HomeMy WebLinkAboutX2021-1680 - Alternative Material & Methods (5)X202 / - 1,68a
F PORT CITY OF NEWPORT BEACH
O �e
{� COMMUNITY DEVELOPMENT DEPARTMENT
u ' T BUILDING DIVISION
" 100 Civic Center Drive I P.O. Box 1768 I Newport Beach, CA 92658-8915
c"<iFon P www.newportbeachca.gov 1 (949) 644-3200
CASE NO.: 2022-101
❑ REQUEST FOR MODIFICATION TO PROVISIONS
OF TITLE 9 (FIRE CODE) OR TITLE 15 (BUILDING CODE)
OF THE NEWPORT BEACH MUNICIPAL CODE
(See Reverse for Basis for Approval) (Fee $291)
REQUEST FOR ALTERNATE MATERIAL
OR METHOD OF CONSTRUCTION
(See Reverse for Basis for Approval) (Fee $291)
For above requests, complete Sections 1, 2 & 3
below by printing in ink or typing.
JOB ADDRESS:
SITE ADDRESS: 1660 Dove Street
Owner Aryabhata Group LLC
Address 520 Newport Center Drive, Suite 480
Newport Beach Zip 92660
Daytime Phone ( ) 440-666-5779
III FOR STAFF USE ONLY III
Plan Check # M-I -�
Occupancy Classification
Use of Building" FD -I
Project Status pf'L,
Construction Type
irl-
Verified by
No. of Items �I
Fee due v
DISTRIBUTION:
❑ Owner
;� Petitioner
❑ Fire
PETITIONER:
# of Stories
A3
wr c, # of Units
Plan Check MY—
❑ Inspector
❑ Other
Petitioner AO (Kara Sutch)
fPet honer to be architect or engineer)
Address 144 N. Orange Street
Orange Zip 92866
Daytime Phone ( ) 714-639-9860
Email:, karas@aoarchitects.com
12 1REQUEST: Submit plans if necessary to illustrate request. Additional sheets or data may be attached.
The proposed fire curtain will separate the M occupancy from the R2 corridor at the first floor so that CBC 705.3, exception 2 can be
applied between the S2 parking structure and the R2 corridor. The fire curtain will provide the equivalent of a 1 hr Fire Barrier as an
Occupancy Separation between the R2 and M occupancies in accordance with CBC Table 508.4 and CBC section 707.
3 JUSTIFICATION/FINDINGS OF EQUIVALENCY: CODE SECTIONS:
508.4, 707.6
The proposed fire rated roll down curtain will be tied to the fire alarm and fire
suppression systems to automatically close in the event of an emergency. Standby
Emergency Power will be provided per CEC Article 700.12. The proposed roll down
curtain, Door Systems model DSI-C3HRM, will provide the equivalent of the required 1
hour wall rating and will provide equivalent Fire Barrier Wall protection at the opening
during a fire. See attached letter.
Position Principal
Petitioner's Kara Sutch 02-06-23
Signature CA Professional Lic. # Steven Gaffney19676 Date:
FOR STAFF USE ONLY
DEPARTMENT ACTION: In accordance with: CBC 104.11/CFC 104.9
(Alternate materials & methods)
❑ Concurrence from Fire Code Official is required. ❑ Approved ❑ Disapproved
By: Date
(� Request (DOES) OES NO essen any fire protection requirements.
Request (DOESessen the structural integrity
ElCBC 104.10/CFC 104.8
(CBC Modification)
❑ Written Comments Attached
The Request Is: 19,Granted ❑ Denied (See reverse for appeal information)
❑ Granted (Ratification required)
Conditions of Approval:
Signature Position CHIEF PIlI! p!NG !lFf=lCael_
Print Name I t �--E- I Ft -a
Date r) 7--t7(., — Zo-Z 3
APPEAL OF DIVISION ACTION TO THE BUILDING BOARD OF APPEALS (See Reverse)
(Signature, statement of owner or applicant, statement of reasons for appeal and filing fees are required.)
CASHIER RECEIPT NUMBER: JNV — 000c,"l,)3 3 Formslmodif 07/01/21
Architecture.
Design.
144 N. Orange Street, Orange, CA 92866 T 714.639.9860 aoarchitects.com Alko
Relationships.
February 6, 2023
City of Newport Beach
Community Development Department
100 Civic Center Drive
Newport Beach, CA 92660
Melissa Kubischta, SE
Civil Engineer- Plan Check
Re: Plan Check Number2117-2020
Newport Crossing Apartments
1660 Dove Street
Newport Beach, CA 92658
Melissa,
As permitted in CBC 104.11, the purpose of this letter is to requestthe use of an alternative material, design and method of construction
for the corridorto breezeway opening.
ub'ect:
Table 508.4 requires a 1 hour occupancy separation between an R-2 and an M occupancy. The project has an R-2 corridorthat
connects to an M breezeway area. The preferred design is to maintain an opening between the two areas.
