HomeMy WebLinkAboutF2022-0187 - Misc2621 - 007 �-O-vO 13tnG�t S7
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE 0
LISTING No.
i?125078'5 o1r8 Page 1 of 1
CATEGORY:
7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE:
Cooper Wheelock Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Thomas Conover (941) 487-2336
Email: thomaslconover@eaton.com
DESIGN:
Exceder Series: Models 1 strobe }iS hornastrotie and HN horn. Model ST is a synchronous
and non -synchronous strobe light. Model HS a visual/audible appliance and Model HN is an
audible signal appliance. All units followed by R (red) or W (white). Additionally, a'C' may be
added for ceiling models and/or a'-NR' may be added for non-resettable models. For non
-NR models and optional'S'for silver fascia may be added*. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING:
Electrical: 12 VDC/24VDC/FWR
Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185
Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. All models are for indoor use
and for wall mount only or ceiling mount only*
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when
used with separately listed electrically compatible fire alarm control units. Refer to listee's
Installation Instructions Manual for details.
*Rev. 9-24-09 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
sgE the test results and/or other data but does not make an independent verification of any claims. This listing is not
`�' an endorsement or recommendation of the item listed. This listing should not be used to verify correct
10
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
nd Horn
Notification Appliances
Description:
The Wheelock® Exceder^^ Series of notification appliances feature
a sleek modern design that will please building owners with reduced
total cost of ownership. Installers will benefit from its comprehensive
feature list, including the most candela options in one appliance,
low current draw, no tools needed for setting changes, voltage test
points, 12/24 VDC operation, universal mounting base and multiple
mounting options for both new and retrofit construction.
The Wheelock® Excederrm Series incorporates high reliability and
high efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe
models feature an industry first of 8 candela settings on a single
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of tool and are located behind the appliance to prevent tampering.
Wall models feature voltage test points to take readings with a
voltage meter for troubleshooting and AHJ inspection.
The Wheelock® Exceder"" Series of wall and ceiling notification
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting
base can be pre -wired to allow full testing of circuit wiring before
the appliance is installed and the surface is finished. It comes
completewith a Contact Cover for protection againstdirt, dust, paint
and damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre -wire testing forcommon wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while
it is on the UMB. When the Contact Cover is removed the circuit
will show an open until the appliance is installed. The UMB allows
for consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra
secure installation, while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
COOPER Notification
- Save up to 48% in current draw*
- Up to 9 models now in 1 appliance
- Save up to 14% cost of installation**
[(O>] Sleek Modern Aesthetics
Finger Slide Switches
Voltage Test Points
Multiple Voltages
CO3
Audible Settings
90, 95, 99 d8
8 Candela Settings
Wall - 15/1575/30/75/95/110/135/185
5/1
Ceiling - 15/30160/75/95/115/150/177
Universal Mounting Base `#*
V
Ceiling and Wall
Mounts to 5 Backbox Types
Environmentally Friendly
Low Current Draw
Compatibility and Requirements '
-Synchronize using the Wheelock° Sync Modules or panels with built-in Wheelock' Patented Sync Protocol
CompatiblewithUL"Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage
-Strobes produce 1 Flash per second over the"Regulated Voltage' range
-Compared to competitive models *** Patented
** Compared to previous models
NOTE: All CAUTIONS and. WARNINGS are identified by the
A'WARNING: PLEASE READ THESE SPECIFICATIONS AND AS:
OR APPLYING THIS PRODUCT. VISIT: WWW.000PERNOTIFICATIO
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OFTHESE INST
I A. All
-0
in bold capital letters.
i CAREFULLY BEFORE USING, SPECIFYING
TION FOR THE CURRENT INSTALLATION
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
General Notes:
• Strobes are designed to flash at 1 gash persecond`minimum overtheir "Regulated Voltage Range". "
• All candela ratings represent minimum effective strobe intensity based an UL Standard 1971
• Series'Exceder Strobe products are Listed. under UL Standards 1971 and 464 for indoor use with a temperature range of 32Fto 120°F (0°C to 49°C) and
maximum humidity of 93% (t 2%) UL 464 (85 % ILL 1971). _
• Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Low
Strobe Ratings per UL Standard 1971
Current Draw = Fewer Power Supplies
UL Max Current'
24VDC/24FWR
12VDC
Model
Regulated Voltage
Range VDC
15
LO'O/7
30
60
75
95
110
115
135
750
177
185
15
15/75
ST
8.0-33.0
0.057
0.085
0.135
0.163
0.182
0.205
0.253
0.110
0.140
Elm
8.0-33.0
0.061
0.085
0.103
0.135
0.163
0.182
0.205
0.253
0.110
Horn Strobe Ratings per UL 1971
&Anechoic at 24VDC
UL
Max Current* at
Anechoic
99 dBA
24 VDC
12 VDC
Regulated Voltage
Model
15
15/75
30
60
75
95 110
115
135
150
177
185
15
15/75
Range VDC
HS
8.0-33.0
0.082
1 0.095
1 0.102
MI
0.148
0.176 0.197
0.242
0.282
0.125
0.159
} K
8.0-33.0
TOM
0.102
0.141
0.148
0.176
0.197
0.242
0.282
0.125
UL
Max Current* at
Anechoic
95 .:
24VDC
12 VDC
Model
Regulated Voltage
15
15/75a306O75
95 110111351118515
15/75
RangeVDCHS
8.0-33.0
0.073
0.083
.139
0.163 0.186
0.2300.272
0.122
0.153HSC
8.0-33.0
0.073
.139
0.163
0.186
0.230
0.272
0.122
24VDC
12VDC
Regulated Voltage
Model
15
15/75
30
60
75
95 110
115
135
150
177
185
15
15/75
Range VDC
HS
8.0-33.0
0.065
0.075
0.084
0,136
0.157 0.184
0.226
0.267
0.120
0,148
HSC
8.0-33.0
0.065
0.084
0.120
0.136
0.157
0.184
0.226
0.267
0.120
Horn Ratings
per ULAnechoic
Model
Regulated Voltage
99dB
95dB
90dB
Range VDC
F
-
HN
16-33.0
0.064
0.044
0.022
HNC
16-33.0
0.084
0.044
0.022
HN
8.0-17.5
0.047
0.026
0.017
HNC
8.0-17.5
0.047
0.026
0.017
UL max current rating is the maximum RMS current within the listed voltage range (16 33 VDC. for 24 VDC units) For strobes the
UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the
maximum listed voltage (33 VDC for 24 VDC units) For unfiltered ratings, see installation instructions.
