PLAN REVIEW CORRECTIONS
Plan Check No.
0781-2022
Project Description
ESS system
Project Address
1951 Port Dunleigh
Reviewed By
Jon Reid, Life Safety Specialist II
Jreid@nbfd.net
(949) 644-3107
Date Comments Issued
3/24/2022
All corrections and changes shall be clouded and readily identifiable on plans.
1. Provide labels on plans that identify AC disconnect for ESS. Use the sample placard
below.
,PV,0` &43. Individual units shall be separated from each other by at least 3 feet except where
smaller separation distances are documented to be adequate based on large-scale fire
testing complying with Section 1203.1.3 of the 2019 California Fire Code. Show
C�Ot� distances on plans.
N—O\3. CFC 1206.11.3 — ESS shall be located not less than 3 feet from doors and windows
—01 directly entering the dwelling unit. Indicate distance from any doors or windows on
plans per CFC 1206.11.3.
1 4. ESS installed in a location subject to vehicle damage shall be protected by approved
n, �+e 'R&Y,, barriers per California Fire Code 1206.11.7.
N ,*@s
Sample Placard for ESS Disconnect
CITY OF NEWPORT BEACH
FIRE DEPARMENT
FIRE PREVENTION DIVISION
100 Civic Center Drive I P.O. Box 1769 1 Newport Beach, CA 92658-8915
www.newportbeachca.gov (949)-644-3200
i
ESS AND
PHOTOVOLTAIC
EMERGENCY
SHUTDOWN
SWITCH
FOR EMERGENCY PERSONNEL ONLY
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive I P.O. Box 1768 1 Newport Beach, CA 92658-8915
www.newportbeachca.gov 1 (949) 644-3200
COUNTER PLAN REVIEW COMMENTS
Project Description: SFR SOLAR PHOTOVOLTAIC 10kw, (25) ROOF MOUNTED PANELS & (2)
TESLA ENERGY STORAGE SYSTEM
Project Address: 1951 PORT DUNLEIGH CIR
Permit App. Date: 03/24/2022
Plan Check No.: 0781-2022
Valuation: $75,000
Plan Reviewer: Yoko Tanaka, SE Phone:
ytanaka@newportbeachca.gov
949-644-3202
The project plans were reviewed for compliance with the following codes and standards:
2019 CRC; 2019 CBC; 2019 CPC; 2019 CEC; 2019 CMC; 2019 California Energy Code; 2019 California
Green Building Standards Code (CG); & Chapter 15 of the Newport Beach Municipal Code (NBMC).
COMMENTS:
GENERAL
Obtain approval from the following:
a. Building Division
b. Electrical review
C. Planning Division
d. Fire Department
2. Indicate on the Title page of the plans the following:
17\(_0 1 ----a. PV -01: Update number of stories to 2 story+ basement;
7U -0I --"b. Indicate if the solar panels are on the first -floor roof or the second floor roof etc.;
fh PV -02: Update existing roofing called out to concrete slate tile roofing per drawings for new
house with plan check number 1518-2020
3. All sheets must be signed by the State of California licensed contractor who prepared them with a
classification of "A", "B", "C-46" or "C-10." Provide the individual's printed name with signature
and license class and number on each sheet. This correction shall be revisited at time of each
submittal.
4. Ongoing projects, new single family dwelling or addition, with an open Building Permit and an
Engineer of Record (EOR), will require that EOR's review stamp of approval on this solar plan sheet
which indicates the location of the panels, due to the additional weight onto the EOR's initial design
for the structure. The EORfor new house with plan check number 1518-2020 is Dale Loren Forbes.
This correction shall be revisited at the time of each submittal. Engineer is encouraged to call the
plan checker to discuss comments prior to re -submittals.
BUILDING
_(){ 5. Calculation sheet 5: Update calculation with concrete slate tile roofing.
--06. Provide anchorage detail for wall mounted storage system.
FIRE / BUILDING
'i -W. PV -01: Use larger texts for dimensions shown on Roof Plan. The dimensions are not legible.
City of Newport Beach
Community Development Department
100 Civic Center Drive / P.O. Box 1768
Newport Beach, CA 92658
Phone: (949) 644-3200
www.newportbeachca.gov
Plan Checker Liz Westmoreland
Phone No: 949.644.3234
Email Address: Iwestmoreland@newportbeachca.gov:
PLANNING DIVISION
PLAN CHECK
CORRECTIONS
PLAN CHECK NO. 0 � 1 _202;;, I ADDRESS: 1951 Port Dunleigh
CORRECTION DATE: 3/24/22
CORRECTIONS:
Please make the following corrections.
1. There is equipment proposed in the garage (tesla batteries and other solar equipment). Please
show the two single -car garage spaces on the plans to demonstrate that the equipment can be
p J^Qt located outside of the required 10' wide by 20' deep dimensions. If the equipment protrudes
into the clear dimensions then it will need to be relocated to another location outside of the
Y garage.
Note: Based on the approved plans for the new house the garages are 11' wide by 20' deep.