Loading...
HomeMy WebLinkAboutPV2022-077 - MiscCITY OF NEWPORT BEACH T I0 W1k1l,gVl FIRE DEPARMENT FIRE PREVENTION DIVISION 100 Civic Center DriveI P.O. Box 1769 1 Newport Beach, CA 92658-8915 www.newportbeachca.gov (949)-644-3200 PLAN REVIEW CORRECTIONS Plan Check No. 0781-2022 Project Description ESS system Project Address 1951 Port Dunleigh Reviewed By Jon Reid, Life Safety Specialist II Jreid@nbfd.net (949) 644-3107 Date Comments Issued 3/24/2022 All corrections and changes shall be clouded and readily identifiable on plans. 1. Provide labels on plans that identify AC disconnect for ESS. Use the sample placard below. ,PV,0` &43. Individual units shall be separated from each other by at least 3 feet except where smaller separation distances are documented to be adequate based on large-scale fire testing complying with Section 1203.1.3 of the 2019 California Fire Code. Show C�Ot� distances on plans. N—O\3. CFC 1206.11.3 — ESS shall be located not less than 3 feet from doors and windows —01 directly entering the dwelling unit. Indicate distance from any doors or windows on plans per CFC 1206.11.3. 1 4. ESS installed in a location subject to vehicle damage shall be protected by approved n, �+e 'R&Y,, barriers per California Fire Code 1206.11.7. N ,*@s Sample Placard for ESS Disconnect CITY OF NEWPORT BEACH FIRE DEPARMENT FIRE PREVENTION DIVISION 100 Civic Center Drive I P.O. Box 1769 1 Newport Beach, CA 92658-8915 www.newportbeachca.gov (949)-644-3200 i ESS AND PHOTOVOLTAIC EMERGENCY SHUTDOWN SWITCH FOR EMERGENCY PERSONNEL ONLY CITY OF NEWPORT BEACH COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DIVISION 100 Civic Center Drive I P.O. Box 1768 1 Newport Beach, CA 92658-8915 www.newportbeachca.gov 1 (949) 644-3200 COUNTER PLAN REVIEW COMMENTS Project Description: SFR SOLAR PHOTOVOLTAIC 10kw, (25) ROOF MOUNTED PANELS & (2) TESLA ENERGY STORAGE SYSTEM Project Address: 1951 PORT DUNLEIGH CIR Permit App. Date: 03/24/2022 Plan Check No.: 0781-2022 Valuation: $75,000 Plan Reviewer: Yoko Tanaka, SE Phone: ytanaka@newportbeachca.gov 949-644-3202 The project plans were reviewed for compliance with the following codes and standards: 2019 CRC; 2019 CBC; 2019 CPC; 2019 CEC; 2019 CMC; 2019 California Energy Code; 2019 California Green Building Standards Code (CG); & Chapter 15 of the Newport Beach Municipal Code (NBMC). COMMENTS: GENERAL Obtain approval from the following: a. Building Division b. Electrical review C. Planning Division d. Fire Department 2. Indicate on the Title page of the plans the following: 17\(_0 1 ----a. PV -01: Update number of stories to 2 story+ basement; 7U -0I --"b. Indicate if the solar panels are on the first -floor roof or the second floor roof etc.; fh PV -02: Update existing roofing called out to concrete slate tile roofing per drawings for new house with plan check number 1518-2020 3. All sheets must be signed by the State of California licensed contractor who prepared them with a classification of "A", "B", "C-46" or "C-10." Provide the individual's printed name with signature and license class and number on each sheet. This correction shall be revisited at time of each submittal. 4. Ongoing projects, new single family dwelling or addition, with an open Building Permit and an Engineer of Record (EOR), will require that EOR's review stamp of approval on this solar plan sheet which indicates the location of the panels, due to the additional weight onto the EOR's initial design for the structure. The EORfor new house with plan check number 1518-2020 is Dale Loren Forbes. This correction shall be revisited at the time of each submittal. Engineer is encouraged to call the plan checker to discuss comments prior to re -submittals. BUILDING _(){ 5. Calculation sheet 5: Update calculation with concrete slate tile roofing. --06. Provide anchorage detail for wall mounted storage system. FIRE / BUILDING 'i -W. PV -01: Use larger texts for dimensions shown on Roof Plan. The dimensions are not legible. City of Newport Beach Community Development Department 100 Civic Center Drive / P.O. Box 1768 Newport Beach, CA 92658 Phone: (949) 644-3200 www.newportbeachca.gov Plan Checker Liz Westmoreland Phone No: 949.644.3234 Email Address: Iwestmoreland@newportbeachca.gov: PLANNING DIVISION PLAN CHECK CORRECTIONS PLAN CHECK NO. 0 � 1 _202;;, I ADDRESS: 1951 Port Dunleigh CORRECTION DATE: 3/24/22 CORRECTIONS: Please make the following corrections. 1. There is equipment proposed in the garage (tesla batteries and other solar equipment). Please show the two single -car garage spaces on the plans to demonstrate that the equipment can be p J^Qt located outside of the required 10' wide by 20' deep dimensions. If the equipment protrudes into the clear dimensions then it will need to be relocated to another location outside of the Y garage. Note: Based on the approved plans for the new house the garages are 11' wide by 20' deep. Flare f" etvi�me•.� vn ti t o�qu�ngr ;s fcr-eene� from v]er, G,T 7vLil,c c Ahi D� WGr� anZ a Jj rc6j cer4exikAl yrry6445 qt irr�-, orN par'a� `shove grotw�• Get,ifewe^I ceirL,;re iv ncaL 4e Sr rcrr_-_rJ' or is I 4e, '0ae;s Vlo�- 0a F:\Users\CDD\Shared\Admin\Planning_Division\Current_ Templates Revised 09-11-18— CDD