Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
1200 ESSEX LN
NEWPORT BEACH, CA 92660
Job: TAYLOR, JOSH
Prepared For:
ENLIGHTENED SOLAR
2377 S EL CAMINO REAL
#200
SAN CLEMENTE CA 92672
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16
2 - Wind: 110 MPH, Exposure: B
3 - Wood Species: DF-L No. 2 (SG = 0.5 )
Notice: Use restrictions of these calculations.
- The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
IV 1�
1-844-PV ELITE I info@yoursolarplans.com
3000 E. Birch Street Suite 2011 Brea CA 92821
BUILDING DIVISION
Dec 01 2021
11/24/21, 3:15 PM
JftTC Hazards by Location
Search Information
Address:
Coordinates:
Elevation:
Timestamp:
Hazard Type:
ASCE 7-16
1200 Essex Ln, Newport Beach, CA 92660,
USA
33.6261673,-117.9003897
88 It
2021-11-24T23:15:36.157Z
Wind
ASCE 7-10
ATC Hazards by Location
MR110-Year ._.._..___--____
66 mph
MRI10-Year ------ .._-___-
72 mph
MRI25-Year -------------------
71 mph
MRI25-Year ---------------
79 mph
MRI50-Year -------------------
77 mph
MR150-Year _______----
85 mph
MRI100-Year__.------------
-_- 81 mph
MR1100-Year .__._:__-____
91 mph
Risk Category I ---- -..--- -... 89 mph
Risk Category II -____-_- ___ 95 mph
Risk Category III _--_-..--- 102 mph
Risk CategoryIV ----- -------- 106 mph
Risk Category I ___..__--..- 100 mph
Risk Categoryll ______ 110 mph
Risk Category III -IV .--.--- 115 mph
ASCE 7-05
ASCE 7-05 Wind Speed ---- __ 85 mph
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building
code adoption process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction before
proceeding with design.
Disclaimer
Hazard loads are interpolated from data provided in ASCE 7 and rounded up to the nearest whole integer. Per ASCE 7, islands and coastal
- - - areas outside the last contour should use the last wind speed contour of the coastal area — in some cases, this website will extrapolate past
the last wind speed contour and therefore, provide a wind speed that is slightly higher. NOTE: For queries near wind-borne debris region
boundaries, the resulting determination is sensitive to rounding which may affect whether or not it is considered to be within a wind-borne
debris region.
Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility
or liability for its accuracy. The material presented in the report should not be used or relied upon for any specific application without
competent examination and verification of its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does
not intend that the use of this information replace the sound judgment of such competent professionals, having experience and knowledge
in the field of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the results of the
report provided by this website. Users of the information from this website assume all liability arising from such use. Use of the output of
this wehsite dnes not imnly annroval by the onvernina buildina code bodies resnnnsihle for huildino ande annroval and internretatinn for the
https:/Ihazards.atcouncil.org/#/wind?lat=33.6261673&ing=-117.9003897&address=l200 Essex Ln%2C Newport Beach%2C CA 92660%2C USA 112
ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes.
Roof Slope
0
= 31 °
Roof Shape
Gable
Tributary Width
s
= 5.33 ft
Tributary Length
I
= 2.88 It
Effective Area
AE
= 15.32 ft2
Height of Structure
h
= 25 ft
Wind Speed
V
= 110 mph
Exposure Category
B
Building Width
B
= 33 ft
- Building Length
L
= 78 ft
Zone Width
a
= 3.3 ft
- Elevation Height
z9
= 88 ft
- - Wind Directionality
Kd
= 0.85
- -" Topography Factor
Kl
= 1.00
Ground Elevation Factor
KE
= 1.00 -
Velocity Pressure Exposure Coefficient
K�
= 0.70
_- - - -- - -- - Velocity Pressure
q� = 0.00256K�K�lK,KEV2 =
18.39 psf
Solar Array Pressure Equalization
Y. =
0.78
Array Edge Factor
YE =
1.50
_..
Zone
GCp
p=q.(GC )f
3
-
-
-
3r
1.97
-42.23
-
3e
3.10
-66.41
2
2r
1.74
-37.28
2e
_....
2n
1.97
42.23
1
1'
rowmo.
OA4r!'�,Mmly Wb.N wlnrmug4r.M1Nbau 4n®°I
u•Jmun+al0@9mAl(mminMet•+bgtle M#Jirru°rIJ14rteJUW (p[IRwI� N#t1�
Icweq°reMttlJart•.
9.IMLmYtlmeum JhYw°I�veawN1em°Wm mr WlJlm•b�•.Nrt b).
LeJLWOW
B.AgIeMpYrcJM6wn Rural b Oapm
FibmIRP Cxflkpnb
O w
N .r
j -
Tr
pp
99
P
PI'
I
IIOYM.0
110r
m 41•V WN/u9t•(e )®A
A.
p.IM1rcnWW.IRP'Prl^n.
