Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
David &Victoria Collins Residence (*Exp.
ROFEss ro1615 Bayadere Terrace,Newport Beach, CA 92625No. C58724
3-31.23
Applicable Codes:
2019 California Building Code, 2019 California Electric Code, `�
2019 California Mechanical Code, American Society of Civil Engineers
Standard ASCE 7-16 Minimum Design Loads for Buildings and Other
Structures, American Wood Council 2018 National Design Specification
for Wood Construction, Local Municipal Code, and all other codes which
are adopted by reference or enacted by law.
Assumed Design Parameters:
The existing structure has been built under a building permit and is in its
original condition. The existing roof structure is capable of its code
required live load and the ability of the roof structure to support live loads
has not been substantially reduced by the age of the structure, termites or
mold, or unauthorized modifications to the existing structure. Solar Energy
Contractor shall make inspection of the existing roof framing system prior
to installation of the roof mounted solar energy system to verify that the
existing roof is capable of supporting minimum roof live loads.
Assumed Design Parameters:
All 2x members are grade Douglas Fir #2 or better
All 4x members are grade Douglas Fir #1 or better
All Roof Connectors are Simpsons Strong -Tie or Equal
All Concrete Foundations are fc = 2500 psi or stronger
Original Structure was built to the Type-V Wood Framed Standards
of the Applicable Building Code at the time of Construction.
Sht # 1 of 7
2022-1352 Green Road Solar Date: March 24, 2022
David & Victoria Collins Residence
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Note to Building Official:
Based upon a review of the proposed plans I am confident that the
existing roof framing system is capable of safely supporting the additional
loads caused by the solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permitted
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the
roof members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
Check 2x4 Rafters 0-) 24" O.C.*:
(Assume max rafter span = 6.9 ft.)
wDL+LL
w = 30 psf x 2 ft. = 60 pif I 9
R1 R2
6.9'
Total load on rafter = 60 plf x 6.9 ft. = 414 Ibs
No. C58724
Exp. 3-31-23
C
*Note: Contractor to Field Verify Framing
Sht # 2 of 7
2022-1352 Green Road Solar Date: March 24, 2022
David & Victoria Collins Residence
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check 2x4 Rafters (a)_ 24" O.C.:
P P P
6 66
w DL
wDL.LL=30psfx2ft. =60pif I I I
R1 R2
Total load on rafter = 28 plf x 6.9 ft. + ( 4' x 2.75' x 3 psf x 3 )
= 292 Ibs < 414 Ibs OK
Check attachment of Support to Existina Structure for Wind Uplift
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16 WIND LOADS ON BUILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE - ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
"FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH."
EFFECTIVE AREA = 15 SQ FT
2022-1352 Green Road Solar
David & Victoria Collins Residence
No. C58724
Exp.3.31-23
Sht # 3 of 7
Date: March 24, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
For Sloped Roof Connection:
Tributary Area to Each Solar Mount = 4 ft. x 2.75 ft. = 11 sq. ft. ( Max)
Calculate Design Wind Pressure at each support (Wind Speed 110 mph Exposure C):
p=gh(GCp)(yE)(y.) Eq'n 29.4-7 ASCE 7-16
qh=0.00256KZKZtKdK,V2 Eq'n 26.10-1 ASCE 7-16
Note:
KZ = velocity pressure coefficient, Section 26.10.1 ASCE 7-16
KZ = 0.9 (Exposure C, Height = 20 ft or less) w.
KZt = Topographical Factor = 1.0 LNo.Kd = Wind Directionality Factor = 0.85 Ke = Ground Elevation Factor= 1.0 V = 110 mph; VASD= 85 mph Table 1609.3.1 2019 CBC
qh = 0.00256 (0.9) (1.0) (0.85) (1.0) (85)2
qh =14.1 psf
GCp = -2.0 (Zone 2 ; Effective Area = 15 sq. ft. )
YE = Exposure Factor = 1.5
y,, = Solar Array Pressure Equalization Factor = 0.7 Fig. 29.4-8 ASCE 7-16
p = qh (GCp) (YE) (Y. )
p =14.1 psf (-2.0) (1.5) (0.7) = -29.7 psf
Nominal (Unfactored) Uplift at each support = 29.7 psf x 11 sq. ft. = 327 Ibs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for Allowable Stress
Design. Note: Applicable Load Combination #5 (D + 0.6W)
Sht # 4 of 7
2022-1352 Green Road Solar Date: March 24, 2022
David & Victoria Collins Residence
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Dead Load = 3.0 psf
Wind Load = 29.7 psf
Design (Factored) Load at each support:
3 psf + (0.6 x 29.7 psf) = 20.8 psf
where:
Y = Distance between 2 lag screws
= 1.2"
Y' = Moment arm to 1 st lag screw
= 5.6"
Moment due to Load = (20.8 psf x 11 sq. ft.) x 5.6 inches
= 1,281 in -lb
Load to lag screw = 1,281 in -lb / 1.2 in
= 1,068lbs
Determine allowable load per 5/16" lag screw w/ 3.25" embedment into wood below
according to the 2018 NDS.
