DATE: 10/ 6/ 2021
TO: Ali Addo
EMAIL: aaafireco@gmail.com
SUBJECT: Static Pressure Test
66N
In response to your request, the static pressure at 1712 Tradewinds
Ln. is 90 psi.
The Meter is a New 1" AMI meter.
If you need further assistance, please contact me.
Sincerely,
Matt Aman
Utilities Inspector
Office: 949-718-3410
Fax: 949-646-5204
Email: Maman@newportbeachca.gov
Utilities Yool:949 W"t 16th Street - Newport Beach, Ccoi;onniu 92663 - Telephone: (949) 644-3011-- Fax: (949) 6,16-5204
+Moding Address. Po,;t Of ce Box 1765, Newport Deach, ('o4joinfa'926.5S-f3915 - www,nekvportheachco.aov
Page 1 of 5
m Arm FREEDOM° RESIDENTIAL
• to • CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Viking FreedomO Residential Concealed Pendent Sprinkler VK494 is a small
thermosensitive, glass -bulb residential sprinkler designed for installation on
concealed pipe systems where the appearance of a smooth ceiling is desired. The
orifice design, with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient
use of available water supplies for the hydraulically designed fire -protection
system. The fast response glass bulb operating element and special deflector
characteristics meet the challenges of residential sprinkler standards.
The sprinkler is pre -assembled with a threaded adapter for installation with a
low -profile small -diameter cover assembly installed flush to the ceiling. The two-
piece design allows installation and testing of the sprinkler prior to installation
of the cover plate. The "push -on", "thread -off' design of the concealed cover
plate assembly allows easy installation of the cover plate after the system has
been tested and the ceiling finish has been applied, while also providing up to
1/2" (13 mm) of vertical adjustment. The cover assembly can be removed
and reinstalled, allowing temporary removal of ceiling panels without taking
the sprinkler system out of service or removing the sprinkler. The Electroless
Nickel PTFE (ENT) coating has been investigated for installation in corrosive
atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the
Approval Charts. The ENT finish is only available for the sprinkler assembly, the
cover plate is not plated.
2. LISTINGS AND APPROVALS
c UL . UL Listed (C-UL-US-EU): Category VKKW
eg Referto the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
WARNING: Cancer anO Repmtluctive Herm-
www.P65Waminga.ca.gw
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to
500 psi (34.5 bar).
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 4.9 U.S. (70.6 metric*)
Glass -bulb fluid temperature rated to -65 *F (-55 *C)
" Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the
metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-051000
Deflector Pins: Stainless Steel UNS-S30200
Button: Brass UNS-C36000
Pip Cap and InsertAssembly: Copper UNS-C11000 and SS UNS-S30400
Compression Screw: 18-8 Stainless Steel
Yoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-051000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Shipping Cap: Polyethylene
Cover Plate Materials:
Cover Plate Assembly: Copper UNS-Cl1000 and Brass UNS-C26800 or Stainless Steel UNS-S30400
Spring: Beryllium Nickel
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Freedom® Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:
Sprinkler: Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the
temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A and ENT = JN
Temperature Suffix: 155 'F (68 *C) = B, 200 °F (93 *C) = E
For example, sprinkler VK494 with a Brass finish and a 200 °F (93 *C) temperature rating = Part No. 20759AE.
Standard Cover Plates: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter),
or Base Part No. 15394 (square cover plate, 3-5/16")
Stainless Steel Cover Plates (not availble with any finish or paint): Base Part No. 21876 (2-3/4" diameter) or Base Part No.
21875 (3-5/16" diameter).
Form No. F_012116 18.10.11 Rev 18.1.P65 Replaces Form No. F_012116 Rev 18.1
(Added P65 Warning.)