I. Vm4°Icwh°m1IX%i) �°RmN.4pp�.
xlwm.JamaNm.rtaaR.wm�wmlwA
an. mfmlm°Jw•Iwlhwa...+nlelle.w.a...t u.. m.rePnnery.
a kxpm�m. Cr. wpaONpsf (m w:ecplee.ma0%PRr•m+'>d
rllarINaeRsy4ukryumemmVtw •peraNbrnwraer.
tl tsa6nmvJtiveeumJUY W14Y'M WY LY mS °r.MnYYm®n.N We
M° P°vrmc oLLUY h menwN Mm IR mrFle NR rt Ne
°m W.1°�
PPFE]pY3Odq°�n#�NpmiFwniwtlp311A mApw RwwrOeMYn4(Ogl,gfn[4W NP°WM
6°WUY WCpr-OWYPmX. YI'.YYN
1
of
w
5
� aY
0.i
t Io tW 1
EMeedve Wlntl Area, A,M
FlWPEtH.HSdYr Pertl Pmau° Epe9vWn h[be.tr. lu EzbaO W
LAG SCREW ANALYSIS
Loads
Wind Pressures
-42.23 psf
Solar Panel Load
QD
= 3 psf
Panel Length
1
= 5.750 ft
Panel Width
b
3.4167 ft
Attachment Spacing
s
= 5.33 ft
Portrait
Tributary Area
A,
= 15.32 ft2
- -
Wind Load
Pw = q� * A,
_ -647 lbs
Dead Load
PD = OD * A,
= 45.971 Ibs
Uplift
Pa=0.6 PD+0.6 Pv,
_ -361 lbs
Landscape
-- - --
Tributary Area
A, = b' s
= 9.1054 ft2
-
Wind Load
Pw=q=*A,
_ -384 lbs
Dead Load
PD = QD ` A4
= 27.316 lbs
-- - -- --.
Uplift
P. = 0.6 PD + 0.6 Pw
= -214 lbs
Lag Screw
Specific Gravity of Lumber
SG
= 0.50 (Douglas Fir -Larch)
-
Diameter of Lag Screw
D
= 5/16 in
Withdraw Design /in
1800•SGw� D"4
= 266 lbs/in
- -.
Depth of Embedment
Ip
= 2.50 in
Total Nominal Withdrawal Value
W =W ` I p
665 Ibs
Load Duration Factor
CD
= 1.6
�. -- ------ -
Withdrawal Design Value
W' = W' CD
= 1064 Ibs
Demand Capacity Ratio
DCR = Pa / W'
= 0.34 < 1 OK
ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check
Roof Slope
0
= 31 '
Roof Shape
Gable
Tributary Width
s
= 1.33 ft
Tributary Length
L
= 16.00 ft
Effective Area
A = L ( MAX [ s , L/3])
= 85 ft,
Height of Structure
h
= 25 ft
Wind Speed
V
= 110 mph
Exposure Category
B
Building Width
B
= 33 ft
Building Length
L
= 78 ft
Zone Width
a
= 3.3 ft
- Elevation Height
Z9
= 88 ft
Wind Directionality
Kd
= 0.85
-- Topography Factor
K,
= 1.00
Ground Elevation Factor
Kb
= 1.00
Velocity Pressure Exposure Coefficient
K�
= 0.70
- -- Velocity Pressure
qz= 0.00256K�KnKtlKeV2
= 18.39 psf
-..... Internal Pressure Coefficient
(GCpi) =
-0.18
Zone
GCp
p = q, [(GC) - (Gcpi)]
3
3r
1.60
-32.79
3e
2.58
-50.84
2
2r
0.96
-21.02
2e
-
-
2n
1.60
-32.79
1
_
_
ICI mml ��
xebn,,,
bnnbYObbamwYAA.IIM'erlr,pYlenbewkwNnaJMrp W yayypyyy
e•aNm011e
3p(4omx VnamWrnuu,Yearyr eaaurYW hinwmlm,pw{k dF�Jlb
MvvYuinmMruW bavq,eYedFNu�xe WIIallxbYnYamAnrNUM1n
e.iaabwumwma mYbb�.wmYn.nam..mxbnra.
A• ks b(bpa.NV lm�
•ne1kY Wn %mtOmbnvnY k Rp¢r.
6brv)VrtqureCw/(xbnb
y J 0 0
i 1
xo,Y I uJl F-F L:
b
r�wMi lbiYw AM qv 4YM YT
1 R1WM1r(4� F�VnMNJgM1IU�I
Nxln
•Yiuk
21ir- J;q eRxlD,e•W bM1titfx(p),
JW m•W v,mY,mm
erw�. "`r
ix wl��lJ'elr.mrw.we.brww..we,a��m.
