HomeMy WebLinkAboutPA2023-0076_20230803_Incomplete Letter 2023-08-03 I:\Users\PLN\Shared\PA's\PAs - 2023\PA2023-0076\Correspondence\Incomplete Letter\2023- 08-03\PA2023-0076 Incomplete Letter 2023-08-03.docx Page 2 b. Provide any proposed maps and plans in accordance to the requirements of the Lot Line Adjustment/Lot Merger information sheet. 3. Site Development Review: Please review and provide all of the required submittal contents for a Site Development Review, as required by the Back Bay Landing Planned Community Text (PC 9) under Section VII, Letter D. The following documents need to be provided: a. (10) A comprehensive, cohesive and coordinated lighting plan of exterior and parking structure lighting, including locations, fixture height, fixture product type and technical specifications. See redmarks for photometric study. The study needs to be produced at a higher resolution for legibility and some areas near the western property line need light candle projections. b. (14) A statement that the proposed new structure is consistent with the goals, policies, and actions of the General Plan and Planned Community Development Plan. c. Please review the linked list to ensure all documents are accounted for. 4. Coastal Hazards Report (PDF Page 65): a. The report addresses the finished floor elevation of the entrance to the underground station and how it is safe from sea-level rise impacts. However, please address the underground pumps, which is shown to be approximately -22.0 feet on the provided Section Plans. Are the underground elements of the project safe from sea-level rise (SLR)? Please address within the Coastal Hazards Report. Does the entrance to the underground pump station well at 15.5 feet protect the underground well? Can a clear statement be added that it will protect it from flooding? b. The Report’s projected SLR numbers for H++ scenario do not match the State of California’s Sea Level Rise Guidance (see Table 28). Please verify all SLR projection numbers and provide a table which outlines the projected SLR and demonstrate that the proposed facility is protected. Thank you for clarifying the use of the critical infrastructure sea level guidance. However, with 6.6’ rise, what is the baseline of measurement? The maximum bay water elevation is typically 7.7’ NAVD. This is not stated in the report. If it is 7.7’ NAVD, adding 6.6’ equals to 14.3 feet, which is higher than the finished floor of the odor control room and generator room finished floor. The report states that the 14 feet minimum floor elevation is conservative, so please clarify how it complies with sea level rise guidance. 5. Water Quality Management Plan: As a part of the Coastal Development Permit requirements, please submit a Water Quality Management Plan (WQMP) for City review. See comments from City’s Geotechnical Engineer. A meeting has been set up for August 8, 2023 to discuss with the requirements of the preliminary WQMP for City review. This is required for the Coastal Development Permit review findings. 6. Visual Impact Analysis (PDF Page 351): a. Please remove the “Potential Future Coastal Public View Tower” from all plans, as it is no longer a part of the Back Bay Landing project. I:\Users\PLN\Shared\PA's\PAs - 2023\PA2023-0076\Correspondence\Incomplete Letter\2023- 08-03\PA2023-0076 Incomplete Letter 2023-08-03.docx Page 3 b. For all view simulations, please provide an existing vs. proposed (side by side) for effective comparisons. 7. Construction Management Plan (CMP) (PDF Page 372): a. Please note that the use of Lower Castaways Park for construction staging is still being discussed and subject to change. Upon further discussion with city staff, the following direction has been given: i. The lease agreement for Lower Castaways Park needs to be completed and potentially requires review by the City Council (TBD). ii. The terms of the lease agreement is expected to affect the CMP, which was not resubmitted during this review round. iii. Once the lease agreement is approved and completed, please submit the revised CMP for review by Planning and Public Works. This is required prior to any public hearing takes place. 8. Notice of Application Filing: Please provide verification that a completed Notice of Application Filing has been posted to the project site. This can be in the form of a photo of the notice posted on site. See page 8 of linked document for the notice template. 9. Public Noticing Materials: Please note that public noticing materials are required. Per previous discussions, this will be provided once certain project details are resolved (construction staging). As discussed via email, radius map will be required for three separate locations: Pump station site, west-side of the bridge area, and Lower Castaways Park. Please provide all remaining labels. 10. Department Reviews: Please see linked reviews from Geotechnical (dated July 26, 2023). Please note that additional comments from Public Works may come from future review of Construction Management Plan. Upon verification of completion, the application will be processed and scheduled for a Zoning Administrator Hearing. Should you have any questions regarding submittal requirements, please contact David Lee, Senior Planner at 949-644-3225, dlee@newportbeachca.gov. By: David Lee, Senior Planner c: Cindy Murra cmurra@ocsan.gov 550 Newport Center Drive Newport Beach CA 92660 Arcadis U.S., Inc. 445 South Figueroa Street Suite 3650 Los Angeles California 90071 Phone: 213 486 9884 Fax: 213 486 9894 www.arcadis.com 1/7 David Lee Senior Planner City of Newport Beach 100 Civic Center Drive, Newport Beach, CA 92658 Date: July 05, 2023 Subject: 250 East Coast Highway – Notice of Incomplete Filing Dear Mr. Lee: Thank you for your comments on the initial LCP and Development Permit filing for the Orange County Sanitation District’s Bay Bridge Pump Station dated May 1, 2023. Specific comments from the City are shown in bold and responded below. Comments from Fire, Building, and Geotechnical departments are also included below. A list of attachments are provided at the end of this document. 1. Project Description and Justification: Please provide the following project justification and response to findings: a. Site Development Review (20.52.080.F) b. Back Bay Landing Site Development Review (PC 9 Section VII, Letter C) c. Coastal Development Permit (21.52.015.F) The Project Description and Justification submittal has been updated including the finding statements in (a) Site Development Review (20.52.080.F), (b) Back Bay Landing Site Development Review (PC 9 Section VII, Letter C), and (c) Coastal Development Permit (21.52.015.F) per comments received. See Attachment A - Project Description and Justification_Rev 1 d. Lot Line Adjustment (19.76.020.I). See Comment No. 2, below for more additional details. The information for (d) Lot Line Adjustment (19.76.020.I) is provided in response to No. 2 below. e. Include information as provided in emails to the City on April 21, 2023, regarding the status of the Addendum to the EIR and the exemption from City-issued building permits. Per California Code, 53091 d, as a local wastewater agency OC San is exempt from building ordinances for wastewater facilities. The Addendum to the EIR is planned to be adopted at a future Board of Directors Meeting. The addendum will include additional clarification on project staging areas and does not change the project description or analysis. 2. Lot Line Adjustment: a. More information is required regarding the future lot lines of the project site. Provide a written narrative regarding the existing and proposed property lines and the status of the Responses to Notice of Incomplete Filing July 2023 www.arcadis.com 2/7 eminent domain. Preliminarily, the City has determined that Lot Line Adjustment (LLA) is required for the project. However, more details and background would help City Departments solidify that determination (for example, to determine that it is an LLA instead of a lot merger). A Lot line Adjustment (LLA) is not required. The Subdivision Map Act does not apply to property conveyed to or from a governmental agency or public entity. (Gov. Code §66428(a)(2).) Here, OC San owns the property where the existing pump station is located (Parcel 1 of Document recorded in Book 7661, Page 741 of Official Records-4,879 sf) and is acquiring from adjacent property (APN 440-132-60) 9,713 square feet of land for the expansion of OC San’s existing facility. The land being acquired is the subject of an eminent domain case (OC San v. Bayside Village Marina LLC, et. al., OCSC Case No.: 30-2022-01251890) wherein OC San has secured an order of immediate possession. At the conclusion of the eminent domain case, OC San will record a final order of condemnation (Code of Civil Procedure section 1268.030), which will have the effect of creating the new parcel boundaries. The recorded final order of condemnation will be provided to the County Assessor’s office, who will revise the assessor parcel maps accordingly. Attachment B includes a figure illustrating the existing property and the property being acquired. b. Provide any proposed maps and plans in accordance to the requirements of the Lot Line Adjustment/Lot Merger information sheet. As discussed in connection with Comment a above, a lot line adjustment is not required. The revised boundaries of the properties will be created by the recording of the final order of condemnation at the conclusion of the eminent domain case. The County Assessor will revise the assessor parcel maps upon receipt of the final order of condemnation in accordance with the final order of condemnation. Attachment C includes the legal description and plat map of the property being acquired in fee for the expansion of the pump station. 3. Site Development Review: Please review and provide all of the required submittal contents for a Site Development Review, as required by the Back Bay Landing Planned Community Text (PC 9) under Section VII, Letter D. The following documents need to be provided: a. (10) A comprehensive, cohesive and coordinated lighting plan of exterior and parking structure lighting, including locations, fixture height, fixture product type and technical specifications. The requested lighting information has been included in Attachment D, Lighting Plan, Datasheet, and Specification. b. (14) A statement that the proposed new structure is consistent with the goals, policies, and actions of the General Plan and Planned Community Development Plan. The statement has been included in Attachment A, Project Description and Justification_Rev 1. Also see response to Comment No. 1. Responses to Notice of Incomplete Filing July 2023 www.arcadis.com 3/7 c. Please review the linked list to ensure all documents are accounted for. The requirements identified in the Back Bay Landing Planned Community (PC 9) Site Development Review under Section VII, Letter D have been reviewed and verified. All the applicable documents are provided either through the original application and/or this response letter. 4. Coastal Hazards Report (PDF Page 65): a. The report addresses the finished floor elevation of the entrance to the underground station and how it is safe from sea-level rise impacts. However, please address the underground pumps, which is shown to be approximately -22.0 feet on the provided Section Plans. Are the underground elements of the project safe from sea-level rise (SLR)? Please address within the Coastal Hazards Report. Yes, the underground pump station is also safe from the sea-level rise (SLR) since the entrance to the underground pump station is at the same elevation as the electrical room at 15.50 feet NAVD88. The following sentence has been included in the Coastal Hazardous Report, “The entrance to the underground pump station dry well is elevated to the same elevation of the electrical building finished floor at 15.5 feet NVAD88.” b. The Report’s projected SLR numbers for H++ scenario do not match the State of California’s Sea Level Rise Guidance (see Table 28). Please verify all SLR projection numbers and provide a table which outlines the projected SLR and demonstrate that the proposed facility is protected. The Bay Bridge Pump Station is designed considering a more conservative SLR reference from the State of California’s Sea Level Rise Guidance and Critical Infrastructure at Risk: Sea Level Rise Planning Guidance for California’s Coastal Zone. Final Adopted Guidance. November 17, 2021 as shown in the table below. The State of California’s Sea Level Rise Guidance reference has also been included in the updated Coastal Hazardous Report in Attachment E. Year Critical Infrastructure at Risk: Sea Level Rise Planning Guidance for California’s Coastal Zone State of California’s Sea Level Rise Guidance – Table 28 2050 2.7 2.6 2080 6.6 6.4 5. Water Quality Management Plan: As a part of the Coastal Development Permit requirements, please submit a Water Quality Management Plan (WQMP) for City review. A Water Quality Management Plan has been developed and included as Attachment F. Responses to Notice of Incomplete Filing July 2023 www.arcadis.com 4/7 6. Visual Impact Analysis (PDF Page 351): a. Please remove the “Potential Future Coastal Public View Tower” from all plans, as it is no longer a part of the Back Bay Landing project. The “Potential Future Coastal Public View Tower” has been removed from all plans. See the updated Visual Impact Analysis_Rev 1 included in Attachment G. b. For all view simulations, please provide an existing vs. proposed (side by side) for effective comparisons. Existing vs. proposed (side by side) visual simulation comparisons are included in the Visual Impact Analysis_Rev 1 in Attachment G. 7. Construction Management Plan (PDF Page 372): a. Please note that the use of Lower Castaways Park for construction staging is still being discussed and subject to change. It is noted that the use of Lower Castaways Park for construction staging is still being discussed and subject to change. 8. Notice of Application Filing: Please provide verification that a completed Notice of Application Filing has been posted to the project site. This can be in the form of a photo of the notice posted on site. See page 8 of linked document for the notice template. Notice of Application Filing has been posted on the project site. See Attachment H – Site Photos for Notice of Application Filing. 9. Public Noticing Materials: Please note that public noticing materials are required. Per previous discussions, this will be provided once certain project details are resolved (construction staging). Noted. The public noticing materials are under development and will be provided when ready. 10. Department Reviews: Please see linked reviews from Building, Fire, Geotechnical, and Municipal Operations. Please note that additional comments from Public Works and Utilities Departments are pending and will be provided when ready. FYI, these comments may further affect the project resubmittal. Fire Comments: 1) Provide premise identification per NBFD guideline. The premise identification of 250 address ID has been included in the design. The detail of the address ID has been included in Attachment I - Updated Architectural Drawings. 2) Provide Knox box for emergency access. Knox boxes are provided near the north and south gates of the project site. See the updated Architectural Drawings in Attachment I. 3) Provide NFPA 704 placarding for onsite hazards. NFPA 704 signs will be installed where required. Responses to Notice of Incomplete Filing July 2023 www.arcadis.com 5/7 Building Comments: 1) A second means of egress will be required from the basement and roof levels if the exit access travel distance exceeds 75 feet (100 feet if the building is equipped with an NFPA 13 fire sprinkler system) from the most remote location in on each level to the exit door at the ground floor level (CBC 1006.3.4). The occupancy classification for the pump station is F-1 (CBC 306). Means of Egress comment: The project site is exempted from the requirement of the second means of egress per the following CBC code sections: 405.1 General “Exceptions: 6. Pumping stations and other similar mechanical spaces intended only for limited periodic use by service or maintenance personnel.” 1006.2.1 Egress Based on Occupant Load and Common Path of Egress Travel Distance “Exceptions: 3. Unoccupied mechanical rooms and penthouses are not required to comply with the common path of egress travel distance measurement.” The proposed occupancy classification for the pump station is Factory Industrial F-2 Low Hazard Occupancy. This is in line with other pump stations OC San owns throughout the City including the Rocky Point and Bitter Point Pump Stations. 2) The proposed project is in a Soils Liquefaction Seismic Hazard Area. The soils report shall include the analyses described in City of Newport Beach Building Code Policy CBC 1803.5.11-12 and recommendations for the mitigation of the effects of soils liquefaction. The soils report submitted with the original application included evaluation of liquefaction potential and mitigation measures. Geotechnical Comments: 1) The site is located in a Liquefaction Seismic Hazard Zone, for purposes of Geotechnical and Structural design of the building the Project is assumed to be in Seismic Risk Category IV per Table 1604.5 of the 2022CBC. To reduce the Risk to Category III the project engineer must prove that the building will not exceed the maximum allowable quantities per control area as given in Table 307.1(2) of the 2022CBC. The Geotechnical Engineer must determine Site Classification per ASCE7-16 Chapter 20, Table 20-3-1 with supporting blow count or shear wave velocities. Soils vulnerable to potential failure due to liquefaction, sensitive clays and collapsible weakly cemented soils are required to perform a Site-Specific Ground Motion for Seismic Design with exception of buildings having a fundamental period of vibration equal to or less than 0.5 seconds. If the exception is stablished the site class is permitted to be determined in accordance with section 20.3 and the corresponding values of Fa and Fv determined from Tables 11-4-1 and 11-4-2. The Bay Bridge Pump Station is designed based on Risk Category IV for all structures. Responses to Notice of Incomplete Filing July 2023 www.arcadis.com 6/7 2) The geotechnical report must also provide estimated differential settlement for the proposed structure and proposed 30”-inch and 24”-inch sewer lines along with remedial recommendations to prevent damage. Differential settlement is provided in the project Geotechnical Report provided with the original submittal: 6.9.1 Pump Station and Pipeline Differential Settlement Some materials encountered in the pump station area indicate that liquefaction could occur during a seismic event. Based on our analyses, settlement up to about 4 inches at the ground surface and up to about 6 inches of lateral spreading could occur. Foundations extending more than about 25 feet bgs (elevation -13 ft or deeper) could experience about 1 inch of post-liquefaction settlement. Although the probability of liquefaction occurring in all layers susceptible to liquefaction should be considered small, if the resulting differential movements from post-earthquake liquefaction movement cannot be tolerated, flexible pipe connections should be considered to reduce the risk of damage resulting from soil movement, and mitigation of underlying soils (e.g., grout injection, over excavation) should be considered to help lessen the magnitude of potential soil movement. To mitigate the differential settlement associated with utilities and shallow foundations, soil improvements will be completed. 