Page 2 of 5
NIKI
4 to)FREEDOM® RESIDENTIAL
• CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed
Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B
Temperature Suffix: 135 °F/57 °C = A
For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 "C temperature rating = 13504FA.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches**:
A. Heavy Duty Part No. 14047W/B** (available since 2006), or
B. Head Cabinet Wrench Part No. 14031*** (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)
D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a I/V ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the heat -sensitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly.. Water flowing through the sprinkler
orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-
sure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Ordinary 155 °F (68 °C) 100 °F (38 °C) 135 °F (57 °C) 13504 or 13642 or 15394 Red
21876" 1 21875"
Intermediate 200''F (93 *C) 150 °F (65 °C) 135 °F (57 °C). 13504 or 13642 or 15394 Oteen
21876" 1 21875"
Sprinkler Finishes: Brass and ENT
Cover Plate Finishes": Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
Corrosion Resistant Coatings": ENT
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
z Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
a. Maximum ambient temperature for cover assembly is 100 "F (38 "C).
4. Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
" The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville
spring is exposed.
a. Stainless Steel versions are not available with any finishes or paint.
Form No. F_012116 18,10.11 Rev 18.1.P65
Page 3 of 5
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877.384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Sprinkler Base
NPT Thread Size
Nominal K-Factor Maximum Water Wor-
SIN
Inches
mm
Part Number
U.S. metric' king Pressure
20759
VK494
1/2
15
4.9
70.6
175 psi (12 bar)
Max. Coverage
6
Flow
GPM
Pressure
Listings and
Minimum
Area
W X L
(LPM)
PSI (bar)
Deflector to
Installation
Approvalsl,5
Spacing
Ft. X Ft.
Ceiling
Type
Ft.
(m)
155 °F (681`% 200 °F (93 °C) Temperature
c 6t as 4
(m X m)
Rated Sprinklers
eu
12 X 12
13
7.0
(3.7 X 3.7)
(49.2)
(0.48)
14 X 14
13
7.0
(4.3 X 4.3)
(49.2)
(0.48)
Concealed with
Cover Plate
See Footnotes 7,9, 10,
8
16 X 16
13
7.0
(4.9 X 4.9)
(49.2)
(0.48)
Refer to Figure 2
Assembly.
See Footnote8.
& 11
(2.4)
1&X18'
17
124
(5.5 X 5.5)
(64.4)
(0.83)
20 X 20
20
16.7
(6.1 X 6.1)
(75.7)
(1.15)
Footnotes
+. Part number shown is the base part number. For complete part number, refer to current Viking price schedule.
Z Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
]. This chartshows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
Refer also to Design Criteria.
4 Listed by Underwriter's Laboratories, Inc. for use in the U.S., Canada, and European Union.
e. Meets New York City requirements, effective July 1, 201
s For areas of coverage smaller than shown, use the "Flow" and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum "Flow" and "Pressure" used.
I. Cover Temperature Rating is 135'F (57'C). Cover Part No, 13504', 13642' (large diameter), or 15394' (square cover plate).
e. Other paint colors are available on request with the same listings as the standard finish colors. Stainless Steel cover plates are not available with any finishes or paint.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly.
Refer to Figure 3.
a Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black a.
,-C-UL-US-EU Listed as corrosion resistant - Eectroless Nickel PTFE (ENT)
++.Stainless Steel Cover plate temperature rating is 135 °F (57 ^C). Stainless Steel Cover Part Numbers: 21876' and 21875' (large diameter).
Form No. F_012116 18.10.11 Rev 18.1.P65
Page 4 of 5
V'� ® FREEDOM® RESIDENTIAL
� CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269.818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical datapage www.vikinggroupinc.com
UL Listing Reouirements (C-UL-US-EU):
When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-
age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 11 The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, Pr
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area' in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13,
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT: Always refer to Bulletin Form No. F_080415 - Best Practices for Residential Sprinkler Handling and Installation.
