Loading...
HomeMy WebLinkAboutPV2022-160 - Calcs5/27/2022 �I h are, D►- ours®l r � lons... P ENGINEERING SOLUTIONS F 10R ALL YOUR SOLAR NEEDS Structural Calcc�3ations for SOLAR POWER SYSTEM CO=%INECTION CHECK AT: 3710 SEASHOR7E-- DRIVE NEWPORT BEACEK:L, CA 92663 Job: RANGER, ROBERT Prepared For: GROUNDED ELECTRIC, INC. P.O. BOX 73548 SAN CLEMENTE, CA 92673 (949)370-8766 Design Criteria 1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16 2 - Wind: 95 MPH, Exposure: D 3 - Wood Species: DF-L No. 2 (SG = 0.5 ) Notice: Use restrictions of these calculations. The attached Calculations are valid only when bearing original signam� xc hereon. Contractor/Client to verify existing dimensions/conditions prior to corzstmction & solar racking is installed per manufacturer span requirements. The use of these calculations is solely intended for the above mentioned project. �y�Q�;tJG T RCi No, C70784 1-844-PV ELITE I info@yoj�rsolarplans.com 3000 E. Birch Street Suite 201 l Brea CA 92821 /5/27/22, 8:19 AM p ITC Hazards by Location i Search Information Address: 3710 Seashore Dr, Newport Beach, CA 92663, USA Coordinates: 33.6171855,-117.9359986 Elevation: 12 ft Timestamp: 2022-05-27T15:19:28.468Z Hazard Type: Wind ATC Hazards by Location ASCE 7-16 ASCE 7-10 MRI 10-Year 66 mph - - MR1 10-Year 72 mph MRI25-Year _---- 71. mph MR150-Year ,__......... .. 76 mph MRI100-Year.------------------ 81 mph Risk Category I __.__- ------ 89 mph Risk Category 11-...._........____-._ 95 mph RiskCategorylll ...__. ..... . 102 mph Risk CategoryIV ........ ..------ 106 mph MRI25-Year _._..__------- 79 mph MRI50-Year _.._..__.____.. 85 mph MRI100-Year _---- .------- 91 mph Risk Category I _....__..._._ 100 mph Risk Category11 ........__. 110 mph Risk Category III -IV .._.__... 115 mph ASCE 7-05 ASCE 7-05 Wind Speed 85 mph The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building code adoption process. Users should confirm anyoutput obtained from this tool with the local Authority Having Jurisdiction before Proceeding with design. Disclaimer Hazard loads are interpolated from data provided in ASCE 7 and rounded up to the nearest whole integer. Per ASCE 7, islands and coastal areas outside the. last contour should use thelast wind speed contour of the coastal area — in some cases, this website will extrapolate past the last wind speed contour and therefore, provide a wind speed that is slightly higher. NOTE: For queries near wind-borne debris region boundaries, the resulting determination is sensitive to rounding which may affect whether or not it is considered to be within a wind-borne debris region. Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions. While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility or liability for its accuracy. The material presented in the report should not be used or relied upon for any specific application without competent examination and verification of its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does not intend that the use of this information replace the sound judgment of such competent professionals, having experience and knowledge in the field of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the results of the report provided by this website. Users of the information from this website assume all liability arising from such use. Use of the output of thle wsbsltP. does not Imniv annmval by the oovernlno hnlldlno cods bndip% rP.snonSlhlP.. for hlllldlno nnnp.. annmval and InternrP.tatlon for the hftps://hazards.atcouncil.org/#/wind?lat=33.6171855&ing=-117,9359986&address=3710 Seashore Dr%2C Newport Beach%2C CA 92663%2C USA 1/2 ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes Roof Slope 0 = 10 Roof Shape Gable Tributary Width s = 4.00ft Tributary Length 1 = 2.83 ft Effective Area Aft = 11.30 ft2 Height of Structure h = 25 ft Wind Speed V = 95 mph Exposure Category D Building Width B = 30 ft Building Length L = 55 It Zone Width a = 3 It Elevation Height Z9 = 12 ft - - Wind Directionality Kd = 0.85 - Topography Factor K, = 1.00 Ground Elevation Factor Ka = 1.00 Velocity Pressure Exposure Coefficient K. = 1.13 - Velocity Pressure q,=0.00256K�KnKdKftV2 = 22.10 psf _- .SolarArray Pressure Equalization Y. = 0.79 Array Edge Factor YE = 1.50 Zone GCp p = q=(GC )1 3 - - - 3r 3.57 -94.11 - - 3e 2.99 -78.71 2 2r 2.99 -78.71 2e - - - _ 2n 2.99 -78.71 1 1' war.,rb $-r1--+�I--w- .. �+m��.w,awuma �.r,a�rrww.bea�uaan,mr e.wO4apsRIXmpnm 4nm.W.,e.krrm. Ed��. dwHblmr. r I I � _ .wn. E Rw°m,rmeymerafr�mnewu�a l.`Rldl 4. W nLLm u�� ,�pyuuwW rw�N W aOlrwrYwlm.nRn4m. . e�"arr�.,r.Aa°rwro�a,ixixn�•.•.mm4.4°rwmeu °,w.aw...m.a .m.au�.°. w,e�m.wc°.mawe Wwamemmc W , ro rood EftwIWe and Am,A,m PtlIRES9M8Wr VWI VAr,u, EpoRv,br fl[brr.. MCrtbeG W gMf[y EMObO CYgyr OrpRMdjIN Loads Wind Pressures q. _ -78.71 psf Tributary Length I = 2.83 It Attachment Spacing w = 4.00 ft Tributary Area At = 11.3 ft' Solar Panel Load Qo = 3 psf Wind Load Pw = q, * At _ -889 Ibs Dead Load Po = QD * At = 33.9 Ibs Uplift Pa 0.6 + P. _ -513 lbs Clamp Ultimate Load P = 1819 Ibs (ICC 1976) Factor of Safety W = 3 Allowable Withdrawal per Attachment Ta = T * ns = 606.3 Ibs Demand Capacity Ratio DCR = Pa / Te = 0.85 < 1 OK EISMIC WEIGHT COMPARISON / ANALYSIS .(PER CEBC 2019 Part 10 Chapter 5 Section 502.51 w Module Model Panel Weight Number of Panels Total PV System Weight Panasonic Wpanel NPv WPV = Wpanel * NPV 43 lbs 24 = 1032 Ibs Roof Weight Qp = 5.0 psf Building Length Lbeild = 55 ft - Building Width Wbuild = 30 ft Roof Area AbOd 1650 fe .... Building Perimeter Pbuild = 170 ft _— Wall Height h, = 8 it Wall weight Qwall = 15 psf - -- Interiorwallweight Qint = 10 psf = Roof Load Wnoor = Abuild * Qo = 8250 Ibs - -- -- Wall Load Nwall = hl /2 * Qwall * Pbulld � Abuiw * Clint /: = 18450 Ibs - - -.�LTotal Story Weight Wbuild = Wnoor+ Wwall = 26700 Ibs Percentage Weight Increase WPV / Wbuid = 3.87% < 10% OKAY