3) Provide specifications for the construction and removal of existing lines. The existing pipelines will not be removed, rather they will be filled with 1-sack slurry and abandoned in place. Following review of the above responses and associated attachments, please feel free to reach out with any questions. Furthermore, we are eager to schedule the Zoning Administrator Hearing with the City and Orange County Sanitation District, if one is deemed necessary. Please reach out with your preferred timing and location and how we can be of further assistance. Sincerely, Arcadis U.S., Inc. Harmik Aghanian Project Manager Email: Harmik.Aghanian@arcadis.com Direct Line: 213-797-5285 CC. Cindy Murra, Orange County Sanitation District Responses to Notice of Incomplete Filing July 2023 www.arcadis.com 7/7 Enclosures: Attachment A – Project Description and Justification_Rev 1 Attachment B – Lot Lines and Easements Attachment C – Legal Descriptions for Acquisition Parcels Attachment D – Lighting Plan, Datasheet, and Specification Attachment E – Coastal Hazardous Report_Rev 1 Attachment F – Water Quality Management Plan Attachment G – Visual Impact Analysis_Rev 1 Attachment H – Site Photos for Notice of Application Filing Attachment I – Updated Architectural Drawings Attachment A Project Description Justification _Rev 1 Bay Bridge Pump Station Replacement Project No. 5-67 Project Description and Justification Orange County Sanitation District (OC San) owns, operates, and maintains the wastewater pump stations and Newport Force Main (NFM) network along the Pacific Coast Highway (PCH) in the City of Newport Beach (City), California. The network conveys wastewater to the Plant No. 2 wastewater treatment facility in Huntington Beach. The existing Bay Bridge Pump Station (BBPS) conveys approximately half the wastewater flow generated in the City and the wastewater will eventually be treated at OC San Plant No.2. The locations of the existing and proposed pump stations are shown on Figure ES-1 and Figure ES-2. The existing BBPS was constructed in 1966 (Project No. 5-12) and upgraded in 1995 with new pumps, piping and ventilation modifications, structural upgrades, architectural revisions, and a standby generator (Project 5-33). In 2014, another pump was added for increased capacity and reliability (under Project 5- 60). The existing BBPS has been over 50 years and requires replacement. The Bay Bridge Pump Station Replacement Project (Project 5-67) includes the replacement of both the pump station and the associated force mains. The work includes demolition of the existing pump station building, construction of a new underground pump room (approximately. 2,500 sf), and above grade facilities consisting of an electrical room, an odor control facility, and a generator room (three buildings; totaling approximately 3,630 sf). The new dual force main alignment is approximately 1,300 linear feet and is located adjacent to the existing force mains. The project is in compliance of the following requirements as stated in Site Development Review (20.52.080.F), Back Bay Landing Site Development Review (PC 9 Section VII, Letter C), Coastal Development Permit (21.52.015.F): 1) Allowed within the subject zoning district; 2) Compliance with the Site Development Review, the General Plan, the Zoning Code, Coastal Land Use Plan, Back Bay Landing Planned Community Development Plan, any applicable specific plan, and other applicable criteria and policies related to the use or structure; 3) The efficient arrangement of structures on the site and the harmonious relationship of the structures to one another and to other adjacent developments; and whether the relationship is based on standards of good design; 4) The compatibility in terms of bulk, scale, and aesthetic treatment of structures on the site and adjacent developments and public areas; 5) The development shall be sited and designed to maximize the aesthetic quality of the project as viewed from surrounding roadways, properties, and waterfront, with special consideration given to providing a variety of building heights, massing, and architectural treatments to provide public views through the site; 6) The adequacy, efficiency, and safety of pedestrian and vehicular access, including drive aisles, driveways, and parking and loading spaces; 7) The adequacy and efficiency of landscaping and open space areas and the use of water efficient plant and irrigation materials; 8) The protection of significant views from public right(s)-of-way and compliance with Section 20.30.100 (Public View Protection); Bay Bridge Pump Station Replacement Project No. 5-67 9) Not detrimental to the harmonious and orderly growth of the City, nor endangers, jeopardizes, or otherwise constitutes a hazard to the public convenience, health, interest, safety, or general welfare of persons residing or working in the neighborhood of the proposed development; and 10) Conforms to all applicable sections of the certified Local Coastal Program; Per California Code, 53091 d, as a local wastewater agency OC San is exempt from building ordinances for wastewater facilities. An EIR was prepared for the Bay Bridge Pump Station Replacement Project in August 2020 and the document can be accessed via https://ceqanet.opr.ca.gov/Project/2016111031. REGIONAL VICINITY MAP NO R T H \\n a . a e c o m n e t . c o m \ l f s \ A M E R \ O r a n g e - U S O R A 1 \ D C S \ P r o j e c t s \ W T R \ 6 0 5 5 8 5 5 0 _ B a y B r i d g e \ 5 0 0 - D e l i v e r a b l e s \ 5 0 9 - D e s i g n M e m o 6 - 2 0 2 1 \ F i g u r e s a n d T a b l e s \ D W G s \ F i g u r e E S - 1 . d w g L A Y O U T : F I G U R E 1 S A V E D : 8 / 1 3 / 2 0 2 1 1 1 : 1 8 A M A C A D V E R : 2 3 . 1 S ( L M S T E C H ) P A G E S E T U P : - - - - P L O T S T Y L E T A B L E : - - - - PL O T T E D : 8 / 2 6 / 2 0 2 1 7 : 3 8 A M B Y : P R O C T O R , A L A N FIGURE ES-1 LEGEND PROJECT LOCATION COUNTY BOUNDARY N BAYSIDE PROPOSED PUMP STATION EXISTING PUMP STATION P A C I F I C COAST HWY PROJECT LOCATION MAP Scale: 1 in = 200 ft 0 200'400' NO R T H FIGURE ES-2 Attachment B Lot Lines and Easements ENTRANCE & EXIT ON BAY SIDE DRIVE 4,879 SF 9,713 SF Attachment C Legal Descriptions for Acquisition Parcels Page 1 of 2 EXHIBIT “A-1” 1 2 LEGAL DESCRIPTION 3 PARCEL 5-67-01 (FEE) 4 5 ORANGE COUNTY SANITATION DISTRICT 6 BAY BRIDGE PUMP STATION 7 8 That certain parcel of land situated in the City of Newport Beach, County of Orange State of 9 California, being that portion of Parcel 3 of Parcel Map No. 93-111 filed in Book 278, Pages 10 40 through 45 of Parcel Maps in the Office of the County Recorder of said Orange County, 11 described as follows: 12 13 COMMENCING at the easterly terminus of that certain course in the centerline of the East 14 Coast Highway shown as “North 87°36’58” West 160.15 feet” on said Parcel Map No. 93-111, 15 said point also being marked with a “spike and washer tagged DOH per Caltrans F.B. SR. 16 81-115/11” per said Parcel Map No. 93-111; 17 thence along said centerline North 87°36’58” West 160.15 feet to the northwesterly terminus 18 thereof, said point also being marked with a “spike and washer tagged DOH per Caltrans F.B. 19 SR. 81-115/11” per said Parcel Map No. 93-111; 20 thence leaving said centerline at right angles North 02°23’02” East 85.94 feet to a line shown 21 as “North 87°36’16” West 123.34 feet” in the southerly boundary of said Parcel 3, said line 22 also being the northerly Right-of-Way line of the East Coast Highway as shown on said Parcel 23 Map No. 93-11 and also shown on a Caltrans Right-of-Way Map No. 25491-C for 07-ORA-1 24 18.3; 25 thence along said southerly line of Parcel 3 North 87°36’16” West 65.10 feet to the intersection 26 of the southerly boundary of said Parcel 3 and the easterly line of Parcel 1 Dedicated to the 27 Orange County Sanitation District in a document recorded September 10, 1965 in Book 7661, 28 Page 741 of Official Records, in the Office of said Orange County Recorder, said point also 29 being the TRUE POINT OF BEGINNING; 30 thence North 13°39'41" East 71.32 feet; 31 thence North 76°24'23" West 173.32 feet; 32 thence South 13°39'46" West 79.83 feet to a line shown as “North 66°24’24” West 284.74 33 feet” in said southerly boundary of Parcel 3; 34 thence along said southerly boundary of Parcel 3 the following six (6) courses: 35 (1) South 66°24'24" East 8.72 feet to an angle point therein; 36 (2) South 73°06'54" East 43.65 feet to an angle point therein; 37 (3) South 83°06'23" East 60.83 feet to an angle point therein; 38 (4) North 01°46'10" West 60.00 feet to an angle point therein; 39 (5) North 88°13'14" East 60.00 feet to an angle point therein; 40 ORANGE COUNTY SANITATION DISTRICT BAY BRIDGE PUMP STATION PARCEL 5-67-01 (FEE) Page 2 of 2 (6) South 01°46'46" East 70.87 feet to an angle point therein to the TRUE POINT OF 41 BEGINNING. 42 43 CONTAINING: 9,713 Square Feet more or less. 44 45 EXHIBIT “A-2” attached and by this reference made a part hereof. 46 47 48 49 50 51 52 53 54 Steven C. Slocum, P.L.S. 9044 Date 55 56 Michael Baker International 57 5 Hutton Centre Drive, Suite 500 58 Santa Ana, California 92707 59 Project No. 163755 60 H:\pdata\163755\CADD\Mapping\Exhibits\Pump Station Legals and Exhibits\Legal\163755-00A1 - Legal Fee Parcel.docx 61 08/17/2021 5 Hutton Centre Drive, Suite 500 Santa Ana, CA 92707 (949) 472-3505 ·MBAKERINTL.COM 5 Hutton Centre Drive, Suite 500 Santa Ana, CA 92707 (949) 472-3505 ·MBAKERINTL.COM Attachment D Lighting Plan, Datasheet, and Specification TRANSFORMER ACCESS HATCH GENERATOR ROOM RAISED PLATFORM ELECTRICAL ROOM ODOR CONTROL AREA PUMP STATION (BELOW GRADE) NORTH GATE 24' WIDE SWING GATE SOUTH GATE 24' WIDE SWING GATE WEST GATE 18' WIDE CANTILEVER SLIDING GATE MANHOLE COVERS, TYP. SEE STRUCTL DWGS RAISED PLATFORM 45.57' 16.23' 9.52' TOW = 29.33' PEDESTRIAN GATE 8' HIGH WALL 10' HIGH WALL 8' HIGH WALL F U T U R E A C C E S S R O A D P A C I F I C C O A S T H I G H W A Y (E) BUILDING STRUCTURE OUTLINE 10' HIGH WALL 8' HIGH WALL 10' HIGH WALL 15' HIGH WALL 15' HIGH WALL A2001 1 A20012 A2001 3 A2001 4 173.84' 57.26' 18.00' 4.44' EXTERIOR WALL BOUNDARY SWITCHBOARD 106.32' 133.53' 39.48' 24.00' 43.99' LANDSCAPE AREA (SEE LANDSCAPE DWGS) 6' - 5 1/8" LANDSCAPE AREA (SEE LANDSCAPE DWGS) TOW = 24.00' TOW = 24.00' TOW = 24.00' TOW = 24.83' TOW = 22.83' TOW = 21.50' TOW = 21.50' 6' - 10" 23' - 7 5/8" 41' - 7 7/8" TOW = 21.50' 9 TOW = 24.83' TOW = 29.33' 5.07' TOW = 22.83' TOW = 22.83' TOW = 29.33' TOW = 29.33' SWITCHBOARD PLATFORM (REMOVABLE) FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2 3 4 5 6 7 8 9 10 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 4/20/2023 6:17:34 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt A1001 BAY BRIDGE PUMP STATION REPLACEMENT SITE PLAN 30259 JOHN ERIC CHUNG RUOTIAN CAI SIEGFREDO LOPEZ SCALE: 1/8" = 1'-0" SITE PLAN MARK DESCRIPTION DATE APPR. E3 CITIZEN LED, 17W, APPROXIMATE 10 FT AFG. TYP OF 10. (GENERATOR AND ELECTRICAL ROOM AREA) E3 CITIZEN LED, 17W, APPROXIMATE 10 FT AFG. TYP OF 10. (GENERATOR AND ELECTRICAL ROOM AREA) WE-EF PLS420 LED, 18W, APPROXIMATE 8 FT AFG. TYP OF 4. (INSIDE PERIMETER WALL) E3 CITIZEN LED, 17W, APPROXIMATE 10 FT AFG. TYP OF 10. (GENERATOR AND ELECTRICAL ROOM AREA) WE-EF PLS420 LED, 18W, APPROXIMATE 8 FT AFG. TYP OF 4. (INSIDE PERIMETER WALL) VIGILANT LED AREA LIGHT ALU7AC26DWNNGN, 40W, AFG APPROXIATE 10-11 FT. TYP OF 5. (ELECTRICAL ROOM AREA) ALU7AC26DWNNGN, 40W, APPROXIMATE 9 FT AFG. TYP OF 4. (ODOR CONTROL AREA) LIGHT FIXTURE SCHEDULE TYPE WATTS MOUNT DESCRIPTION MANUFACTURER AW PENDANT%RAC.ETWALL MULTI9OLT LED LINEAR FIXTURE INCHES IN LENGTH WITH A MINIMUM LIGHT OUTPUT OF  LUMENS COLOR RENDERING INDEX  AND LED COLOR TEMPERATURE %E . FIXTURE SHALL %E ENCLOSED GAS.ETED AND SUITA%LE FOR USE IN WET LOCATIONS PRO9IDE FIXTURE WITH U9STA%ILI=ED HIGHIMPACT FROSTED ACRYLIC LENS FOR UNIFORM LIGHT OUTPUT AND HIGH IMPACT RESISTANCE FIXTURE SHALL %E PRO9IDED WITH HIGH EFFICIENCY LEDS 9 DIMMING STANDARD FOR A DIMMING RANGE OF  TO  FIXTURE SHALL HA9E SURGE PROTECTION SINGLE FUSE AND AN IP RATING FIXTURE SHALL %E SUITA%LE FOR WET LOCATIONS WITH AM%IENT TEMPERATURE UP TO  DEGREES FAHRENHEIT FIXTURE SHALL %E A DESIGNLIGHTS CONSORTIUM 4UALIFIED PRODUCT AND SHALL %E UL LISTED HOLOPHANE LIGHTING EMS SERIES OR E4UAL AEM W PENDANT%RAC.ETWALL MULTI9OLT LED LINEAR FIXTURE INCHES IN LENGTH WITH A MINIMUM LIGHT OUTPUT OF  LUMENS COLOR RENDERING INDEX  AND LED COLOR TEMPERATURE %E . FIXTURE SHALL %E ENCLOSED GAS.ETED AND SUITA%LE FOR USE IN WET LOCATIONS PRO9IDE FIXTURE WITH U9STA%ILI=ED HIGHIMPACT FROSTED ACRYLIC LENS FOR UNIFORM LIGHT OUTPUT AND HIGH IMPACT RESISTANCE FIXTURE SHALL %E PRO9IDED WITH HIGH EFFICIENCY LEDS 9 DIMMING STANDARD FOR A DIMMING RANGE OF  TO  FIXTURE SHALL HA9E SURGE PROTECTION SINGLE FUSE AND AN IP RATING FIXTURE SHALL %E SUITA%LE FOR WET LOCATIONS WITH AM%IENT TEMPERATURE UP TO  DEGREES FAHRENHEIT FIXTURE SHALL %E A DESIGNLIGHTS CONSORTIUM 4UALIFIED PRODUCT AND SHALL %E UL LISTED FIXTURE SHALL INCLUDE EM SELFDIAGNOSTICS %ATTERY PAC. HOLOPHANE LIGHTING EMS SERIES OR E4UAL AW PENDANT%RAC.ETWALL SAME AS LIGHT FIXTURE TYPE A EXCEPT WITH A MINIMUM LIGHT OUTPUT OF  LUMENS HOLOPHANE LIGHTING EMS SERIES OR E4UAL AEM W PENDANT%RAC.ETWALL SAME AS LIGHT FIXTURE TYPE AEM EXCEPT WITH A MINIMUM LIGHT OUTPUT OF  LUMENS HOLOPHANE LIGHTING EMS SERIES OR E4UAL %W WALL 9 LED WALLPAC. LED COLOR TEMPERATURE OF . AND  CRI TYPE I9 MEDIUM LIGHT DISTRI%UTION HOUSING SHALL %E HEA9Y GRADE A CAST ALUMINUM WITH IP RATING FOR USE IN WET LOCATIONS CONTROLS SHALL CONSIST OF AN INTEGRAL %UTTON STYLE PHOTOCONTROL PRO9IDE WITH SINGLE FUSE INTEGRAL SURGE PROTECTION AND TAMPER RESISTANT HARDWARE WEEF PLS LED OR E4UAL C W WALLCEILING 9 LED TYPE HA=ARDOUS AREA LIGHTING FIXTURE HEA9Y DUTY UL LISTED CLASS  DI9ISION  GROUP D LOCATIONS IP RATED  LENGTH  LUMENS DIMMA%LE . WALLCEILING MOUNTING HOLOPHANE HXPL SERIES D W RECESSED E CITI=EN LED ER ELEMENT  ROUND ƒ DEGREE %EAM  ƒ TILT CRI . 9 FLANGED HEA9YGAUGE HOUSING DIECAST ALUMINUM TRIM ANTI4UE %RON=E FINISH %E9EL STYLE ETL LISTED WET LISTED TECH LIGHTING ELEMENT  LED FIXED DOWNLIGHT EMW WALL 9 TWO  WATT LED LAMPS INDUSTRIAL EMERGENCY LIGHT WET LOCATION AND NEMA X RATED FIXTURE SHALL PRO9IDE SAME LE9EL OF LUMEN OUTPUT FOR FULL  MINUTES OF %ATTERY DISCHARGE WITH NO LIGHT DEGRADATION EMERGENCY LIGHT FIXTURE SHALL %E PRO9IDED WITH SELFDIAGNOSTICS TO MONITOR LED STATUS LED DRI9ER CIRCUIT %ATTERY CAPACITY AND CHARGER FUNCTION AND SHALL DISPLAY ANY FAULT DETECTION %Y MEANS OF FLASHING CODE FLAMERATED U9 STA%LE THERMOPLASTIC HOUSING FULLY GAS.ETED AND CORROSION RESISTANT LED %ASED LAMPHEADS CONSTRUCTED OF HIGH STRENGTH DIECAST ALUMINUM WITH POLYCAR%ONATE LENS %ATTERY SHALL %E MAINTENANCEFREE LITHIUM IRON PHOSPHATE TYPE AND SHALL PRO9IDE  MINUTES OF EMERGENCY POWER UL LISTED FOR CLASS  DI9ISION  GROUP D HA=ARDOUS LOCATIONS LED COLOR TEMPERATURE SHALL %E . PRO9IDE %RAC.ETS FOR SURFACE MOUNT AS RE4UIRED HU%%ELL LIGHTING DUAL LITE DYNAMO DYN SERIES OR E4UAL EEMW WALL WALL MOUNT 9 W EXIT SIGN WITH TWIN W HALOGEN LAMP EMERGENCY LIGHT COM%INATION CONSTRUCTED OF IMPACTRESISTANT FI%ERGLASS REINFORCED POLYESTER HOUSING ONEPIECE FORMED GAS.ET AND CORROSIONRESISTANT HARDWARE LAMP HEADS SHALL %E POLYCAR%ONATE PAR SEALED %EAM FIXURE SHALL %E PRO9IDED WITH SELFDIAGNOSTICS TO MONITOR LAMPS %ATTERY AND CHARGER %ATTERY SHALL %E MAINTENANCEFREE SEALED NIC.ELMETAL HYDRIDE TYPE AND SHALL PRO9IDE  MINUTES OF EMERGENCY POWER LETTERS SHALL %E RED INCHES HIGH WITH INCH STRO.E WITH FEET 9IEWING DISTANCE RATING UL  LISTED UL LISTED FOR CLASS  DI9ISION  GROUP D HA=ARDOUS LOCATIONS MULE LIGHTING S9XH SERIES OR E4UAL EW WALL M9OLT LED LAMP INDUSTRIAL AND SUITA%LE FOR DAMP LOCATIONS EXIT SIGN SHALL MEET UL NFPA  CURRENT LIFE SAFETY CODE  NEC AND OSHA ILLUMINATION STANDARDS ALUMINUM HOUSING UNI9ERSAL DIRECTIONAL INDICATOR .NOC.OUTS AND MOUNTING LETTERS SHALL %E  INCHES HIGH  INCH STRO.E WITH  FEET 9IEWING DISTANCE RATING %ASED ON UL STANDARD LITHONIA LIGHTING LE SERIES OR E4UAL F W %RAC.ETWALL MULTI9OLT LOW PROFILE AREA LED LIGHT WITH MINIMUM LIGHT OUTPUT OF  LUMENS COLOR RENDERING INDEX  LED COLOR TEMPERATURE . AND 9 DIMMING FOR A DIMMING RANGE OF  TO  FIXTURE HOUSING SHALL %E COPPERFREE ALUMINUM WITH DUAL SEALED POLYESTER GRAY COLOR TOPCOAT FINISH FIXTURE LENS SHALL %E CLEAR IMPACT RESISTANT TEMPERED GLASS WITH DEGREES %EAM DISTRI%UTION PRO9IDE FIXTURE WITH INDI9IDUAL WIRE LEADS FOR TERMINATION IN FXTURE HOUSING AND A DEGREE MOUNTING %RAC.ET FOR MOUNTING ON STEEL COLUMN FIXTURE SHALL %E FACTORY SEALED UL LISTED FOR OUTDOOR LOCATIONS VIGILENT LED AREA LIGHT SERIES OR EQUAL G W  DEGREE STANCHION  9OLT LED AREA LED LIGHT WITH MINIMUM LIGHT OUTPUT OF  LUMENS COLOR RENDERING INDEX  LED COLOR TEMPERATURE . FIXTURE HOUSING SHALL %E COPPERFREE ALUMINUM WITH DUAL SEALED POLYESTER GRAY COLOR TOPCOAT FINISH FIXTURE LENS SHALL %E POLYCAR%ONATE LENS DEGREES %EAM DISTRI%UTION PRO9IDE FIXTURE WITH INDI9IDUAL WIRE LEADS FOR TERMINATION IN FXTURE HOUSING AND A DEGREE MOUNTING %RAC.ET FOR MOUNTING ON  CONDUIT FIXTURE SHALL %E FACTORY SEALED UL LISTED FOR CLASS  DI9ISION  GROUP D LOCATIONS DIALIGHT SAFESITE SERIES OR EQUAL E0005  LIGHTING FIXTURE SCHEDULE -EFF SO.OL CHRISTINA LAN=EL %RIAN YOUNG A 1 2 3 4 5 6 7 8 9 10 B C D E F MARK DATE APPR.DESCRIPTION DW G  C  ? U V H U V ? C L D Q ] H O ? A C C D R F V ? A U F D G L V ? A U S           O C S D ²     % D \ % U L G J H P X P S S W D W L R Q ? P U R M H F W F L O H V ? F D S ? A X W R C A D ? S H E E T S ? E L E C ?      E      G Z J DA T E  A S U            S P U S E R  C L D Q ] H O DRAWING NO IF NOT SCALE ACCORDINGLY AT FULL SI=E LINE IS  INCHES ORANGE COUNTY SANITATION DISTRICT FDS APRIL 2023 NOT FOR CONSTRUCTION DRAWN %Y DESIGNED %Y CHEC.ED %Y BAY BRIDGE PUMP STATION REPLACEMENT 5-67 OFSHEET NO MC CB CB W( B ) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B) J J JJ J E ( B ) E( B ) E( B ) E( B ) E(B) E(B) T ( B ) T(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B) J J J CB W( B ) ST(B) ST(B)ST(B)ST(B)ST(B)ST(B)ST(B) J J E ( B ) E( B ) E( B ) E( B ) E(B) E(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B) TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B) J A 1 2 3 4 5 6 7 8 9 10 B C D E F MARK DATE APPR.DESCRIPTION DW G : C : \ U s e r s \ C L a n z e l \ A C C D o c s \ A r c a d i s \ A U S - 3 0 0 0 1 6 8 7 - O C S D – 5 - 6 7 B a y B r i d g e P u m p S t a t i o n \ P r o j e c t F i l e s \ F D S \ A u t o C A D \ S H E E T S \ E L E C \ 5 - 6 7 - E 1 0 0 1 . d w g DA T E : A p r 1 9 , 2 0 2 3 6 : 0 4 p m U S E R : C L a n z e l DRAWING NO. (IF NOT 2"-SCALE ACCORDINGLY) AT FULL SIZE LINE IS 2 INCHES ORANGE COUNTY SANITATION DISTRICT FDS APRIL 2023 NOT FOR CONSTRUCTION DRAWN BY: DESIGNED BY: CHECKED BY: BAY BRIDGE PUMP STATION REPLACEMENT 5-67 302OFSHEET NO.: 10'20'0'10' SCALE: 1" = 10' Underground Service Alert TWO WORKING DAYS BEFORE YOU DIG Call:811 E1001 165 ELECTRICAL SITE PLAN CHRISTINA LANZEL BRIAN YOUNG JEFF SOKOL IRRIGATION CONTROLLER EXISTING SOUTHERN CALIFORNIA EDISON (SCE) UNDERGROUND PULLBOX FOR ACQUISITION OF TEMPORARY CIRCUIT. COORDINATE ALL WORK WITH SCE. EXISTING TELEPHONE COMPANY UNDERGROUND PULLBOX FOR ACQUISITION OF NEW COMMUNICATIONS CIRCUIT. COORDINATE ALL WORK WITH TELEPHONE COMPANY. NOTES: 1.JUNCTION BOX SHALL BE 12"Hx12"Wx6"D, NEMA 4X WITH TOP AT 72" AFF. 2.FURNISH AND INSTALL 3/4" CONDUIT WITH 2-#12, 1-#12G BETWEEN LIGHT FIXTURES AND ROUTE A HOMERUN TO LIGHTING CONTROL PANEL 1 INSIDE OF THE ELECTRICAL ROOM. 3.INSTALL UNDERGROUND DUCTANKS IN ACCORDANCE WITH OCSAN STANDARD DETAIL S-400 AND RESPECTIVE DUCTBANK SECTIONS. 4.JUNCTION BOX FOR FUTURE ACCESS CONTROL DEVICES AND CABLES AT PERSONNEL GATE. SEE DRAWING D6014 FOR REQUIREMENTS. METERING SWITCHBOARD SCE UTILITY TRANSFORMER PROVIDE CONCRETE PAD, PRIMARY DUCTBANK AND SECONDARY DUCTBANK IN ACCORDANCE WITH SCE REQUIREMENTS. ELECTRICAL ROOM SEE E1002 TO E1009 GENERATOR ROOM SEE E1016, E1017, E1018 ODOR CONTROL AREA SEE E1019, E1020, E1021 8'-0" AFG (NOTE 2) 8'-0" AFG (NOTE 2) 18 B 18 B 8'-0" AFG (NOTE 2) 18 B 55JSWB126 UTILITY POWER HIGH RESISTANCE GROUNDING SYSTEM 55JLE035 S55J035 S55J050 55JAE050 55JLE038 S55J941 S55J038 N55JTTBA 55JSJB8022 S55J8022A 55JZSC634 N55J036RI N55J036MI N55J036PI P55J696B S55J8022B (NOTE 1) 11 E3 0 0 8 2 E3 0 0 8 22 E3 0 0 8 1 E3008 2 1 E 3 0 0 8 8'-0" AFG (NOTE 2) 18 B PNL-A CKT 38 PNL-A CKT 38 PNL-A CKT 38 PNL-A CKT 38 EXISTING SCE TRANSFORMER TEMPORARY UNDERGROUND PRIMARY CIRCUIT FOR EXISTING SCE TRANSFORMER DURING CONSTRUCTION. PROVIDE UNDERGROUND DUCTBANK PER SCE REQUIREMENTS. EXISTING PUMP STATION TEMPORARY POWER PLAN SECURITY CAMERA #5 SECURITY CAMERA #1 SECURITY CAMERA #3 SECURITY CAMERA #4 SECURITY CAMERA #2 SECURITY CAMERA #7 C55J634C 55JZSC634A METERING SWITCHBOARD TVSS UNIT EXISTING SOUTHERN CALIFORNIA EDISON (SCE) UNDERGROUND PULLBOX FOR ACQUISITION OF NEW PRIMARY CIRCUIT. COORDINATE ALL WORK WITH SCE. NOTE 3 (TYP) SECURITY CAMERA #8 NOTE 4 ZSC062H NOTE 4 INTRINSICALLY SAFE RELAY PANEL COMBUSTIBLE GAS CALIBRATION PANEL S55J942 N55JTTBB S55J943 IS55J040 55JLSH040 EF WALL MOUNT WITH 45 DEGREE ANGLE BRACKET 9'-0" AFF EEM1 36 MOUNT ABOVE DOOR D 17 MOUNT RECESSED IN CANOPY D 17 MOUNT RECESSED IN CANOPY E1 5 MOUNT ABOVE DOOR D 17 MOUNT RECESSED IN CANOPY A1/EM 50 E1 5 MOUNT ABOVE DOOR PHOTOCELL F 40 EXTERIOR FIXTURES SHOWN IN APPROXIMATE LOCATION. