MR1100-Year -------- 91 mph
89 mph RiskCategoryl __..-------- 100 mph
95 mph
_ Risk Category III ..-------- .----- 102 mph
Risk Category IV 106 mph
Risk Categoryll .._._____ 110 mph
Risk Category III -IV _..----- 115 mph
ASCE 7-05
ASCE 7-05 Wind Speed ______ 85 mph
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building
code adoption process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction before
proceeding with design.
Disclaimer
Hazard loads are interpolated from data provided in ASCE 7 and rounded up to the nearest whole integer. Per ASCE 7, islands and coastal
areas outside the last contour should use the last wind speed contour of the coastal area — in some cases, this website will extrapolate past
the last wind speed contour and therefore, provide a wind speed that is slightly higher. NOTE: For queries near wind-borne debris region
boundaries, the resulting determination is sensitive to rounding which may affect whether or not it is considered to be within a wind-borne
debris region.
Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility
or liability for its accuracy. The material presented in the report should not be used or relied upon for any specific application without
competent examination and verification of its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does
not intend that the use of this information replace the sound judgment of such competent professionals, having experience and knowledge
in the field of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the results of the
report provided by this website. Users of the information from this website assume all liability arising from such use. Use of the output of
this wehsite dnes not imnly annrnval by the onverninn huildinn node hodies resnonsihle for huildinn cnde annrnval and internretation for the
https:Hhazards.atcouncil.org/#/wind?lat=33.6231513&ing=-117.8543578&address=1949 Port Ramsgate PI % 2C Newport Beach%2C CA 92660%2C USA 112
ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes
Roof Slope
0 =
23 °
Roof Shape
Hip
TributaryW idth
s =
6.00 ft
Tributary Length
1 =
3.08 ft
Effective Area
Ae =
10.28 f?
Height of Structure
h =
25 ft
Wind Speed
V =
95 mph
Exposure Category
C
Building Width
B =
50 ft
Building Length
L =
60 ft
Zone Width
a =
5 ft
Elevation Height
Z =
231 ft
Wind Directionality
Kd =
0.85
Topography Factor
Ki =
1.00 -
Ground Elevation Factor
K. =
0.99
Velocity Pressure Exposure Coefficient
K. =
0.95
Velocity Pressure
q, = 0.00256K�KnKdKXV2 =
18.41 psf
Solar Array Pressure Equalization
yX =
0.80
Array Edge Factor
YE =
1.50
u.Rnn.
IIebIMn
a.lpidkaYMWwY6em6av414•KKknrl,wWe. W Mlm OmgMV}dky hti¢ny
v)IIN➢m}I(unvvquW.ve°IRXure YW hmnmtllmlhumb N/e W qe
9. W Ww16v.r°udhvWPawNsroilmMNpaJm.bieYl¢il¢bt nl°euM/Smvv.
/•e1m�4W mn1AT
10 a m
{
ii nzgl
n$�
01 XbrewwAwe}.1�
1. VmiXeLL6avm IC%)b�mpNJpA.
i )unmvJ etle kxm mmrt Ntl me b nl ldl.
119emtei°n RV v/eXPpmonvigwN W rvyfmmhwReemRJb!
A. �e�mvme+wu ba�.uw�4mmwbw w m6abPmeo.
s. vmdmgl w�wraee�.wlebxrm�wwwmmmlwmeww.eb...wm�m.
naa«mbwm/ m..wbe dmwaRcuam. � mm�mw a.®m wu.