Discussion:
A fire rated curtain is proposed in orderto provide the required opening protection within a 1 hourfire barrier at separated occupancies.
• Per 508.4.4.1 an occupancy separation is to be constructed as a fire barrier in accordance with 707.
• Per707.6, the protection for an opening in a fire barrier should be in accordance with 716. Also, per707.6 exception 1, opening
size is not limited due to the project having an automatic sprinkler system per 903.3.1.1.
Per Table 716.1(2) the opening protection would be required to be 45 minutes with a D-H label.
o A fire curtain will provide the rating with the required label.
• Table 716.1(1) requires thatthe D-H label complies with NFPA 252 or UL 10B or UL 10C.
o The C3HRM fire curtain is compliant with UL 10B and 10C.
o The C31-IRM fire curtain is listed with Cal Fire under listing number4077-2312:0501.
• The area where the fire curtain occurs will normally be open.
o The fire curtain has an automatic closing feature.
o The fire curtain will close upon fire alarm and or fire sprinkler activation.
Conclusion:
In our opinion, the use of a 3 hour fire curtain such as the DSI-C3HRM (C3HRSM) or equal meets and exceeds the opening protection
requirements forthe occupancy separation.
Thank you for your consideration. Please feel free to contact AO with any further questions.
Kara Sutch I Principal
karas(@aoarchitects.com
Page 1 of 1
MODEL DSI-C3HR
Smoke and Fire Curtain
The DSI-C3HR Smoke and Fire Curtain is totally gravity
fail safe, resets automatically, and incorporates the latest in
electronic technology. As a result, DSI-C3HR Curtain is one of
the most advanced, yet cost effective systems on the market.
The DSI Smoke and Fire Curtain Model DSI-C3HRSS single
barrel configuration for widths under 16ft and Model DSI-
C3HRSM multi barrel configurations for widths over 16ft create
a three hour opening protective smoke and fire barrier.
The assembly comprises a fire rated fiberglass fabric wound
around a roller which encases a compact head box that is
typically installed above the ceiling with side guides that are
buried in the wall. This makes the system virtually invisible until
activated.
Compliant with...
Code Description
UL 10 D Fire protective Smoke Curtains- 180 minutes
UL 1784 Air leakage test of door assemblies
UL 10C Without Hose Stream Test -20 minutes
UL 10B Without Hose Stream -20 minutes
UL 864 Control Units for Fire Protective Signaling Systems
ADVANTAGES:
• Cost effective
• Creates open space for your building design
• Compact design, low headroom requirements
• Almost completely hidden
• Lightweight, requires little to no structural support
• Unlimited width, custom sizes
• Code compliant
• Multiple egress options
• Battery backup system standard
• Fail safe system with automatic reset
GUARANTEED QUALITY
Door Systems guarantee high quality products,
tested to both UL and BS standards.
MODEL DSI-C3HR
Smoke and Fire Curtain
HEADBOX FINISHING OPTIONS
Flush to Ceiling (HBFC_01)
SIDE GUIDE MOUNTING OPTIONS
Exposed Flush (SGMEF_01)
SINGLE ROLLER MOUNTING OPTIONS
Fixed Mount (SRMFM_01)
Fired directly to the lintel above an opening.
MULTIPLE ROLLER MOUNTING OPTIONS
Exposed Mount (HBEM_01)
Butt to Wall Flush (SGMBWF_01)
Soffit Fixed Mount (SRMSFM_01)
Fixed directly to the underside of the soffit slab.
Shadow Gap (HBSG_ 1)
Inset in Wall Flush (SGMIWF_01)
0
Suspended Soffit Mount (SRMSSM_01)
Suspend from soffit via unistruts and all thread.
u
Over/Under Arrangement (MRMOU_01) Side by Side Arrangement (MRMSS_01) Suspended Over/Under Arrangement
Fixed directly to the lintel above an opening. Fixed directly to the underside of the soffit slab. (MRMSOU_01)
Suspend from soffit via unistruts and all thread.
CERTIFICATE OF COMPLIANCE
Certificate Number
20220406-R39636
Report Reference
R38702
Issue Date
2022-April 06
Issued to: Door Systems Inc
1150 Las Brisas PI
Placentia, CA 92870 USA
This certificate confirms that Fire -protective Curtains
representative samples of
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for safety: UL 10D, "Fire Tests of Fire Protective Curtain Assemblies."
UL 1784, "Air Leakage Tests of Door Assemblies."