Also refer to Form No. F 080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever
applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities
Sprinkler and Adapter Assembly
• Protective cap removed
• Use wrench 14047W/B**
Step 1:
Carefully slide the
wrench sideways around
the deflector and pins
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise
1 to 1-1/2 turns beyond finger tight.
2-1/4" (57 mm)
neter opening
/fired in the
ing.
Step 2:
Carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
Sprinkler
wrench flat
Figure 1: Sprinkler Installation and Proper Wrench Usage
** A 1/2" ratchet is required (Not available from Viking)
Sprinkler
frame arms
Form No. F_012116 18.10.11 Rev 18.1.P65
Page 5 of 5
FREEDOM® RESIDENTIAL
• � • CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Figure 3: Identification of Custom Paint for Concealed Covers
_.._ ._........
Figure 4: Square Cover Assembly 15394
Form No. F_012116 18.10.11 Rev 18.1.P65
Replaces Form No. F_012116 Rev 18.1
(Added P65 Warning.)
AAA Fire Protection
142 E. Bonita Ave 454
San Dimas, CA 91773
HYDRAULIC CALCULATIONS FOR
Michael and Marina Samen Residence
1712 Tradewinds Ln
Newport Beach, CA 92660
DRAWING NUMBER: DATE: 12/1/21
-DESIGN DATA -
REMOTE AREA NUMBER: 1 REMOTE AREA LOCATION: FP-2
OCCUPANCY CLASSIFICATION: Light Hazard (NFPA 13D)
DENSITY: 0.05 gpm/sq. ft.
AREA OF APPLICATION: 2 Heads sq. ft.
COVERAGE PER SPRINKLER: 18' x 18' sq. ft.
TYPE OF SPRINKLERS CALCULATED: Viking VK494
NUMBER OF SPRINKLERS CALCULATED: 2
*IN -RACK SPRINKLER DEMAND: gpm
HOSE -STREAM DEMAND: 5 gpm
TOTAL WATER REQUIRED (INCLUDING HOSE): 39.6 gpm
FLOW AND PRESSURE (AT BASE OF RISER): 34.6 gpm 0 46.6 psi
TYPE OF SYSTEM: Wet Pipe
*VOLUME OF DRY OR PREACTION SYSTEM:
*DETAILS:
WATER SUPPLY
Source: City Test Date: 10/6/21 Test By: CNPBUD
Location: 1712 Tradewinds Ln
Static: 90 psi Residual: 75 psi Flow: 400 gpm
Source Elevation Relative to Finished Floor Level: ft.
INSTALLING CONTRACTOR
Name: AAA Fire Protection
Address:
Phone: (310) 569-4122 Certification number: 807294
NAME OF DESIGNER: Delbar Rashidi
AUTHORITY HAVING JURISDICTION: Newport Beach Fire Department
NOTES:
Calculations performed by HASS under license # 38011909 ,
granted by HRS SYSTEMS, INC.
(Notes continue after pipe calculations results.)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2.
DATE: 6/30/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS85\1712 TRADEWINDS LN.SDF
JOB TITLE: Samen Res
r
W
0 4 m 0 w o a w m m a a w — a M . --
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3.
DATE: 6/30/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS85\1712 TRADEWINDS LDT.SDF
JOB TITLE: Samen Res
NFPA WATER SUPPLY DATA
SOURCE
STATIC
RESID. FLOW
AVAIL.
TOTAL
REQ'D
NODE
PRESS.
PRESS. @
PRESS.
@ DEMAND
PRESS.
