HomeMy WebLinkAboutPV2022-164 - CalcsITSP2=
C SLING ?Wi (b0V "►qn
76 North Meadowbrook Drive
Scott E Wyssling, PE Alpine, UT 84004
Jon P. Ward, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
June 6, 2022 BUILDING DIVISION
Jun 07 2022
Current Insight
2852 W. Amin! Way
South Jordan, UT 84095 BY: S.E.C.
Re: Engineering Services
Baudry Residence
3107 Corte Marin, Newport Beach CA
6.250 kW System
To Whom It May Concern:
We have received information regarding solar panel installation on the roof of the above referenced
structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system.
A. Site Assessment Information
1. Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system.
B. Description of Structure:
Roof Framing:
2 x 10 dimensional lumber spaced at 16" on center
Roof Material:
Composite Asphalt Shingles
Roof Slope:
21 degrees
Attic Access:
Accessible
Foundation:
Permanent
C. Loading Criteria Used
Dead Load
o Existing Roofing and framing= 10 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 13 PSF
• Live Load = 20 psf (reducible) — 0 psf at locations of solar panels
• Ground Snow Load = 0 psf
• Wind Load based on ASCE 7-16
o Ultimate Wind Speed = 95 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the 2019 California Building Code, including provisions allowing existing structures to not
require strengthening if the new loads do not exceed existing design loads by 105% for gravity
elements and 110% for seismic elements. This analysis indicates that the existing framing will
support the additional panel loading without damage, if installed correctly.
Page 2 of 2
D. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent Unirac installation manual.
If during solar panel installation, the roof framing members appear unstable or deflect non -
uniformly, our office should be notified before proceeding with the installation.
2. The maximum allowable withdrawal force for a 5/4' lag screw is 235 lbs per inch of penetration as
identified in the National Design Standards (NDS) of timber construction specifications. Based on
a minimum penetration depth of 2%', the allowable capacity per connection is greater than the
design withdrawal force (demand). Considering the variable factors for the existing roof framing
and installation tolerances, the connection using one 5/15" diameter lag screw with a minimum of
2'/" embedment will be adequate and will include a sufficient factor of safety.
3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of
the roof, the panel supports shall be placed no greater than 48" on centers.
4. Panel supports connections shall be staggered to distribute load to adjacent framing members.
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing
roof system will adequately support the additional loading imposed by the solar system. This evaluation is in
conformance with the 2019 California Building Code, current industry standards, and is based on information
supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Ah"
y your
Scott E. fyss4'
li , PE
California License N 4
WYSSLING
co
Wyssling Consulting
76 N. Meadowbrook Drive
Alpine, UT 84004
V=
Exposure
K, =
Kv =
Kd =
Ke
9t, _
Roof Angle =
Roof Type
S.6�r =
Atds =
95
C
0.85
1
0.85
1.000
16.7 psf
21
Gable
48 in
11.52 sf
Wind Uplift
Rooftop Solar Panels Parallel to Roof Surface
ASCE 7-16, Section 29.4.4
Basic Wind Speed
ASCE 7-16, Section 26.7
Velocity Pressure Coefficient, ASCE 7-16, Figure 26.10-1
Topographic Factor, ASCE 7-16, Section 26.8.2
Directionality Factor, ASCE 7-16, Section 26.6
Ground Elevation Factor, ASCE 7-16, Section 26.9
qh = 0.00256KXvKdK,V2 (ASCE 7-16 Eq. 26.10-1)
deg
Horizontal spacing of roof anchors
Panel Area tributary to each roof anchor
(201) 874-3483
swyssling@wysslingconsulting.com
Baudry Residence
3107 Corte Marin
Newnart RParh CA
GCP
5/16 in
External Pressure Coefficient, ASCE 7-16, Figure 30.3-2
<r4j Q X'-
RoofZone
Zone 1
2e 2n 2r 3e
3r
No. of Screws
-1.50
-1.50 -2.49 -2.49 -2.49
-3.31 - Signed 6-6-22
ga =
0.79
Pressure Equalization Factor, ASCE 7-16 Figure 29A-8
Cu =
9E =
1.00
Edge Array Factor, ASCE 29.4.4 edges < 0.5*building height,
and panel spacing < 411.
p„. =
ghGCPgEg, =
Design Wind Pressure, ASCE 7-16, Equation 29.4-7
W =
Roof Zone
1
2e 2n 2r 3e
3r
298 Ib/in
-20 psf
-20 psf -33 psf -33 psf -33 psf
-44 psf Min Pressure = -16 psf
745 IN
Use 20 psf
Use 20 psf Use 33 psf Use 33 psf Use 33 psf Use
44 psf ULTIMATE
x 0.6 =
16 psf
16 psf 20 psf 20 psf 20 psf
26 psf ALLOWABLE
Connection to Existing Roof Framing
F.S. = 1 Additional Factor of Safety applied to withdrawl force, if desired
A,db = 11.5 ftp
DLpavel = 2 psf
Roof Zone 1 2e 2n 2r 3e 3r
W.PI;n = 20 psf 20 psf 33 psf 33 psf 33 psf 44 psf
Peas = F.S. x A,,, x (0.61)- 0.6W) = Withdrawl force for each roof anchor
Roof Zone 1 2e 2n 2r 3e 3r
-120.0 Ibs -120.0 Ibs -210.2 IN -210.2 lbs -210.2 lbs -285.2 lbs
Connection Capacity
db =
5/16 in
Lag Screw diameter
Dpen =
2 1/2 in
Lag Screw penetration into existing framing member
No. of Screws
1
Screws per Connection
Douglas Fir -Larch
Species of wood framing
Cu =
1.6
Load Duration Factor for Wind Loading, NDS Table 2.3.2
C, =
0.7
Temperature Factor, NDS Table 10.3.4
W =
266 lb/in
Withdrawl Capacity, NDS Equation 11.2-1
W' = Co x C, x W =
298 Ib/in
Adjusted withdrawl value
P.,.. = Dp,„ x W' =
745 IN
Ibis analysts calculates the
capacity of the lag screws
Roof Zone
1
2e 2n 2r 3e 3r
only. For capacity of the
DEMAND =
120 lbs
120 lbs 210 lbs 210 lbs 210 lbs 285 lbs
complete mounting system,
CAPACITY =
745 lbs
745 lbs 745 lbs 7451bs 745 lbs 745 lbs
please see manufacturer's
up to72in ok
up to72in ok up to72in ok up to72in ok up to72in ok up to72in ok recommendations.