Loading...
HomeMy WebLinkAboutX2021-3166 - Misc (2)STATE OF CALIFORNIA VALVE LEAKAGE TEST CEC-NRCA-MCH-O&A (Revised 01/20) XZozl - 3(66 �1t92�„ �ngon pd CERTIFICATE OF ACCEPTANCE NRCA-MCH-08-A Valve Leakage Test (Page 1 of 2) ProjeR Name: Brighton Chiller Replacement EnFomement Ageaq: pgud ,FW0 '(AEA 5ft/� permit Numher: X2 PmJed Add,esa: 4627 Brighton Rd `i":Corona Del Mar rip code:92625 System Name or Identifiadon/Tag: Air Cooled Chiller System tnadon or Area Served: Basement Compliance Results: Enforcement Agency Use: Checked by/Date Complies Q Does NOTComply P(W"(,d-0-rrAeW,4y ,S.E,pw/,t S-f n(2ge-Z Ensure that control valves serving variable flow systems can withstand the pump pressure over the full range of operation. Intent: Submit one Certificate of Acceptance for the system that must demonstrate compliance, attach additional functional tests only (NOT additional construction inspections) for each additional Pump Tad ID. J1A 'o StruGtio a Jon;MMEMMEW guilEing: Floor: Room/Area/Zone: Control/System: House Basement Basement Delta Prior to Functional Testingverify and document the following: 1. Required documentation(checkall of thefollowing): a. Valve and pipingdesign drawing asapproved bythe authority having jurisdiction b. Documentationshowing the shut-off head pressure for each pump in the system. 2. Installation inspection (check all of the following): a. I Valve and piping arrangements are'nstalled as specified by the design drawings. (NA7.5.7.1(al) Construction Inspection Compliance Results: Complies Q Does NOT Comply 14 '8=� uIct!o�s,Tsting.:. eullding: House t Floor Basement Room/Area(Zone: Basement Control/System: T\Y�e -I-4. Pumphglp: J/G" Steps: Results 1 For each of the pumps serving the distribution system, dead head the pumps using the discharge isolation valves at the pum s, Document the following: (NA7.5.7.2 (Step 1)) ��SS a. Record the differential pressure across the pumps. (NA7.5.7.2 (Step. Sal) 5 Ft. w.c. b From the required documentation in Construction Inspection 1b; record the shut-off head pressure for the Pump Tag ID. Ft. w.c. c. Calculate : 100 x (la- lb)/lb (note: may result in a positive or negative percentage) 01-000 % d. Verify that Step lc is between -5% and +5%. (N62.5.7.2 (Step lbl) P/F Q 2 Reopen the pump discharge isolation valves. Automatically close all valves on the systems being tested. If 3-way valves are present, close off the bypass line. Verify and document the following: (NA7.5.7.2 (Step 2)) s�UE.SS a. Verify that the 2-way valve automatically close. (NA7.5.7.2 (Step 2a1) FtSS his Record the pressure differential across the pump. (NA7.5.7.2 (Step 261) -- Ft. w.c. c. Calculate : 100 x (2b- lb)/1b (note: may result in a positive or negative percentage) % d. Verify that Step 2c is between -5% and +5%. (NA7.5.7.2 (Step 2c)) er P/F Q 3 Restore system to normal operating conditions. Fu notional Testing Compliance Results: gComplies QDoes NOTComply CA Building Energy Efficiency Standards -2019 Nonresidential Compliance January 2020 STATE OF CALIFORNIA VALVE LEAKAGE TEST CEC-NRCA-MCH-08-A Revised 01120 CALIFORNIA ENERGY COMMISSION CERTIFICATE OF ACCEPTANCE NRCA-MCH-08-A Valve Leakage Test (Page 2 of 2) Protect Name: Brighton Chiller Replacement Enforcement Agency: Permit Number: X2 Pro;emAadms,:4627 Brighton Rd cityCorona Del Mar To Code: 92625 SYctem Name or Identiflcetimurrag: Air Cooled Chiller system W.V..or Area Served: Basement DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Name: Kevin GruSs Documentation Author Signature: Documentation Author Company Name: Diversified Thermal Sea Date Signed: Address: 1220 N Barsten Way ATT Certification Identification (If applicable): city/state/zip: Anaheim, CA 92806 Phone: 714-632-7401 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Acceptance is true and correct. 2. 1 am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). 