FIRE SPRINKLER NFPA 13D SYSTEM
FINAL CHECKLIST
(RESIDENTIAL)
YES
NO
1.
Water meter proper size
❑
2.
Fire sprinkler system installed per the approved plans
❑
3.
All construction covers removed from sprinkler heads
❑
4.
Cover plates are NOT to be installed, but shall be available on the Jobsite
❑
5.
All tape and paint removed from sprinkler heads
❑
6.
Finish trim installed around sprinkler heads
❑
7.
Proper signage posted at all required locations
❑
8.
Flow test conducted and bell tested
❑
9.
Location of inspector's testing valve in approved location
❑
SYSTEMS:
10.
Clearances around sprinkler heads and riser - no obstructions
❑
11.
Operating pressure gauge installed at riser showing proper water pressure
❑
12.
Back flow preventer installed
❑
13.
System installed per manufacturers specifications
❑
NOTES:
FIRE SPRINKLER NFPA 13D SYSTEM FINAL APPROVED:
a.
PERMIT #: /
niqv
gY, DATE: '!o " GC/
Forms\ Fire Sprinkler NFPA 13D Syrtem -FINAL Checklise RESIOENiIAL OS/12/2015
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive l P.O. Box 1768 1 Newport Beach, CA 92658-8915
www.newportbeachca.gov 1 (949) 644-3200
FIRE SPRINKLER NFPA 13D SYSTEM
ROUGH INSPECTION CHECKLIST
1. Riser Construction and Location Approval
a. Drain valve
b. Backflow device (single check)
c. Bell activation device
d. Inspectors test valve
e. Riser sized per approved plans
2. Pressure Test
a. System tested at operating pressure for 2 hours
b. Pressure gauge installed
3. Sprinkler Heads shall not be Installed In the flttings prior to the fittings
being cemented in place (temporary test plugs)
a. Installation and spacing of temporary test plugs
4. Piping
a. Material installed per plan
b. Hangers per codes/prevent upward movement
C. All CPVC piping shall be installed by persons who have been
certified by the manufacturer for installation of CPVC piping
d. Piping protected from damage
5. Bell
a, Wiring installed per code
b. Boxes installed at proper locations
NOTE: CPVC plastic pipe in the garage shall not be exposed. Sprinklers that are
Response" or "Residential" must be used.
CORRECTIONS AND
FIRE SPRINKIL NF 13D SYST OUCH INSPECTION APPROVED:
PERMIT*
BY: DATE: