Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Te1:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
Elizabeth Hunt Residence
16 Cape Danbury, ��QROFESS/p��
Newport Beach, CA 92660 r y
No. C58724
Applicable Codes:
2019 California Building Code, 20
2019 California Mechanical Code,
Standard ASCE 7-16 Minimum bE
Structures, American Wood C6"" -
for Wood Construction, Lo l M4
are adopted by reference 44noa
Assumed Design
Exp. 3.31.23
'ic Code,
of Civil Engineers
*ngs and Other
which
\\� SSC UROi,nG,ST�y�1p`SFA�� o'cp
The existing structure has been b
original condition. The existing roof st uctur FeC i �!b its
required live load and the ability of the ro s Its Eve
has not been substantially reduced by the a b, ort Cave loads
�, tr��t�re, termites or
mold, or unauthorized modifications to the existif 6d.. s # . Solar Energy
Contractor shall make an inspection of the existing(aming system
prior to installation of the roof mounted solar energy sy tem to verify that
the existing roof is capable of supporting minimum roof live loads.
Assumed Design Parameters: BUILDING DIVISION
All 2x members are grade Douglas Fir #2 or better
All 4X members are grade Douglas Fir #1 or better
All Roof Connectors are Simpson Strong -Tie or Equal BY YT
All Concrete Foundations are fc = 2500 psi or stronger
Original Structure was built to the Type -V Wood Framed Standards
of the Applicable Building Code at the time of Construction.
2022-1107 Effect Energy Elizabeth Hunt Residence Sht # 1 of 7
Date: March 15, 2021
Loyd W. Martin Professional Engineer Inc
9924 universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.Ioydwmartin.com
Note to Building Official:
Based upon a review of the proposed plans and information, the
existing roof framing system is capable of safely supporting the additional
loads caused by the new solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permited
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the roof
members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
=AMuna Lx4 Koot Ratters iL 24" fB fv • * o
max rafter span = 7.8 ft.) `�` No. C58724
* Exp. 3.31.23
W oL. LL = 30 psf x 2 ft. = 60 plf 9
R1
Total load on rafter = 60 plf x 7.8 ft. = 468 lbs
-Note: Contractor to Field Verify Framing
9
7.8' R2
2022-1107 Effect Energy Elizabeth Hunt Residence Sat # 2 of 7
Date: March 15, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email:loydwmartin@gmail.com www.loydwmartin.com
Check Existing 2x4 Roof Rafters A- 24" O.C.:
P P P P P
wWLL
DL6 66 66
9 �
R1
w DL+LL = 30 psf x 2 ft. = 60 plf
M
Total load on rafter = 28 plf x 7.8 ft + (6'x 1.65'x 3 psf x 5 )
= 367 lbs < 468 lbs OK
Check attachment of Support to Existing Structure for Wind Uplift
ZN
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16WIND LOADS ON BUILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE - ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
"FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH."
EFFECTIVE AREA = 15 SQ FT
No. C58724
Exp. 3-31-23
—� Sht # 3 of 7
2022-1107 Effect Energy Elizabeth Hunt Residence Date: March 15, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Tributary Area to Each Solar Mount = 6 ft. x 2.75 ft. = 16.5 sq. ft. ( Max )
Calculate Design Wind Pressure at each support (Wind Speed 130 mph Exposure C):
p=gh(GCp)(yE)(ya) Eq'n 29.4-7 ASCE 7-16
qh= 0.00256 KZKatKdK, r Eq'n 26.10-1 ASCE 7-16
Note:
KZ = velocity pressure coefficient Section 29. 10.1 ASCE 7-16
Kz = 0.9 (Exposure C, Height = 20 ft or less)
Kzt = Topographical Factor= 1.0
Kd = Wind Directionality Factor = 0.85
Ke = Ground Elevation Factor = 1.0
V = 130 mph; VASB=I 01 mph Table 1609.3.1 2019 CBC
qh = 0.00256 (0.9) (1.0) (0.85) (1.0) (101)2
qh = 20 psf
GCp = -2.0 (Zone 2 ; Effective Area = 15 sq. ft. )
yE = Exposure Factor = 1.5
7a = Solar Array Pressure Equalization Factor = 0.7
P = qh (GC,) (YE) (7a)
p = 20 psf (-2.0) (1.5) (0.7) = 42 psf
No. C58724
Exp. 3-31.23
�—("IVI\i
Fig. 29.4-8 ASCE 7-16
Nominal (Unfactored) Uplift at each support = 42 psf x 16.5 sq. ft. = 693 lbs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for Allowable Stress
Design. Note: Applicable Load Combination #5 (D + 0.6W)
Design (Factored) Uplift at each support = 0.6 x 693 lbs = 416 lbs
Load per lag screw = 416 lbs / 1 = 416 lbs
Sht # 4 of 7
2022-1107 Effect Energy Elizabeth Hunt Residence Date: March 15, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Confd
Determine allowable load per 5/16" lag screw w/ 2.5" embedment into wood below
according to the 2018 NDS.