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION. (TYP) WALL MOUNT WITH 45 DEGREE ANGLE BRACKET 9'-0" AFF WALL MOUNT WITH 45 DEGREE ANGLE BRACKET 9'-0" AFF SWITCH FOR RESTROOM LIGHTS 0-30 MINUTE TIMER SWITCH FOR EXHAUST FAN A1/EM 50 A1 50 3 3 PNL A CKT 16 NL/EM PNL A CKT 16 PNL A CKT 16 PNL A CKT 16 NL/EM PNL A CKT 16 NL/EM PNL A CKT 16 PNL A CKT 16 PNL A CKT 16 NL/EM GFCI PNL A CKT 14 NOTE 1 PNL A CKT 18 PNL A CKT 18 EM CONTINUE TO FIXTURE IN STAIRWELL SEE E1003 PNL A CKT 20 EM PNL A CKT 16 PNL A CKT 16 PNL A CKT 42 PNL A CKT 40 PNL A CKT 40 PNL A CKT 40 PNL A CKT 40 PNL A CKT 40 PNL A CKT 42 PNL A CKT 42 PNL A CKT 4 PNL A CKT 4 WP/GFCI PNL A CKT 8 PNL B CKT 12 PNL A CKT 1 PNL A PNL A PNL A LIGHTING CONTROL PANEL 1 PNL A CKT 26 PNL A CKT 26 PNL A PNL A PNL A LIGHTING CONTROL PANEL 1 LIGHTING CONTROL PANEL 1 LIGHTING CONTROL PANEL 1 CONTINUE TO FIXTURES AT MEZZANINE LEVEL SEE E1013 MEZZANINE LEVEL LIGHT SWITCH LOWER LEVEL LIGHT SWITCH WALL SWITCH PNL A CKT 18 PANELBOARD A 55JBCP034 P55J322A TPC1000 480V RECEPTACLE (36" AFG) PNL B CKT 1 PNL B PNL A PNL A A1/EM 50 9'-0" AFF (TYP) WP/GFCI PNL A CKT 8 WP/GFCI PNL A CKT 8PNL A PNL B CKT 10 PNL B A1 50 9'-0" AFF (TYP) C 74 WALL MOUNT 7'-0" AFF DATA OUTLET WITH (4) RJ45 JACKS NETWORK RACK PNL A D 17 MOUNT RECESSED IN CANOPY PNL A CKT 42 D 17 MOUNT RECESSED IN CANOPY PNL A CKT 42 F 40 F 40 F 40 F 40 F 40 PNL A CKT 40 PNL A CKT 42 PNL A CKT 42 D 17 MOUNT RECESSED IN CANOPY D 17 MOUNT RECESSED IN CANOPY FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2 3 4 5 6 7 8 9 10 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/7/2023 3:57:42 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-E-BBPS.rvt E1008 BAY BRIDGE PUMP STATION REPLACEMENT ELECTRICAL ROOM LIGHTING AND RECEPTACLE PLAN 302172 JEFF SOKOL CHRISTINA LANZEL BRIAN YOUNG SCALE: 3/8" = 1'-0" ELECTRICAL ROOM LIGHTING AND RECEPTACLE PLAN 0'2'6'4' NOTES: 1.MOUNT RECEPTACLE 18" AFF FOR INSTANT WATER HEATER. MARK DESCRIPTION DATE APPR. MOUNT RECESSED IN CANOPY MOUNT ABOVE DOOR 9'-0" AFF A1 50 9'-0" AFF A1 50 E1 5 A1/EM 50 D 17 6 MOUNT ABOVE TRANSOM CKT 25 GFCI WP PNL A CKT 25 GFCI PNL A CKT 25 GFCI PJB55J8000 PJB55J8000 LIGHTING CONTROL PANEL 1 PNL A CKT 27 PNL A CKT 27 EM PNL A CKT 27 PNL A CKT 27 EM PNL A CKT 27 PNL A CKT 27 EM PNL A CKT 27 PNL A CKT 42 POWER JUNCTION BOX PJB55J8000 9'-0" AFF A1/EM 50 9'-0" AFF A1 50 9'-0" AFF A1/EM 50 MOUNT RECESSED IN CANOPY D 17 PNL A CKT 42 MOUNT RECESSED IN CANOPY D 17 PNL A CKT 42 FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2 3 4 5 6 7 8 9 10 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/7/2023 4:05:09 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-E-BBPS.rvt E1017 BAY BRIDGE PUMP STATION REPLACEMENT GENERATOR ROOM LIGHTING AND RECEPTACLE PLAN 302181 JEFF SOKOL CHRISTINA LANZEL BRIAN YOUNG SCALE: 1/2" = 1'-0" GENERATOR ROOM LIGHTING AND RECEPTACLE PLAN 0'2'4'1' MARK DESCRIPTION DATE APPR. 8'-10" AFG 9'-0" AFF B 18 A2 62 8'-0" AFF A2 62 8'-10" AFG B 18 MOUNT ABOVE DOORE1 5 8'-10" AFG B 18 8'-0" AFF A2 62 8'-0" AFF A2 62 8'-0" AFF A2 62 9'-0" AFF A2 62 9'-0" AFF A2 62 8'-0" AFF A2 62 NL/EM MOUNT ON EQUIPMENT RACK A2 62 55JBCP696 CKT 1 GFCI\WP 55JBCP696 MOUNT ON EQUIPMENT RACK A2 62 LIGHTING CONTROL PANEL 2 55JBCP696 CKT 1 GFCI\WP 55JBCP696 CKT 1 GFCI/WP 55JBCP696 55JBCP696 8'-10" AFG B 18 LIGHTING CONTROL PANEL 2 55JBCP696 240/120V PANELBOARD 55JBCP696 CKT 3 GFCI WP 55JBCP696 CKT 4 55JBCP696 CKT 4 55JBCP696 CKT 4 EM 55JBCP696 CKT 4 55JBCP696 CKT 2 55JBCP696 CKT 2 55JBCP696 CKT 2 55JBCP696 CKT 4 55JBCP696 CKT 4 55JBCP696 CKT 4 55JBCP696 CKT 4 EM 55JBCP696 CKT 4 55JBCP696 CKT 4 EM 55JBCP696 LIGHTING CONTROL PANEL 2 55JBCP696 CKT 2 PHOTOCELL FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2 3 4 5 6 7 8 9 10 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 4/20/2023 9:36:41 AM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-E-BBPS.rvt E1020 BAY BRIDGE PUMP STATION REPLACEMENT ODOR CONTROL AREA LIGHTING AND RECEPTACLE PLAN 302184 JEFF SOKOL CHRISTINA LANZEL BRIAN YOUNG SCALE: 3/8" = 1'-0" LIGHTING AND RECEPTACLE PLAN 0'2'6'4' MARK DESCRIPTION DATE APPR. BBPS SITE PHOTOMETRIC PLAN BA Y B R I D G E P U M P S T A T I O N SI T E P H O T O M E T R I C P L A N Designer C. LANZEL Date 06/07/2023 Scale Not to Scale Drawing No. Summary 1 of 1 Schedule Symbol Label Quantity Catalog Number Description Number Lamps Lumens Per Lamp Light Loss Factor Manufacturer Wattage B 8 131-9631_us PLS420 LED, Wall Luminaires / Surface Mounted PLS420 [M] IP66:LED- 6/26W/2.7K;PLS420 LED, Wall Luminaires / Surface Mounted 6 374 1 WE-EF USA 30 F 6 ALU7AC26-XXXXX- N_Simulated VIGILANT AREA LIGHT 1 5501 1 DIALIGHT CORPORATION 40 D 10 E3SFF-LH8306AI ELEMENT E3 ADJUSTABLE HOUSINGW/ 60 DEGREE OPTICS 1 1560 1 TECH LIGHTING 18.1 Statistics Description Symbol Avg Max Min Calc Zone #1 4.7 fc 60.6 fc 0.0 fc Bay Bridge Pump Station Replacement LIGHTING Project No. 5-67 FDS 16500-1 Section 16500 LIGHTING PART 1 - GENERAL 1.1 THE REQUIREMENT A. CONTRACTOR shall furnish and install lighting fixtures, and accessories for all lighting systems, complete and operable, all in accordance with the requirements of the Contract Documents. B. In case of conflict between this specification and the Contract Drawing Fixture Schedule, the latter shall take precedence. 1.2 LIGHTING A. General 1. Fixtures shall include mounting hardware, reflectors, lenses, globes, etc. and shall be supplied as complete operating units. 2. Lighting system installation shall meet the specified seismic requirements. 3. Lighting System shall be easily maintainable. 1.3 RELATED WORK SPECIFIED ELSEWHERE A. The requirements of the following sections and divisions apply to the Work of this section. Other sections and divisions of the Specifications, not referenced below, shall also apply to the extent required for proper performance of this Work. 1. Section 01332, Seismic Design Criteria 2. Section 09800, Protective Coating 3. Section 16010, Electrical General Provisions 4. Section 16050, Basic Materials and Methods 5. Section 16130, Raceway Systems and Pull Boxes 6. Section 16080, Electrical Testing 1.4 REFERENCE SPECIFICATIONS, CODES, AND STANDARDS A. All Work specified herein shall conform to or exceed the applicable requirements of the referenced portions of the following publications to the extent that the provisions thereof are not in conflict with other provisions of these Specifications. B. Comply with the applicable editions of the following codes, regulations, and standards: LIGHTING Bay Bridge Pump Station Replacement Project No. 5-67 16500-2 FDS 1. Codes and Regulations: 29 CFR 1910 Code of Federal Regulations, Title 29, Part 1910, U.S. Occupational Safety and Health Standards (OSHA) CCR California Code of Regulations, Title 8, Div. 1, Chap. 4, Subchap. 5, Electrical Safety Orders CCR California Code of Regulations, Title 24, Part 2, California Building Code (CBC) CCR California Code of Regulations, Title 24, Part 3, California Electrical Code NFPA 70 National Electrical Code (NEC) 2. Industry Standards: ANSI C82.1 For Lamp Ballast - Line Frequency Fluorescent Lamp Ballast ANSI C82.4 For Lamp Ballast - Ballasts for High-Intensity- Discharge and Low-Pressure Sodium Lamps (Multiple-Supply Type) ANSI C82.11 High-Frequency Fluorescent Lamp Ballasts IESNA RP-7 Lighting Industrial Facilities UL 924 Emergency Lighting and Power Equipment 3. Other Standards: ANSI American National Standards Institute ETL Intertek ETL SEMKO IESNA Illuminating Engineering Society of North America NEMA National Electrical Manufacturers Association UL Underwriters Laboratories C. Comply with the applicable reference Specifications as directed in the General Requirements and the Additional General Requirements. 1.5 CONTRACTOR SUBMITTALS A. Submittals shall be in accordance with the General Requirements, the Additional Requirements, and as specified herein. 1. Catalog literature for each fixture specified including description of materials, type of diffuser, hardware, reflector, finish, mounting/support details, weight, electrical, photometric data, and ballast. The submittal shall also show evidence of UL listing or other testing laboratory acceptable to the ENGINEER. 2. If substitution fixtures are proposed, the submittal shall have sufficient information for complete comparison of the proposed fixture to the originally specified fixture. Photometric data shall include coefficients of utilization, average brightness, candlepower distribution curves, and lumen output chart. 3. Pole-mounted fixtures shall include complete data on the pole material, finish, handholes, anchoring, dimensions, structural loading data, and fixture attachment details. Bay Bridge Pump Station Replacement LIGHTING Project No. 5-67 FDS 16500-3 4. Ballast catalog data shall include lamp wattage, ballast efficiency factor (BEF), input watts, sound rating, power factor, and type of ballast. Data for outdoor ballast shall include low-temperature starting characteristics. 5. Photocell submittal shall include voltage and wattage ratings, ambient light level switching control means, and enclosure rating. 6. Lighting Control Panel submittal shall include detail lighting contactor schedule and wiring diagram. The lighting contactor schedule shall include, but not be limited to, all lighting contactors, along with associated lighting circuit number, and load description. 7. Provide lighting calculation based on selected and submitted lighting fixtures. Photometric data, including zonal lumen data, average and minimum ratio, aiming diagram, and computerized candlepower distribution data shall accompany shop drawings. 1.6 QUALITY ASSURANCE A. General: 1. Comply with the requirements specified herein and the applicable reference Specifications of the General Requirements, and the Additional General Requirements. 2. Exterior lighting system operation shall be demonstrated during the hours of darkness to indicate that fixtures are properly focused and aimed, photocell operation is correct, and that fixture switching functions as intended. Similar requirements shall apply to interior lighting. The CONTRACTOR shall also demonstrate that the light fixtures are properly circuited and the panel schedules and the panel directories are correctly documented. 3. Lighting system functionality test shall occur within 2 weeks prior to start of Reliability Acceptance Tests (RAT). 4. Fixture Appearance a. Fixture lenses, diffusers, and reflectors shall be cleaned just prior to system demonstrations. b. Fixture trim, including poles and support brackets, where finish has been damaged, shall be refinished or replaced. 1.7 SITE CONDITIONS A. Seismic requirements shall be in accordance with Section 01332, Seismic Design Criteria and this Specification section. PART 2 - PRODUCTS 2.1 LIGHTING SYSTEMS GENERAL A. Lighting system material shall be UL-listed or listed by an OSHA-recognized testing agency acceptable to the ENGINEER. LIGHTING Bay Bridge Pump Station Replacement Project No. 5-67 16500-4 FDS B. Lighting systems for occupied building spaces shall conform to the latest edition of IESNA requirements. 2.2 FIXTURES A. General: Provide fixtures as shown in fixture schedule, with proper hangers, pendants, canopies, lamps, etc., necessary for complete installation. Provide fixtures having "feed thru" or separate junction boxes. Provide two lamp ballasts wherever possible. Provide fixtures with wire leads not smaller than 18 AWG and with all electrical components easily accessible and replaceable without removing the fixture from the ceiling. B. Special Requirements: 1. Fixtures shall be rated for the locations where they are installed. Refer to Specification section 16010, Electrical General Provisions and the Drawings for area designation. Fixtures installed in wet and corrosive locations shall have a removable prewired driver. 2. Where designated for emergency lighting service provide fixtures containing integral battery module, charger, and control module to illuminate one-half of the lamps in the fixture to a value of approximately 40 percent output for 90 minutes in case of power failure. Furnish unit that automatically recharges the battery on return of normal line voltage. 3. For exterior fixtures with photocells, provide the fixture manufacturer's standard design. Adjust photocells to switch light ON at dusk and OFF at dawn. All exterior light fixtures shall be full-cutoff. 4. Provide pendant type fixtures with a safety cable attached to the structure and the fixture at each support capable of supporting four times the vertical load. 2.3 REFLECTORS A. Reflectors and reflecting cones or baffles shall be as follows: 1. Free of any tooling marks, indentations caused by riveting or other assembly techniques. 2. No rivets, springs, or other hardware visible after installation. 3. First quality polished, buffed, and anodized finish. 4. Low iridescence for fluorescent sources. 5. Finish color as indicated in the Contract Documents. 6. All reflectors and baffles of modified elliptical contour, with no apparent brightness from above 40 degrees above the nadir, with no lamp image or any part of the lamp visible from above 40 degrees above the nadir. 7. Cone flange formed as an integral part of the cone and with identical color and finish, unless specified otherwise. Width of the flange covers all ceiling opening without light leaks or hardware visible. Bay Bridge Pump Station Replacement LIGHTING Project No. 5-67 FDS 16500-5 2.4 LENSES A. All lenses shall be secured by positive means with neoprene or silicone gasket or washers, as required to hold the lens tight within a frame or attaching to the housing. 1. All glass lenses shall be heat treated (tempered) or sealed with a clear acrylic laminate layer to provide a "safety glass" rating. All lenses which require removal for relamping or normal maintenance shall be attached to the fixture housing by a minimal length of safety chain to prohibit the lens from falling and striking surrounding surfaces. Glass edges exposed during the relamping process shall be gasketed to prevent chipping or cracking. 2. Acrylic lenses shall be 100 percent virgin acrylic polymer, colorless. 2.5 LOUVERS (NOT USED) 2.6 FIXTURE MANUFACTURERS A. Fixture manufacturers shall be as called out in the fixture schedule shown on the Drawings, or equal. 2.7 LAMPS (NOT USED) 2.8 BALLASTS (NOT USED) 2.9 LIGHTING CONTROL A. General: Provide lighting control system as indicated in the Contract Documents. B. Lighting Controllers shall be of the non-combination lighting contactor type similar to combination motor starters without overload relays. Circuit breakers shall be of the molded case, thermal-magnetic type. 1. Provide a detailed lighting contactor schedule and wiring diagram. The lighting contactor schedule shall include, but not be limited to, all lighting contactors, along with associated lighting circuit number, and load description. C. Time Switch: Provide a time switch as shown on Contract Drawings with a plain 4- hour dial. D. Photocells: 1. Outdoor lighting shall be controlled by a photoelectric cell in accordance with the Contract Documents. The photocell shall be rated 120 V, 2000 W, 3-wire service, single-pole, single-throw (SPST). 2. The photocell shall be completely self-contained in NEMA 4 housing, ON at dusk and OFF at dawn; time delay feature to prevent false switching; and field adjustable to control operating levels. Photocell shall be Tork Model No. 2101, or equal. E. Dimming System: (NOT USED) F. Motion Sensors: (NOT USED) LIGHTING Bay Bridge Pump Station Replacement Project No. 5-67 16500-6 FDS 2.10 LIGHTING FIXTURE SCHEDULE: SEE DRAWINGS 2.11 EMERGENCY LIGHTING A. Emergency lighting units shall be as specified on the fixture schedule. The two lighting heads shall consist of sealed beam lamps. The unit shall be able to accommodate additional remotely located fixtures when specified in the Contract Documents. Batteries shall be the sealed nickel cadmium, maintenance-free type rated for a minimum of 90 minutes. An integral battery charger shall automatically provide a high-rate charge immediately upon restoration of normal power to the unit. When float voltage is reached, the charge level shall be maintained continuously. Time delay shall be provided to maintain emergency lighting for 15 minutes after normal power restoration. The fixtures shall be UL-listed, and shall be in accordance with UL 924. B. Test Push Button: The emergency lighting units shall have push-to-test button as part of the unit to simulate loss of power and demonstrates unit operability. C. Integral Self-Test: Factory- installed electronic device automatically initiates code- required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED. 2.12 EXIT SIGNS A. Exit signs shall be red, light-emitting diode (LED) type. LEDs shall be provided to illuminate letters from within the exit sign. They shall be designed to remain illuminated upon failure of the normal power supply via an internal nickel cadmium battery. An integral battery charger shall automatically provide a high-rate charge immediately upon restoration of normal power to the unit. When float voltage is reached, the charge level shall be maintained continuously. The number of faces, arrow signage, and enclosure type shall be as shown on the Drawings. The exit signs shall be Chloride Systems, Dual-Lite, Lithonia Lighting, or equal. B. Test Push Button: The exit sign shall have push-to-test button as part of the unit to simulate loss of power and demonstrates unit operability. C. Integral Self-Test: Factory- installed electronic device automatically initiates code- required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED. 2.13 LED LUMINAIRES AND DRIVERS A. All Luminaires 1. Comply with IES LM-79-08 Approved Method for measuring lumen maintenance of LED light sources. 2. Comply with IES LM-80-08 Approved Method for electrical and photometric measurement of SSL product. 3. Luminaire shall be mercury and lead free, and (RoHS) compliant. 4. LED arrays shall be sealed, high performance, long life type; minimum 70% rated output at 50,000 hours. Bay Bridge Pump Station Replacement LIGHTING Project No. 5-67 FDS 16500-7 5. Drivers shall be solid state and accept 120 through 277VAC at 60Hz input. 6. LED light source shall be fully dimmable with the use of compatible dimmers switch designated for low voltage loads. 7. Luminaire shall have a maximum Total Harmonic Distortion (THD) of 20% at full power and across specified voltage range. 8. Luminaire shall operate normally for input voltage fluctuation of plus or minus 10 percent. 9. Luminaires shall be accessible from below ceiling plane for all maintenance work. 10. Luminaire Color Rendering Index (CRI) shall be a minimum CRI of 85 for interior luminaires and 70 for exterior luminaires. 11. LED driver shall have a minimum power factor (pf) of 0.9 and a maximum crest factor (cf) of 1.5 at full power and across specified voltage range. 12. LED driver shall be compatible with dimming controls where dimming is indicated on the contract documents. 13. Wiring connection to LED drivers shall utilize polarized quick-disconnects for field maintenance. 14. The LED luminaire shall carry a limited 5-year warranty minimum for LED light engine(s)/board array, and driver(s). 15. Provide all of the following data on the submittals: a. Delivered lumens b. Input watts c. Efficacy d. Color Rendering Index 16. Luminaire manufacturers shall adhere to device manufacturer guidelines, certification programs, and test procedures for thermal management. 2.14 HARDWARE A. Hardware for fixtures located outdoors, in wet and corrosive areas shall be Type 316 stainless steel. Lighting pole hardware including nuts, bolts and washers for anchoring shall be Type 316 stainless steel. PART 3 - EXECUTION 3.1 FIXTURES A. General LIGHTING Bay Bridge Pump Station Replacement Project No. 5-67 16500-8 FDS 1. Install each fixture as recommended by the fixture manufacturer, per National Electrical Code and California Electrical Code requirements and as shown on the Drawings. 2. Install fixtures plumb, level, straight, and true with reference to adjacent walls. 3. Where fixtures height is indicated on the Drawings, the height shall be as measured from the bottom of the fixture to finished floor or finished grade, whichever is applicable. 4. After construction of total Project is completed, clean fixtures and lenses. Replace all lamps used for lighting during construction. 5. Circuit directories in panelboard door pockets shall be typewritten to identify all circuits. 6. All flood and spotlights shall be aimed as shown on the Drawings. 7. Install all recessed fixtures tight with the finished surface so that no spill light shall show between the ceilings and the sealing rings, and furnish plaster frames when required by ceiling construction. 8. Provide each fluorescent recessed fixture with two safety chains or two 12 AWG soft-annealed galvanized steel wire of length needed to secure fixture to building structure independent of ceiling structure. Tensile strength of chain or wires and fastening to structure shall be adequate to support weight of fixture. Fasten a chain or wires to each end of fixture. 9. Coordinate fixture locations with other utility systems (e.g., Plumbing, HVAC). Relocate fixtures to avoid conflict with these other systems and to avoid blockage of fixture light output. Obtain ENGINEER’s acceptance on the new locations. 10. Provide lighting calculation based on selected and submitted lighting fixtures. Photometric data, including zonal lumen data, average and minimum ratio, aiming diagram, and computerized candlepower distribution data shall accompany shop drawings. 3.2 BALLASTS (NOT USED) 3.3 LIGHTING CONTROL A. Install lighting control as shown on Drawings. B. Provide ballasts compatible with the dimming system. 3.4 FIXTURE MOUNTING A. Surface-mounted and flush-mounted fixtures shall be solidly connected to a junction box. * * * * * * Equipment Data and Catalog Cuts Electrical VFD MCC Switchboard 480/120 V Transformer SCE Requirements Overvoltage Protection High Resistance Grounding – Low Voltage Cam Locks and Cabinet Automatic Transfer Switch Reduced Voltage Soft Starters (RVSS) Lighting Fixtures Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice. EMS LED Page 1 of 6 Catalog Number Notes Type Capable Luminaire This item is an A+ capable luminaire, which has been designed and tested to provide consistent color appearance and out-of-the-box control compatibility with simple commissioning. • All configurations of this luminaire meet the Acuity Brands’ specification for chromatic consistency • This luminaire is part of an A+ Certified solution for nLight® or XPoint™ Wireless control networks marked by a shaded background* To learn more about A+, visit www.acuitybrands.com/aplus. *See ordering tree for details FEATURES & SPECIFICATIONS INTENDED USE — A general purpose and energy-efficient surface-mounted or suspended LED fixture, suitable for wet, damp and/or cold locations. For vapor-tight demanding environments where moisture or dust is a concern and where relatively low fixture mounting heights and wide fixture spacing are common. Typical applications include industrial facilities, parking garages, retail malls, multi-purpose rooms, garden centers, and food processing. Certain airborne contaminants can diminish the integrity of acrylic and/or polycarbonate. Click here for Acrylic-Polycarbon- ate Compatibility table for suitable use. Certain airborne contaminants may adversely affect the functioning of LEDs and other electronic components, depending on various factors such as concentrations of the contaminants, ventilation, and temperature at the end-user location. Click here for a list of substances that may not be suitable for interaction with LEDs and other electronic components. CONSTRUCTION — One-piece 5VA fiberglass housing with integral perimeter channel utilizing continuous poured-in-place NEMA 4X gasket. Approved as a wireway and for through wiring. Captive polymeric latches are standard. Stainless steel latches (#316) available as an option for food process- ing or more demanding applications. Power connection is easily accomplished through pre-drilled holes. Fixture easily mounts to ceilings and other solid structures, or can be suspended with chain, cable or rod using stainless steel mount- ing brackets (included). OPTICS — Injection molded, acrylic lens (.080” thick) provides high impact-resistance comparable to 100% DR. A UV stabilized polycarbonate diffuser is available (.080" thick) in clear or frosted for additional impact strength where vandal protection is desired. Expected service life of 60,000 hours at 80% lumen maintenance (L80); predicted life of more than 100,000 hours. ELECTRICAL — Utilizes high-efficiency LEDs mounted to core circuit boards. High-efficiency drivers operate 120-277 (MVOLT) and 347-480 (HVOLT) offered with 0-10 volt dimming. Standard Luminaire Surge Protection Level: 6kV/3kA Surge Rated per ANSI C82.77-5-2015. INSTALLATION — Fixture can be surface or suspended mounted. Pre-punched stainless steel mounting brackets are included (two per luminaire) for easy field-attachment of bolts, screws and other mounting hardware. A covered ceiling is not required to maintain wet location listing or IP rating. LISTINGS — CSA Certified to UL and C-UL Standards. Suitable for wet location. Covered ceiling not required to maintain wet location listing or IP ratings. IP65,IP66, IP67 rated and certified to meet NSF Splash Zone 2. NEMA 4X rated. Sensors maintain IP65 and IP66 only. See chart on page 5 for Ambient Temperatures. DesignLights Consortium® (DLC) Premium qualified product and DLC qualified product. Not all ver- sions of this product may be DLC Premium qualified or DLC qualified. Please check the DLC Qualified Products List at www.designlights.org/QPL to confirm which versions are qualified. WARRANTY — 5-year limited warranty. Complete warranty terms located at: www.acuitybrands.com/support/customer-support/terms-and-conditions NOTE: Actual performance may differ as a result of end-user environment and application. All values are design or typical values, measured under laboratory conditions at 25 °C. Specifications subject to change without notice. Low-Profile Enclosed and Gasketed Industrial EMS LED SURFACE/ SUSPENDED MOUNT Deep Lens Low profile with sensor Low profile AA1, A2, A1/EM, A2/EM Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice. EMS LED Page 2 of 6 EMS LED Low-Profile Enclosed and Gasketed ORDERING INFORMATION Lead times will vary depending on options selected. Consult with your sales representative.Example: EMS L48 4000LM IMAFL WD MVOLT GZ10 40K 80CRI Series Length Nominal Lumens Diffuser Distribution Voltage Driver Color temperature CRI EMS L24 24" ‡ L48 48" ‡ L96 96" ‡ 2000LM 2,000 lumens 3000LM 3,000 lumens 4000LM 4,000 lumens 6000LM 6,000 lumens 3000LM 3,000 lumens 4000LM 4,000 lumens 6000LM 6,000 lumens 8000LM 8,000 lumens 10000LM 10,000 lumens 12000LM 12,000 lumens 9000LM 9,000 lumens 12000LM 12,000 lumens 15000LM 15,000 lumens 18000LM 18,000 lumens 20000LM 20,000 lumens 24000LM 24,000 lumens IMAFL Acrylic, lineal ribbed frosted lens IMACD Acrylic, clear deep lens IMAFD Acrylic, deep frosted lens LPAFL Acrylic, low profile frosted lens LPACL Acrylic, low profile clear lens LPPCL Polycarbonate, low profile clear lens LPPFL Polycarbonate, low profile frosted lens MD Medium WD Wide PGD Parking garage MVOLT MVOLT HVOLT 347-480 ‡ 120 120V 277 277V 347 347V 480 480V GZ10 0 - 10V dimming 30K 3000K 35K 3500K 40K 4000K 50K 5000K 80CRI 80 CRI 90CRI 90 CRI Options E10WMCP EM Self-diagnostics battery pack, MVOLT, 10W, Constant Power Certified in the California Title 20 Modernized Appliance Efficiency Database (MAEDBS) ‡ BE6WCP Cold Weather EM battery pack, 120/277V, 6W, Constant Power Certified in the California Title 20 Modernized Appliance Efficiency Database (MAEDBS) ‡ BGTD Generator transfer device SPD Surge protection device, additional 10kV/6kA WLF Wet location fitting (two outboard, top(L24 - 20 inches off-center, L48 - 48 inches off-center, L96 95.7 inches off-center)) WLFEND Wet location fitting (one end) WLFEND2 Wet location fitting (both ends) ‡ WLFPMP Wet location pendant monopoint ‡ ANGBKT Angle bracket shipped with fixture CPSB16YWLBH 6' Brad Harrison 16/3 cord and straight blade plug set ‡ CPSB16YWL12FTBH 12' Brad Harrison 16/3 cord and straight blade plug set ‡ CRSB16YWLBH Brad Harrison receptacle ‡ CNP16WWL 6' white cord, 16/3, no plug, wet location CNP16WWL12FT 12' white cord, 16/3, no plug, wet location CNP164CWWL 6' white cord, 16/4, no plug, wet location (for use when unswitched circuit is required with battery pack) TRS Tamper Resistant Torx® T10 screws DPMB Dual pendant mounting bracket STSL Stainless steel latches Individual Controls: SBOR10 Low mount 360° integral motion sensor, wet location, On/Off operation SBOR10 HL 3V Low mount 360° integral motion sensor, wet location, High/Low operation (bi-level) SBOR10 P Low mount 360° integral motion sensor, wet location, On/Off operation for motion sensing, override Off due to daylight Xpoint Wireless: XPA SBOR10 Xpoint wireless integral motion sensor, On/Off operation for motion sensing, override Off due to daylight ‡ XAD XPoint™ wireless controller, 0-10V dimming ‡ nLight Air: NLTAIR2 RSBOR10 nLight AIR generation 2 enabled 306 low mount motion sensor NLTAIR2 RIO nLight (wireless) gen 2 dimming & switching module NOTE: ‡ indicates option chosen has ordering restrictions. Please reference ordering restrictions chart, page 3. Options are sorted alphanumerically. A+ Capable options indicated by this color background. See Accessories and ordering restrictions on next page. ELE/GEN ROOM - ODOR CONTROL - Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice. EMS LED Page 3 of 6 EMS LED Low-Profile Enclosed and Gasketed ‡ Option Value Ordering Restrictions Option value Restriction L24 Not available with BE6WCP. L48 Not available with WLFPMP. L96 Not available with WLFPMP HVOLT When ordered with L24 available with 6000LM only. When ordered with L48 not avaialble with 3000LM or 4000LM. Not available with XAD or XPA SBOR10. BE6WCP Not available with L24 length. Order with CNP164CWWL when unswitched hot is required for battery. E10WMCP Order with CNP164CWWL when unswitched hot is required for battery. WLFEND Available with cord or sensor option. Choose only one. WLFEND2 Not available with sensor or cord options. WLFPMP Available only with L24. CNP16WWL Not available with BE6WCP or E10WMCP. CNP16WWL12FT Not available with BE6WCP or E10WMCP. CPSB16YWLBH Not available with BE6WCP or E10WMCP. CPSB16YWL12FTBH Not available with BE6WCP or E10WMCP. CRSB16YWLBH Not available with BE6WCP or E10WMCP. XPA SBOR6 Not available with HVOLT. XAD Not available with HVOLT. Accessories: Order as separate catalog number. MHCH 36 Jack chain 36" (pair) MHHK120 10' single leg air craft cable (ships as pair) MHHK120SS 10' single leg air craft cable, stainless steel (ships as pair) RK1 T10BIT W/PIN U Hex-base driver bit, Torx TX10, for tamper resistant screws with center reject pin FEMDPMB Dual pendant mounting bracket (ships as a pair) FEMANGBKT Angle bracket (ships as pair) FEMSMB Surface mount bracket (ships as pair) MOUNTING OPTIONS FEMSMB (304 stainless steel) Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice. EMS LED Page 4 of 6 EMS LED Low-Profile Enclosed and Gasketed OPERATIONAL DATA (80 CRI*, MD**, MVOLT***) Length Package Input Wattage CCT Frosted Lens' Lumens (LPW)Clear Lens' Lumens (LPW) IMAFL IMAFD LPAFL LPPFL IMACD LPACL LPPCL L24 2000LM 13.4 30K 1962 (147)2083 (156)2076 (155)1861 (139)2112 (158)2105 (158)1890 (142) 35K 2002 (150)2126 (159)2118 (159)1899 (142)2155 (161)2147 (161)1929 (144) 40K 2099 (157)2228 (167)2220 (166)1991 (149)2259 (169)2251 (169)2022 (151) 50K 2122 (159)2252 (169)2244 (168)2013 (151)2284 (171)2276 (170)2044 (153) 3000LM 19.9 30K 2869 (144)3046 (153)3035 (153)2721 (137)3088 (155)3077 (155)2764 (139) 35K 2927 (147)3108 (156)3096 (156)2777 (140)3151 (158)3139 (158)2820 (142) 40K 3069 (154)3258 (164)3246 (163)2911 (146)3303 (166)3291 (166)2956 (149) 50K 3102 (156)3293 (166)3281 (165)2942 (148)3339 (168)3327 (167)2988 (150) 4000LM 26.0 30K 3676 (142)3903 (150)3889 (150)3487 (134)3957 (152)3943 (152)3541 (136) 35K 3751 (145)3982 (153)3968 (153)3558 (137)4037 (156)4023 (155)3613 (139) 40K 3932 (152)4174 (161)4159 (160)3730 (144)4232 (163)4217 (162)3788 (146) 50K 3975 (153)4219 (163)4204 (162)3770 (145)4278 (165)4263 (164)3829 (148) 6000LM 39.2 30K 5287 (135)5613 (143)5593 (143)5015 (128)5691 (145)5671 (145)5093 (130) 35K 5395 (138)5727 (146)5707 (145)5117 (130)5806 (148)5786 (147)5196 (132) 40K 5655 (144)6004 (153)5982 (153)5364 (137)6087 (155)6065 (155)5447 (139) 50K 5717 (146)6069 (155)6047 (154)5422 (138)6153 (157)6131 (156)5506 (140) L48 3000LM 18.0 30K 2689 (149)2855 (158)2844 (158)2551 (141)2894 (160)2884 (160)2590 (144) 35K 2743 (152)2912 (161)2902 (161)2602 (144)2953 (164)2942 (163)2643 (146) 40K 2876 (159)3053 (169)3042 (169)2728 (151)3095 (172)3084 (171)2770 (154) 50K 2907 (161)3086 (171)3075 (170)2758 (153)3129 (173)3118 (173)2800 (155) 4000LM 23.8 30K 3543 (149)3762 (158)3748 (157)3361 (141)3814 (160)3800 (160)3413 (143) 35K 3615 (152)3838 (161)3824 (161)3429 (144)3891 (163)3877 (163)3482 (146) 40K 3790 (159)4023 (169)4009 (168)3595 (151)4079 (171)4064 (171)3650 (153) 50K 3831 (161)4067 (171)4052 (170)3634 (153)4123 (173)4109 (173)3690 (155) 6000LM 37.8 30K 5284 (140)5609 (149)5589 (148)5012 (133)5687 (151)5667 (150)5090 (135) 35K 5391 (143)5723 (152)5703 (151)5114 (135)5802 (154)5782 (153)5193 (138) 40K 5651 (150)6000 (159)5978 (158)5361 (142)6083 (161)6061 (161)5444 (144) 50K 5713 (151)6065 (161)6043 (160)5419 (144)6149 (163)6127 (162)5503 (146) 8000LM 50.5 30K 6952 (138)7380 (146)7354 (146)6594 (131)7482 (148)7456 (148)6696 (133) 35K 7093 (141)7530 (149)7503 (149)6728 (133)7634 (151)7607 (151)6832 (135) 40K 7435 (147)7894 (156)7865 (156)7053 (140)8003 (159)7975 (158)7162 (142) 50K 7516 (149)7979 (158)7950 (158)7129 (141)8090 (160)8061 (160)7240 (144) 10000LM 62.0 30K 8646 (140)9179 (148)9146 (148)8201 (132)9306 (150)9273 (150)8328 (134) 35K 8822 (142)9365 (151)9332 (151)8368 (135)9495 (153)9461 (153)8497 (137) 40K 9248 (149)9817 (158)9782 (158)8772 (142)9953 (161)9918 (160)8908 (144) 50K 9348 (151)9924 (160)9888 (160)8867 (143)10061 (162)10026 (162)9004 (145) 12000LM 75.0 30K 10406 (139)11047 (147)11007 (147)9871 (132)11200 (149)11160 (149)10024 (134) 35K 10617 (141)11271 (150)11231 (150)10071 (134)11427 (152)11387 (152)10227 (136) 40K 11130 (148)11816 (157)11773 (157)10557 (141)11979 (160)11937 (159)10721 (143) 50K 11251 (150)11944 (159)11901 (159)10672 (142)12109 (161)12066 (161)10837 (144) L96 9000LM 53.4 30K 7962 (149)8452 (158)8422 (158)7552 (141)8570 (160)8539 (160)7669 (144) 35K 8124 (152)8624 (161)8593 (161)7706 (144)8743 (164)8713 (163)7825 (146) 40K 8516 (159)9040 (169)9008 (169)8078 (151)9166 (172)9133 (171)8203 (154) 50K 8608 (161)9138 (171)9106 (170)8165 (153)9265 (173)9232 (173)8292 (155) 12000LM 75.5 30K 10570 (140)11221 (149)11181 (148)10026 (133)11377 (151)11337 (150)10182 (135) 35K 10785 (143)11449 (152)11408 (151)10230 (135)11608 (154)11567 (153)10388 (138) 40K 11306 (150)12002 (159)11959 (158)10724 (142)12168 (161)12125 (161)10890 (144) 50K 11428 (151)12132 (161)12089 (160)10840 (144)12300 (163)12257 (162)11008 (146) 15000LM 94.3 30K 13399 (142)14225 (151)14174 (150)12710 (135)14422 (153)14371 (152)12907 (137) 35K 13671 (145)14513 (154)14461 (153)12968 (138)14714 (156)14662 (156)13169 (140) 40K 14331 (152)15214 (161)15160 (161)13594 (144)15425 (164)15370 (163)13805 (146) 50K 14487 (154)15379 (163)15324 (163)13741 (146)15592 (165)15537 (165)13954 (148) 18000LM 103.4 30K 15901 (154)16881 (163)16820 (163)15083 (146)17114 (165)17054 (165)15317 (148) 35K 16224 (157)17223 (167)17161 (166)15389 (149)17462 (169)17400 (168)15627 (151) 40K 17007 (164)18055 (175)17990 (174)16132 (156)18305 (177)18240 (176)16382 (158) 50K 17192 (166)18251 (176)18185 (176)16307 (158)18503 (179)18438 (178)16560 (160) 20000LM 125.5 30K 17549 (140)18630 (148)18564 (148)16646 (133)18888 (150)18822 (150)16904 (135) 35K 17906 (143)19008 (151)18940 (151)16984 (135)19272 (154)19204 (153)17247 (137) 40K 18770 (150)19927 (159)19855 (158)17804 (142)20202 (161)20131 (160)18080 (144) 50K 18974 (151)20143 (160)20070 (160)17997 (143)20421 (163)20349 (162)18276 (146) 24000LM 149.5 30K 21142 (141)22445 (150)22364 (150)20055 (134)22756 (152)22675 (152)20365 (136) 35K 21571 (144)22900 (153)22818 (153)20461 (137)23217 (155)23135 (155)20779 (139) 40K 22613 (151)24006 (161)23920 (160)21450 (143)24339 (163)24253 (162)21782 (146) 50K 22858 (153)24266 (162)24179 (162)21682 (145)24602 (165)24516 (164)22018 (147) * For 90CRI, reduce lumen output by 17.1%** For WD reduce output by 4.7%, PGD reduce output by 5.4%*** For HVOLT use scale factor in HVOLT SCALE FACTOR TABLE Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice. EMS LED Page 5 of 6 EMS LED Low-Profile Enclosed and Gasketed CSA LISTED AMBIENT RATING* HVOLT SCALE FACTOR CONFIGURATION WEIGHTS Standard** (surface)" Standard** (suspended)" E10WMCP (surface) E10WMCP (suspended) BE6WCP (surface) BE6WCP (suspended) XAD (surface) XAD (suspended) L24 2000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 3000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 4000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 6000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C L48 3000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 4000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 6000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 8000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 10000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 12000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C L96 9000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 12000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 15000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 18000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 20000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C 24000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C Factor 2000LM 0.814 3000LM 0.814 4000LM 0.814 6000LM 0.835 8000LM 0.845 9000LM 0.850 10000LM 0.850 12000LM 0.845 15000LM 0.860 18000LM 0.880 20000LM 0.845 24000LM 0.865 Standard w/ Sensor w/ Battery L24 8 9 9 L48 11 12 12 L96 23 24 24 *Minimum Ambient is -30°C unless noted, **All options not specifically listed in this table are considered standard NUMBER OF BOARDS AND DRIVERS Lumen package Fixture length Number of boards Number of drivers 2000LM L24 1 1 3000LM 1 1 4000LM 1 1 6000LM 1 1 3000LM L48 2 1 4000LM 2 1 6000LM 2 1 8000LM 2 1 10000LM 2 1 12000LM 2 1 9000LM L96 4 1 12000LM 4 2 15000LM 4 2 18000LM 4 2 20000LM 4 2 24000LM 4 2 Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice. EMS LED Page 6 of 6 EMS LED Low-Profile Enclosed and Gasketed PHOTOMETRICS See www.holophane.com for photometry reports. 51-3/4(131.4) 100-1/4(254.6) DIMENSIONS Specifications subject to change without notice. All dimensions are inches (centimeters) unless otherwise indicated. [10.6]4.2 [11.1]4.4 [14.5]5.7 [17.2]6.8 [17.2]6.8 [17.2]6.8 Diffuser Type: LPAFL LPACL LPPFL LPPCL Weight (may vary with options or accessories) EMS L48: 11.9 lbs (5.397kg) EMS L96: 24.3 lbs (11.022kg) Diffuser Type: IMAFL Diffuser Type: IMAFD IMACD 2734" (703.26)   Description IP66. Class I. IK08. Marine-grade, die-cast aluminum alloy. 5CE superior corrosion protection including PCS hardware. Silicone CCG® Controlled Compression Gasket. CAD-optimized optics for superior illumination and glare control. Integral driver. Advanced thermal management protects LEDs while optimizing lumens output. 0-10V Dimming comes standard with luminaire. Luminaire is factory-sealed and does not need to be opened during installation. Luminaire can be mounted for up or down lighting. Specify product with 7 Digit product code – Finish Color. Accessories, such as mounting, optical, and electrical, must be specified separately. Example: XXX- XXXX-9004 (Black) + XXX-XXXX (Accessory 1) PLS420 LED Surface Mounted Wall Luminaires 1/7 WE-EF LIGHTING USA LLC Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42 Technical modifications and errors excepted TYPE B Material Specification Body:Marine-grade, die-cast aluminium alloy Lens:Safety glass lens Colours: RAL9004 Black RAL9007 Grey Metallic RAL9016 White RAL8019 Dark Bronze Quick Ship Quickship features a one week ship time for Steplights and two week ship time for the rest of our Core products. All applicable information must be included for orders to be processed and colors must be in one of our 4 standard finishes. A maximum order quantity of 30 pieces applies. Gasket:Silicone CCG® Controlled Compression Gasket Fasteners:PCS hardware Ingress protection:IP66 Impact protection:IK08 Corrosion protection:5CE Listings:ETL listed. Suitable for wet locations. Specifications Electrical Specification Power supply:Integral [ECG] electronic driver 120V-277V. 0-10V dimmable, to be specified with order. Driver / Ballast:Integral EC electronic converter Lifetime Ta=25°/40° L90B10 > 90000h PLS420 LED Surface Mounted Wall Luminaires 2/7 WE-EF LIGHTING USA LLC Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42 Technical modifications and errors excepted Choices Light Distributions  Nominal Lumen Nominal Watt Colour Temperatures Colours [S70] Type II Short [A60] Type IV Very Short [R65] Type IV Medium symmetric, medium beam [M] symmetric, narrow beam [N]  1398 1476 2220 2340 2700 2839 2993 3453 12 18 26  2700 K  3000 K  4000 K  RAL9004 Black  RAL9007 Grey Metallic  RAL9016 White  RAL8019 Dark Bronze PLS420 LED Surface Mounted Wall Luminaires 3/7 WE-EF LIGHTING USA LLC Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42 Technical modifications and errors excepted Configurations Light Distributions  Part ID Light Source Delivered Lumens Rated Input Power CRI Weight Link  131-9629 LED-6/12W / 700 mA - 2700 K 1122.5 15 80 9.30 131-9581 LED-6/12W / 700 mA - 3000 K 1185.1 15 80 9.30 131-9582 LED-6/12W / 700 mA - 4000 K 1185.1 15 80 9.30 131-9630 LED-6/18W / 1050 mA - 2700 K 1755.1 21 80 9.30 131-9583 LED-6/18W / 1050 mA - 3000 K 1850 21 80 9.30 131-9584 LED-6/18W / 1050 mA - 4000 K 2134.6 21 80 9.30 131-9631 LED-6/26W / 1400 mA - 2700K 2244.5 30 80 9.30 131-9585 LED-6/26W / 1400 mA - 3000 K 2366.2 30 80 9.30 131-9586 LED-6/26W / 1400 mA - 4000 K 2729.9 30 80 9.30   symmetric, medium beam [M]  131-9632 LED-6/12W / 700 mA - 2700 K 1055.6 15 80 9.30 131-9587 LED-6/12W / 700 mA - 3000 K 1114.5 15 80 9.30 131-9588 LED-6/12W / 700 mA - 4000 K 1114.5 15 80 9.30 131-9633 LED-6/18W / 1050 mA - 2700 K 1779.9 21 80 9.30 131-9589 LED-6/18W / 1050 mA - 3000 K 1876.1 21 80 9.30 131-9590 LED-6/18W / 1050 mA - 4000 K 2164.7 21 80 9.30 131-9634 LED-6/26W / 1400 mA - 2700K 2276.2 30 80 9.30 131-9591 LED-6/26W / 1400 mA - 3000 K 2399.7 30 80 9.30 131-9592 LED-6/26W / 1400 mA - 4000 K 2768.5 30 80 9.30   symmetric, narrow beam [N]  131-9620 LED-6/12W / 700 mA - 2700 K 835.5 15 80 9.30 131-9562 LED-6/12W / 700 mA - 3000 K 882.1 15 80 9.30 131-9564 LED-6/12W / 700 mA - 4000 K 882.1 15 80 9.30 131-9621 LED-6/18W / 1050 mA - 2700 K 1290.6 21 80 9.30 131-9565 LED-6/18W / 1050 mA - 3000 K 1360.4 21 80 9.30 131-9566 LED-6/18W / 1050 mA - 4000 K 1569.7 21 80 9.30 131-9622 LED-6/26W / 1400 mA - 2700K 1650.5 30 80 9.30 131-9567 LED-6/26W / 1400 mA - 3000 K 1740 30 80 9.30 131-9568 LED-6/26W / 1400 mA - 4000 K 2007.5 30 80 9.30   [S70] Type II Short  131-9626 LED-6/12W / 700 mA - 2700 K 811.4 15 80 9.30 131-9575 LED-6/12W / 700 mA - 3000 K 856.7 15 80 9.30 131-9576 LED-6/12W / 700 mA - 4000 K 856.7 15 80 9.30 131-9627 LED-6/18W / 1050 mA - 2700 K 1216.5 21 80 9.30 131-9577 LED-6/18W / 1050 mA - 3000 K 1282.3 21 80 9.30 131-9578 LED-6/18W / 1050 mA - 4000 K 1479.6 21 80 9.30 131-9628 LED-6/26W / 1400 mA - 2700K 1555.7 30 80 9.30 131-9579 LED-6/26W / 1400 mA - 3000 K 1640.1 30 80 9.30 131-9580 LED-6/26W / 1400 mA - 4000 K 1892.2 30 80 9.30   [A60] Type IV Very Short  131-9623 LED-6/12W / 700 mA - 2700 K 759.5 15 80 9.30 131-9569 LED-6/12W / 700 mA - 3000 K 801.9 15 80 9.30 131-9570 LED-6/12W / 700 mA - 4000 K 801.9 15 80 9.30 131-9624 LED-6/18W / 1050 mA - 2700 K 1183.1 21 80 9.30 131-9571 LED-6/18W / 1050 mA - 3000 K 1247 21 80 9.30 131-9572 LED-6/18W / 1050 mA - 4000 K 1438.9 21 80 9.30   [R65] Type IV Medium PLS420 LED Surface Mounted Wall Luminaires 4/7 WE-EF LIGHTING USA LLC Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42 Technical modifications and errors excepted Configurations Light Distributions  Part ID Light Source Delivered Lumens Rated Input Power CRI Weight Link  131-9625 LED-6/26W / 1400 mA - 2700K 1513 30 80 9.30 131-9573 LED-6/26W / 1400 mA - 3000 K 1595 30 80 9.30 131-9574 LED-6/26W / 1400 mA - 4000 K 1840.2 30 80 9.30   [R65] Type IV Medium Related Families / PLS400 Family  Dimensions Wattage Nominal Lumen Links Links Download Data Sheet PLS420 LED 10.43 x 8.86 12 -26 W 1398 -3453 PLS430 LED 13.78 x 8.86 24 -52 W 2796 -6907 PLS420 LED Surface Mounted Wall Luminaires 5/7 WE-EF LIGHTING USA LLC Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42 Technical modifications and errors excepted Bird deterrent 131-9600 Bird deterrent BD Mounting Accessories Light shield 430-0029 LS180 430-0038 LS180-[A60] Honeycomb louvre C1 H1 131-9596 Honeycomb louvre IW 8.82 2.80 Optical Accessories Electrical Accessories PLS420 LED Surface Mounted Wall Luminaires 6/7 WE-EF LIGHTING USA LLC Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42 Technical modifications and errors excepted Emergency Lighting Package 620-7400 _LS420/430 LED Emergency Lighting Package Photocell 620-8001 PLS420 Button Photocell Kit Control PLS420 LED Surface Mounted Wall Luminaires 7/7 WE-EF LIGHTING USA LLC Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42 Technical modifications and errors excepted Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice. HXPL Page 1 of 4 HXPL Series Hazardous Area Lighting Fixtures Catalog Number Notes Type Dimensions: Inches (millimeters) unless otherwise noted. See individual fixture dimensions and weight specifications on page 2. • Paint Spray Booth • Coal & Dust Storage • Petroleum Refineries • Ethanol Facilities • Chemical Plants • Waste Water & Water Treatment Plants • Power Generation Plants Typical Applications Description• Versatile heavy-duty, explosion-proof LED fixture designed for hazardous environments where flammable gases or vapors, flammable liquids, combustible dust and/or ignitable fibers may exist. • Suitable for wet locations and marine environments where saltwater spray is an issue. • Also suitable for indoor and outdoor areas where corrosive chemicals exist. • Certain airborne contaminants may adversely affect the functioning of LEDs and other electronic components, depending on various factors such as concentrations of the contaminants, ventilation, and temperature at the end-user location. Click here for a list of substances that may not be suitable for interaction with LEDs and other electronic components. Optics• Explosion-proof, impact and heat resistant glass tubes, provide LED protection.• Optional wire guard and/or clear polycarbonate shield available for additional security.• Heavy gauge extruded aluminum reflectors (2.5 millimeters thick), with high gloss reflective finish. Resists dents and corrosion. Easy, quick removal for cleaning.• 84CRI is standard. Electrical• 0-10 Volt driver.• Driver has 1.5kV surge protection, for additional surge protection against power line transient surges, installer will need to provide remote surge protection. Mechanical• Factory sealed. • Fixture constructed of corrosion-resistant, copper-free aluminum alloy (less than 0.4% copper). • Over-sized, finned driver housing provides greater heat dissipation and extended driver life.• Maintenance can be done quickly from either end of the fixture. All access covers are screw type and interchangeable with O-ring seals. Easily accessible and externally mounted. Listings• UL Listed to US and Canadian standards.• Suitable for use in Hazardous Locations. • Class I, Division 1, Groups C and D• Class I, Division 2, Groups C and D• Class II, Division 1, Groups E, F, and G• Class II, Division 2, Groups E, F, and G• Class III• Simultaneous presence• Zone Equivalency Markings (See chart on page 5)• -4°F (-20°C) to 131°F (55°C) (see chart on page 4)• Marine Rated.• NEMA 4X, 7CD & 9EFG Rated.• IP66 Rated.• Paint Spray Booth Warranty5-year limited warranty on the fixture. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions Note: Actual performance may differ as a result of end-user environment and application. All values are design or typical values, measured under laboratory conditions at 25 °C. Specifications subject to change without notice. C Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice. HXPL Page 2 of 4 HXPL Series Hazardous Area Lighting Fixtures ORDERING INFORMATION Example: HXPL L24 2 3000LM AS DM 30K Series Fixture Length Number of Tubes Lumens Voltage Dimming Color Temperature Options HXPL L24 2 foot L48 4 foot 2 2 tubes 3 3 tubes ‡ 4 4 tubes 3L 3000 nominal lumens (2ft, 2 tube) 4L 4000 nominal lumens (2ft, 3 tube) 5L 5000 nominal lumens (4ft, 2 tube) 8L 8000 nominal lumens (4ft, 3 tube) 10L 10000 nominal lumens (4ft, 4 tube) AS 120-277V, 50/60Hz 120 120V, 50/60Hz 208 208V, 50/60Hz 240 240V, 50/60Hz 277 277V, 50/60Hz DM Dimmable (0-10V DC) ‡ NDM Non-Dimming Driver 30K 3000K 40K 4000K 50K 5000K EM10WCP EM battery backup, 10W, Certified in CA Title 20 MAEDBS ‡ EMO Emergency operation only ‡ DS Outboard option IF In-line Fusing ‡ Accessories: Order as separate catalog number. HXPL22TSSG Stainless steel guards (L24 2 3L only) HXPL42TSSG Stainless steel guards (L48 2 5L only) HXPL43TSSG Stainless steel guards (L48 3 8L only) HXPL44TSSG Stainless steel guards (L48 4 10L only)‡ HXPL23TPS Polycarb shield (L24 3 4L only) HXPL22TPS Polycarb shield (L24 2 3L only) HXPL42TPS Polycarb shield (L48 2 5L only) HXPL43TPS Polycarb shield (L48 3 8L only) ‡ HXPL44TPS Polycarb shield (L48 4 10L only) ‡ HXPLWCMK Wall/ceiling mounting kit ‡ HXPLSMK Shock mounting kit ‡ HXPLDMK Drop mounting kit ‡ HXPLBMK Beam mounting kit ‡ HXPLUMK Unistrut mounting kit ‡ ‡ Option Value Ordering Restrictions & Notes Option value Restriction 3 tubes The 3 tube option does not have an available accessory mounting kit available. See page 2 for drawing detailing the 3/4" NPT hubs used to mount the fixture. DM Not available with EM10WCP or EMO. EM10WCP Available with L48, 4 foot versions of the fixture only. Not available with DM option. Nameplate label on the fixture will show EM to indicate a battery is included. EMO Available with the L24 2 3L (3000 lumen) version of the fixture only. Not available with DM option. Fixture operation: Under normal power conditions, battery will charge and fixture will be OFF. If Power is lost then battery will power the LEDs until the power is restored or a min of 90 minutes has elapsed. HXPL44TSSG Will ship with a qty of 2 HXPL42TSSG guards. HXPL44TPS Will ship with a qty of 2 HXPL42TPS guards. HXPL43TPS 3 tube fixtures with polycarb shields require a qty of 1 HXPL43TSSG stainless steel guard. HXPLWCMK, HXPLSMK, HXPLDMK, HXPLBMK Available with 2 tube fixtures only. HXPLUMK Available with 4 tube fixtures only. IF External Fusing. Not marine listed. Must specify voltage at time of order. Nameplate label on the fixture will show AS to indicate the voltage. Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice. HXPL Page 3 of 4 DIMENSIONAL DATA HXPL Series Hazardous Area Lighting Fixtures Package A B C D E Boxed Weight Two-tube, four-foot 53"48.5"6.5"7"11.5"65 lbs. Two-tube, two-foot 29"24.5"6.5"7"11.5"40 lbs. Package A B C D Boxed Weight Three-tube, four-foot 53"48.5"8.9"16.3"78 lbs. Three-tube, two-foot 29"24.5"8.9"16.3"47 lbs. 2 tube fixture dimensions 3 tube fixture dimensions 4 tube fixture dimensions Package A B C D E Boxed Weight Four-tube, four-foot 53"49.4"6.8"11.3"23.2"138 lbs. Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice. HXPL Page 4 of 4 HXPL Series Hazardous Area Lighting Fixtures OPERATIONAL DATA Operating Characteristics Package Ambient Rating (120V - 277V) Delivered Lumens 4000 K CCT @ 25C ‡Wattage @ 120V LPW @ 4000 K HXPL L24 2 3L AS -4°F to 131°F (-20°C to 55°C)2783 26.6 104.6 HXPL L24 3 4L AS -4°F to 131°F (-20°C to 55°C)4110 36.75 111 HXPL L48 2 5L AS -4°F to 131°F (-20°C to 55°C)5450 46.9 116.2 HXPL L48 3 8L AS -4°F to 131°F (-20°C to 55°C)8220 73.5 111.8 HXPL L48 4 10L AS -4°F to 131°F (-20°C to 55°C)10918 93.6 116.6 Operating Temperature Code for Hazardous Locations: Package ‡Max Ambient Range Class I Division 1 Groups C, D Class II Division 1, Groups E, F, G, Class III Simultaneous Presence Class I & Class II HXPL L24 2 3L 55°C T6 T4A T4A HXPL L24 3 4L 55°C T6 T5 T5 HXPL L48 2 5L 55°C T6 T4A T4A HXPL L48 3 8L 55°C T6 T5 T5 HXPL L48 4 10L 55°C T6 T4A T4A Package ‡0 Hours 15,000 Hours 30,000 Hours 45,000 Hours 60,000 Hours HXPL L48 4 10L AS @ 25°C 1.0 0.95 0.91 0.87 0.83 HXPL L48 4 10L AS @ 40°C 1.0 0.94 0.89 0.85 0.80 HXPL L48 4 10L AS @ 55°C 1.0 0.92 0.86 0.80 0.74 Projected Lumen Maintenance (TM-21) ‡ Notes Delivered Lumens 4000 K CCT @ 25C Absolute photometry calculated in accordance with IESNA LM-79-08. ‡ Notes Package Project lumen maintenance factors at max. ambient temperature per lumen package. ‡ Notes Package Supply wire temperature is 75°C. Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com © 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice. HXPL Page 5 of 4 How to Estimate Delivered Lumens in Emergency Mode Use the formula below to estimate the delivered lumens in emergency modeDelivered Lumens = P x LPW P = Output power of emergency driver LPW = Lumen per watt rating of the luminaire. (See charts on page 7) The LPW rating is also available at Designlight Consortium P = 10 watts for E10WCP Emergency Lumen Output Example - 10 Watt Battery Approximate Luminaire Efficacy Approximate Lumens at 1 Minute Approximate Lumens at 45 Minutes Approximate Lumens at 90 Minutes 100 LPW 1000 1000 1000 110 LPW 1100 1100 1100 120 LPW 1200 1200 1200 130 LPW 1300 1300 1300 140 LPW 1400 1400 1400 150 LPW 1500 1500 1500 Emergency Lumen Output HXPL Series Hazardous Area Lighting Fixtures Zone Equivalency Markings NEC Protections Area Protection Techniques Zone Equivalency Markings Class I Division 1 Intrinsic Safety CLASS I, DIV 1, GROUP D CLASS I, ZONE 1 GROUP IIA Explosion Proof CLASS I, DIV 1, GROUP C CLASS I, ZONE 1 GROUP IIB Division 2 Hermetically-sealed CLASS I, DIV 2, GROUP D CLASS I, ZONE 2 GROUP IIA Nonincendive CLASS I, DIV 2, GROUP C CLASS I, ZONE 2 GROUP IIB Class II Division 1 Intrinsic Safety CLASS II, DIV 1 GROUP E, F, OR G CLASS II ZONE 20 AND ZONE 21Dust-ignitionproof Pressurized Division 2 Dust tight CLASS II, DIV 2, GROUP F OR G CLASS II, ZONE 22 Hermetically-sealed Nonincendive Pressurized Any Class II, Division 1 technique Class III Division 1 Intrinsic Safety N/A N/ADust tight Hermetically-sealed Division 2 Nonincendive N/A N/AAny Class III, Division 1 technique 1 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT The ELEMENT 3" Next Generation Fixed recessed downlight features a patented high/low lamp positioning which allows the LED to be positioned closer to the aperture for maximum light output and efficiency or higher in the ceiling to minimize glare and flash on the trim. LED options include premium Warm Dimming, Tunable White, Xicato and Xicato Artist Series. Trim options include Flanged or Flangeless and Flangeless in Wood Ceiling. • Housing reduced by 60% • Patented high/low lamp positioning • 2-step standard • Standard dimming down to 1% • Trim reflector options • Solite Soft Focus lens option LUMEN MULTIPLIER (CRI/CCT) CCT 80 CRI MULTIPLIER 90 CRI MULTIPLIER 2700K 0.95 0.80 3000K 1.00 0.85 3500K 1.05 0.90 Lumen output will vary by CCT and CRI. See photometric charts for output information. SPECIFICATIONS STATIC WHITE XICATO WARM DIM TUNABLE WHITE HIGH OUTPUT LOW OUTPUT STANDARD SERIES ARTIST SERIES HIGH OUTPUT LOW OUTPUT HIGH OUTPUT (5000K) HIGH OUTPUT (4000K) DELIVERED LUMENS 1800/1450 1319/1124 1129 945 1300 900 1272 1150 WATTS 17 12 15 15 17 12 18 18 EFFICACY 106/85 110/94 75 63 76 75 72 64 CRI 80+/90+80+95+90+90+ CBCP 10° - 19,414 | 18° - 5,848 25° - 5,416 | 40° - 3,230 60° - 2,305 21° - 3,184 43° - 2,733 60° - 1,014 18° - N/A | 25° - N/A | 40° - 1,622 | 60° - N/A CCT 2700K, 3000K, or 3500K 2700K, 3000K, or 3500K3 3000K - 1800K 5000K - 2700K 4000K - 1800K COLOR CONSISTENCY 2-step 1 X 2-step 3-step 2-step VOLTAGE 120V or 277V DIMMING1 Standard reverse-phase, forward-phase, TRIAC, and 0-10V dimming (down to 1%) Lutron Hi-lume EcoSystem (down to 0.1%) Lutron Hi-lume 2-Wire (down to 1%) | eldoLED 0-10V or Dali (down to 0.1%) eldoLED 0-10V or Dali (down to 0.1%) POWER SUPPLY Constant current driver with +.9 power factor and +80% efficiency OPTICS Field changeable: 10°, 18°, 25°, 40°, or 60° TIR Field changeable: 21°, 43°, or 60° Reflector Field changeable: 18°, 25°, 40°, or 60° TIR ADJUSTABILITY High/low lamp positioning; 45° collar rotation CEILING APPEARANCE Flanged, Flangeless or Flangeless in Wood Ceiling CEILING THICKNESS Flanged: Up to 2-1/2" Flangeless: No ceiling thickness limitations | Flangeless in Wood Ceiling: 1/2" to 2" Note: Thicker ceilings impact light cutoff CEILING APERTURE 3-7/8" ceiling cutout HOUSING IC Airtight, Non-IC Airtight, Chicago Plenum. IC suitable up to R60 spray foam insulation. Sauna/Steam-room use available only with combination of H Shower trim, LO Low Output housing, and I IC housing rating. CONSTRUCTION Housing: Heavy-Gauge, Cold-Rolled Steel | Trim: Die-Cast Aluminum FINISH Housing: Black Powder Coat | Trim: Antique Bronze, Black, Satin Nickel, White (paintable) GENERAL LISTINGS ETL listed. Damp listed. Shower version Wet listed. CALIFORNIA TITLE 24 Registered CEC Appliance Database. Can be used to comply with CEC 2019 Title 24 Part 6 (JA8-2016, JA8-2019) (for 90 CRI versions). L70 50,000 hours min WARRANTY2 5 years Data in chart reflect 3000K/80 CRI values unless noted. Custom Output/Custom RAL/Custom CCT available, Contact Quotes Department Ordering grids available on page 2. Accepts two optical controls and an optional trim-mounted lens. 1See ELEMENT-Lighting.com for dimmer compatibility. 2Visit ELEMENT-Lighting.com for specific warranty limitations and details. 33500K Xicato module not available for Artist series. SHOWN IN FLANGELESS BEVEL SQUARE UPDATED 3/11/21 TYPE D 2 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT ORDERING GRIDS TRIM PRODUCT CEILING APPEARANCE STYLE APERTURE FINISH E3R ELEMENT 3" ROUND E3S ELEMENT 3" SQUARE L FLANGELESS F FLANGED UP TO 1" CEILING THICKNESS F15 FLANGED 1.1"-1.5" CEILING THICKNESS F20 FLANGED 1.6"-2.0" CEILING THICKNESS F25 FLANGED 2.1"-2.5" CEILING THICKNESS B BEVEL F FLAT -O NO LENS -H SHOWER1 -L LENSED Z ANTIQUE BRONZE B BLACK S SATIN NICKEL W WHITE - Wood Ceiling option accommodates Flangeless trims only. 1H - Sauna/Steam-room use available only with combination of H Shower trim, LO Low Output housing, and I IC housing rating. REPLACEMENT OPTICS PRODUCT BEAM SPREAD 353E4LEDCOPT 18 18°25 25°40 40°60 60° 353E4LEDCOPT REPLACEMENT REFLECTORS1 PRODUCT BEAM SPREAD 352LEDXREF 21 21°43 43°60 60° 352LEDXREF 1For use with Xicato modules only. HOUSING PRODUCT CEILING APPEARANCE OUTPUT LAMP BEAM SPREAD FUNCTION HOUSING RATING DRIVER E3R ELEMENT 3" ROUNDE3S ELEMENT 3" SQUARE LF FLANGELESSFF FLANGEDWC WOOD CEILING1 -LH HIGH OUTPUT, 17W2 -LO  LOW OUTPUT, 12W3 -X XICATO, HIGH OUTPUT, 14W9 827 80 CRI, 2700K, 2-STEP830 80 CRI, 3000K, 2-STEP835 80 CRI, 3500K, 2-STEP927 90 CRI, 2700K, 2-STEP930 90 CRI, 3000K, 2-STEP935 90 CRI, 3500K, 2-STEPWD 90 CRI, 3000-1800K, WARM DIM, 3-STEPTW52 90 CRI, 5000K-2700K, TUNABLE WHITE, 2-STEP4 TW41 90 CRI, 4000K-1800K, TUNABLE WHITE, 2-STEP4 I27 80 CRI, 2700K, 1X2-STEP, XICATOI30 80 CRI, 3000K, 1X2-STEP, XICATOI35 80 CRI, 3500K, 1X2-STEP, XICATOA27 95 CRI, 2700K, 1X2-STEP, XICATO ARTISTA30 95 CRI, 3000K, 1X2-STEP, XICATO ARTIST 0 10°5 1 18°2 25°4 40°6 60° 21 21° XICATO43 43° XICATO60 60° XICATO D DOWNLIGHT I IC AIRTIGHTN NON-IC AIRTIGHTC CHICAGO PLENUM INTEGRATED DRIVERS 120V/277V UNIVERSAL PHASE/0-10V 1% (LEAVE BLANK)6 -ELD0 ELDOLED 0.1% 0-10V LINEAR7 -ELD0A ELDOLED 0.1% 0-10V LOGARITHMIC7 -ELDD ELDOLED 0.1% DALI7 -ELT0 ELDOLED TUNABLE WHITE 0.1% 0-10V LINEAR4,7 -ELTD ELDOLED TUNABLE WHITE 0.1% DALI4,7 -HLECO LUTRON HI-LUME 0.1% ECOSYSTEM8 INTEGRATED DRIVERS 120V-HL2W LUTRON HI-LUME 1% 2-WIRE7 -D Trims are required and must be ordered separately. For dimming details, refer to Dimmer Compatibility Chart. 1WC - Wood Ceiling option accommodates Flangeless trims only. 2LH - High Output available for Wet applications. Not available for Sauna/Steam-room. 3LO - Sauna/Steam-room use available only with combination of H Shower trim, LO Low Output housing, and I IC housing rating. 4TW52/TW41/ELT0/ELTD - Tunable White only available in High Output, only available with ELT0 (0-10V, linear), or ELTD (Dali). For 0-10V logarithmic dimming consult Quotes Department. 50 - 10° optic has a unique LED module not available with Warm Dim or Tunable White. Changing optics to 18°, 25°, 40° or 60°, will require a new LED module. 6Universal dimming is reverse-phase, forward-phase, and TRIAC. 7Lutron Hi-lume and eldoLED drivers not compatible with Round Flangeless (E3RLF) or Round Wood Ceiling (E3RWC) housings. 8HLECO - Lutron has put their entire 0.1% ECO drivers on indefinite hold which impacts all -HLECO item numbers. Please consult factory for alternatives. This does not impact -HL2W. 9X - XICATO housings utilize dedicated Standard Phase, 0-10V, 120V and 277V drivers. If ordering Xicato with Standard Drivers (non-Lutron or eldoLED), at the end of the item number please specify: -010 for 0-10V 120V, -277 for Phase 277V or -010-277 for 0-10V 277. For example: E3RLF-XA2743DI-010 or E3RLF-XA2743DI-277 or E3RLF-XA2743DI-010-277. PREMIUM LENS HOLDER PRODUCT LENSES 240E3LENSHLDR 1 ONE LENS 2 TWO LENSES 240E3LENSHLDR The premium, threaded lens holder provides more secure mounting of additional lenses as compared to the standard lens holder that ships with each fixture. LENSES / LOUVERS1 PRODUCT 140MR16SF SOLITE SOFT FOCUS LENS 140MR16SB SANDBLASTED LENS 140MR16LL LINEAR SPREAD LENS 140MR16DF DIFFUSER SPREAD LENS 140UVMR16 CLEAR GLASS LENS EL2RHCBK EGGCRATE/HEXCELL LOUVER 1For additional lenses, louvers, optical controls and accessories, reference ELEMENT-lighting.com/Products/Accessories. ELEMENT allows up to two Lenses or Louvers per fixture. 