Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
Suneel Shorey Residence
22 Cape Danbury,
Newport Beach, CA 92660
Applicable Codes:
BUILDING DIVISION
BY. vr.
Exp. 3-31-23
2019 California Building Code, 2019 California Electric Code,
2019 California Mechanical Code, American Society of Civil Engineers
Standard ASCE 7-16 Minimum Design Loads for Buildings and Other
Structures, American Wood Council 018 National Design Specification
for Wood Construction, Local MunigiRa ode, and all other codes which
are adopted by reference or enac . e!�'
Assumed Design Parameters:
The existing structure has be�orbpyi I d is in its
original condition. The exisf 1 MR%c I
required live load and the �naRfst (9Is
has not been substantially i' y 1ya or
0 � 3ij dy i a0 y" of %bg H
mold, or unauthorized modiii tft$��re. ergy
a � o � r lw a SS �,
Contractor shall make an inspectit �t�.� igg -em
prior to installation of the roof mountd Q14"� s�ws ify that
the existing roof is capable of supporting r%1t�iI,e.
Assumed Design Parameters:
All 2x members are grade Douglas Fir #2 or better
All 4X members are grade Douglas Fir #1 or better
All Roof Connectors are Simpson Strong -Tie or Equal
All Concrete Foundations are f = 2500 psi or stronger
Original Structure was built to the Type -V Wood Framed Standards
of the Applicable Building Code at the time of Construction.
Sht # 1 of 7
2022-1435 Effect Energy Suneel Shorey Residence Date: March 29, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Note to Building Official:
Based upon a review of the proposed plans and information, the
existing roof framing system is capable of safely supporting the additional
loads caused by the new solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permited
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the roof
members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
Check Existing 2x4 Roof Trusses A- 24" O.C.:
No. C58724
* Exp, 3.31.23
W DL+LL
W DL+LL = 30 psf x 2 ft.= 60 plf
R1 22.2' R2
Total load on truss = 60 plf x 22.2 ft. = 1,332 lbs
'Note: Contractor to Field Verify Framing
Sht # 2 of 7
2022-1435 Effect Energy Suneel Shorey Residence Date: March 29, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel: 1.310.464.1804
Email:loydwmartin@gmail.com www.loydwmartin.com
Check Existing 2x4 Roof Trusses A 24" O.C.:
P PP PP PP P
WLL 6 66 66 66 f�
I I
R1
R2
W pL+LL = 30 psf x2 ft.= 60 plf 22.2'
19.8' 12.411
Total load on truss = 60 pif x 2.4 ft + 28 plf x 19.8 ft + (6'x 2.75'x 3 psf x 6 )
+ (6'x 1.65'x 3 psf x 2 )
= 1,055 lbs < 1,332 lbs OK
Check attachment of Support to Existing Structure for Wind Uplift
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16 WIND LOADS ON BUILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE - ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
"FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH."
EFFECTIVE AREA = 15 SQ FT
No. C58724
Exp. 3.31.23
Sht # 3 of 7
2022-1435 Effect Energy Suneel Shorey Residence Date: March 29, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Conrd
Tributary Area to Each Solar Mount = 6 ft. x 2.75 ft. = 16.5 sq. ft. ( Max )
Calculate Design Wind Pressure at each support (Wind Speed 130 mph Exposure C):
p= gh(GCp)(yE)(ya) Eq'n 29.4-7 ASCE 7-16
qh= 0. 00256 Kz Kzt KdKe r Eq'n 26.10-1 ASCE 7-16
Note:
KZ = velocity pressure coefficient Section 29.10.1 ASCE 7-16
KZ = 0.9 (Exposure C, Height = 20 ft or less)
KZr = Topographical Factor= 1.0
Kd = Wind Directionality Factor = 0.85
Ke = Ground Elevation Factor = 1.0
V = 130 mph; VASB= 101 mph Table 1609.3.1 2019 CBC/
qh = 0.00256 (0.9) (1.0) (0.85) (1.0) (101)2
qh = 20 psf
GCp = -2.0 (Zone 2 ; Effective Area = 15 sq. ft. )
YE = Exposure Factor = 1.5
Ya = Solar Array Pressure Equalization Factor = 0.7
p = qh (GCp) (yE) (y.)