Additional Information: See the UL Online Certifications Directory at
https://ig.uIprospector.com for additional information.
This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow -Up
Services Procedure provides authorization to apply the UL Mark.
Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL's
Follow -Up Services.
Look for the UL Certification Mark on the product.
See addendum pages 2-3.
9ruca MaM1renM1alx, Uinacfor NotlM1 American Certification Grogram
UL LLL
Any Information and dommentaEon Involving UL Mark skMcea are pmvMSE on beM1a11 of UL LLC JUL) or any autM1otlxetl licensee of UL. for questlon, please
contact a local UL Cuslomer Servos Napresentative at M1ito'I ul mmlaboutullloaationsl
Page 1 of 4
CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date
20220406-R39636
R38702
2022-April 06
This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
Model(s) below are for use in gypsum or masonry wall type constructions, maximum 3657 mm (144 in.) wide
by 3048 mm (120 in.) high. When greater than 3657 mm (144 in.) wide by 3048 mm (120 in.) high, the single
barrel and multibarrel assemblies are eligible for the Oversized Label and may be produced up to 6 m (19.7 ft.)
wide by 12 m (39.4 ft.) high and up to 300 m (984.3 ft.) wide by 12 m (39.4 ft.) high, respectively.
Fire -protective curtain:
DSI-C1 HRS Smoke and Fire Curtain, 1 hr fire rating.
DSI-600S1 Elevator Smoke Containment System, 1 hr fire rating
DSI-C1 HRM Smoke and Fire Curtain, 1 hr fire rating.
DSI-600M1 Elevator Smoke Containment System, 1 hr fire rating.
DSI-C3HRS Smoke and Fire Curtain, 3 hr fire rating.
DSI-600S3 Elevator Smoke Containment System, 3 hr fire rating.
DSI-C3HRM Smoke and Fire Curtain, 3 hr fire rating.
DSI-600M3 Elevator Smoke Containment System, 3 hr fire rating.
DSI-D1 HRS Automatic Smoke Draft Curtain, 1 hr fire rating.
DSI-D1HRM Automatic Smoke Draft Curtain, 1 hr fire rating.
DSI-D3HRS Automatic Draft Curtain, 3 hr fire rating.
DSI-D3HRM Automatic Draft Curtain, 3 hr fire rating.
Model(s) above may have suffix "E" for egress option.
e,ua mamenhma, obeme, noun gmeHon c.mdwden preeram
UL UC
Any Information and doamentallon Involving UL Mark services are provided on behalf of UL LLC (UL) or any alltMHZ" licensee of UL For questions, pleas
contact a local UL Customer Service Representative at hUnJal.condaboubuillocatInnal
Page 2 of 4
CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date
20220406-R39636
R38702
2022-April 06
Model(s) below are for use in masonry or gypsum wall type constructions, maximum 3657 mm (144 in.) length by 3048
mm (120 in.) high. When greater than 3657 mm (144 in.) length by 3048 mm (120 in.) high, the assembly is eligible for
the Oversized Label and may be produced up to 250 m (820.2 ft.) length by 12 m (39.4 ft.) high.
Fire protective curtain:
DSI-A1HR Accordion Smoke and Fire Curtain, 1 hr fire rating.
DSI-A4HR Accordion Smoke and Fire Curtain, 4 hr fire rating.
Model(s) below are for use in masonry floor type constructions, maximum 10000 mm (394 in.) travel by 8000 mm (315
in.) wide and maximum 8000 mm (315 in.) travel by 10000 mm (394 in.) wide.
Fire protective curtain:
DSI-H1HR Horizontal Fire Curtain, 1 hr fire rating
DSI-H3HR Horizontal Fire Curtain, 3 hr fire rating
D51-H1HR Horizontal Fire Curtain, 1 hr fire rating Oversized.
DSI-H3HR Horizontal Fire Curtain, 3 hr fire rating Oversized.
The products below have been additionally investigated to ANSI/UL 1784
Fire -protective curtain:
DSI-C1HRSS Smoke and Fire Curtain, lhr fire rating
DSI-CIHRSM Smoke and Fire Curtain, 1hr fire rating
DSI-C3HRSS Smoke and Fire Curtain, 3hr fire rating
DSI-C3HRSM Smoke and Fire Curtain, 3hr fire rating
DSI-DIHRSS Automatic Draft Curtain DSI-D1HRSM Automatic Draft Curtain
DSI-D3HRSS Automatic Draft Curtain DSI-D3HRSM Automatic Draft Curtain
arm.