�. vYnWlrurlbn,r„�n..m,NJ.xFn.am.ma.k.l wm
�Nnvnw.Ibe�.nb,wmaJl�mm�lbbueNvm nY�enia�A..mw
�
J'.t•Y.�...,,.NJNmno.x
Nn�mm.sbF WN.nw�.
4WI[AfIDOgemb NClwlp�M1'yntl�4�aq n�•4nb, (OCrAb Nebu]NIMWM
bNwr••M1SbWMYr4
Beam/Top Chard Check Lumbar: DF-L No.2
# of Attachment per Rafter NA= 4 Span: 1 2 3 4 Eave
Lenght(ft): 15.00 0.00 0.00 0.00 1.00
Dead Load
Roof Material: Id. Shlni Qp= 10.00
psi
Live Load
0,= 20
psi
Wind Load
p= -32.79
psi
Snow Load
Qs = 0.00
psf
Rafter Spacing
s= 16
in
Wind Load, Portrait Portrait UL=
Wind Load, Landscape Landscape Uw=
AT(fts)
I P.(lb.)
I P..(Ibs)
Pc(Ibs)
15.324
9.1054
45.971
27.318
.503
.299
0
0
Linear Dead Load wa = 13.3 plf
- Live Load wLr= 26.7 pit Start
0
it Start
14.60 ft
- End
3
It End
16.00 it
Snow Load we= 0 plf Start
0
ft Start
14.50 ft
End
3
It End
16.00 It
M„ Moment
D
787 lb-ft
D+Lr
825 lb-ft
D+S
787 lb-ft
0.6D+0.6W -
2266 lb-ft
D+0.45W+0.75Lr
1266 lb-ft
2500.0
2000.0
1500.0
1000.0
500.0
00
Orientation
j
I i(ft)
I pd�llhsi
p„,,Ilbs
p,0bs)
Portrait
1
2
3.7
8.0
46.0
46.0
-503
-503
Portrait
3
4
9.5
13.8
46.0
46.0
-503
S03
D+0.45W+0.75S 1266 lb-ft M(x)=Rr(x-LI)-P x-1 wexa
/�- 2
Moment Capacity Framing MemberSize 2X10 Lumber Grade: DF-L No.2
CM=1 Ct=1 Cr= 1.15 Cr= 1.1 fb= 900 psi ON= 1.0 C,=1
Breadth b= 1.50 in
Depth d = 9.25 in
-- Section Modulus S,=bd2/6= 21A in'
Bending Stress Capacity Fb= CM' Ct' Cr' Cs `fb= 1139 psi Table 4.3.1 NDS 2015
Co
F,'=Cc'F
ASO Load
M,/S,
DCR
0.9
1025 psi
D
442 psi
1 OA3
O KAY
1.25
1423 psi
D+Lr
463 psi
0.33
OKAY
1.15
1309 psi
D+S
442 psi
0.34
OKAY
1.6
1822 psi
0.6D+0.6W
1271 psi
0.70
OKAY
1.6
1822 psi
+0.45W+0.75L
710 psi
0.39
OKAV
1.6
1822 psi
D+0.45W+0.755
770 psi
0.39
OKAY
Deflection Limit
E = 1600 ksi I =
98.93 in°
Transient Deflection
0.459 in
Transient Deflection Allowed
392 >
180
[OKAY]
Total Deflection
0.539 in
Total Deflection Allowed
334 >
120
[OKAY]
EISMIC WEIGHT COMPARISON / ANALYSIS -(PER CEBC.2019 Part 10 Chapter 5 Section 502.5)
PV
Module Model
Hanwha
Panel Weight
Wpanel = 44 Ibs
Number of Panels
Npv = 20
Total PV System Weight
_ Wev =. Wpanel * NPv = 880 Ibs
--. Roof Weight
- Qo =
10.0 psf
Building Length
Lbund =
78 It
Building Width
Wbuiid =
33 t
Roof Area
Abuild =
2574 f
Building Perimeter
Pbuild =
222 It
Wall Height
h, =
8 It
-. Wall weight
Qwan =
15 psf
- Interior wall weight
Qint =
10 psf
Roof Load
Wnoor = Abuild * Qn =
25740 Ibs
Wall Load Nwall
= h, /2 * Qwali * Pbuild + Abuild * Clint /% =
26190 Ibs
"Total Story Weight
Wbuim = Wewr+ Wwall =
51930 Ibs
Percentage Weight Increase WPy / Wbulld = 1.69% < 10% OKAY
SOLAR IS
CONCENTRATED
ON LOCAL AREA.
CHECK ROOF ON
WHERE SOLAR
PANELS ARE.