3 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT IC AIRTIGHT / NON-IC AIRTIGHT / CHICAGO PLENUM HOUSING 4"102 mm 9.5" 241 mm 12.5"318 mm 5.2"132 mm COLLAR HEIGHT 0.75" (19 MM) (SEE INSTRUCTIONS FOR CEILING THICKNESS < 0.75") TRIMS ROUND BEVEL SQUARE BEVELROUND BEVEL ROUND FLATROUND FLAT SQUARE BEVEL SQUARE FLATSQUARE FLAT FLANGED FLANGELESS 3.2"81 mm 1.7"43 mm 1.7"43 mm 3.2"81 mm 3.2"81 mm 1.7"43 mm 4.3"109 mm 1.7"43 mm 1.7"43 mm 3.2"81 mm 1.7"43 mm 4.3"109 mm 4.3"109 mm 3.2"81 mm 1.7"43 mm 1.7"43 mm 4.3"109 mm 3.2"81 mm FINISH ANTIQUEBRONZE BLACK SATIN NICKEL WHITE(PAINTABLE) FLANGELESS IN WOOD CEILING LENS OPTION ROUND BEVEL (ANTIQUE BRONZE) ROUND FLAT (ANTIQUE BRONZE) 3.2"81 mm 1.7"43 mm 1.7"43 mm 3.2"81 mm 3.2"81 mm 1.7"43 mm 1.7"43 mm 3.2"81 mm SQUARE BEVEL (SATIN NICKEL) SQUARE FLAT (SATIN NICKEL) SHOWN WITH AND WITHOUT A LENS (SQUARE FLANGED BEVEL) SHOWN WITH AND WITHOUT A LENS (ROUND FLANGELESS BEVEL) 4 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT FLANGELESS IN WOOD CEILING TRIM ADAPTER Wood Ceiling housings (“WC” designation in the ordering grid) ship with an adjustable trim adapter that inserts into the housing aperture and allows standard ELEMENT 3" Flangeless trims to achieve a truly flangeless, flush ceiling appearance in special applications such as wood or stone installation. For use in new construction. Consult installation instructions regarding plenum requirements and ceiling thickness ratios. TRIM ADAPTER INSTALLED INSTALL BEFORE CEILING TRIM ADAPTER HOUSINGCOLLAR HOUSING TRIM ADAPTER FLUSH HOUSING COLLAR.85"22 mm HOUSING TRIM ADAPTER EXTENDED HOUSING COLLAR .625" 16 mm 1.5"38 mm 5 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT ELEMENT Specular Reflectors reduce glare while creating a clean, quiet ceiling appearance. Available finishes include Anodized Gold and Silver for a decorative accent or Anodized Black for an ultimate quite ceiling aesthetic. These beautiful trim accessories have been specifically designed to minimize any effect on light performance, color and output. Specular Reflectors are available for both Adjustable and Fixed downlights and are compatible with ELEMENT 3" trims and housings. • Can be easily installed or removed • Assembles to existing trim • Compatible with Fixed and Adjustable Housings • Finish Options: Anodized Gold (G), Anodized Black (B) or Anodized Silver (S) SHOWN IN ANODIZED BLACK (REFLECTOR ONLY) SHOWN IN ANODIZED BLACK (BELOW CEILING VIEW) E3 TRIM-MOUNTED REFLECTORS PRODUCT STYLE FINISH E3TREF NS1 NON-SLOTTED NS2 NON-SLOTTED NS3 NON-SLOTTED NS4 NON-SLOTTED NS5 NON-SLOTTED NS6 NON-SLOTTED B ANODIZED BLACK G ANODIZED GOLD S ANODIZED SILVER E3TREF Reflectors are placed on top of the inside of the trim or affixed via screws (only if provided). ORDERING GRID SHOWN IN ANODIZED GOLD (BELOW CEILING VIEW) SHOWN IN ANODIZED SILVER (BELOW CEILING VIEW) SHOWN IN ANODIZED GOLD (TRIM MOUNTED) COMPATIBLE TRIMS NON-SLOTTED (FOR FIXED) 3" round, flanged, bevel 2.6"66 mm2.6"66 mm 1.9"48 mm 1.3"33 mm E3TREFNS1 (B, G, S) 3" square, flanged, bevel 3.2"81 mm2.7"69 mm3.2"81 mm 1.6"41 mm 1.3"33 mm E3TREFNS5 (B, G, S) 3" round, flanged, flat 2.6"66 mm2.6"66 mm 1.9"48 mm 1.3"33 mm E3TREFNS1 (B, G, S) 3" square, flanged, flat 2.8"71 mm2.8"71 mm 1.9"48 mm 1.2"30 mm E3TREFNS3 (B, G, S) 3" round, flangeless, bevel 2.1"53 mm2.1"53 mm 1.9"48 mm 1.3"33 mm E3TREFNS2 (B, G, S) 3" square, flangeless, bevel 2.9"74 mm2.9"74 mm 1.9"48 mm 1.2"30 mm E3TREFNS6 (B, G, S) 3" round, flangeless, flat 2.1"53 mm 2.1"53 mm 1.9"48 mm 1.3"33 mm E3TREFNS4 (B, G, S) 3" square, flangeless, flat 2.8"71 mm2.8"71 mm 1.9"48 mm 1.2"30 mm E3TREFNS3 (B, G, S) May require lamp to be placed in high position. Not compatible with lensed trims. SPECIFICATIONS 4.3"109 mm 1.7"43 mm 1.7"43 mm 4.3"109 mm 4.3"109 mm 3.2"81 mm 1.7"43 mm 4.3"109 mm 3.2"81 mm 1.7"43 mm 1.7"43 mm 4.3"109 mm 3.2"81 mm 1.7"43 mm 3.2"81 mm 1.7"43 mm 3.2"81 mm 3.2"81 mm 1.7"43 mm 3.2"81 mm 1.7"43 mm TRIM-MOUNTED REFLECTORS 6 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT Description: 3" LED Module 25° Beam - 0° Tilt, 80 CRI, 3000K Model: E3 Citizen LED Input Power (Watts): 18.3 Input Power Factor: 0.98 Absolute Luminous Flux (Lumens): 1754 Lumen Efficacy (Lumens per Watt): 95.5 Description: 3" LED Module 18° Beam - 0° Tilt, 80 CRI, 3000K Model: E3 Citizen LED Input Power (Watts): 18.1 Input Power Factor: 0.98 Absolute Luminous Flux (Lumens): 1598 Lumen Efficacy (Lumens per Watt): 88.1 Description: 3" LED Module 10° Beam - 0° Tilt, 80 CRI, 3000K Model: E3 Citizen LED Input Power (Watts): 16.3 Input Power Factor: 0.98 Absolute Luminous Flux (Lumens): 1337 Lumen Efficacy (Lumens per Watt): 82 Output difference between CCTs ~ 5%, CRIs ~ 15%. ANGLE 0°45°90° 0°19414 19414 19414 5°10254 10254 10254 10°3511 3511 3511 15°1342 1342 1342 20°383 383 383 25°126 126 126 30°84 84 84 35°54 54 54 40°31 31 31 45°22 22 22 50°18 18 18 55°11 11 11 60°6 6 6 65°3 3 3 70°2 2 2 75°0 0 0 80°0 0 0 85°0 0 0 90°0 0 0 ANGLE 0°45°90° 0°5848 5848 5848 5°5500 5478 5491 10°3919 3944 3905 15°2103 2212 2149 20°1058 1199 1075 25°507 548 508 30°250 237 250 35°148 140 141 40°93 98 94 45°51 69 61 50°33 46 37 55°21 27 24 60°4 15 10 65°2 3 2 70°2 2 2 75°0 0 0 80°0 0 0 85°0 0 0 90°0 0 0 ANGLE 0°45°90° 0°5422 5416 5427 5°4916 4872 4888 10°3800 3718 3721 15°2040 2115 2016 20°870 979 900 25°400 441 414 30°190 190 196 35°103 103 105 40°60 65 61 45°27 43 31 50°16 25 17 55°7 12 7 60°2 5 2 65°2 2 2 70°1 1 2 75°0 0 0 80°0 0 0 85°0 0 0 90°0 0 0 PHOTOMETRICS 6718fc 1783fc 777fc 432fc 282fc 1.7' 3.3' 5' 00.9' 8.3' 6.7' 0 3333 6667 10,000 13,333 16,667 20,000 90˚ 80˚ 70˚ 60˚ 50˚ 40˚30˚20˚10˚0˚ 0˚ 0˚45˚ 90˚45˚ 90˚ 1899fc 504fc 220fc 122fc 78fc 1.7' 3.3' 5' 02.8'4.6' 8.3' 6.7' 2024fc 537fc 234fc 130fc 85fc 1.7' 3.3' 5' 02.2'3.7' 8.3' 6.7' 0 917 1833 2750 3667 4583 5500 90˚ 80˚ 70˚ 60˚ 50˚ 40˚30˚20˚10˚0˚ 0˚ 0˚45˚ 90˚45˚ 90˚ 0 983 1967 2950 3933 4917 5900 90˚ 80˚ 70˚ 60˚ 50˚ 40˚30˚20˚10˚0˚ 0˚ 0˚45˚ 90˚45˚ 90˚ 7 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT Description: 3" LED Module 60° Beam - 0° Tilt, 80 CRI, 3000K Model: E3 Citizen LED Input Power (Watts): 18.4 Input Power Factor: 0.98 Absolute Luminous Flux (Lumens): 1536 Lumen Efficacy (Lumens per Watt): 83.5 Description: 3" LED Module 40° Beam - 0° Tilt, 80 CRI, 3000K Model: E3 Citizen LED Input Power (Watts): 16.9 Input Power Factor: 0.98 Absolute Luminous Flux (Lumens): 1774 Lumen Efficacy (Lumens per Watt): 104.6 Output difference between CCTs ~ 5%, CRIs ~ 15%. ANGLE 0°45°90° 0°3230 3230 3230 5°3107 3126 3159 10°2824 2830 2871 15°2415 2407 2463 20°1863 1866 1937 25°1111 1125 1128 30°490 521 479 35°221 232 205 40°115 114 110 45°65 64 59 50°30 38 22 55°14 22 11 60°6 9 4 65°1 3 1 70°1 1 1 75°1 1 1 80°0 0 0 85°0 0 0 90°0 0 0 ANGLE 0°45°90° 0°2305 2305 2305 5°2313 2298 2268 10°2295 2248 2155 15°2219 2116 1938 20°1964 1876 1714 25°1548 1544 1330 30°1113 1176 1013 35°749 835 704 40°450 511 428 45°230 283 221 50°94 140 91 55°38 69 35 60°18 31 16 65°8 13 6 70°0 4 0 75°0 0 0 80°0 0 0 85°0 0 0 90°0 0 0 PHOTOMETRICS 0 396 791 1187 1584 1979 2375 90˚ 80˚ 70˚ 60˚ 50˚ 40˚30˚20˚10˚0˚ 0˚ 0˚45˚ 90˚45˚ 90˚ 576fc 144fc 64fc 36fc 2' 4' 6' 04.1'8.1' 8' 1118fc 297fc 129fc 72fc 47fc 1.7' 3.3' 5' 04'6.7' 8.3' 6.7' 0 550 1100 1650 2200 2750 3300 90˚ 80˚ 70˚ 60˚ 50˚ 40˚30˚20˚10˚0˚ 0˚ 0˚45˚ 90˚45˚ 90˚ 8 ©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting. Tech Lighting reserves the right to change specifications for product improvements without notification. ELEMENT™ 3" LED FIXED DOWNLIGHT 8 7400 Linder Ave., Skokie, IL 60077 T 847.410.4400 www.techlighting.com PROJECT INFORMATION JOB NAME AND INFORMATION FIXTURE TYPE AND QUANTITY NOTES Series Face type Housing color Number of faces Letter color Input voltage Operation Options LE LED, surface mount LRE LED, re-cessed S Stencil P Panel 1 (blank)Matte black, brushed aluminum face BZ Dark bronze W White B Matte black 1 Single face 2 Double face 2 R Red G Green (blank)Universal input voltage (120-277V, 50 or 60 HZ) (blank)AC only EL N Nickel-cadmium battery back-up X2 Lamp wired on two separate AC circuits 3 (blank)None TP Two tamper proof Torx-head screws VR Vandal-resistant shield (1/8” thick polycarbonate) 4 FI FA Field selectable fire alarm interface or flashing emergency operation with intermittent audible alarm (one flash per minute) 5 FI Fire alarm flashing interface 6 FA Flashing emergency operation and intermittent audible alarm 7 SD Self-diagnostics 7 BAA BAA Buy America(n) Act Compliant 8 ORDERING INFORMATION For shortest lead times, configure products using bolded options. Example: LE S 1 R EL N SD EMERGENCY LE-LRE Die-Cast Aluminum Exits LE and LRE FEATURES & SPECIFICATIONS INTENDED USE — Ideal for applications requiring attractive die-cast aluminum signage, superior il- lumination and low energy consumption. CONSTRUCTION — Precision-molded, die-cast aluminum construction — ultra-slim, compact housing. Fine-grain brushed aluminum faceplate with matte black electrostatic polymeric trim. Clear lacquer finish on brushed face inhibits fingerprints and other surface contaminants. All electronics located inside housing. Fully overlapping light seal prevents light leaks. Universal directional chevron knockouts are completely concealed and easily removed. Hinged faceplate and spring latches for easy lamp compartment access, no exposed hardware. Letters 6" high with 3/4" stroke, with 100 ft viewing distance rating, based upon UL924 standards. U.S. Patent No. 5,739,639, 5,954,423 and 6,502,044. Canada Patent No. 2,204,218. Other patents pending. OPTICS — Lamp is constructed using new LED technology. Provides perfectly uniform illumination to meet 3/4" letter stroke required by code. The typical life of the exit LED lamp is 10 years, based on continuous operation. Unique LED lamp platform accommodates both single-face and double-face exits. Low energy consumption — red exit consumes std .81W, 1.3W (120V), green exit consumes std is 1W, 1.5W (120V). Universal input voltage capabilities (120V through 277V, 50 or 60 HZ). ELECTRICAL — Solid-state electronic elements to eliminate risk of electromechanical failures. Surge protection meets ANSI/IEEE C62.41 category B and IEC 1000 immunity standards for high voltage surges, electrostatic discharges, high frequency electrical fast transients and line voltage dips/swells. Emergency Operation (for EL N option only): Battery: Sealed, maintenance-free nickel-cadmium battery delivers 90 minutes capacity to lamp. Self-diagnostics (SD option only): Two-state constant-current charger maximizes battery life and automatically recharges after battery discharge. Test switch provided for manual testing. Self-diagnostic testing for five minutes every 30 days, 30 minutes at 180-day interval, and 90 minutes annually. Diagnostic evaluation of LED light source, AC to DC transfer, charging and battery condition. Continuously monitors AC functionality. Low voltage disconnect prevents excessive deep discharge that can permanently damage the battery. Single-point microcomputer control for all electronic features. Crystal oscillator timing system with watchdog protection for precision accuracy. AC/LVD reset allows battery connection before AC power is applied and prevents battery damage from deep discharge. Brownout protection is automatically switched to emergency mode when supply voltage drops below 80% of nominal. Single multi-chromatic LED indicator to display two-state charging, test activation and three-state diagnostic status. Test switch provides manual activation of 30-second diagnostic testing for on-demand visual inspection. INSTALLATION — Universal mounting (top, end or back). Double face available with top or end mounting only. LRE: Trim ring has 3/4” depth adjustment to ensure a flush fit against the surface. Protrudes 1/10” from the surface. No exposed hardware. Die-cast aluminum canopy provided for surface mount only. LISTINGS — UL damp location listed 50°F - 104°F (10°C - 40°C). Meets UL 924, NFPA 101 (current Life Safety Code), NEC and OSHA illumination standards. North Carolina Department of Insurance. BUY AMERICAN — Product with the BAA option is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT. Please refer to www.acuitybrands.com/buy-american for additional information. WARRANTY — 5-year limited warranty. (Battery is prorated.) This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions Note: Actual performance may differ as a result of end-user environment and application. All values are design or typical values, measured under laboratory conditions at 25 °C. Specifications subject to change without notice. Notes 1 Panel face available for special wording only (see Custom Signage spec sheet). 2 Not available with LRE models. 3 UL Listed as emergency lighting. 4 VR contains tamper proof screws. 5 Available with SD option only. 6 Available with AC only or EL N operation only. 7 Available with EL N option only. 8 BAA only available for LE. 9 Add W for white. Catalog Number Notes Type LE surface LRE recessed Accessories: Order as separate catalog number. ELA US12 12” stem kit (see spec sheet ELA-StemKits) 2,9 ELA WG1 Back-mount wire guard (see spec sheet ELA-WG) 2 ELA WGEXT Top-mount wire guard (see spec sheet ELA-WG) 2 ELA WGEXE End-mount wire guard (see spec sheet ELA-WG) 2 ELA ERK Recess mounting rough-in kit for LRE only (see spec sheet ELA-ERK) † Small Battery Chargers Certified in the CA Title 20 Appliance Efficiency Database. † Buy American E1 SPECIFICATIONS LE-LRE LED, Signature MOUNTING All dimensions are in inches (centimeters). For VR option, add 1/4" to height and width. Add 1/8" depth for single face; 1/4" depth for double face. Shipping weight: LE - 4 lbs (1.8 kgs) LE EL N- 5 lbs (2.3 kgs) LRE - 4 lbs (1.8 kgs) LRE EL N - 5 lbs (2.3 kgs) SELF-DIAGNOSTICS (SD option only) The typical life of the exit LED lamp is 10 years. KEY FEATURE LE - End Mounting LE - Top Mounting LE - Back Mounting 1-5/8(4.1) 1-3/4(4.4) 9-1/2(24.0) 4-1/2(11.4) 6(15.2) 5-3/4(14.4) 13(33.0) 7-7/8(20.0) 7-7/8(20.0)4(10.2) 11-3/8(28.9) 11-3/8(28.9) • Five-minute test every 30 days • 30-minute test every six months • 90-minute test annually • Diagnostics evaluate the battery, lamp, charger and AC to DC transfer. Condition Indication Normal mode Steady green Self-testing Flashing green Emergency mode Off Hi-charge Steady red Battery failure Single-flash red Lamp failure Double-flash red Circuit failure Triple-flash red Notes 1 The typical life of the exit LED lamp is 10 years, based on continuous operation. 2 At 77°F (25°C). 3 All life safety equipment, including emergency lighting for path of egress must be maintained, serviced, and tested in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the required maintenance, service, or testing could jeopardize the safety of occupants and will void all warranties. 4 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower temperatures affect life and capacity. ELECTRICAL Primary circuit Type Typical LED life1 Supply voltage Input watts Max. amps Red LED AC only 10 Years 120 0.81 0.05 277 1.2 0.06 Green LED AC only 10 Years 120 1.05 0.05 277 1.32 0.06 Red LED emergency 10 Years 120 1.3 0.06 277 1.4 0.07 Green LED emergency 10 Years 120 1.5 0.07 277 1.7 0.07 BATTERY Sealed Nickel-Cadmium Shelf life2 Typical life2 Maintenance3 Temperature range 4 3 years 7-9 years none 50°F – 104°F (10°C – 40°C) LE-LRE EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone:800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 1994-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/08/22 9-7/16(24.0) 12-3/8(31.4) 8-7/8(22.5) 4(10.2) 12-15/16(32.9) STANDARD MOUNTING Trim ring brackets(provided) Trim ring (provided) J-box(contractor furnished) Wall opening dimensions: 8-3/4” H x 12-3/8” W x 1-3/4” D MOUNTING WITH OPTIONAL ROUGH-IN KIT (ELA ERK) Contractorfurnishedsupports Wall opening dimensions: 8-7/8” H x 12-3/8” W x 4” D Mule Lighting , Inc. 46 Baker Street Providence, RI 02905 800 556-7690 P 401 941-2929 F www.mulelighting.com SVXH CLASS 1 DIVISION 2 LED EXIT SIGN COMBO HAZARDOUS LOCATION SERIES LED ILLUMINATION SPECIFICATIONS Red or green LED (Light Emitting Diode) light strips provide brilliant and powerful EXIT illumination while consuming less than 5 watts of electricity at all times. The SVXH Class 1 Division 2 Exit Sign & Emergency Lights Combo is designed for use in hazardous locations that feature flammable and explosive gases, vapors, and dust. Such environ-ments include power plants, chemical processing facilities, and oil refineries. This Class 1 Div 2 exit sign is waterproof and weatherproof, it can be installed both indoors and out, including in freezing environments. The body of the SVXH is made from aluminum and features a vandal proof polycarbonate faceplate that protects the unit from moisture and abuse. The polycarbonate faceplate is fully gasketed and and fastened with stainless steel tamper resistant screws. A poly-vinyl chloride frame features a built-in gasket that seals out moisture. This hazardous location exit sign is corrosion and and flame resistant. 120 or 277V dual voltage operation. UL 924 Listed, Class 1 Division 2, Groups A, B, C, and D. Two 10-watt, bottom-mounted MR16 Halogen lamps (LED also) provide powerful egress illumination. The lamps are easily positions and protected by a polycarbonate shield. The nickel cadmium exit sign emergency light battery backup system operates the fixture for at least 90 minutes after AC power loss. • Rated for Class 1 Division 2 Groups A, B, C and D• 2 for 1 exit sign and emergency light solution• Push-to-test button with LED charging indicator• NEMA 3, 4, 4x, and 12 Rated• UL 924 Listed for the USA• 3 year warranty OVERVIEW FEATURES DIMENSIONS ORDERING INFORMATION SERIES H (6V 20W NiCad) H12N (12V 24W NiCad) R (red) G (green) D (self-diagnostic) AD (audible SD) 0 (0 heads) 2 (2 heads) LETTER COLOR OPTIONS # OF HEADS LA (6V 4W LED) LG (12V 4W LED) LI (12V 5W LED) LJ (12V 6W LED) LAMP TYPEOPERATION SVX TYPE EEM1 BATTERY INTERNAL HEATER OPTION ELECTRICAL SPECIFICATIONS Mule Lighting , Inc. 46 Baker Street Providence, RI 02905 800 556-7690 P 401 941-2929 F www.mulelighting.com EXTERNAL SPECIFICATIONS This Class 1 Division 2 exit sign and emergency lights combo is composed of an aluminum housing paired with a polycarbonate faceplate that cover the LED exit sign and halogen emergency lamps. The housing and faceplate are sealed together to prevent fluids, vapors, and gases from entering the inside of the SVXH exit sign combo with emergency lights. The housing is tamper-resistant and features a hermetically sealed magnetic test switch that allows for easy testing of the nickel cadmi-um battery backup system. The entire housing is vandal resistant and approved for use in high abuse areas such as schools and prisons.These types of fixtures are known as explosion proof exit signs, because the housing is hermetically sealed to prevent the intrusion of any type of gas, vapor, or liquid which could ignite a fire or explo-sion. Class 1 Division 2 exit signs are designed for hazardous locations and are thus designed and built under the strictest quality control standards. If you need a model that has emergency lights attached to it. UL924 Listed for the U.S. and Canada, CS860, NFPA, Life Safety 101, UL Listed for Damp Locations. UL Listed for Wet Locations. CODE COMPLIANCE Standard Self-Diagnostic circuitry continuously monitors every critical function of the unit. If a problem occurs, a single fault indicator on the outside of the fixture flashes immediately. A detailed diagnostic display is located internally. The detailed display will further indicate the nature of the fault as either a battery fault, load fault or a charger fault. Audible self-diagnostics available. SELF-DIAGNOSTIC TESTING • LA - 6V 4W MR16 LED• LG - 12V 4W MR16 LED• LI - 12V 5W MR16 LED• LJ - 12V 6W MR16 LED LAMP SELECTION GUIDE The SVXH Series comes with a 3-year factory warranty. The lamps are not covered. Deliberate damage, misuse, or improper installa- tion effectively cancel the warranty. Battery features a 20% per year pro-rata warranty. Class 1 Div 2 exit sign combos feature a maintenance-free Nickel Cadmium exit sign battery provides 90 minutes of emergency support and lasts for 5-7 years. The SVXH Class 1 Division 2 Exit Sign Combo can be upgraded to a Nickel-Metal Hydride battery which lasts up to 10 years long and features a 12V 40W capacity. The unit can be outfitted with an internal heater that keeps battery backup system ready for emergency mode operation for applications that feature freezing temperature environments (up to -4o F) 120/277V AC dual-voltage operation is standard. Other voltages available upon request such as 220v and 240v. T6 (maximum 85°C/185°F). Evaluated to UL 924 and UL1598 standards. WARRANTY