nnol;hoMb h Arm,can canleudon Program Y
ULLLc
Any Information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any Autbudzed licensed of UL. For questions, please
con ent a local UL Customer Service Repreaenralile at M d
Page 3 of 4
CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date
20220406-R39636
R38702
2022-April 06
DSI-A4HR Accordion Smoke and Fire Curtain, 4 hr fire rating
DSI-A1HR Accordion Smoke and Fire Curtain, 1 hr fire rating
DSI 60051 Elevator Smoke Containment System, 1hr fire rating
DSI 600M1 Elevator Smoke Containment System, 1hrfire rating
DSI 60053 Elevator Smoke Containment System, 3hr fire rating
DSI 6001V13 Elevator Smoke Containment System, 3hr fire rating
Rmca MaM1renM1al; Miredor North Ametlwn Cerlifiollon pwgrem
ULLLC
Any In formation and domememation Involving UL Mark serelces am
mpwvMed on behalf of UL LLC(Uy or any adhorrsed Ileensee of UL For quesllons,please
el contact a local UL Cuomer Service RepmeenFaMe at d Uons/
Page 4 of 4
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION S
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE `J
LISTING No. 4077-2312:0501 Page 1 of 2
CATEGORY: 4077 — FIRE PROTECTIVE CURTAIN
LISTEE: Door Systems, Inc.1150 Las Brisas Place, Placentia, CA 92870
Contact: Jeff Bonnema (714) 222-3769 Fax (714) 258-7171
Email: jeff@doorsysinc.com
DESIGN: Models C1HRS, C1HRM, C3HRS, C3HRM, D1HRS, D1HRM, D3HRS, D3HRM, DSI-600S1,
DSI-600M1, DSI-600S3, and DSI-600M3 fire -protective smoke curtains consist of a woven
glass fiber, silver polyurethane coated fabric attached to rollers contained within a surface or
between -jamb mounted steel curtain box. The curtain shall overlap a minimum 19.7 in. for
multiple barrel assemblies. The maximum opening size is 236.2 in. wide by 472.4 in. high for
single barrel assemblies and 1417.3 in. wide by 472.4 in. high for multiple barrel assemblies.
Models Al HR and A4HR fire -protective smoke curtains consist of a woven glass fiber, silver
polyurethane coated fabric contained within a surface or between -jamb mounted steel ceiling
tray. The opening type is a single barrel accordion, using Dunkermotoren GMBH motors
(Models GR53x30 and GR42x40) installed at the header and barrel assembly. The maximum
opening size is 236.2 in, wide by 472.4 in. high for single barrel assemblies and 1417.3 in.
wide by 472.4 in. high for multiple barrel assemblies.
Refer to listee's data sheet for additional product description and operational considerations.
RATING: UL 10D:
Models C1HRS, C1HRM, DIHRS, D1HRM, DSI-600S1, DSI-600M1 - 1 hr classification
Models C3HRS, C3HRM, D3HRS, D3HRM, DSI-600S3, DSI-600M3 - 3 hr classification
Model Al HR - 1 hr classification
Model A4HR - 3 hr classification for gypsum wall type construction, 4 hr classification for
masonry wall type construction
UL 1784:
Models DSI-600 ELEV1S, DSI-600 ELEVIM, DSI-600 ELEV3S, DSI-600 ELEV3M:
1.57 CFM/FT' ambient; 0.47 CFM/FT' 400°F; 0.05" water column
2.31 CFM/FT' ambient; 0.79 CFM/FT' 400'F; 0.10" water column
5.28 CFM/FT' ambient; 2.91 CFM/FT' 400°F; 0.20" water column
14.00 CFM/FT' ambient; 0.30" water column
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, and UL label.
APPROVAL: Listed as fire -protective smoke curtains for use in gypsum or masonry wall type
04-06-20 Vww
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
T the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021 Listing Expires June 30, 2022
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
Listing No. 4077-2312:0501
Page 2 of 2
constructions. For use where allowed by the California Building Code and the authority
having jurisdiction. Refer to listee's Installation Instruction Manual for details.
NOTE: This item is for nonstructural applications and NO hose stream tests were conducted.
XLF: 4077-2311:0501
04-06-20 vtvw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: ,July 01, 2021 Listing Expires June 30, 2022
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
2-HR. aF
SAGEWAY q3
L�
W
Exiting is provided
from the R-2 corridor
without going through
the M Occupancy
Breezeway
M Occupancy
R-2 Corridor
1
ih
��• II II
I I
II II
M Occupancy
Breezeway
RUML
IN
Proposed Fire Curtain
location at opening
between the M
Occupancy Breezeway
and the R-2 Corridor
W.as
RUAL III p ANL
RHML
M Occupancy
R-2 Corridor
Exiting is provided
from the R-2 corridor
without going through
the M Occupancy
\ Breezeway
V
XI