Specification & Ordering Information
Sync wl
Model
Strobe
DSM or
12124 VDC*
Mounting
Candela
Wheelock Power
Options
Supplies
HSR
1511575/301751951110/135/185
X
X
UMB**
HSW
15/1575/30175195/1101135/185
X
X
UMB**
HSRC
15/30160/75/95/115/1501177
X
X
UMB**
HSWC
15/30/60175/95/115/150177
X
X
UMB**
•
'
STIR
15/1575/30/75/95/110/135/185
X
X
UMB'*
STW
15/1575/30/75/951110/1351185
X
X
UMB**
•
RC
15/30/60/75/95111511501177
X
X
UMB**
'
STWC
•
15/30/60175/95/115/150/177
X
X
UMB**
UMB**
HNR X
X
HNW
X
X
UMB**
HNRC
,.
X
X
UMB**
HNWC
X
X
UMB**
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions.
Architects and Engineers Specifications
The notification appliances shall be Wheelock' Exceder- Series HS Audible Strobe appliances, Series ST Visual Strobe appliances
and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency
Devices for the Hearing -Impaired) for Indoor Fire Protection Service. The Series HS and HNAudibles shall be UL Listed under Standard
464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with
standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC.
Indoor wall models shall incorporate voltage test points for easy voltage inspection.
The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated
Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design.
Where Multi -Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110,
135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 15175 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with
75 candela on -axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible
location at all times when installed.
The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal
(Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single -gang, double -gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire
appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to
attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of
an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same
base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24"
H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series
HNC ceiling shall have a diameter of 6.68" x 1.50" D.
When synchronization is required, the appliance shall be compatible with Wheelock®'s DSM Sync Modules, Wheelock® Power Supplies
or other manufacturer's panels with built-in Wheelock° Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync protocol fails to operate, the strobe shall revert to a non -synchronized flash -rate and still maintain (1)
flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced
while maintaining strobe activation when used with Wheelock® synchronization protocol.
Wall Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Ceiling Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
1_
Me.b
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Exceder - Spec Sheet 6/11
Wheelock° M®C SAFEPATW
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE 0
LISTING No. 712520785�0152 Page 1 of 1
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Cooper yalheeloa)Ss nc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Thomas Conover (941) 487-2336
Email: thomaslconover@eaton.com
DESIGN: Models *ET70-241575W, ET70-24MCW, ET70-24MCC, ET70-24MCWH, ET70-24MCCH,
*ET80-241575W, ET80-24MCW, ET80-24MCWH, *ET90-241575W, ET90-24MCW,
ET90-24MCC, ET90-24MCWH, ET90-24MCCH, E70-24MCW, E70-24MCC, E70-24MCWH,
E70-24MCCH, E90-24MCW E90`=24MCC�E90-24MCWH, and E90-24MCCH multi -candela
speaker/strobes. Models E60-R, E60-W, E60-24MCC-FW, E60-24MCCH-FR,
E60-24MCCH-FW, E60EXT-R and E60-EXT-W multi -candela speaker/strobes. May be
followed by suffixes to designate lens lettering and plate color. *Lens color may be Clear,
Red (R), Blue (B), Green (G), or Amber (A). EXT is an extender ring that mounts behind the
speaker. Intended for indoor use only. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: Electrical: 16-33 VDC, 25/70 VRMS
_ Flash rate: 60 Flashes/min
Candela: MCW=15cd,30cd,75cd or 110cd
MCC=15cd,30cd,75cd or 95cd
MCWH = 135cd,185cd
MCCH = 115cd,177cd
*1575 = 15 cd/75cd on axis
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction. Models followed by W or WH
are wall mounts; C or CH are ceiling mounts. All models are for indoor use.
MARKING: Listee's name, model number, electrical and candela rating, and UL label.
APPROVAL: Listed as strobe speakers suitable for the hearing impaired when used in conjunction with
separately listed electrically compatible fire alarm control units. For synchronization strobes,
Models SM-12/24 or DSM-12/24 synchronized control modules (CSFM Listing No.
7300-0785:132) must be used. Refer to manufacturer's Installation Manual for details.
NOTE: These units do not generate a temporal pattern signal. If the distinctive three -pulse Temporal
Pattern Fire Alarm Evacuation signal (for total evacuation) in accordance with NFPA 72, 2002
Edition is required, the appliance must be used with a fire alarm control unit that can
generate the temporal pattern signal.
*Rev. 07-30-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
-s° an endorsement or recommendation of the item listed. This listing should not be used to verify correct
10
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
Z1 z1= u k A q` "';4r_
.,_
Description
The Wheelock E70 Wall and E90 Ceiling Speakers and Speaker
Strobes are designed for high efficiency sound output for indoor
:: --
applications. The E product line features intelligible communications
y ..
with crisp, clear voice messages and tone signaling, ideal for mass
notification, and voice evacuation.
Providing a sleek aesthetic appearance, the Wheelock Series E
High Speaker Strobes feature dual voltage (25/70 VRMS) capability
- -.
and field selectable taps from 1/8 to 2 watts. The low profile
design incorporates a speaker mounting plate for faster and easier
Installation. Each model has a built-in level adjustment feature and an
aesthetic two (2) screw grille cover.
For visible signaling to meet the hearing impaired, the E Speaker
Strobe models incorporate the Low Current draw RSS Strobes.
Strobe options for wall mount models include 1575 or Wheelock
patented MCW multi -candela strobe with field selectable candela
settings of 15/30/75/110cd or the high intensity MCWH strobe with
••••�••• �
field selectable 135/185cd.
;�
Ceiling mount models are available in Wheelock patented MCC
multi -candela ceiling strobe with field selectable intensities
of 15/30/75/95cd or the high intensity MCCH strobe with field
selectable 115/177cd.
The strobe portion of all E Speaker Strobes may be synchronized
when used in conjunction with the Wheelock DSM Sync Modules,
.,
Wheelock Power Supplies or other manufacturers panels
incorporating the Wheelock Patented Sync Protocol. Wheelock
synchronized strobes offer an easy way to comply with ADA
recommendations concerning photosensitive epilepsy
F 1. E
The E Speaker Strobes are UL Listed for indoor use under Standard
_
1971 (Signaling Devices for the Hearing -Impaired) and Standard 1480
(Speaker Appliances). All inputs employ IN/OUT wiring terminals for
fast installation using #12 to #18 AWG wiring.
Color options for the E Speakers and Speaker Strobes are red and
white.
FAXON
Powering Business Worldwide
Technical Data TD450024EN
Effective April 2018
Features
• Intelligible Communications
• Efficient design for high intelligibility at minimum wattage
across a frequency range of 400 to 4000 HZ
• Field Selectable Settings
• Wall mount models are available with Field Selectable Candela
Settings of 15/30/75/110cd or 135/185cd (Multi -Candela models)
• Ceiling mount models are available with field selectable candela
settings of 15/30/75/95cd or 115/177cd (Multi -candela models)
• Field Selectable Taps
• 1/8 watt up to 2 watts
• 25 or 70 VRMS operation
• Easy -to -Install
• Low profile design incorporates speaker mounting plate for
faster and easier installation
• Built- in level adjustment feature and an aesthetic two (2)
screw grille cover.
• Quick installation with IN/OUT screw terminals using #12 to
#18 AWG wires
• 4" square backbox prevents wire damage
• E70 No extension ring required
• E90 Optional extender (E90 Ext) is available for mounting to 4"
square backboxes
• Strobe Synchronization Components
• Meet synchronizing standards with Wheelock's DSM Sync
Modules, Power Supplies or SAFEPATH products
• Compliance
• UL 1971, UL 1480
• California State Fire Marshal (CSFM)
• ADA/NFPA/ANSI/OSHA
• FCC Part 15, ICES
Note: Please read these specifications and associated installation instruc-
tions, before using, specifying, or installing this product. Visit Eaton.com/
mass notification for current installation instructions.
Wheelock E70 & E90
Speakers & Speaker Strobes
Drawings
Oo
00000000
p
z,
—z..e
0
° %��
oe
ovo°
oe o
°
a c... vas°oe°
00800$0
0
Figure 1. E701top) and E90 (bottom) Speakers - Front & Side Views
I'�I
Figure 2. E70 (top) and E90 (bottom) Speaker Strobes - Front & Side Views
General Notes
• Strobes are designed to flash at 1 flash per second minimum over
their "Regulated Voltage Range" Note that NFPA-72 specifies a
flash rate of 1 to 2 flashes per second and ADA Guidelines specify
a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity
based on UL 1971.
2 EATON...eatnnx.rn
Wheelock E70 & E90
Speakers & Speaker Strobes
Table 1. Maximum RIMS Current
Technical Data TD450024EN
Effective April 2018
UL Max Current (D
24MCW/24MCC 24MCWH/24MCCH
Regulated Voltage
Model Range VOC 15 30 75 95 110 115 135 177 185
E70 16.0-33.0 0.060 0.092 0.165 0.220 0.300 0.420
-90 16.0-33.0 0.065 0.105 0.189 0.249 0.300 0.420
Table 2. UL Listed Models and Ratings
UL Reverberant dBA at 10 Feet 9
1/8 watts
Model
(D
114 watts
112 watts
1 watts
2 watts
E70 Speaker
72
75
78
81
83
E90 Speaker
72
75
78
81
B2
E70 Speaker Strobe
71
75
78
81
83
E90 Speaker Strobe
74
77
80
82
85
Table 3. Specification
& Ordering
Information
Model
Order#
Strobe Candid.
Red
White
Lettering Wall C
Speakers
E70-R
9865
X
No
Lettering X
E70-W
9866
X
No
Lettering X
E90-R
9875
X
No
Lettering X
E90-W
9876
X
No
Lettering X
P, Q
P, Q
P,Q
P, (I
Syync w/ DSM or
Wheeloclr Power
Speaker Strobes
E70-24MGW-FR
0183
15/30175/110
X
FIRE
X
P, Q
X
E70-24MCW-FW
0184
15130R51110
X
FIRE
X
P,Q
X
E70-24MCW-NW
9748
15/30/75/110
X
No Lettering
X
P, Q
X
E70-24MCW-ALR
4123
15/30/75/110
X
ALERT
X
P,Q
X
E70-24MCW-ALW
4124
15/30/75/110
X
ALERT
X
P,Q
X
E70-24MCWH-FR
0185
135/165
X
FIRE
X
P, Q
X
E70-24MCWH-FW
0186
135/185
X
FIRE
X
P, Q
X
E70-24MCWH-ALW
4456
135/185
X
ALERT
X
P, Q
X
E70-24MCC-ALR
4308
15/30/75195
X
ALERT
X
P, (IX
E70-24MCC-ALW
583E
15/30/75195
X
ALERT
X
P, [IX
E70-24MCC-NW
1000
15/30/75/95
X
No Lettering
X
P, Q
X
E90-24MCC-FR
0191
15/30/75/95
X
FIRE
X
P, Q
X
E90-24MCC-FW
0192
15/30175/95
X
FIRE
X
P, Q
X
E90-24MCC-NW
3181
15/30175/95
X
No Lettering
X
P,a
X
E90-24MCC-ALW
41 B9
15/30/75/95
X
ALERT
X
P,a
X
E90-24MCC-ALR
4309
15/30/75/95
X
ALERT
X
E,, Q
X
E90-24MCCH-FR
0194
115/177
X
FIRE
X
P, Q
X
E90-24MCCH-FW
0193
115/177
X
FIRE
X
P, Q
X
E90-24MCCH-ALR
0980
115/177
X
ALERT
X
P, Q
X
E90-24MCCH-ALW
2975
115/177
X
ALERT
X
P, Q
X
E90-24MCCH-NW
2974
115/177
X
No Lettering
X
P, C.