aeQePimrc.. JYlhvnvd 6mi Ik °IYk WRaJnmoEmi
Zone 1 GCc I o =
3r
3e
2
2r 2.00 -44.08
2e 2.00 -44.08
2n - -
1 1.40 -30.84
1'
1
RP
a
`
-
Ra
Pa
1 m Im ImJ
EX W. MW ARM, A.M
A W RE 3RM 6du Pbel Pnuu� 6p W vLLn hM). v. b Xu W G uM P W R/ EntlmM RWMAp °I RY XNply
LAG SCREW ANALYSIS
Loads
Wind Pressures
q�
_ -44.08 psf
Solar Panel Load
QD
= 3 psf
Panel Length
1
= 6.167 it
Panel Width
b
3.425 ft
Attachment Spacing
s
= 6 ft
Tributary Area
A,
= 18.50 ft`
Wind Load
Pw = q� * A,
_ -816 Ibs
Dead Load
Pp = QD * A,
= 55.5 Ibs
Uplift
Pa = 0.6 PD + 0.6 Pw
= -456 Ibs
Tributary Area
A, = b * s
= 10.275 ft`
Wind Load
Pw = q� * A,
_ -453 Ibs
Dead Load
PD = QD ; At
= 30.825 be
Uplift
Pa=0.6 PD+0.6 Pw
= -253 lbs
Lao Screw
. Specific Gravity of Lumber
SG
= 0.50 (Douglas Fir -Larch)
Diameter of Lag Screw
D
= 5116 in
Withdraw Design /in
1800*SG312*Da4
= 266 Ibs/in
Depth of Embedment
It,
= 3.25 in
Total Nominal Withdrawal Value
W = W * I a
= 864 Ibs
Load Duration Factor
Co
= 1.6
Withdrawal Design Value
W' = W * Co
= 1383 be
Demand Capacity Ratio
DCR = Pa / W'
= 0.33 < 1 OK
ASCE 30.3.2 Design Wind Pressure
Koor Slope
0
= 23 '
Roof Shape
Hip
Tributary Width
s
= 2.00ft
Tributary Length
L
= 18.00 ft
Effective Area
A = L ( MAX [ s , L/3])
= 100 ft2
Height of Structure
h
= 25 ft
Wind Speed
V
= 95 mph
Exposure Category
C
Building Width
B
= 50 ft
Building Length
L
= 60 ft
Zone W idth
a
= 5 ft
Elevation Height
Z9
= 231 ft
Wind Directionality
Kd
= 0.85
Topography Factor
K,
= 1.00
Ground Elevation Factor
Kn
= 0.99
Velocity Pressure Exposure Coefficient
K�
= 0.95
Velocity Pressure
q. = 0.00256K�KnKtlKeV2
= 18.41 psf
Internal Pressure Coefficient
(GCpi)
= -0.18
Zone
GCp
p = q� [(GC) - (Gcpi)]
3
1.53
31.41
3r
-
-
3e
2
2r
1.53
-31.41
2e
1.53
-31.41
2n
1
0.80
-18.04
1'
ww5m5
:,a; -
I
y
nlvxrov
TM` pAV
Ibr4m
aslPiYbNMNJJ�4ep44MiekveYw,Ib.W MAv Wee4t,Kdkw bNrtxJ
9�nYanlON9n4Yuorelvq ea W,. W tlp.ONveuVlEem:uiM(mn,kmWk �QeMPe
•.1 Y6mtm6nN WAgmewNb¢m�YnvY°dy�N�W'e,EW; IrtLY nl egMSfumtn
A.Ks rsIkIlY.Yl1 (m)
• uM ✓ps amarmm ewmJ. Y tym..
ewwv,..P.a.xdmN
40 n m y° n m
i4
It
:= r
r;
if i.t
Iw iw,
m Sa9:®
Pmm.
omrtlN.,urnn'Nh� elMgS'�nl
wY.
i lbivuJ vYetrnm'CeRnIrt Mf Nwe is nfld4
x Im.m mo � JNrS m+�m=nw e..a m,.n r� x wm �wa.Jl.
a w.mv� rrt � °.wm rrtmw�o rs�• w we. pom..
xvmmla Il.i,wmea.d Yee.er�m+Jl.uomr�wweww�eua.<Wrr>.
cua,.e.wwm.w�,5wm..,ue�m✓u.Yivawu Ime+�lm.ws®aomio-.
