FIRE SPRINKLER NFPA 13D SYSTEM
FINAL CHECKLIST
(RESIDENTIAL)
1. Water meter proper s¢e
2. Fire sprinkler system installed per the approved plans
3. All construction covers removed from sprinkler heads
4. Cover plates are NOT to be installed. but shall be available on the jobsite
6. All tape and paint removed from sprinkler heads
6. Finish trim installed around sprinkler heads
7. Proper signage pasted at all required locations
8_ Flow test conducted and bell tested
9. Location of inspectors testing valve in approved location
SYSTEMS:
10. Clearances around sprinkler heads and riser - no obstructions
11. Operating pressure gauge installed at riser showing proper water pressure
12 Back flow preventer installed
13. System installed per manufacturers specificat ons
z
FIRE SPRINKLER NFPA 13D SYSTEM FINAL APPROVED:
YES
L�
PERMFrt#.. F2027 =oq 6 �
DATE: G `
Forms\ Ere Sprinkler NFPA nO System- FINAL Cnecklkt RUIDFN IALOS/12/XM
CITY OF NEWPORT BEACH
COMNIONITIf DEVELOPNWNr DEPARTnnNr
BUILD3NG DIVISION
100 Civic Center Drive i P.O. Box 17681 Newport Beach, CA 92658-8915
wwwnewportheachca.gov 1 (949) 644-3200
FEE SPRAT MER NFPA 13D SYSTEM
ROUGH INSPECTION CHECKLIST
1. Riser Construction and Location Approval
a. Drain valve
b. Bacddlow device (single check)
a Bell activation device
d. Inspectors test valve
e. Riser s¢ed per approved plans
2. Pressure Test
a. System tested at operating pressure for 2 hours
b. Pressure gauge insta➢ed
3. Sorinider Heads shall not be irtstafled in the fittings prior to the frttinos
betna cemented in place ftern orary test Pit as)
a. Istaflaton and spacing of temporary test plugs
4. Pipara
a. Material installed per plan
b- Hangers per codes/prevent upward movement
c. All CPVC piping shag be installed by persons who have been
certified by the manufacturer for installation of CPVC piping
d. Piping protected from damage
5. Ben
a. Wining InsWed per code
b. Boxes Installed at proper locations
YES I NO
NOTE CPVC plastic pipe in the garage shall not he expeaed. Sparklers that are listed as
Response' or °Residential" must be used.
CORRECTIONS AND
FIRE SPRINKLER NFPA 13D SYSTEM ROUGH INSPECTION APPROVED:
Forms\Fire Sprinkler N A 1 D Sys -Bough O pe on Che Uk DS/12/201