SVXH CLASS 1 DIVISION 2 LED EXIT SIGN COMBO HAZARDOUS LOCATION SERIES Application The “Dynamo” DYN Series is a highly versatile superior lumen output, industrial application emergency lighting unit, designed to provide a minimum of 90 minutes illumination when primary power is lost. The DYN Series provides the same level of lumen output with no light degradation for the full 90 minutes of battery discharge. It has a flame-rated, UV stable thermoplastic housing which is fully gasketed and corrosion resistant with a gray finish. LED based lamp-heads are made of high strength die-cast aluminum with polycarbonate lens. Includes micro-controller based 3-stage charger and Lithium Iron Phosphate(LiFePO4) battery. The DYN Series accepts 120 through 277VAC input at 50 or 60Hz. Not designed for self-diagnostic operation at 220-240VAC input. Universal mounting plate made of painted stamped steel. The Dynamo is specifically designed for demanding environments, high reliability operation in industrial settings such as wet location or hose-down, food processing, food storage, production facilities, chemical plant and wastewater treatment. Hazardous location emergency lighting units with optional C1D2 listed for use in NEC Class I, Division 2, Groups A, B, C and D and Class 1, Zone 2, Groups IIA, IIB, IIB+H2, IIC. Hazardous Location Emergency Lighting Units with optional C2D1 listed for use in NEC Class II, Division 1, Groups E, F and G, and Zone 20, 21 and Class 3. Construction The DYN series housing, covers, remote housing and shield are made of polycarbonate. Lamp-heads are made of die-cast aluminum for thermal dissipation. LED lenses are made of polycarbonate. The Food Processing(FP) and Class 2, Division 1(C2D1) optioned DYN includes a clear polycarbonate shield which fully covers the lamp-heads. Installation The unit includes a universal mounting plate which facilitates mounting to a truss or I-beam, pole, column, or wall. Included is a special bracket to ensure positive pole gripping when using bands. In wet or NEMA 4X applications, use UL listed water tight conduit fittings that meet the requirements of the UL 514B Standard for Conduit Tubing and Cable Fittings when using knockouts on the side or top of unit. All fittings supplied by others. C1D2 and C2D1 listed models include 2 each hazardous location rated conduit hubs with ground provision. Illumination The DYN series provides bright and uniform illumination and is specifically designed for higher mounting heights above 9’. Coverage provided by 2 sealed aluminum lamp-heads using 3 high power LEDs each. The LEDs are located in a specially designed heat dissipating lamp-head which is fully adjustable and can be locked into position. The DYN is designed for full lumen output across the entire 90 minutes of operation. This ensures maximum visibility of the egress path over the full 90 minute discharge period. Warranty LED Lifetime Warranty DYN Standard Model- 3 Year Full DYN Spectron Model- 5 Year Full FEATURES Dynamo DYN Series NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light Catalog Number Comments Type ACCESSORIES DYNRS-4X NEMA 4X Rated Single Head Remote DYNRD-4X NEMA 4X Rated Double Head Remote DYNRS-4X-FP Food Processing rated Single Head Remote (Includes Polycarbonate Shield) DYNRD-4X-FP Food Processing rated Double Head Remote (Includes Polycarbonate Shield) WGA2 Wire Guard (Does not include Food Processing option) 15”H x 14”L x 7”D DYNRD-C1D2 Class 1, Div. 2 Remote, 3W heads, 1 conduit hub included DYNRD-C2D1 Class 2, Div. 1 Remote, 3W heads with shield, 1 conduit hub included ORDERING GUIDE Model DYN Blank Wet Location 4X NEMA 4X/IP66 Rated FP Food Processing Rated 4 HTR Heater for Cold Temp 5 C1D2 Class 1 Div. 2 6 C2D1 Class 2 Div. 1 7 Application 1. Only available on DYN with 12 watt capacity 2. DYN6 only available in the following configurations-DYN6, DYN6I, DYN6-4X, DYN6I-4X, DYN6I-4X-HTR, DYN6I-4X-FP, DYN6I-4X-HTR-FP 3. DYN12 only available in the following configurations-DYN12, DYN12I, DYN12-4X, DYN12-4X-FP, DYN12I-4X, DYN12I-4X-HTR, DYN12I-4X-FP, DYN12I-4X- HTR-FP, DYN12-06L, DYN12I-06L, DYN12-4X-06L, DYN12-4X-FP-06L, DYN12I-4X-06L, DYN12I-4X-HTR-06L, DYN12I-4X-FP-06L, DYN12I-4X-HTR-FP-06L 4. FP option must be ordered with 4X option. Example: DYN6I-4X-FP 5. HTR option only available with Spectron® 6. C1D2 Option only available with DYN6I-C1D2, DYN12I-C1D2, and DYN12I-C1D2-06L 7. C2D1 Option only available with DYN6I-C2D1, DYN12I-C2D1, and DYN12I-C2D1-06L which includes shield Patent Pending Capacity 6 6 Watt 2 12 12 Watt 3 Blank Wet Location I Spectron® Self Diagnostics Self-Diagnostics Lamp Blank 3 Watt LED lamps 06L 6 Watt LED lamps 1 Compliances Listed to UL924 Standard, NFPA 101, NFPA 70 Wet Location, NEMA 4, 4X rated UL Sanitation Certified with FP Option IP66 rated for 4X models only C1D2 and C2D1 optioned products; Listed to Standard 924 and Standard 844 (Hazardous Location) NEC Class 1 Division 2 Groups A, B, C, D NEC Class 2, Division 1 Groups E, F and G NEC Class 3 CEC T20 Compliant EM2 Electronics Upon failure of the normal utility power, a LED driver is automatically activated to power the emergency LED lamp-heads. At resumption of normal utility power, the LED driver is turned off. The battery is recharged through a micro-controller based 3-stage charger. The battery is a maintenance-free Lithium Iron Phosphate (LiFePO4) type. The EVHC series accepts dual-voltage input of 120 through 277VAC at 50 or 60 Hz. A low voltage battery disconnect(LVD) feature protects the battery from severe damage during prolonged power failures. Manual testing is available at any time using the push-to-test button. The optional heater features a heating wrap and thermostat to maintain optimal battery temperature during charge or discharge. The DYN remote can be located up to 100’ from the source unit using 12 gage wire. Number of Lamps: 2 lamp-heads with 3 high-power LEDs per head Lamp Color: Cool White, 5000K Total Lamp Output: Standard Model, 331 lumens per lamp-head Optional 6W Lamps, 514 lumens per lamp-head Rated LED Lifecycle: Greater than 100,000 hrs Standard Features Include: • Wet location operation with lock-down head positioning(no shield) • Sealed external push-to-test switch and AC-on indicator • Battery re-charge within 24 hours • AC Lock-out circuit • Low voltage battery disconnect • Conduit entry knock-out located at the top center and upper half of each side • Micro-controller based 3-stage charger • Flashing service alert code for “Battery Disconnect” or “Charger Fault” in compliance with UL 924 Optional Feature Include: • 4X -NEMA4, 4X option fully sealed and gasketed for indoor/outdoor use, splash and hose-down environments and corrosion resistance • FP- Food processing option is UL Sanitation certified for use in food preparation and storage, and in food service establishments • HTR- Includes a heating wrap and thermostat to maintain optimal battery temperature in cold environments to -22°F(-30°C) Optional Spectron Includes: • Self-diagnostics monitors LED status, LED driver circuit, battery capacity and charger function and displays any fault detection by means of a flashing code • Self-Test feature automatically runs a 1 minute test once a month and an alternating 30-60 minute test once every 6 months. Multi-color LED indicator provides visible fault detection and charging status • User initiated 1, or 90-minute system test feature • 15 minute re-transfer delay • Automatic unit transfer in brown-out conditions (below 80% of nominal AC input voltage) SPECIFICATIONS INPUT POWER CONSUMPTION Photometrics available for download at www.dual-lite.com Maintenance Mode Power Consumption 120VAC- 0.33W Maintenance Mode Power Consumption 277VAC- 0.36W Battery Capacity Lamp(W)Lumens per Lamp Remote Lamp Watts Run-Time Extended Runtime Remote Capable Remote Part Number DYN6 LiFePO4 6 watts 3 watts 331 0 90 min No No N/A DYN6I LiFePO4 6 watts 3 watts 331 0 90 min No No N/A DYN12 LiFePO4 12 watts 3 watts 331 6 90 min Yes Yes DYNR DYN12I LiFePO4 12 watts 3 watts 331 6 90 min Yes Yes DYNR DYN12-06L LiFePO4 12 watts 6 watts 514 0 90 min No No N/A DYN12I-06L LiFePO4 12 watts 6 watts 514 0 90 min No No N/A Operating Temperature: Wet/NEMA 4X Location Listed: 50° to 122°F(10° to 50°C) Heater Option Models: -22° to 122°F(-30° to 50°C) Additional Product Information Input Voltage Amps.Max. Watts DYN6 120 0.03 3.40 277 0.04 3.49 DYN6 with heater 120 0.18 20.94 277 0.08 21.13 DYN12 120 0.05 5.98 277 0.04 6.52 DYN12 with heater 120 0.21 25.30 277 0.09 25.60 Dynamo DYN Series NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light Operating Temperature in °C Ambient °C CLASS 1 DIV. 2 A, B, C, D CLASS 2 DIV. 1 E, F, G Supply Wire Temp. °C Min. 40 T6 T6 75 50 T5 T6 75 Temperature Codes and Maximum Temperature Ratings APPLICATION INFORMATION * Multiple unit spacing based on 6’ path Ceiling Mount 6’ Path SPACING (SEE CHART) MOUNTING HEIGHT (SEE CHART) Industrial Parameters CH=30’, R=10/10/10, Ceiling mounted (Multiple Unit Spacing), 6’ Path DYN12-06L (6 watt lamp option)DYN6 (3 watt lamps) Mounting Height 20’18’16’14’12’10’7.5’Mounting Height 20’18’16’14’12’10’7.5’ Max Spacing @ 1 FC Avg 62’65’68’71’74’77’81’Max Spacing @ 1 FC Avg 43’45’48’51’53’56’59’ Max Spacing @ 1 FC Min 35’34’34’33’32’31’29’Max Spacing @ 1 FC Min 28’28’27’27’26’24’22’ Meets Life Safety Code minimum illuminance of 0.1 fc and average illuminance of 1.0 fc. Photometry files available on the Dual-Lite web site (www.dual-lite.com). Dynamo DYN Series NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light DIMENSIONS 5.15” 4.34” 4.25” 11.25”11.61” 9.78”9.78” 1.24” 5.15” 6.04” 3.54” 6.3” 10.54” 3.72” 4.94” 9.75” 11.04” 10.54” 3.72” 4.94” 9.75” 11.04” 6.11” Web: www.dual-lite.com • Tech Support: (866)-313-3909701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright © Dual-Lite, a division of Hubbell Lighting, Inc., All Rights Reserved Specifications subject to change without notice. • Printed in U.S.A.0603637 A 03/18 5.15” 4.34” 4.25” 11.25”11.61” 9.78”9.78” 1.24” 5.15” 6.04” 3.54” 6.3” 10.54” 3.72” 4.94” 9.75” 11.04” 10.54” 3.72” 4.94” 9.75” 11.04” 6.11” Dynamo DYN Series NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light Industrial Applications | Area Light 44 www.dialight.com Vigilant® LED Area Light 100-277 VAC, 120-250 VDC Dimensions in inches [mm] Mechanical Information: Fixture weight: 10 lb (4.5 kg) - Polycarbonate lens 12 lb (5.5 kg) - Tempered glass lens with stainless steel bracket: 13 lb (5.9 kg) - Polycarbonate lens 15 lb (6.8 kg) - Tempered glass lens Shipping weight: Add 2 lb (0.91 kg) to weights above Impact rating: IK10 - Polycarbonate lens IK07 - Tempered glass lens Cabling: 10’ STOOW 1.02 mm 18 AWG Mounting: Secondary retention standard Electrical Specifications: Operating voltage: 100-277 VAC 50/60Hz, 120-250 VDC Operating temperature: -40°F to +149°F (-40°C to +65°C) EMC: FCC Title 47, Subpart B, Section 15, Class A device CISPR-15 RF Immunity 20V/m 80MHz-1GHz. Transient protection: 6 kV, 2 Ohm line-line and line-ground Harmonics: IEC 61000-3-2, Class C THD: < 20% Power factor: > 0.9 Construction: Housing: Copper-free aluminum Finish: Superior dual coat finish - Sealed polyester topcoat Lens: Hard-coated polycarbonate Tempered glass Photometric Information: CRI: 80 CCT: 5000K (cool white) 4000K (neutral white) Optics: 360° 180° forward throw for 45° mounting Wide for 0° mounting All values typical unless otherwise stated (tolerance +/- 10%) *ETL listed Tempered Glass Lens Polycarbonate Lens Certifications & Ratings* • 10 year warranty • UL 1598/A • CSA C22.2 No. 250 • IP66 / 67 / 69 • NEMA 4X WARNING: INSTALLATION & SECONDARY RETENTION: The use of this product without proper installation and inspections, including secondary safety retention/securing, could cause severe injury or death. Dialight recommends that all installations should use secondary retention (appropriate to the installation environment) where applicable. It is the exclusive responsibility of the contractor, installer and/or end customer to: (a) determine the suitability of the product for its intended application; and, (b) ensure that the product is installed safely (with secondary retention where appropriate) and in compliance with all applicable laws and regulations. To the extent permissible under the relevant law, Dialight disclaims all responsibility for personal injury and/or other damage resulting from any dislodgement or other dislocation of this product. TYPE F Industrial Applications | Area Light www.dialight.com 45 Vigilant® LED Area Light 100-277 VAC, 120-250 VDC with Mounting Adapters Mechanical Information: Fixture weight: UMA models: 12 lb (5.5 kg) - Polycarbonate lens 15 lb (6.8 kg) - Tempered glass lens Wall mount models: 15 lb (6.8 kg) - Polycarbonate lens 18 lb (8.2 kg) - Tempered glass lens 45° wall mount models: 14 lb (6.4 kg) - Polycarbonate lens 17 lb (7.7 kg) - Tempered glass lens 45° stanchion mount: 15 lb (6.8 kg) - Polycarbonate lens 18 lb (8.2 kg) - Tempered glass lens Shipping weight: Add 2 lb (0.91 kg) to weights above Impact rating: IK10 - Polycarbonate lens IK07 - Tempered glass lens Cabling: 14” leads 1.02 mm 18 AWG Mounting: Secondary retention standard Electrical Specifications: Operating voltage: 100-277 VAC 50/60 Hz, 120-250 VDC Operating temperature: -40°F to +149°F (-40°C to +65°C) EMC: FCC Title 47, Subpart B, Section 15, Class A device CISPR-15 RF Immunity 20V/m 80MHz-1GHz. Transient protection: 6 kV, 2 Ohm line-line and line-ground Harmonics: IEC 61000-3-2, Class C THD: < 20% Power factor: > 0.9 Construction: Housing: Copper-free aluminum Finish: Superior dual coat finish - Sealed polyester topcoat Lens: Hard-coated polycarbonate Tempered glass Photometric Information: CRI: 80 CCT: 5000K (cool white) 4000K (neutral white) Optics: 360° 180° forward throw for 45° mounting Wide for 0° mounting All values typical unless otherwise stated (tolerance +/- 10%) *ETL listed Certifications & Ratings* • 10 year warranty • UL 1598/A • CSA C22.2 No. 250 • IP66 / 67 / 69 • NEMA 4X Universal Mounting Adapter Wall Mount 45o Stanchion Mount 45o Wall Mount For use with HZXW01, HZXW45 or HZXS45 brackets sold separately HZXW01 HZXS45 HZXW45 WARNING: INSTALLATION & SECONDARY RETENTION: The use of this product without proper installation and inspections, including secondary safety retention/securing, could cause severe injury or death. Dialight recommends that all installations should use secondary retention (appropriate to the installation environment) where applicable. It is the exclusive responsibility of the contractor, installer and/or end customer to: (a) determine the suitability of the product for its intended application; and, (b) ensure that the product is installed safely (with secondary retention where appropriate) and in compliance with all applicable laws and regulations. To the extent permissible under the relevant law, Dialight disclaims all responsibility for personal injury and/or other damage resulting from any dislodgement or other dislocation of this product. 46 www.dialight.com Industrial Applications | Area Light AL 2 D G N Product Code Cert.Lens Material Beam Dist. CCT & CRI Oper. Voltage Lumen Type Controls Mounting Options HW Access. Elect. Access.Coatings Product Code AL Area Light Certification U UL 1598/A CSA 22.2 No. 250.0 Lens Material 5 Polycarbonate - Diffused 7 Glass - Clear Beam Distribution A 180° B 360° W Wide CCT & CRI C Cool White 5000K - 80 CRI N Neutral White 4000K - 80 CRI Operating Voltage 2 100-277 VAC, 120-250 VDC Lumen Type 3 3,001 - 4,000 Lumens 4 4,001 - 5,000 Lumens 6 5,001 - 6,000 Lumens 7 6,001 - 7,000 Lumens 9 8,001 - 9,000 Lumens Controls D Dimming (0-10V) Mounting Options A Appleton Mercmaster III B Swivel Bracket, Locking 0°- 90° 316 Stainless Steel C Crouse-Hinds - Champ G GE Filtr-Gard H Thomas & Betts Hazlux K Killark Certilite & Certilite V M Appleton Mercmaster II N 3/4” NPT S 45° Stanchion Mount U UMA - Mounting Hub V 0° Wall Mount W 45° Wall Mount Coatings G Gray (RAL 7040) Universal Mounting Adapter (UMA) Notes 1) When ordering Beam Distribution W - Wide: Lumen Type = 7. 2) When ordering Mounting Options “UMA” or “Retro-fit”: Hardware Accessories = N. 3) When ordering Mounting Option U - UMA Mounting Hub HZXW01, HZXW45, HZXS45 or HZXCV34 are required. See page 37 for details. U Hardware Accessories N For Mounting Options - A, C, G, H, K, M, S, U, V, W, Y (individual wire leads are terminated in adapter housing) W 10 ft (3 meter) Power Cable for Mounting Options - B, N Electrical Accessories N No Option Retro-fit Adapter Battery Battery N No Option *For lumen output see page 10 Specifications Vigilant® LED Area Light 100-277 VAC, 120-250 VDC Project Information Part Number: Project: Fixture Type: Date: Ordering Information N DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail. 7 A C 6 W N www.dialight.com 47 Industrial Applications | Area Light Ordering Information Vigilant® LED Area Light - 100-277 VAC, 120-250 VDC 100-277 VAC, 120-250 VDC Model Part Number Lumens Wattage lm/W CCT CRI Lens Beam Distribution Controls Option Mounting ALU-7BC2-9DNW-NGN 9,000 66 136 CW 80 Glass 360° Dimming 3/4" Conduit ALU-5BC2-9DNW-NGN 8,300 66 126 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit ALU-7BC2-7DNW-NGN 7,300 52 140 CW 80 Glass 360° Dimming 3/4" Conduit ALU-5BC2-7DNW-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit ALU-5AC2-7DNW-NGN 6,600 52 127 CW 80 Polycarbonate Diffused 180° Dimming 3/4" Conduit ALU-7BC2-6DNW-NGN 5,700 40 143 CW 80 Glass 360° Dimming 3/4" Conduit ALU-5BC2-6DNW-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit ALU-5AC2-6DNW-NGN 5,100 40 128 CW 80 Polycarbonate Diffused 180° Dimming 3/4" Conduit ALU-7BC2-4DNW-NGN 4,200 30 140 CW 80 Glass 360° Dimming 3/4" Conduit ALU-5BC2-4DNW-NGN 3,900 30 130 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit ALU-7BC2-4DNW-NGN 4,200 30 140 CW 80 Glass 360 Dimming 3/4" Conduit 100-277 VAC, 120-250 VDC Model with Retro-fit Adapters Part Number Lumens Wattage lm/W CCT CRI Lens Beam Distribution Controls Option Mounting ALU-7BC2-9DCN-NGN 9,000 66 136 CW 80 Glass 360° Dimming Crouse-Hinds Retro-fit ALU-5BC2-9DCN-NGN 8,300 66 126 CW 80 Polycarbonate Diffused 360° Dimming Crouse-Hinds Retro-fit ALU-5BC2-7DAN-NGN 6,700 69 97 CW 80 Polycarbonate Diffused 360° Dimming Appleton M III Retro-fit ALU-5BC2-7DCN-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming Crouse-Hinds Retro-fit ALU-5BC2-7DGN-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming GE H2 Retro-fit ALU-7BC2-6DCN-NGN 5,700 40 143 CW 80 Glass 360° Dimming Crouse-Hinds Retro-fit ALU-5BC2-6DAN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Appleton M III Retro-fit ALU-5BC2-6DCN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Crouse-Hinds Retro-fit ALU-5BC2-6DGN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming GE H2 Retro-fit ALU-7AC2-4DAN-NGN 4,100 30 137 CW 80 Glass 180° Dimming Appleton M III Retro-fit All values typical unless otherwise stated (tolerance +/- 10%). See ordering chart for additional options. All values typical unless otherwise stated (tolerance +/- 10%). See ordering chart for additional options. DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail. Ordering Information Vigilant® LED Area Light - 100-277 VAC, 120-250 VDC with Mounting Adapters HZXW01 HZXS45 HZXW45 100-277 VAC, 120-250 VDC Model with Mounting Adapters Part Number Lumens Wattage lm/W CCT CRI Lens Beam Distribution Controls Option Mounting ALU-7BC2-9DUN-NGN 9,000 66 136 CW 80 Glass 360° Dimming Universal Mounting Adapter ALU-5BC2-9DUN-NGN 8,300 66 126 CW 80 Polycarbonate Diffused 360° Dimming Universal Mounting Adapter ALU-5BC2-7DSN-NGN 6,700 68 99 CW 80 Polycarbonate Diffused 360° Dimming Stanchion 45° ALU-5BC2-7DWN-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming Wall Mount 45° ALU-5AC2-7DSN-NGN 6,600 52 127 CW 80 Polycarbonate Diffused 180° Dimming Stanchion 45° ALU-5AC2-7DWN-NGN 6,600 52 127 CW 80 Polycarbonate Diffused 180° Dimming Wall Mount 45° ALU-7BC2-6DUN-NGN 5,700 40 143 CW 80 Glass 360° Dimming Universal Mounting Adapter ALU-5BC2-6DSN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Stanchion 45° ALU-5BC2-6DUN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Universal Mounting Adapter ALU-5BC2-6DVN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Wall Mount 0° ALU-5BC2-6DWN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Wall Mount 45° ALU-5AC2-6DSN-NGN 5,100 40 128 CW 80 Polycarbonate Diffused 180° Dimming Stanchion 45° ALU-5BC2-4DSN-NGN 3,900 30 130 CW 80 Polycarbonate Diffused 360° Dimming Stanchion 45° 48 www.dialight.com Industrial Applications | Area Light DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail. All values typical unless