eqe 0uvenaWlGvmW OmKmJ4 n15eMN:
(9YpF1JW RTTOM4YMAN5WeN51Y , WE41wNew�iaPYm41JL,A0NWgeq VmStlr
W YY BJYbiIIY IIM 1 V.5}I' Pod M Pwl`H
Beamf Top Chord Check Lumber: DF-L No. 1
Moment Demand
# of Attachment per Rafter Nq= 4 Span: 1 2 3 4 Eave
Lenght(ft): 8.00 8.00 0.00 0.00 2.00
Dead Load
Live Load
Wind Load
Snow Load
Rafter Spacing
Wind Load, Portrait
Wind Load, Landscape
Linear Dead Load
Live Load
Snow Load
Roof Material: Shake Qo = 10.00 psi
Qi,= 20 psf
p = -31.41 psf
Qa = 0.00 psf
s= 24 In
Portrait UL-
Landscape Uw=
AT (fta)
Pd (Ibs)
I P. (Iba)
I p, (to')
18.5
65.5
Z81
0
110.2751
30.825
-323
0
wd =
20 pit
wLr= 40 pit Start
0
ft Start
14.09 ft
End
4.5
ft End
18.00 It
we = 0 pit Start
0
ft Start
14.09 ft
End
4.5
ft End
18.00 ft
D
M., Moment
234 lb-ft
D+Lr
275 lb-ft
D+S
234 lb-ft
0.6D+0.6W
440 lb-ft
D+OA5W+0.75Lr
247 lb-ft
D+0.45W+0.755
24716-fl
Orientation
]
II (ft)
P.,(Ibs)
p„,(Its
p,(1bs(
Lantlscepe
1
2
5.2
7.3
30.8
30.8
-323
-323
Portrait
3
4
8.7
13.3
55.5
55.5
-581
-581
-:H
M(x)=Rt(+-LJ-P/(x-t/)- 2
Moment Capacity - Framing Member Size 2x4
Lumber Grade:
DF-L No.1
Cm= 1 Ct= 1 Cr= 1.15 Cr=
1.5 fs=
1000 psi Cry= 1.0
0,= 1
Breadth b = 1.50 In
Depth d= 3.501n
Section Modulus S„=bd2/6= 3.06 lns
Bending Stress Capacity Fd=Cv*C�*C,`Ce"fs= 1725 psi Table 4.3.1 NDS 2015
Co
Fe = Co' Fj
ASD Load
M7 S:
DCR
0.9
1553 psi
D
916 psi
0.59
OKAY
1.25
2156 psi
D+Lr
1078 psi
0.50
OKAY
1.15
1984 psi
D+S
916 psi
0.46
OKAY
1.6
2760 psi
0.6D+0.6W
1725 psi
0.62
OKAY
1.6
2760 psi
+0.45W+0.75L
970 psi
0.35
OKAY
1.6
2760 pal
D+0.45W+0.755
970 psi
0.35
OKAY
Deflection Limit
E = 1700 ksi I =
5.36 in
Transient Deflection
0.291 in
Transient Deflection Allowed
330 >
180 [OKAY]
Total Deflection
0.340 in
Total Deflection Allowed
282 >
120 [OKAY]
EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5)
PV System Weight
Module Model Hanwha
Panel Weight Wpanal = 48.5 Ibs
Number of Panels NPV = 40
Total PV System Weight WPV = Wpanal * NPV = 1940 Ibs
Roof
Roof Weight
Qo
= 10.0 psf
Building Length
1-build
= 60 ft
Building Width
Wbulld
= 50 ft
- Roof Area
Abuild
= 3000 ff
Building Perimeter
Pbuild
= 220 ft
_ Wall Height
hi
= 8 It
Wall weight
Qwan
= 15 psf
Interior wall weight
Qint
= 10 psf
Roof Load
WFloor = Abuild " Qo
= 30000 Ibs
Wall Load Nwall
= h, /2 a Qwan ' Pbuild + Abuild `
Clint /. = 28200 Ibs
Total Story Weight
Wbulid = WFloor+ Wwall
= 58200 Ibs
Percentage Weight Increase
WPV / WbUd
= 3.33% < 10% OKAY