p = 20 psf (-2.0) (1.5) (0.7) = 42 psf
No. C58724
Exp. 3.31.23
Fig. 29.4-8 ASCE 7-16
Nominal (Unfactored) Uplift at each support = 42 psf x 16.5 sq. ft. = 693 lbs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for Allowable Stress
Design. Note: Applicable Load Combination #5 (D + 0.6W)
Design (Factored) Uplift at each support = 0.6 x 693 lbs = 416 lbs
Load per lag screw = 416 lbs / 1 = 416 lbs
Sht # 4 of 7
2022-1435 Effect Energy Suneel Shorey Residence Date: March 29, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel: 1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Determine allowable load per 5/16" lag screw w/ 2.5" embedment into wood below
according to the 2018 NDS.
W ' = W x Cd x Ct Table 10.3.1 2018 NDS
where:
W = 266 lbs / in. of embedment per Table 12.2a
Cd = 1.6 per Table 2.3.2 of 2018 NDS
Ct =1.0 per Table 10.3.4 of 2018 NDS
W' = 266 lbs/ in. x 2.5 in. x 1.6 x 1.0 = 1,064 lbs > 416 lbs OK
Use Support connected to 2x Min. Roof Member
w/ (1) 5/16" x 3.5" lag screws per connection minimum.
No. C58724
Exp. 3.31-23
C
Sht # 5 of 7
2022-1435 Effect Energy Suneel Shorey Residence Date: March 29, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check Seismic load due to added dead load of photovoltaic system.
Determine Seismic Weight of Existing Building:
Effective Existing Seismic Weight
Area of (E) Building = Approximately 3,700 Sq. ft.
Approximate
Effective = 3,700 sq. ft. x 30 psf ave. = 111,000 LBS
Seismic Weight
DETERMINE BASE SHEAR
V = Cs W EQ'N 12.8-1 ASCE 7-16
Cs = SDS EQ'N 12.8-2 ASCE 7-16
fRl
le
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R = 6.5 WOOD SHEAR WALLS
le = 1.0 IMPORTANCE FACTOR
SDS = 2/3 x SMS EQ'N 11.4-3 ASCE 7-16
SMS = FAX SS EQ'N 11.4-1 ASCE 7-16
SMS= 1.2x1.5=1.8
SDS = 2/3 x 1.8 = 1.2
1.2
Cs = (6.51 = 0.185
L1
EQ'N 12.8-2 ASCE 7-16
No. C58724
Exp. 3.31-23
Sht # 6 of 7
2022-1435 Effect Energy Suneel Shorey Residence Date: March 29, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
EXISTING BASE SHEAR
V = 0.185 x 111,000 LBS = 20,535 LBS EQ'N 12.8-1 ASCE 7-16
DETERMINE NEW BASE SHEAR
�QROFESS/p4
Determine Seismic Weight of Building with Solar Array:
y o
EXISTING o. C56724
SEISMIC = 111,000 LBS * Exp. 3.31-23
WEIGHT s� pivi.
NEW SOLAR 9 OF CA1 \F -
ARRAY = 3 PSF x 39 PANELS x 3.3'x 55= 2,124 LBS
NEW
SEISMIC = 111,000 LBS + 2,124 LBS = 113,124 LBS
WEIGHT
THEREFORE NEW BASE SHEAR:
V = 0.185 x 113,124 LBS = 20,928 LBS EQ'N 12.8-1 ASCE 7-16
% CHANGE = 20,928 LBS - 20,535 LBS x100%=1.9%<10% OK
20,535 LBS
OK. PER ASCE 7-16 SECTION 11.6.3 ALTERATIONS
EXISTING LATERAL FORCE RESISTING SYSTEM IS EXEMPT
FROM ANALYSIS SINCE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXISTING SEISMIC FORCE.
'Alterations are permitted to be made to any structure without requiring the
existing structure to comply with this standard provided the alterations comply
with the requirements for a new structure. Alterations that increase the
seismic force in any existing structural element by more than 10 percent or
decrease the design strength of any existing structural element to resist
seismic forces by more than 10 percent shall not be permitted unless the
entire seismic force -resisting system is determined to comply with this
standard fora new structure."
End of Calculations
Sht # 7 of 7
2022-1435 Effect Energy Suneel Shorey Residence Date: March 29, 2022