W'= W x Cd x Ct Table 10.3.1 2018 NDS
where:
W = 266 lbs / in. of embedment per Table 12.2a
Cd = 1.6 per Table 2.3.2 of 2018 NDS
Ct = 1.0 per Table 10.3.4 of 2018 NDS
W' = 266 lbs/ in. x 2.5 in. x 1.6 x 1.0 = 1,064 lbs > 416 lbs OK
Use Support connected to 2x Min. Roof Member
w/ (1) 5/16" x 3.5" lag screws per connection minimum.
No. C58724
Exp. 3-31.23
Sht # 5 of 7
2022-1107 Effect Energy Elizabeth Hunt Residence Date: March 15, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email:loydwmartin@gmail.com www.loydwmartin.com
Check Seismic load due to added dead load of photovoltaic system.
Determine Seismic Weight of Existing Building:
Effective Existing Seismic Weight
Area of (E) Building = Approximately 4,100 Sq. ft.
Approximate
Effective = 4,100 sq. ft. x 30 psf ave. = 123,000 LBS
Seismic Weight
DETERMINE BASE SHEAR
V = Cs W EQ'N 12.8-1 ASCE 7-16
Cs = SDS EQ'N 12.8-2 ASCE 7-16
�R1
le
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R = 6.5 WOOD SHEAR WALLS
le = 1.0 IMPORTANCE FACTOR
SDS = 2/3 x SMS EQ'N 11.4- 3 ASCE 7-16
SMS = FA x SS EQ'N 11.4-1 ASCE 7-16
SMS= 1.2x1.5=1.8
SDS = 2/3 x 1.8 = 1.2
1.2
Cs= f 6.51 = 0.185
L1
EQ'N 12.8-2 ASCE 7-16
No. C58724
Exp. 3-31.23
Sht # 6 of 7
2022-1107 Effect Energy Elizabeth Hunt Residence Date: March 15, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
EXISTING BASE SHEAR
V = 0.185 x 123,000 LBS = 22,755 LBS EQ'N 12.8-1 ASCE 7-16
DETERMINE NEW BASE SHEAR
�OQµOFESS/p�
Determine Seismic Weight of Building with Solar Array:
EXISTING
ii?' No. C58724
SEISMIC = 123,000 LBS * Exp. 3.31-23
WEIGHT
NEW SOLAR
ARRAY = 3 PSF x 18 PANELS x 3.3'x 6.5'= 980 LBS
NEW
SEISMIC = 123,000 LBS + 980 LBS = 123,980 LBS
WEIGHT
THEREFORE NEW BASE SHEAR:
V = 0.185 x 123,980 LBS = 22,936 LBS EQ'N 12.8-1 ASCE 7-16
% CHANGE = 22,936 LBS - 22,755 LBS
x100%=0.8%<10% OK
22,755 LBS
OK. PER ASCE 7-16 SECTION 11.B.3 ALTERATIONS
EXISTING LATERAL FORCE RESISTING SYSTEM IS EXEMPT
FROM ANALYSIS SINCE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXISTING SEISMIC FORCE.
'Alterations are permitted to be made to any structure without requiring the
existing structure to comply with this standard provided the alterations comply
with the requirements for a new structure. Alterations that increase the
seismic force in any existing structural element by more than 10 percent or
decrease the design strength of any existing structural element to resist
seismic forces by more than 10 percent shall not be permitted unless the
entire seismic force -resisting system is determined to comply with this
standard for a new structure. "
End of Calculations
Sht # 7 of 7