X
i1) EMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the
UL max current is usually at the minimum listed voltage (t6v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered
FWR ratings, see installation instructions.
b dBA ratings are based on testing under UL Standard 1480,
c 1/8 watt tap is for private mode only.
Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper
Wheelock Inc., dine Eaton standard terms and conditions.
EATON mvveaton.com 3
Technical Data TD450024EN
Effective April 2018
Table 4. Specifications
Wheelock E70 & E90 Speakers & Speaker Strobes
Physical
Material Red or white textured UV stabilized, colored impregnated engineered plastic. Exceeds 94V-0 ULfIaminability rating.
Weight E70 Speaker: 1.7lbs (0.77 kg); E70 Speaker Strobe 1.8 lbs (0.82kg); E90 Speaker: 1.5lbs (0.68 kg); E90 Speaker Strobe 1.6
Ibs (0.73 ke)
Lens GE Lexan 943A
Dimensions E70 Speaker: 5.13" W x 5.13" H x 0.43"D; E70 Speaker Strobe: 5.13" W x 5.13" H x 2.56"D; E90 Speaker: 7.27" Diameter
x 0.43" D: E90 Speaker Strobe: 7.327 Diameter x2.68" D
Rneratinn Temneramre Indoor: 33.8°F to 120.2"F (0°C to 49"C) and maximum humidity of 93%
Mounting & Wire Connections
Mounting (indoor only)
4"square backbox with extension ring prevents wire damage; Sea for surface mount of E70
Wire Connections
#12 through#18 AWG
Power & General
Operating voltage
25/70 VRMS
Strobe Output Rating
UL 1971
Strobe Flash Rate
Strobes are designed to flash at 1 flash per second
Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules, Power Supplies or SAFEPATH products, using
Wheelock patented sync protocol
Franuencv Range 400 Hz to 40DO Hz
Architects and Engineers Specifications
The speaker appliances shall be Wheelock Series E70 or E90
Speakers and Speaker Strobe appliances or approved equals. The
speakers shall be UL Listed under UL 1480 for Fire Protective
Service and speakers equipped with strobes shall be listed under UL
1971 for Emergency Devices for the Hearing -Impaired. In addition,
the strobes shall be certified to meet the requirements of FCC Part
15, Class A.
All speakers shall be designed for a field selectable input of either 25
or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts.
All models shall have listed sound output of up to 87 dB at 10 feet
and a listed frequency response of 400 to 4000 Hz. The speaker shall
also incorporate a sealed back construction. All inputs shall employ
terminals that accept #12 to #18 AWG wire sizes. The strobe portion
of the appliance shall produce a flash rate of one (1) flash per second
over the Regulated Voltage Range. The strobe shall be of low current
design. Where Multi -Candela Speaker Strobes are specified, the
strobe intensity shall have field selectable settings and shall be rated
per UL 1971 at 15/30/75/110cd or 135/185cd for wall mount and
15/30/75/95cd or 115/177cd for ceiling mount. The selector switch
for selecting the candela shall be tamper resistant.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Eaton
1000 Eaton Boulevard
Cleveland, CH 44122
United States
Eatoncom
Eaton
Life safety & mass notification solutions
273 Branchport Ave.
Long Branch, NJ 07740
www.eaton.com/massnnuficahon
O 2018 Eaton
E N
All Rights Reserved
SA
�T•
Pulbl cation No TD450024EN
Powering Business Worldwide
April 2018
When synchronization is required, the strobe portion of the appliance
shall be compatible with Wheelock DSM sync modules, Wheelock
Power Supplies or other manufacturers panels incorporating the
Wheelock Patented Sync Protocol. The strobes shall not drift out of
synchronization at any time during operation. If the sync module
or Power Supply fails to operate, (i.e., contacts remain closed), the
strobe shall revert to a non -synchronized flash rate.
The speaker and speaker strobe appliances shall be designed for
indoor surface or flush mounting. The speaker and speaker strobe
shall incorporate a speaker mounting plate with a grille cover which is
secured with two screws for a level, aesthetic finish and shall mount
to standard electrical hardware requiring no additional trimplate or
adapter.
The finish of the Series E speakers and strobe speakers shall be red
or white.
All speaker and speaker strobe appliances shall be backward
compatible.
UL 1971, UL 1480, CSFM, FCC.
Eaton Is a registered trademark.
All other trademarks are property
of their respective owners.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE ``�`
LISTING No.
(712�p'f$b 0,�6@ Page 1 of 1
CATEGORY:
7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE:
Cooper Wheelock Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Thomas Conover (941) 487-2336
Email: thomaslconover@eaton.com
DESIGN:
Exceder Series: Models ST strobe HS hortt_strd*and HN horn. Model ST is a synchronous
and non -synchronous strobe light. Model HS a visual/audible appliance and Model HN is an
audible signal appliance. All units followed by R (red) or W (white). Additionally, a'C' may be
added for ceiling models and/or a'-NR' may be added for non-resettable models. For non
-NR models and optional'S' for silver fascia may be added*. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING:
Electrical: 12 VDC/24VDC/FWR
Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185
Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. All models are for indoor use
and for wall mount only or ceiling mount only*
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when
used with separately listed electrically compatible fire alarm control units. Refer to listee's
Installation Instructions Manual for details.
