Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
Eric Werner Residence BUILDING DIVISION �OQROFESS/O
1720 Kings Rd., y o
Newport Beach, CA 92663 04/11/2022 W No. C587za
* Exp. 3-31-23
Applicable Codes Bv:v.r. �oFcn��F���\P
2019 California Building Code, 2019 California Electric Code,
2019 California Mechanical Code, American Society of Civil Engineers
Standard ASCE 7-16 Minimum Design Loads for Buildings and Other
Structures, American Wood Council 2018 National Design Specification
for Wood Construction, Local Municipal Code, and all other codes which
are adopted by reference or enacted by law.
Assumed Design Parameters:
The -existing -structure has been -built under a building permit and is in its
original condition. The existing roof structure is capable of its code
required live load and the ability of the roof structure to support live loads
has not been substantially reduced by the age of the structure, termites or
mold, or unauthorized modifications to the existing structure. Solar Energy
Contractor shall make an inspection of the existing roof framing system
prior to installation of the roof mounted solar energy system to verify that
the existing roof is capable of supporting minimum roof live loads.
Assumed Design Parameters:
All 2x members are grade Douglas Fir #2 or better
All 4X members are grade Douglas Fir #1 or better
All Roof Connectors are Simpson Strong -Tie or Equal
All Concrete Foundations are fc = 2500 psi or stronger
Original Structure was built to the Type-V Wood Framed Standards
of the Applicable Building Code at the time of Construction.
Sht # 1 of 7
2022-1611 Effect Energy Eric Werner Residence Date: April 7, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Note to Building Official:
Based upon a review of the proposed plans and information, the
existing roof framing system is capable of safely supporting the additional
loads caused by the new solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permited
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the roof
members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
Check Existinq 2x14 Roof Rafters (cD_ 24" O.C.: * °
d No. C58724
( Assume max rafter span = 13.5 ft. )
* Exp.3-31-23
W DL+LL
yrFOFCpL �Q.\
w DL+LL = 30 psf x 2 ft. = 60 plf 9
R1
Total load on rafter = 60 pif x 13.5 ft. = 810 Ibs
*Note: Contractor to Field Verify Framing
9
13.5' R2
Sht # 2 of 7
2022-1611 Effect Energy Eric Werner Residence Date: April 7, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check Existinq 2x14 Roof Rafters A- 24" O.C.:
P P P P
wWL LLb b6 6®
9 1
W DL+LL = 30 psf x 2 ft. = 60 plf R1 R2
13.5'
12' 1.5'
Total load on rafter = 60 pif x 1.5 ft + 28 plf x 12 ft + ( 6' x Tx 3 psf x 4 )
= 642 Ibs < 810 Ibs OK
Check attachment of Support to Existing Structure for Wind Uplift
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16 WIND LOADS ON BUILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE - ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
"FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH."
EFFECTIVE AREA = 15 SQ FT
No. C58724
Exp. 3.31-23
Sht # 3 of 7
2022-1611 Effect Energy Eric Werner Residence Date: April 7, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email:loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Tributary Area to Each Solar Mount = 6 ft. x 3 ft. = 18 sq. ft. ( Max )
Calculate Design Wind Pressure at each support (Wind Speed 130 mph Exposure C):
p = qh (GCP) (YE) (Ya)
qh = 0.00256KZKZtKdKe r
Eq'n 29.4-7 ASCE 7-16
Eq'n 26.10-1 ASCE 7-16
Note:
KZ = velocity pressure coefficient Section 29.10.1 ASCE 7-16
KZ = 0.9 (Exposure C, Height = 20 ft or less)
Kzt = Topographical Factor = 1.0
Kd = Wind Directionality Factor = 0.85
Ke = Ground Elevation Factor = 1.0
V = 130mph; VASB= 101 mph Table 1609.3.1 2019 CBC
qh = 0.00256 (0.9) (1.0) (0.85) (1.0) (101)'
qh = 20 psf
GCp = -2.0 (Zone 2 ; Effective Area = 15 sq. ft. )
YE = Exposure Factor = 1.5
Ya = Solar Array Pressure Equalization Factor = 0.7
p = qh (GC,) (YE) (Ya )
p = 20 psf (-2.0) (1.5) (0.7) = 42 psf
No. C58724
Exp. 3.31-23
Fig. 29.4-8 ASCE 7-16
Nominal (Unfactored) Uplift at each support = 42 psf x 18 sq. ft. = 756 Ibs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for Allowable Stress
Design. Note: Applicable Load Combination #5 (D + 0.6W)
Design (Factored) Uplift at each support = 0.6 x 756 Ibs = 454 Ibs
Load per lag screw = 454 Ibs / 1 = 454 Ibs
Sht#4 of 7
2022-1611 Effect Energy Eric Werner Residence Date: April 7, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email:loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Determine allowable load per 5/16" lag screw w/ 2.5" embedment into wood below
according to the 2018 NDS.