3. The construction or installation identified on this Certificate of Acceptance compiles with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NAT 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been pis m e available with the building permit(s) issued for the building. Field Technician Name:, John Quenga FieldT Ignat Field Technician Company Name: Diversified Thermal Services (POsItI911th C&w<any (Tit ): Address:1220 N Barsten Way AlT Certification Identification (if applicable): City/State/zip: Anaheim, CA 92806 Phone:714-632-7401 Date V747ILL RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. 1 am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. 1 am eligible under Division 3 of the Business and Professions Code In the applicable classification to accept responsibility forthe system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NAT 4. 1 have confirmed that the Certificate(s) of Installation forthe construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permits) issued forthe building. S. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued forthe building, and made available to the enforcement agencyfor all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Acceptance Personn Name: Kevin Gruss Responsible Acceptance Person Signature: gResppon9s�ibllee � L11VBfs�T b I ng t aicaBNlCeSompany Name: Position with Company (Title): Project Manager Address:1220 N Barsten Way CSLB License: City/State/Zip: Anaheim, CA 92806 Phone:714-632-7401 Date Signed: CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance January 2020 STATE OF CALIFORNIA SUPPLY WATER TEMPERATURE RESET CONTROLS ACCEPTANCE CEC-NRCA-MCH-09-A!Revised 011201 rnl Iantanua vnivvr_v rnnaaalcclnu CERTIFICATE OF ACCEPTANCE NRCA-MCH-09-A Supply Water Temperature Controls Acceptance (Page 1 of 2) "`le"NiT.:Brighton Chiller Replacement Ed.,rementAge.,: PermitNumbecX22t PrmeaAddress: 4627 Brighton Rd `I": Corona Del Mar a, Cede: 92625 o pliance Results: Enforcement Agency Use: Checked by/Date Complies Q Does NOT Comply Ensure that both the chilled water and hot water supply temperatures are automatically reset based on either Intent: building loads or outdoor air temperature, as indicated in the control sequences. (§140.4(k)41 Exception: Hydronic systems that use variable flow to reduce pumping energy. 140.4 k 1) Submit one Certificate of Acceptance far each system that must deolnnStrate rmm.lianrn ulriNrfta�Y:a �arv_.e� 's '''iFePY"_-: '_��.t1 uzwv ura w.tse�` :ty Building: House Floor, gaom/Area/Z,ne: Basement Basement Control/System: Delta 1. equired documentation (check all of the following): a. All factory calibration sheets. 2• riot to Functional Testing, verify and document the following: Er a. I Supply water temperature sensors have een either factory or field calibrated. (NAZ5.8.SIa1I Construction Inspection Compliance Results: Complies 0 Does NOTComply 'ry R,jli<ti A%'s,� •i9��K....i i .L(!��ti��ll xr-.3�hlY'S�'�MYS Steps: Results 1 Change reset control variable to its maximum value. Verify and document the following: (NA7.5.g2 (Step 11) ,f) la`�S a. Chilled or hot water temperature setpoint is reset to appropriate value. (NA75.8.2 (Step 1a1) P/F Q It Verify that actual supply temperature changes to within 2 percent of the new setpoint. (k! .8.2 (Step 1b11 �?P/F O 2 Change reset control variable to its minimum value. Verify and document the following: (NA75.8.2.(Ste o 21 a. Chilled or hot water temperature setpoint is reset to appropriate value. (NA7.5.8.2 (Step 2c1) 0 P/F O b Verify that actual supply temperature changes to within 2 percent of the new setpoint. ( NA7.5.82. (Step 2d1) �P/F 3 Restore reset control variable to automatic control. Verify and document the following: 1) (NA7.5.82 (Step p��s W a: Chilled or hot water temperature set -point is reset to appropriate value. (N675,821Steo 3e1) P/F O b Verify that actual supply temperature changes to within 2 percent of the new setpoint. (NA7.5.8.2 (Step 3f1) �P/F Q Functional Testing Compliance Results: (_ Complies O Does NOT Comply CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance January 2020 STATE OF CALIFORNIA SUPPLY WATER TEMPERATURE RESET CONTROLS ACCEPTANCE CEC-NRCA-MCH-09-A Revised 01120 CALIFORNIA ENERGY COMMISSION CERTIFICATE OF ACCEPTANCE NRCA-MCH-09-A Supply Water Temperature Controls Acceptance (Page 2 of2) Pmlect Name: Brighton Chiller Replacement Enkrcement Agenry: Permit Number; X221 Pmled Address: 4627 Brighton Rd 0"; Corona Del Mar aP`�de 92625 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Name: Kevin GruSs Documentation Author Signature: Documentation Author Company Name: Diversified Thermal Date Signed: Address:1220 N Barsten Way ATr Certification Identification (If applicable): city/State/Zip:Anaheim, CA 92806 Phone:714-632-7401 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Acceptance is true and correct. 