*Rev. 9-24-09 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
TI the test results and/or other data but does not make an independent verification of any claims. This listing is not
'.:� an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
E® M On .: 1orn tGoE' and Horn
EJ?VONotification Appliances
Description:
The Wheelock® Excedeff Series of notification appliances feature
a sleek modern design thatwill please building owners with reduced
total cost of ownership. Installers will benefit from its comprehensive
feature list, including the most candela options in one appliance,
low current draw, no tools needed for setting changes, voltage test
points, 12/24 VDC operation, universal mounting base and multiple
mounting options for both new and retrofit construction.
The Wheelocks ExcederT1" Series incorporates high reliability and
high efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe
models feature an industry first of 8 candela settings on a single
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of a tool and are located behind the appliance to prevent tampering.
Wall models feature voltage test points to take readings with a
voltage meter for troubleshooting and AHJ inspection.
The Wheelock® ExcederTm Series of wall and ceiling notification
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting
base can be pre -wired to allow full testing of circuit wiring before
the appliance is installed and the surface is finished. It comes
complete with a Contact Cover for protection against dirt, dust, paint
and damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre -wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while
it is on the UMB. When the Contact Cover is removed the circuit
will show an open until the appliance is installed. The UMB allows
for consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra
secure installation, while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
Notification
- Save up to 48% in current draw*
- Up to 9 models now in 1 appliance
- Save up to 14% cost of installation**
KO>]
Sleek Modern Aesthetics
WFinger
Slide Switches
QjVoltage
Test Points
Multiple Voltages
3 Audible Settings
90, 95, 99 dB
8 Candela Settings ***
Wall- 1511575/30/75/95/110/135/185
Ceiling - 15130/60/75/951115/150/177
'
Universal Mounting Base ***
CO)
Ceiling and Wall
Mounts to 5 Backboz Types
Environmentally Friendly
Low Current Draw
Compatibility and Requirements
'-SynchronizeusingtheWheelockSync.Modulesorpanelswithbuilt-in Wheelock* Patented Sync Protocol
Compatible with UL'Regulated Voltage" using filtered VDC or unfiltered 'VRMS.input voltage
- Strobes produce 1 flash per second over the"Regulated Voltage'range
* Compared to competitive models ***Patented
** Compared to previous models
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
General Notes:
General Notes:
• Strobes are designed to flash at 1 flashper second minimum over their "Regulated Voltage Range".
• All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
• Sense Exceder:Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32T to 1207 (0"C to 49°C) and
maximum humidity of 93%(t 2%) UL 464 (85% ILL 1971):
• series txceaer norm are anaer UL bMnoam 4b4?or aaolalesignal appliances (I no oar use only).
Low Current Draw
Strobe Ratings per UL Standard 1971
= Fewer Power Supplies
UL Max Current�
24VDC/24FWR
12VDC
Model
Regulated Voltage
Range VDC
15
15/75
30
60
75
95L0182
115
135
150
177
185
15
15/75
ST
8.0-33.0
0.057
0.070
0.085
0.135
0.163
0.205
0.253
0.110
0.140
SIT
8.0-33.0
0.061
0.085
0.103
0.135
0.163
0.182
0.205
0.253
0.110
Horn Strobe Ratings per UL 1971
& Anechoic at 24 VDC
UL
Max Current* at
24VDC
Anechoic
99 dBA
12 VDC
Model
Regulated Voltage
Range VDC
15
15/75
30
60
75
95
110
115
135
150
177
185
15
15/75
HS
8.0-33.0
0,082
0.095
0.102
0.148
0.176
0.197
0.242
0.282
0.125
0.159
KS-08.0-33.0
0.082
0.102
0.141
0.148
0.176
24VDC
0.197
0.242
0.282
0.125
12VDC
Model
Regulated Voltage
Range VDC
15
30
60
75
95
110
115
135
150
177
185
15
15/75
HS
8.0-33.0
0.073.087
J0.083
0.139
0.163
0.186
0.230
0.272
0.122HSC
8.0-33.0
0.073.087
0.128
0.139
0.163
24VDC
0.186
0.230
0.272
0.122
12 VDC
Model
Regulated Voltage
Range VDC
15
15/75
30
60
75
95
110
115
135
150
177
185
15
15/75
HS
8.0-33.0
0.065
0.075
0.084
0.136
0.157
0.184
0.226
0.267
0.120
0.148
HSC
8.0-33.0
0.065
0.084
0.120
0.136
0,157 0.184 0.226 0.267 0.120
I Iy
j
71
Horn Ratings
per ULAnechoic
Model
Regulated Voltage
Range VDC
99 dB
95 dB
90 dB
HN
16-33.0
0.064
0.044
0.022
HNC
16-33.0
0.084
0.044
0.022
HN
8.0-17.5
0.047
0.026
0.017
HNC
8.0-17.5
0.047
0.026
0.017
* UL max current rating is the maximum RMS current within the listed voltage range (16-33 VDC for 24 VDC units). Forstrobes the
UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units), For audibles the max current is usually at the '..
maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, seeinstallation instructions.