W ' = W x Cd x Ct Table 10.3.1 2018 NDS
where:
W = 266 Ibs / in, of embedment per Table 12.2A
Cd = 1.6 per Table 2.3.2 of 2018 NDS
Ct = 1.0 per Table 10.3.4 of 2018 NDS
W' = 266 Ibs/ in. x 3.25 in. x 1.6 x 1.0 = 1,383 Ibs > 1,068 Ibs OK
OK. Use Tile Hooks with (2) 5/16" x 3.5" Lag Screws
with 3.25" min. embedment into wood, at 48" O.C.
max, as per Plans to Manufacturer's instructions.
No. C58724
Exp.3-31-23
[0,
Sht # 5 of 7
2022-1352 Green Road Solar Date: March 24, 2022
David & Victoria Collins Residence
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
For Flat Roof Connection:
Design (Factored) Uplift at each support = 0.6 x 327 Ibs = 196 Ibs
Load per lag screw = 196 Ibs / 1 = 196 Ibs
Determine allowable load per 5/16" lag screw w/ 2.5" embedment into wood below
according to the 2018 NDS.
W ' = W x Cd x Ct Table 10.3.1 2018 NDS
where:
W = 266 Ibs / in. of embedment per Table 12.2A
Cd = 1.6 per Table 2.3.2 of 2018 NDS
Ct = 1.0 per Table 10.3.4 of 2018 NDS
W' = 266 Ibs/ in. x 2.5 in. x 1.6 x 1.0 = 1,064 Ibs > 196 Ibs OK
Use Support connected to 2x Min. Roof Member
w/ (1) 5/16" x 3.5" lag screw per connection minimum.
No. C58724
Exp. 3-31-23
Sht # 5.1 of 7
2022-1352 Green Road Solar Date: March 24, 2022
David & Victoria Collins Residence
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check Seismic load due to added dead load of photovoltaic system.
Determine Seismic Weight of Existing Building:
Effective Existing Seismic Weight
Area of (E) Building = Approximately 5,700 sq. ft.
Approximate
Effective =
Seismic Weight
DETERMINE BASE SHEAR
V=CsW
Cs
SDS
=
rR]le
5,700 sq. ft. x 30 psf ave. = 171,000 LBS
EQ'N 12.8-1 ASCE 7-16
EQ'N 12.8-2 ASCE 7-16
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R = 6.5 WOOD SHEAR WALLS
le = 1.0 IMPORTANCE FACTOR
SDs = 2/3 x SMs_ EQ'N 11.4-3 ASCE 7-16
SMs = FA x Ss EQ'N 11.4-1 ASCE 7-16
SMs= 1.2x1.5=1.8
SDs= 2/3x1.8=1.2
1.2
Cs = �6.5] = 0.185
1
2022-1352 Green Road Solar
David & Victoria Collins Residence
EQ'N 12.8-2 ASCE 7-16
No. C58724
Exp. 3-31-23
Sht # 6 of 7
Date: March 24, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email:loydwmartin@gmail.com www.loydwmartin.com
EXISTING BASE SHEAR
V = 0.185 x 171,000 LBS = 31,635 LBS EQ'N 12.8-1 ASCE 7-16
DETERMINE NEW BASE SHEAR
Determine Seismic Weight of Building with Solar Array:
EXISTING
SEISMIC = 171,000 LBS
WEIGHT
NEW SOLAR
ARRAY = 3 PSF x 54 PANELS x 3.3' x 5.5' = 2,940 LBS
NEW
_SEISMIC__ = 171,000 LBS + 2,940 LBS = 173,940 LBS
WEIGHT
THEREFORE NEW BASE SHEAR:
V = 0.185 x 173,940 = 32,179 LBS EQ'N 12.8-1 ASCE 7-16
% CHANGE = 32,179 LBS - 31,635 LBS x 100 = 1.7 0/6< 10% OK
31,635 LBS
BUILDING DI
OK. PER ASCE 7-16 SECTION 11.13.3 ALTERATIONS
EXISTING LATERAL FORCE RESISTING SYSTEM IS EXEMPT
FROM ANALYSIS SINCE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXISTING SEISMIC FORCE.
'Alterations are permitted to be made to any structure without requiring the
existing structure to comply with this standard provided the alterations comply
with the requirements for a new structure. Alterations that increase the
seismic force in any existing structural element by more than 10 percent or
decrease the design strength of any existing structural element to resist
seismic forces by more than 10 percent shall not be permitted unless the
entire seismic force -resisting system is determined to comply with this
standard for a new structure."
End of Calculations
05/04/2022
BY: Y.T.
gROFESS/pNq
W.lu
r 2 LNo. C58724
Exp.3-31-23
O w \-
�OF C A0F0�
Sht # 7 of 7
2022-1352 Green Road Solar Date: March 24, 2022
David & Victoria Collins Residence