2. 1 am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). 3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. 1 have confirmedthat the Certificate(s) of Installation for the construction or installation Identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permit(s) issued for the building. Field Technician Name: John Quenga Field Technician Signature: Field Technician Company Name: Diversified Thermal Servi Position with Company (Title): Foreman Address:1220 N Barsten Way ATT Certification Identification (if applicable): Ciry/State/Zip: Anaheim, CA 92806 Phone: 714-632-7401 Date Signed: RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. 1 am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified an this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NAT 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. S. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Person Name: Kevin Gruss Responsible Acceptance Person Signature: ResponsiAcceptance Person Company Name: Diversifed Thermal Services eCble Position with Company (Title): Pro Project Manager Address: 1220 N Barsten Way CSLB License: city/state/Zip: Anaheim, CA 92806 Phone:714-632-7401 Date signed: CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance January 2020 STATE OF CALIFORNIA HYDRONIC SYSTEM VARIABLE FLOW CONTROL ACCEPTANCE CEC-NRCA-MCH-10-A (Revised 01120) CALIFORNIA ENERGY COMMISSION 40 CERTIFICATE OF ACCEPTANCE NRCA-MCH-10-A Hydronic System Variable Flow Control Acceptance (Page 1 of 3) Prolect Name: Brighton Chiller Replacement Enforcement Agenq: Permit Number. X221- PmleetAddrm:4627 Brighton Rd `t':Corona Del Mar vPcnde:92625 System Name or Iderdli.don/rag: Air Cooled Chiller System Watson or Area Served: Basement co fiance Results: Enforcement Agency Use: Checked by/Date - Complies C)Does NOT Comply Intent: I Ensure that hydronic pump speed varies with building heating and cooling loads. Submit one Certificate of Acceptance for each system that must demonstrate compliance. a . ;: At CdnsEcutaion�lhs�pon:-� I rjii�� ,d, t Building: House Floor. Room/Area/Lnne: Contras/System: Basement Basement Delta 1. Required documentation (check all of the following): a. I As- built, Design Documents, or mechanical equipment schedules as approved by the authority having jurisdiction. 2• Priorto Functional Testing, verify and document the following: a. For the static pressure location, setpoint, and reset control (check one of the following): (NA7.5A.1fa1I C) I. For systems WITHOUT direct digital control of individual coils reporting to the central control panel, differential pressure shall be measured at the most remote heat exchanger or the heat exchanger requiring the greatest differential pressure. 140.4 k 68i) ' ii. For systems WITH direct digital control of individual coils with a central control panel, the static pressure set point shall be reset based on the valve requiring the most pressure, and the setpoint shall be no less than 80 percent open. Pressure sensors may be mounted anywhere. (4140.4(k16Bii) b. Pressure sensors are either factory or field calibrated. (N67.5.9.1Jb1) Construction Inspection Compliance Results: 075ornplies 0 Does NOT Comply CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance January 2020 STATE OF CALIFORNIA HYDRONIC SYSTEM VARIABLE FLOW CONTROL ACCEPTANCE CEC-NRCA-MCH-10-A (Revised 01120) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF ACCEPTANCE NRCA-MCH-10-A Hydronic System Variable Flow Control Acceptance (Page 2 of 3) ProleRName: Brighton Chiller Replacement Enforcement Agenry: Pb Permit Number: X221 Prate¢ Address: 4627 Brighton Rd cl"; Corona Del Mar 31p Care; 92625 System Name at Identifotan/rag: Air Cooled Chiller System Lrntiva or Area Served: Basement Y�Jl� d BN.nir�onalt[,£,e^6,,,b,,,>,,4w,+.edJ'"kadt�5a:,4"''�at...tdra,.