Specification & Ordering Information
Sync w/
Model
Strobe
DSM or
12/24 VDC*
Mounting
Candela
Wheelock Power
Options
Supplies
HSR
15/1575130175/95/110/135/185
X
X
UMB**
HSW
1511575/30175/95/110/135/185
X
X
UMB**
HSRC
15130/60175195/11511501177
X
X
UMB**
HSWC
15130160175/95/115/150/177
X
X
UMB**
STR
15/1575/30/75195/110/1,95/185
X
X
UMB**
STW
15/1575130/75195/110/135/185
X
X
UMB**
•
STRC
15130/60/75/95/115/150/177
X
X
UMB**
'
STWC
• 15/30/60/75/9511151150/177
X
X
UMB**
•
HNR
'
X
X
UMB**
HNW
X
X
UMB**
HNRC
„
X
X
UMB**
HNWC
X
X
UMB**
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. -
Architects and Engineers Specifications
The notification appliances shall be Wheelock' Exceder- Series HIS Audible Strobe appliances, Series ST Visual Strobe appliances
and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency
Devices for the Hearing -Impaired) for Indoor Fire Protection Service. The Series HS and HNAudibles shall be UL Listed under Standard
464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with
standard reverse polarity supervision of circuitwiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC.
Indoor wall models shall incorporate voltage test points for easy voltage inspection.
The Series HIS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated
Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design.
Where Multi -Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110,
135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with
75 candela on -axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible
location at all times when installed.
The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal
(Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single -gang, double -gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire
appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to
attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of
an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same
base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24"
H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series
HNC ceiling shall have a diameter of 6.68" x 1.50" D.
When synchronization is required, the appliance shall be compatible with Wheelock®'s DSM Sync Modules, Wheelock® Power Supplies
or other manufacturer's panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync protocol fails to operate, the strobe shall revert to a non -synchronized flash -rate and still maintain (1)
flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced
while maintaining strobe activation when used with Wheelock® synchronization protocol.
Wall Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Ceiling Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Exceder - Spec Sheet 6/11
Wheelock° M®C SAFEPATH' WAVE
Notification
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE 0
LISTING No. '7� 125,0785Q152 Page 1 of 1
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Cooper.Wheeloek nc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Thomas Conover (941) 487-2336
Email: thomaslconover@eaton.com
DESIGN: Models *ET70-241575W, ET70-24MCW, ET70-24MCC, ET70-24MCWH, ET70-24MCCH,
*ET80-241575W, ET80-24MCW, ET80-24MCWH, *ET90-241575W, ET90-24MCW,
ET90-24MCC, ET90-24MCWH, ET90-24MCCH, E70-24MCW, E70-24MCC, E70-24MCWH,
E70-24MCCH, E90-24MCW R902ZZG.C. E90-24MCWH, and E90-24MCCH multi -candela
speaker/strobes. Models E60-R, E60-W, E60-24MCC-FW, E60-24MCCH-FR,
E60-24MCCH-FW, E60EXT-R and E60-EXT-W multi -candela speaker/strobes. May be
followed by suffixes to designate lens lettering and plate color. *Lens color may be Clear,
Red (R), Blue (B), Green (G), or Amber (A). EXT is an extender ring that mounts behind the
speaker. Intended for indoor use only. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: Electrical: 16-33 VDC, 25/70 VRMS
Flash rate: 60 flashes/min
Candela: MCW=15cd,30cd,75cd or 110cd
MCC=15cd,30cd,75cd or 95cd
MCWH = 135cd,185cd
MCCH = 115cd,177cd
*1575 = 15 cd/75cd on axis
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction. Models followed by W or WH
are wall mounts, C or CH are ceiling mounts. All models are for indoor use.
MARKING: Listee's name, model number, electrical and candela rating, and UL label.
APPROVAL: Listed as strobe speakers suitable for the hearing impaired when used in conjunction with
separately listed electrically compatible fire alarm control units. For synchronization strobes,
Models SM-12/24 or DSM-12/24 synchronized control modules (CSFM Listing No.
7300-0785:132) must be used. Refer to manufacturer's Installation Manual for details.
NOTE: These units do not generate a temporal pattern signal. If the distinctive three -pulse Temporal
Pattern Fire Alarm Evacuation signal (for total evacuation) in accordance with NFPA 72, 2002
Edition is required, the appliance must be used with a fire alarm control unit that can
generate the temporal pattern signal.
`Rev. 07-30-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
a1 an endorsement or recommendation of the item listed. This listing should not be used to verify correct
" operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021 (LrstingExpires
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE 0
LISTING No. E'126,007Q5`0152 Page 1 of 1
CATEGORY: 7125 - ClF7 ALARM'DEVICES'FOR THE NEARING f gIRED�
LISTEE: Cooper Wheelock Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
DESIGN: Models *ET70-241575W, ET70-24MCW, ET70-24MCC, ET70-24MCWH, ET70-24MCCH,
*ET80-241575W, ET80-24MCW, ET80-24MCWH, *ET90-241575W, ET90-24MCW,
ET90-24MCC, ET90-24MCWH, ET90-24MCCH, E70-24MCW, E70-24MCC, E70-24MCWH,
E70-24MCCH, E90-24MCW iE90=24MCC �90-24MCWH, and E90-24MCCH multi -candela
speaker/strobes. Models E60-R, E60-W, E60-24MCC-FW, E60-24MCCH-FR,
E60-24MCCH-FW, E60EXT-R and E60-EXT-W multi -candela speaker/strobes. May be
followed by suffixes to designate lens lettering and plate color. *Lens color may be Clear,
Red (R), Blue (B), Green (G), or Amber (A). EXT is an extender ring that mounts behind the
speaker. Intended for indoor use only. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: Electrical: 16-33 VDC, 25/70 VRMS
Flash rate: 60 flashes/min
Candela: MCW=15cd,30cd,75cd or 110cd
MCC=15cd,30cd,75cd or 95cd
MCWH = 135cd,185cd
MCCH = 115cd,177cd
*1575 = 15 cd/75cd on axis
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction. Models followed by W or WH
are wall mounts; C or CH are ceiling mounts. All models are for indoor use.
MARKING: Listee's name, model number, electrical and candela rating, and UL label.
APPROVAL: Listed as strobe speakers suitable for the hearing impaired when used in conjunction with
separately listed electrically compatible fire alarm control units. For synchronization strobes,
Models SM-12/24 or DSM-12/24 synchronized control modules (CSFM Listing No.
