RE: Resubmittal | The Stag Bar Occupancy Increase PA2022-0249
A California Corporation
3195 B Airport Loop Drive
Costa Mesa, CA 92626
www.rhainc.net
Telephone: 714. 825. 8888 • Facsimile: 714. 825. 8889
Please find a response list below and revised documents considered and clouded as Delta 1 revisions.
Please let us know if you have any comments or questions.
Please let us know if you have any comments or questions.
Sincerely,
Maria Hallimore
robinson hill architecture, inc. 714.825.8888 ext 110
hallimore@rhainc.net
Response Narrative
Fire Department Comments
Comment Response Sheet(s)
1 Comment: Fire sprinklers are required for A-2 assembly occupancy.
NBFD recommends that the required sprinkler system also protect the
hotel units above this assembly facility.
Response: Fire sprinklers are provided in the facility w/ a 2 hr
separation between ground floor and 2nd floor. Please refer to refer to
sprinkler permits F2019-0435, 0436, 0437
-
2 Comment: A fire alarm system will be required for an occupancy of 300
or more. The proposal shows an occupancy of 292; this may be revised
to a higher number during plan review.
Response: 1st floor facility and hotel have existing fire alarm systems.
Occupancy will increase.
-
3 Comment: The patio dining is described as having 50 occupants.
Based on this assembly occupant load, 2 exits from the patio are
required. Note: patrons cannot re-enter the building to access another
exit.
Response: Patio occupants has increased to 53 occupants. Restaurant
door width accommodates extra patrons from patio.
-