TAG
(PSI)
(PSI) (GPM)
(PSI)
(GPM)
(PSI)
11
90.0
75.0 400.0
89.8
39.6
71.4
AGGREGATE FLOW ANALYSIS:
TOTAL
FLOW AT SOURCE
39.6
GPM
TOTAL
HOSE STREAM ALLOWANCE AT SOURCE
0.0
GPM
OTHER
HOSE STREAM ALLOWANCES
5.0
GPM
TOTAL
DISCHARGE FROM ACTIVE SPRINKLERS
34.6
GPM
NODE ANALYSIS DATA
NODE TAG
ELEVATION
NODE TYPE
PRESSURE
DISCHARGE NOTES
(FT)
(PSI)
(GPM)
1
8.0
K= 4.90
12.0
17.0
2
8.0
K= 4.90
12.8
17.5
3
8.0
- - - -
14.6
- - -
4
8.0
- - - -
19.9
- - -
5
8.0
- - - -
30.3
- - -
6
8.0
- - - -
34.1
- - -
7
8.0
- - - -
40.7
- - -
8
0.0
HOSE STREAM
46.6
5.0
9
0.0
- - - -
59.6
- - -
10
0.0
- - - -
65.6
- - -
11
0.0
SOURCE
71.4
39.6
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4,
DATE: 6/30/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS85\1712 TRADEWINDS LN.SDF
JOB TITLE: Samen Res
NFPA PIPE DATA
Pipe
Tag
K-fac
Add F1 Add F1
To
Fit:
L
C
(Pt)
Frm Node
E1 (ft)
PT
(q)
Node/
Nom
ID
Eq.Ln.
F
(Pe)
To Node
E1 (£t)
PT
Tot-(Q)
Disch
Act
ID
(ft.)
T
Pf/ft.
(Pf)
Pipe:
1
4.90
17.0
Disch
5.00
150
0.8
2
8.0
12.8
0.0
F1.000
T: 5.0
10.00
0.0
1
8.0
12.0
17.0
1.101
L: 5.0
15.00
0.050
0.8
Pipe:
2
4.90
17.5
Disch
4.67
150
1.8
3
8.0
14.6
17.0
1
F1.000
L: 5.0
5.00
0.0
2
8.0
12.8
34.5
1.101
9.67
0.187
1.8
Pipe:
3
0.0
0.0
23.42
150
5.3
4
8.0
19.9
34.5
2
F1.000
L: 5.0
5.00
0.0
3
8.0
14.6
34.5
1.101
28.42
0.187
5.3
Pipe:
4
0.0
0.0
50.75
150
10.4
5
8.0
30.3
34.5
3
F1.000
T: 5.0
5.00
0.0
4
8.0
19.9
34.5
1.101
55.75
0.187
10.4
Pipe:
5
0.0
0.0
15.42
150
3.8
6
8.0
34.1
34.5
4
F1.000
1: 5.0
5.00
0.0
5
8.0
30.3
34.5
1.101
20.42
0.187
3.8
Pipe:
6
0.0
0.0
25.25
150
6.6
7
8.0
40.7
34.5
5
F1.000
2L:10.0
10.00
0.0
6
8.0
34.1
34.5
1.101
35.25
0.187
6.6
Pipe:
7
0.0
0.0
8.00
150
5.9
8
0.0
46.6
34.5
6
F1.000
L: 5.0
5.00
-3.5
7
8.0
40.7
34.5
1.101
13.00
0.187
2.4
Pipe:
8
H.S.
5.0
Disch
35.33
150
13.0
9
0.0
59.6
34.5
7
L1.000
E: 3.0
3.00
0.0
8
0.0
46.6
39.5
1.025
38.33
0.340
13.0
Pipe:
9
0.0
Fixed
Pressure
Loss
Device
10
0.0
65.6
39.5
8
6.0
psi,
39.5 gpm
9
0.0
59.6
39.5
Pipe:
10
Source
0.0
10.00
150
5.8
11
0.0
71.4
39.6
9
L1.000
1: 7.0
7.00
0.0
10
0.0
65.6
39.6
1.025
17.00
0.341
5.8
NOTES
(HASS):
(1) Calculations
were performed
by the HASS 8.5
computer program
under
license
no. 38011909
granted
by
HRS Systems,
Inc.
208 Southside
Square
Petersburg,
TN
37144
(931)
659-9760
Notes