7300-0785:132) must be used. Refer to manufacturer's Installation Manual for details.
NOTE: These units do not generate a temporal pattern signal. If the distinctive three -pulse Temporal
Pattern Fire Alarm Evacuation signal (for total evacuation) in accordance with NFPA 72, 2002
Edition is required, the appliance must be used with a fire alarm control unit that can
generate the temporal pattern signal.
*Rev. 07-30-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering
staff has reviewed
the test results and/or other data but does not
make an independent verification of any claims.
This listing is not
it
an endorsement or recommendation of the
item listed. This listing should not be used
to verify correct
operational requirements or installation criteria.
Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 cLlsting EXpire June 3Q, 2021�
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
YCc
Speakers
Description
The Wheelock E70Wall and E90 Ceiling Speakers and Speaker
Strobes are designed for high efficiency sound output for indoor
applications. The E product line features Intelligible communications
with crisp, clear voice messages and tone signaling, ideal for mass
notification, and voice evacuation.
Providing a sleek aesthetic appearance, the Wheelock Series E
High Speaker Strobes feature dual voltage (25170 VRMS) capability
and field selectable taps from 1/8 to 2 watts. The low profile
design incorporates a speaker mounting plate for faster and easier
installation. Each model has a built-in level adjustment feature and an
aesthetic two (2) screw grille cover.
For visible signaling to meet the hearing impaired, the E Speaker
Strobe models Incorporate the Low Current draw RSS Strobes.
Strobe options for wall mount models Include 1575 or Wheelock
patented MCW multi -candela strobe with field selectable candela
settings of 15/30/75/110cd or the high intensity MCWH strobe with
field selectable 135/185cd.
Ceiling mount models are available In Wheelock patented MCC
multi -candela ceiling strobe with field selectable Intensities
of 15/30/75/95cd or the high intensity MCCH strobe with field
selectable 115/177cd.
_. - --
The strobe portion of all E Speaker Strobes may be synchronized
when used in conjunction with the Wheelock DSM Sync Modules,
Wheelock Power Supplies or other manufacturers panels
Incorporating the Wheelock Patented Sync Protocol. Wheelock
synchronized strobes offer an easy way to comply with ADA
_
recommendations concerning photosensitive epilepsy
F 'I R E
The E Speaker Strobes are UL Listed for indoor use under Standard
fi d• - I
1971 (Signaling Devices for the Hearing -Impaired) and Standard 1480
(Speaker Appliances). All Inputs employ IN/OUT wiring terminals for
fast installation using #12 to #18 AWG wiring.
Color options for the E Speakers and Speaker Strobes are red and
white.
E:T• N
Powering Business Worldwide
Technical Data TD450024EN
Effective April 2018
Features
• Intelligible Communications
• Efficient design for high Intelligibility at minimum wattage
across a frequency range of 400 to 4000 HZ
• Field Selectable Settings
Wall mount models are available with Field Selectable Candela
Settings of 15/30/75/110cd or 135/185cd (Multi -Candela models)
Ceiling mount models are available with field selectable candela
settings of 15/30/75/95cd or 115/177cd (Multi -candela models)
• Field Selectable Taps
• 1/8 watt up to 2 watts
• 25 or 70 VRMS operation
• Easy -to -Install
• Low profile design incorporates speaker mounting plate for
faster and easier installation
• Built- in level adjustment feature and an aesthetic two (2)
screw grille cover.
• Quick installation with IN/OUT screw terminals using 412 to
#18 AWG wires
• 4" square backbox prevents wire damage
• E70 No extension ring required
• E90 Optional extender (E90 Ext) is available for mounting to 4"
square backboxes
• Strobe Synchronization Components
• Meet synchronizing standards with Wheelock's DSM Sync
Modules, Power Supplies or SAFEPATH products
• Compliance
• UL 1971, UL 1480
• California State Fire Marshal (CSFM)
• ADA/NFPA/ANSI/OSHA
• FCC Part 15, ICES
Note: Please read these specifications and associated installation instruc-
tions, before using, specifying, or installing this product. Visit Eaton.com/
massnonfication for current installation instructions.
Wheelock E70 & E90
Speakers & Speaker Strobes
Drawings
Figure 1. E70 (top) and E90 (bottom) Speakers - Front & Side Views
0020000202
10,100,111,
Figure 2. E70 (top) and E90 (bottom) Speaker Strobes - Front & Side Views
General Notes
• Strobes are designed to flash at 1 flash per second minimum over
their "Regulated Voltage Range" Note that NFPA-72 specifies a
flash rate of 1 to 2 flashes per second and ADA Guidelines specify
a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe Intensity
based on UL 1971.
EATON www.nt.r....