^r A nai tip ,� t rr }tIF t -i Fa`. _ S Y� } -,.., THbi f" >...�.. .�C.;,,7as✓,:,a„Cr�z.u7�>c__un. ". G`4.#rl-��r._ih;:xir im n..iy.., ^', Building: House Naar: Basement Room/Area/Zone: Control/System: Basement Delta Steps: Results 1 Modulate control valves to reduce water flow to 50 percent of the design flow or less, but not lowerthan the pump minimum flow. NOTE: in the rare case that the pump minimum flow is greater than 50 percent of the design flow, modulate the control values to the pump minimum flow. Verify and document the following:. (NA7.5.9.2 (Stec 11) V a. Pump operating speed decreases (for systems with DDC to the zone level). (N67.5.9.2 (Step 1a)) P F 0 b. Current operating setpoint has not increased (for all other systems that are not DDC). (NA7.5.9.2 (Step lb)) P QF O NA O c. Record the system pressure as measured at the control sensor. (either ft. w.c. or psig) LV RLV1A J. Record the system pressure setpoint. (either ft. w.c. or psig) e. Calculate: 100 x(Sc-id)/1d % f System pressure is within 5 percent of current operating setpoint (le between -5% and +5%). (NA7.5.9.2 (Step 1c)) P F / O g. System operation stabilizes within 5 minutes after test procedures are initiated. (N67.5.9.2 (Step 1d)) 2 Open control valves to increase water flow to a minimum of 90 percent design flow. Verify and document the following: (NA7.5.9.2 (Step 21) S a. Pump speed increases. (NA7.5.9.2 (Stec 2e1) P Q b. Pumps are operating at 100 percent speed. (NA7.5.9.2 (Step 2fl) _. P/F O c. Record the system pressure as measured at the control sensor (either ft. w.c. or psig) d. Record the system pressure setpoint. (either ft. w.c. or psig) e. System pressure setpoint in 2d is greater than the setpoint in Step 1d. (N67.5.9.2 (Ste o gel) P/F O f. Calculate: 100 x(2c-2d)/2d % g System pressure is either within ±5 percent of current operating setpoint (2f is between -5% and +5%). (NA7.5.9.21Step 2h1) P/F O h. System operation stabilizes within 5 minutes after test procedures are initiated. (N67.5.9.2 (Step 2h1) P/F Q 3 Restore system to normal operatin conditions. (NA7.5.9.2 (Step 3)) Functional Testing Compliance Results: Complies O Does NOT Comply CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance January 2020 STATE OF CALIFORNIA HYDRONIC SYSTEM VARIABLE FLOW CONTROL ACCEPTANCE CEC-NRCA-MCH-1n-A (Revised 011201 nAl ianoAnn cr.lcor-vn0AftM1ee1na1 CERTIFICATE OF ACCEPTANCE NRCA-MCH-10-A Hydronic System Variable Flow Control Acceptance (Page 3 of 3) Pmiect Name: Brighton Chiller Replacement Enforcement Agency: Permit Number: X221- Pmjo&Aaemss:4627 Brighton Rd c""Carona Del Mar Zip Code;92625 System Name or Identmostion/rse: Air Cooled Chiller System Location or area Served: Basement DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Name: Kevin Gruss Documentation Author Signature: Documentation Author Company Name: Diversified Thermal Se Date Signed: Address: 1220 N Barsten Way ATT Certification Identification (If applicable): City/State/Zip: Anaheim, CA 92806 Phone:714-632-7401 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Acceptance is true and correct. 2. 1 am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). 3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permit(s) issued for the building. Field Technician Name: John Quenga Field Technician Signature: Field Technician Company Name: Diversified Thermal Services Position with Company (Title): Foreman Address:1220 N Barsten Way ATT Certification Identification (if applicable): City/State/Zip: Anaheim, CA 92806 Phone:714-632-7401 Date Signed: RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. 1 am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. S. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Person Name: Kevin Gruss Responsible Acceptance Person Signature: Responsible Acceptance Person Company Name: Diversifed Thermal Services Position with Company (Title): Project Manager 1 Address:1220 N Barsten Way CSLB License: City/State/Zip: Anaheim, CA 92806 Phone: 714-632-7401 Date Signed: CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance January 2020