W ' = W x Cd x Ct Table 10.3.1 2018 NDS
where:
W = 266 Ibs / in. of embedment per Table 12.2a
Cd = 1.6 per Table 2.3.2 of 2018 NDS
Ct = 1.0 per Table 10.3.4 of 2018 NDS
W' = 266 Ibs/ in. x 2.5 in. x 1.6 x 1.0 = 1,064 Ibs > 454 Ibs OK
Use Support connected to 2x Min. Roof Member
w/ (1) 5/16" x 3.5" lag screws per connection minimum.
24
ll*� Exp.3-31723
Sht # 5 of 7
2022-1611 Effect Energy Eric Werner Residence Date: April 7, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check Seismic load due to added dead load of photovoltaic system.
Determine Seismic Weight of Existing Building:
Effective Existing Seismic Weight
Area of (E) Building = Approximately 1,700 sq. ft.
Approximate
Effective = 1,700 sq. ft. x 30 psf ave. = 51,000 LBS
Seismic Weight
DETERMINE BASE SHEAR CtExp.
V = Cs W EQ'N 12.8-1 ASCE 7-16 SDs Cs = EQ N 12.8-2 ASCE 7-16 le
R
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R = 6.5 WOOD SHEAR WALLS
le = 1.0 IMPORTANCE FACTOR
SDs = 2/3 x SMs EQ'N 11.4-3 ASCE 7-16
SMs= FA x Ss EQ'N 11.4-1 ASCE 7-16
SMs= 1.2x1.5=1.8
SDs = 2/3 x 1.8 = 1.2
1.2
Cs = f 6.5] = 0.185
L1
EQ'N 12.8-2 ASCE 7-16
Sht # 6 of 7
2022-1611 Effect Energy Eric Werner Residence Date: April 7, 2022
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email:loydwmartin@gmail.com www.loydwmartin.com
EXISTING BASE SHEAR
V = 0.185 x 51,000 LBS = 9,435 LBS EQ'N 12.8-1 ASCE 7-16
DETERMINE NEW BASE SHEAR
Determine Seismic Weight of Building with Solar Array: w.
� o
EXISTING E2 No. C58724
SEISMIC = 51,000 LBS * Exp.3-31-23
WEIGHT
NEW SOLAR
ARRAY = 3 PSF x 40 PANELS x 3.3' x 6' = 2,376 LBS
NEW
SEISMIC = 51,000 LBS + 2,376 LBS = 53,376 LBS
WEIGHT
THEREFORE NEW BASE SHEAR:
V = 0.185 x 53,376 LBS = 9,875 LBS EQ'N 12.8-1 ASCE 7-16
% CHANGE = 9,875 LBS - 9,435 LBS x 100 % = 4.7 % < 10% OK
9,435 LBS
OK. PER ASCE 7-16 SECTION 11.13.3 ALTERATIONS
EXISTING LATERAL FORCE RESISTING SYSTEM IS EXEMPT
FROM ANALYSIS SINCE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXISTING SEISMIC FORCE.
'Alterations are permitted to be made to any structure without requiring the
existing structure to comply with this standard provided the alterations comply
with the requirements for a new structure. Alterations that increase the
seismic force in any existing structural element by more than 10 percent or
decrease the design strength of any existing structural element to resist
seismic forces by more than 10 percent shall not be permitted unless the
entire seismic force -resisting system is determined to comply with this
standard fora new structure."
End of Calculations
Sht # 7 of 7