Wheelock E70 & E90
Speakers & Speaker Strobes
Table 1. Maximum RMS Current
UL Max Current n
24MCW/24MCC
24MCWH/24MCCH
Technical Data TD450024EN
Effective April 2018
Regulated Voltage
Model Range VOC 15 30 75 95 110 t15 t35 177 185
E70 16.0-33.0 0.060 0.092 0.165 0.220 0.300 0.420
R9. 16.0-33.0 0.065 0.105 0.189 0.249 0.300 0.420
Table 2. UL Listed Models and Ratings
UL Reverberant dBA at 10 Feet 0
1/8 watts
Model Oa 114 watts 112 wet
E90 Speaker 72 75 78 81 82
E70 Speaker Strobe 71 75 78 81 83
E90 Speaker Strobe 74 77 80 82 85
Table 3. Specification & Ordering Information
Mounting Sync w/ OSM or
Model
Order #
Strobe Candela Red
White
Lettering
Wall
Ceiling
Options Wheelock Power Supplies
Speakers
E70-R
9B65
X
No Lettering
X
P, Cl
E70-W
986B
X
No Lettering
X
P, Q
E90-R
9875
X
No Lettering
X
P, Q
E90-W
9876
X
No Lettering
X
P, Q
Speaker Strobes
E70-24MCW-FR
E70-24MCW-FW
E70-24MCW-NW
E70-24MCW-ALR
E70-24MCW-ALW
E70-24MCWH-FR
E70-24MCWH-FW
E70-24MCWH-ALW
E70-24MCC-ALR
E70-24MCC-ALW
E70-24MCC-NW
E90-24MCC-FR
E90-24MCC-FW
E90-24MCC-NW
E90-24MCC-ALW
E90-24MCC-ALR
E90-24MCCH-FR
E90-24MCCH-FW
E90-24MCCH-ALR
E90-24MCCH-ALW
E90-24MCCH-NW
0183
0164
9748
4123
4124
0185
018B
4456
4308
5838
1000
0191
0192
3181
4189
4309
0194
0193
0980
2975
2974
X
FIRE
X
P, Q X
X
FIRE
X
P, Q X
X
No Lettering
X
P, Q X
X
ALERT
X
P, Q X
X
ALERT
X
P, Q X
X
FIRE
X
P, Q X
X
FIRE
X
P, Q X
X
ALERT
X
P, Q X
X
ALERT
X
P, Q X
X
ALERT
X
P, Q X
X
No Lettering
X
P, Q X
X
FIRE
X
P,Q X
X
FIRE
X
p,a X
X
No Lettering
X
P, Q X
X
ALERT
X
P, Q X
X
ALERT
X
P, Q X
X
FIRE
X
P, Q X
X
FIRE
X
P, Q X
X
ALERT
X
P, Q X
X
ALERT
X
P, ❑ X
X
No Lettering
X
P, Q X
iD RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the
UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered
FWR ratings, see installation instructions.
b dBA ratings are based on testing under UL Standard 1480.
c 1/8 watt tap is for private mode only.
Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper
Wheelock Inc., dba Eaton standard terms and conditions.
EATON...eatonauur 3
Technical Data TD450024EN
Effective April 2016
Table 4. Specifications
Wheelock E70 & E90 Speakers & Speaker Strobes
Physical
Material Red or white textured UV stabilized, colored impregnated engineered plastic. Exceeds 94V-0 UL flammability rating.
Weight E70 Speaker: 1.7 Ibs (0.77 kg); E70 Speaker Strobe 1.8Its (0.82kg); E90 Speaker: 1.5 ins (0.68 kgi E90 Speaker Strobe 1.6
Lens GE Lexan 943A
Dimensions E70 Speaker: 5.13" W x 5.13" H x 0.43"D; E70 Speaker Strobe: 5.13" W x 5.13" H x 2.56" D; E90 Speaker: 7.27" Diameter
x 0.43" D; E90 Speaker Strobe: 7.327 Diameter x 2.68" D
Operating Temperature Indoor: 33.8°F to 1207F (0°C to 49°C) and maximum humidity of 93%
Mounting & Wire Connections
Mounting (indoor only)
4"square backbox with extension ring prevents wire damage; SEE for surface mount of E70
Wire Connections
#12through#18 AWG
Power & General
Operating voltage
25/70 VRMS
Strobe Output Rating
UL 1971
Strobe Flash Rate
Strobes are designed to flash at 1 flash per second
Synchronization Models
Strobes can be synchronized with Wheelock's DSM Sync Modules, Power Supplies or SAFEPATH products, using
Wheelock patented sync protocol
Frequency Range 400 Hz to 4000 Hz
Architects and Engineers Specifications
The speaker appliances shall be Wheelock Series E70 or E90
Speakers and Speaker Strobe appliances or approved equals. The
speakers shall be UL Listed under UL 1480 for Fire Protective
Service and speakers equipped with strobes shall be listed under UL
1971 for Emergency Devices for the Hearing -Impaired. In addition,
the strobes shall be certified to meet the requirements of FCC Part
15, Class A.
All speakers shall be designed for a field selectable input of either 25
or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts.
All models shall have listed sound output of up to 87 d8 at 10 feet
and a listed frequency response of 400 to 4000 Hz. The speaker shall
also incorporate a sealed back construction. All inputs shall employ
terminals that accept #12 to #18 AWG wire sizes. The strobe portion
of the appliance shall produce a flash rate of one (1) flash per second
over the Regulated Voltage Range. The strobe shall be of low current
design. Where Multi -Candela Speaker Strobes are specified, the
strobe intensity shall have field selectable settings and shall be rated
per UL 1971 at 15/30/75/1 Iced or 135/185cd for wall mount and
15/30/75/95cd or 115/177cd for ceiling mount. The selector switch
for selecting the candela shall be tamper resistant.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton
Life safety & mass notification solutions
273 Branchi Ave.
Long Branch, NJ 07740
vvvvvveafton.com/maseratification
O 2018 Eaton
All
ights Reserved
Pried is USA
FAT, N Publiation No. TD450024EN
Powering Business Wmlolvide April 201E
When synchronization is required, the strobe portion of the appliance
shall be compatible with Wheelock DSM sync modules, Wheelock
Power Supplies or other manufacturers panels incorporating the
Wheelock Patented Sync Protocol. The strobes shall not drift out of
synchronization at any time during operation. If the sync module
or Power Supply fails to operate, (i.e., contacts remain closed), the
strobe shall revert to a non -synchronized flash rate.
The speaker and speaker strobe appliances shall be designed for
indoor surface or flush mounting. The speaker and speaker strobe
shall incorporate a speaker mounting plate with a grille cover which is
secured with two screws for a level, aesthetic finish and shall mount
to standard electrical hardware requiring no additional trimplate or
adapter.
The finish of the Series E speakers and strobe speakers shall be red
or white.
All speaker and speaker strobe appliances shall be backward
compatible.
UL 1971, UL 1480, CSFM, FCC.
Eaton is a registered trademark.
All othaltrad.m.to are property
of their respective owners.