otherwise stated (tolerance +/- 10%). See ordering chart for additional options. www.dialight.com 49 Industrial Applications | Area Light Vigilant® LED Area Light Lumen Tables 100-277 VAC, 120-250 VDC Output Family Beam Distribution Lens Wattage Lumens 5000 CCT 5000 CCT lm/W Lumens 4000 CCT 4000 CCT lm/W Lumens 2700 CCT 2700 CCT lm/W 9,000 360° 1/4" AR Glass 66 9000 136 8800 134 8200 124 Class I, Div 1 Glass 8600 131 8400 128 7900 120 Polycarbonate 8300 127 8100 123 7600 115 180° 1/4" AR Glass 8800 134 8600 131 8000 121 Class I, Div 1 Glass 8400 128 8200 125 7700 117 Polycarbonate 8100 124 7900 120 7400 112 7,300 360° 1/4" AR Glass 52 7300 140 7100 138 6700 129 Class I, Div 1 Glass 7000 135 6800 132 6400 123 Polycarbonate 6700 131 6500 126 6100 117 180° 1/4" AR Glass 7100 138 6900 134 6500 125 Class I, Div 1 Glass 6800 132 6600 128 6200 119 Polycarbonate 6600 128 6400 124 6000 115 Wide 1/4" AR Glass 64 7300 114 7100 112 6700 105 Class I, Div 1 Glass 7000 110 6800 107 6400 100 Polycarbonate 6700 106 6500 103 6100 95 5,700 360° 1/4" AR Glass 40 5700 143 5500 140 5200 130 Class I, Div 1 Glass 5400 137 5200 132 4900 123 Polycarbonate 5300 133 5100 130 4800 120 180° 1/4" AR Glass 5500 140 5300 135 5000 125 Class I, Div 1 Glass 5300 134 5100 130 4800 120 Polycarbonate 5100 130 4900 125 4600 115 4,200 360° 1/4" AR Glass 30 4200 140 4100 137 3800 127 Class I, Div 1 Glass 4000 134 3900 131 3600 120 Polycarbonate 3900 130 3800 127 3900 130 180° 1/4" AR Glass 4100 137 4000 134 4100 137 Class I, Div 1 Glass 3900 132 3800 127 3900 130 Polycarbonate 3800 127 3700 124 3400 113 3,100 360° 1/4" AR Glass 24 3100 129 3000 127 2800 117 Class I, Div 1 Glass 2900 124 2900 121 2600 108 Polycarbonate 2800 120 2700 114 2500 104 180° 1/4" AR Glass 3000 127 2900 123 2700 113 Class I, Div 1 Glass 2900 121 2800 118 2600 108 Polycarbonate 2800 118 2700 114 2500 104 All values typical unless otherwise stated (tolerance +/- 10%). For lighting layouts, please find IES files at www.dialight.com DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail. Polycarbonate Lens - Option 5 Glass Lens - Option 7 Industrial Applications | Area Light 50 www.dialight.com Vigilant® LED Area Light Beam Distribution & Dimensional Drawings Beam Distribution 180o 360o Wide DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail. www.dialight.com Industrial Applications | Area Light Vigilant® LED Area Light Accessories 51 Please reference spec sheet at www.dialight.com for all dimensional drawings of mounting options. HZXW3 • 316 stainless steel bracket HZXSTAN100S • 1.00” (1.315” Pole OD) Slip-fit stanchion mount HZXSTAN125S • 1.25” (1.660” Pole OD) Slip-fit stanchion mount HZXSTAN150S • 1.50” (1.900” Pole OD) Slip-fit stanchion mount HZXSTAN200S • 2.00” (2.375” Pole OD) Slip-fit stanchion mount HZXSTAN100T • 1.00” (1.315” Pole OD) NPT threaded stanchion mount HZXSTAN125T • 1.25” (1.660” Pole OD) NPT threaded stanchion mount HZXSTAN150T • 1.50” (1.900” Pole OD) NPT threaded stanchion mount HZXSTAN200T • 2.00” (2.375” Pole OD) NPT threaded stanchion mount HZXW4 • 316 stainless steel bracket with pipe clamp HZXSAFECBLS • Safety cable kit Certified to: UL 50E • CSA C22.2 No. 94.2-07 HZXJB075 • 0.75” Ceiling / Wall / Pole mount junction box HZXJB100 • 1.00” Ceiling / Wall / Pole mount junction box HZXJB125 • 1.25” Ceiling / Wall / Pole mount junction box HZXJB150 • 1.50” Ceiling / Wall / Pole mount junction box HZXJB075PC1 • 0.75” Junction box with photocell HZXJB100PC1 • 1.00” Junction box with photocell HZXJB125PC1 • 1.25” Junction box with photocell HZXJB150PC1 • 1.50” Junction box with photocell Certified to: UL 50E • CSA C22.2 No. 94.2-07 Certified to: UL 50E • CSA C22.2 No. 94.2-07 HBXC1 • 0.75” NPT Ceiling mount Certified to: UL 50E • UL 1203 ISA 12.12.01 • CSA C22.2 No. 94.2-07 Fixtures are available with a universal mounting adapter factory installed, see product N-chart for details. Choose from one of the four available mounting options: Wall Mount HZXW01 45° Wall Mount HZXW45 45° Stanchion Mount HZXS45 ALxxxx2xDUNxGN 34mm Slip-fit Pole Mount HZXCV34 HZXW7 • Aluminum bracket HZXW8 • Aluminum bracket with pipe clamp DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail. TYPE G Attachment E Coastal Hazardous Report_Rev 1 Memo SUBJECT PROJECT Coastal Hazards Analysis Bay Bridge Pump Station Replacement Project (5-67) TO DATE Orange County Sanitation District June 2023 Introduction This memorandum summarizes the analysis for coastal hazards for the Bay Bridge Pump Station (BBPS) Replacement Project, Newport Beach, Orange County, California. The Orange County Sanitation District (OC San) proposes to replace the existing BBPS with a new pump station and force main infrastructure. The existing BBPS is over 50 years old, outdated, and no longer meets structural, electrical, and maintenance standards. The Project includes replacing the existing pump station and force mains with a new pump station, replacement force mains, a new electrical building, a new emergency generator building, and an odor control structure. The new pump station will include a trench-type wet well and a dry well for housing the pumps, motors, and other mechanical equipment. As shown on Figure 1, the pump station site also includes an electrical building, a generator building, and an odor control structure. The proposed electrical building includes the electrical equipment, instrumentation, control equipment, and restroom. The electrical building has a finished floor elevation of 15.50 feet NAVD88 and is elevated from the grade level. The entrance to the underground pump station dry well is also elevated to the same elevation of the electrical building finished floor at 15.5 feet NVAD88. The generator room finished floor is 14.17 feet NAVD88 and the generator will be mounted on a 2-ft-high belly fuel tank. The odor control structure finished floor is 14.00 feet NAVD88. The new force main will be installed beneath the Newport Bay Channel and would not be affected by coastal processes and is not included in the analysis. This memorandum summarizes the potential impacts on the BBPS resulting from anticipated sea level rise, coastal geologic instability, and flooding per the requirements of the Newport Beach Local Coastal Plan Policies LUPs 2.8.1-1, 2.8.-2 and 2.8.1-4 and per Section 30253 of the Coastal Act. Site Characteristics and Land Use The Project site is located within a fully developed and urbanized area north of East Coast Highway. The existing BBPS is approximately 4,800 square feet, occupied by a single-story pump station building. The perimeter of the pump station building is surrounded by concrete masonry walls on all sides with two entrance gates. The existing facility is located on a parcel that is surrounded to the north, east, and west by a recreational vehicle storage area. Seven acres of the site are planned for a mixed-use development. Surrounding land uses include residential, commercial, and commercial recreational marine uses. Within the vicinity of the Project, East Coast Highway, also known as State Route 1 is a 7 to 8 lane roadway including a bridge that crosses the Newport Bay Channel. Bayside Drive is located to the east of the Project and is a 4 lane, designated secondary road. Sea Level Rise Evaluation and Flooding Several analyses have been conducted to understand the potential for anticipated Sea Level Rise (SLR) to impact the BBPS and whether the facility is at risk. In 2019, OC San prepared the Resiliency Study SP-152 (Resiliency Study) which examined the potential climate change impact, including SLR on OC San facilities throughout its service area. The Resiliency Study used SLR projections from the Rising Seas Report and California’s Fourth Assessment (Hall 2018) as representing the state Orange County Sanitation District Coastal Hazard Analysis June 2022 www.arcadis.com Coastal Hazards Analysis 2/3 of science for SLR for the Orange County area. Relying on Hall 2018, OC San used SLR increases of 1.54 feet for 2050 and 3.71 feet for the year 2070 (Hazen 2019) to determine the potential risk of SLR in 2050 and 2070. Using the 2050 and 2070 projections, the Resiliency study did not identify the BBPS site as having a significant risk associated with SLR in Year 2050 or 2070 (Hazen 2019). The design also considers the most conservative SLR reference from the State of California’s Sea Level Rise Guidance (California Ocean Protection Council 2018) and Critical Infrastructure at Risk: Sea Level Rise Planning Guidance for California’s Coastal Zone (California Coastal Commission 2021). According to the State of California’s Sea Level Rise Guidance (California Ocean Protection Council 2018), the H++ scenario SLR for Los Angeles are 2.6 feet by 2050, 6.4 feet by 2080, and 9.9 feet by 2100. According to the State Sea-Level Rise Guidance, under the H++ SLR scenario, 2.7 feet of SLR can be expected by 2050, 6.6 feet by 2080, and 10.2 feet by 2100 (California Coastal Commission 2021). The life expectancy of the new pump station will be around 50 years and the 6.6 feet SLR of Year 2080 based on California Coastal Commission 2021 will be used for evaluation. The Our Coast Our Future (OCOF) map with projection of 6.6-ft SLR above mean high water (MHW) is shown on Figure 2. A portion of the existing site is shown inundated based on the 2080 SLR of 6.6-ft SLR Above MHW (11.15 feet NAVD88). In developing the design for the new BBPS, the engineers used both SLR and potential tsunami run up elevations when determining ground elevations for the Project. The BBPS design took a conservative approach of designing to a minimum floor elevation of 14.00 feet NAVD88 as shown on Figure 1. Using this minimum floor elevation, construction of the new BBPS would avoid SLR impacts for the anticipated life of the facility. Flooding & Tsunami According to the Federal Emergency Management Agency (FEMA) 2019 FIRM map, the Project is not located within the 100 year flood hazard zones (Figure 3). As analyzed in the 2020 Recirculated Environmental Impact Report (Michael Baker International 2020), less than significant impacts are anticipated in the event of the 100- year flood. The Project site is located within the designated tsunami zone (California Department of Conservation 2022). During design of the BBPS, the engineers used the American Society of Civil Engineer’s (ASCE) Tsunami Design Zone (TDZ) to determine the Maximum Considered Tsunami (MCT). In the event of a tsunami, the Project site could be expected to see some minor flooding and the run up elevation at the Project site is 7.24 feet above MHW or 11.74 feet NAVD88 (Figure 4 and 5). Figure 4 shows that in the event of tsunami, the parking areas may be expected to see minor flooding. However, because the minimum floor elevation of the new BBPS would be 14.00 feet NAVD88, the new facilities would not be subjected to inundation. Furthermore, onsite drainage is routed to the BBPS. The pump station is designed to operate even if the site is inundated. Therefore, the risk of flooding the pump station is minimal. Ground Improvements and Shoring The Project site is located in an area of potential liquefaction. To mitigate the potential for liquefaction, static settlement, and differential settlement, the new pump station will be excavated over 35 feet deep such that the impacts from liquefaction are not anticipated. The ground improvement plan for the overall pump station site can be referenced to the Geotechnical Design Report enclosed in the permitting package. Deep excavation will require shoring and design is exploring several techniques including, but not limited to slurry diaphragm wall, secant pile wall shoring, solid sheet pile wall, or a combination of shoring techniques. Erosion and Shoreline Loss Orange County Sanitation District Coastal Hazard Analysis June 2022 www.arcadis.com Coastal Hazards Analysis 3/3 The location of the BBPS is located within a developed area and is not located at the shoreline or at the bank of the Newport Bay Channel. The Project site is not subject to erosion and shoreline loss. The BBPS would not be subjected to erosion or shoreline loss as a result of waves or wave run up. The Project does not include, and does not require shoreline protection. Summary and Conclusion The BBPS Project has been analyzed with regards to postal coastal hazards, including SLR, flooding, tsunami, and geologic stability. The new BBPS will be located in a developed area, including the location of the existing BBPS. The new BBPS is designed to ensure that the facilities would not be subjected to the SLR and tsunami impacts. References: Michael Baker International. 2020. Bay Bridge Pump Station and Force Mains Replacement Project (Project No. 5-67) 2020 Recirculated Environmental Impact Report. May 2020. Arcadis. 2022. Preliminary Design Report Project No. 5-67 Bay Bridge Pump Station Replacement. California Coastal Commission. 2021. Critical Infrastructure at Risk: Sea Level Rise Planning Guidance for California’s Coastal Zone. Final Adopted Guidance. November 17, 2021. California Department of Conservation. 2022. Orange County Tsunami Hazard Areas. Website located at https://www.conservation.ca.gov/cgs/tsunami/maps/orange. Retrieved June 17, 2022 California Ocean Protection Council. 2018. State of California’s Sea Level Rise Guidance. March 14, 2018. Hall, Alex, Neil Berg, Katharine Reich. (University of California, Los Angeles). 2018. Los Angeles Summary Report. California’s Fourth Climate Change Assessment. Publication number: SUM-CCCA4-2018-007 Hazen. 2019. Climate Resiliency Study. Final Report. SP-152. November 27, 2019. Our Coast Our Future Mapping Tool. 2022. Website located at: https://ourcoastourfuture.org/ retrieved June 10, 2022 Enc. [Enclosures] Figure1 Site Plan Orange County Sanitation District Bay Bridge Pump Station Replacement Project TRANSFORMER ACCESS HATCH GENERATOR ROOM RAISED PLATFORM ELECTRICAL ROOM ODOR CONTROL AREA PUMP STATION (BELOW GRADE) NORTH GATE 24' WIDE SWING GATE SOUTH GATE 24' WIDE SWING GATE WEST GATE 18' WIDE CANTILEVER SLIDING GATE MANHOLE COVERS, TYP. SEE STRUCTL DWGS RAISED PLATFORM 45.57' 16.23' 9.52' TOW = 29.33' PEDESTRIAN GATE 8' HIGH WALL 10' HIGH WALL 8' HIGH WALL F U T U R E A C C E S S R O A D P A C I F I C C O A S T HI G H W A Y (E) BUILDING STRUCTURE OUTLINE 10' HIGH WALL 8' HIGH WALL 10' HIGH WALL 15' HIGH WALL 15' HIGH WALL A2001 1 A20012 A2001 3 A2001 4 173.84' 57.26' 18.00' 4.44' EXTERIOR WALL BOUNDARY SWITCHBOARD 106.32' 133.53' 39.48' 24.00' 43.99' LANDSCAPE AREA (SEE LANDSCAPE DWGS) 6' - 5 1/8" LANDSCAPE AREA (SEE LANDSCAPE DWGS) TOW = 24.00' TOW = 24.00' TOW = 24.00' TOW = 24.67' TOW = 23.33' TOW = 22.00' TOW = 22.00' 6' - 10" 23' - 7 5/8" 41' - 7 7/8" TOW = 22.00' 9 TOW = 24.67' TOW = 29.33' 5.07' TOW = 23.33' TOW = 23.33' TOW = 29.33' TOW = 29.33' SWITCHBOARD PLATFORM (REMOVABLE) SCALE: 1/8" = 1'-0" SITE PLAN FF = 14.17 FF = 15.50 FF = 14.00 Figure2 6.6-Foot Sea Level Rise Map Orange County Sanitation District Bay Bridge Pump Station Replacement Project Project Location Source: Our Coast Our Future: https://ourcoastourfuture.org/hazard-map/ BAY BRIDGE PUMP STATION PROJECT SITE Figure3 FEMA Map Orange County Sanitation District Bay Bridge Pump Station Replacement Project Legend Offshore Tsunami Amplitude Runup Elevation Point Inundation Depth Point Earthquake Induced Regional Ground Subsidence (ft) Tsunami Design Zone World Imagery Low Resolution 15m Imagery High Resolution 60cm Imagery High Resolution 30cm Imagery Citations 60cm Resolution Metadata Maxar | City of Newport Beach, County of Los Angeles, Esri, HERE, Garmin, INCREMENT P, USGS, Bu Orange County Sanitation District Bay Bridge Pump Station Replacement Project GENERATOR BLDG ELECTRICAL BLDG ODOR CONTROL AREA ASCE Tsunami Hazard Tool with Bay BridgePump Station BAY BRIDGE PUMP STATION Source: ASCE Tsunami Hazard Tool - ASCE Tsunami Design Geodatabase Version 2016-1.0 Figure 4 Legend Offshore Tsunami Amplitude Runup Elevation Point Inundation Depth Point Earthquake Induced Regional Ground Subsidence (ft) Tsunami Design Zone World Imagery Low Resolution 15m Imagery High Resolution 60cm Imagery High Resolution 30cm Imagery Citations 60cm Resolution Metadata Maxar | City of Newport Beach, County of Los Angeles, Esri, HERE, Garmin, INCREMENT P, USGS, Bu Runup Elevation Point Latitude Longitude Runup Elevation (MHW) (ft.)Runup Elevation (NAVD88) (ft.) 33.61667 -117.90222 7.24 11.74 Earthquake Induced Regional Ground Subsidence (ft.): 0 Zoom to ASCE Tsunami Hazard Tool with RunupElevation Orange County Sanitation District Bay Bridge Pump Station Replacement ProjectSource: ASCE Tsunami Hazard Tool - ASCE Tsunami Design Geodatabase Version 2016-1.0 Figure5 Attachment F Water Quality Management Plan Memo 1/1 SUBJECT Water Quality Management Plan PROJECT 5-67 Bay Bridge Pump Station Replacement Project TO Orange County Sanitation District FROM Tim J. Rumbolz, CPESC, QSD, QISP timothy.rumbolz@arcadis.com 408-797-2009 DATE June 2023 This memo is to discuss the Water Quality Management Plan (WQMP) for the Bay Bridge Pump Station (BBPS) Replacement project. Per the City of Newport Beach Coastal Development Permit application, Supplemental Materials Checklist, this memo will present the WQMP as specified in Section 21.35.050. The existing ground surface at the BBPS site (pre-construction) consists of impermeable surfaces, primarily asphalt paving and some small structures. No significant changes to the ground surface type are planned for the project. During construction, water quality will be controlled using an Erosion and Sediment Control Plan (ESCP) designed by a QSD (Qualified SWPPP Developer). Note: the project disturbance area is under one acre, so a SWPPP is not required. Site grading is designed to direct stormwater flows within the paved area to onsite drainage inlets (drop inlets / catch basins) and conveyed in a separate piping system. This system will consist of three exterior catch basins as well as three floor drains located within the Odor Control Area, and the storm drain pipes are sized to capture 10- year storm. The onsite drainage discharged to the pump station wet well will eventually be conveyed to the Orange County Sanitation District (OC San) Treatment Plant No. 2 for treatment via the existing sanitary sewer system. The onsite drainage system is shown as the orange-highlighted piping on Drawings C1003 and M1011. The amount of onsite flow is summarized in Table 1. Table 1 Onsite 10-Year Stormwater Runoff Condition Onsite Drainage Area Runoff Flow ft3/s gpm Existing Pump Station* 3,877 SF / 0.09 acres 0.22 99 Proposed Pump Station* 14,592 SF / 0.33 acres 0.82 368 *The pump station onsite drainage area does not include pump station rights within the Public Right of Way. For the proposed pump station, over 90% of the onsite drainage will flow to the pump station wet well and less than 10% of onsite drainage for the landscape and driveway will discharge to the existing Caltrans storm drain. The project will also reroute the existing flows from areas that are not impacted by the project (offsite drainage). The offsite drainage will be collected in a series of four stormwater catch basins located around the perimeter of the BBPS. The catch basins will be connected via underground piping to the existing Caltrans storm drain system. See the blue-highlighted piping on Drawing C1003 for details. Offsite drainage flows are not impacted by the project. Enc. Drawing C1003 – Grading and Drainage Plan Drawing M1011 – Odor Control Area, Mechanical & Plumbing Plan PB PBPB PB CONC. PCH CONC. CB DWY 24W( D ) 24W( D ) 24W( B ) 24W( B ) 24W(B ) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(B) 24W(D)24W(D) 21 S E W ( C ) 21 S E W ( C ) 24SD(C) 24SD(C) 24SD(C) 24SD(C) 24SD(C) 24SD(C) 18 S D ( C ) 18 S D ( C ) 18 S D ( C ) 30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C) 18 S D ( C ) 18 S D ( C ) CB CB 30W ( D ) 30W ( D ) 30W ( D ) 30W ( D ) 30W ( D ) 30W ( D ) 30W( D ) 30W ( D ) 30W ( D ) 30W ( D ) 30W ( D ) ST(B) ST(B) ST(B ) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B) ST(B)ST(B) ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B) J J CTV ( B ) CTV ( B ) CTV( B ) CTV( B ) CTV(B ) CTV(B ) CTV(B ) CTV(B) CTV(B) CTV( B ) CTV( B ) CT V ( B ) CT V ( B ) CTV( B ) CTV(B) CTV(B) CTV(B) CTV(B)CTV(B)CTV(B) CTV ( B ) CTV ( B ) CTV(B)CTV(B)CTV(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B) TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B) D S ELECTRICAL ROOM FF=15.50 ODOR CONTROL AREA FF=14.00 1211 11 1 4 13 12 1 3 15 13 16 17 GENERATOR ROOM FF=14.17 OC SA N PRIVAT E CALTRANS CAL T R A N S PRIV A T E P R O P E R T Y PRIVATE PRIVATE PROPERTY PAD=15.50 FS=11.80± MATCH EX. FS=13.75 INV=8.00 FS=13.50 FS=13.50 FS=13.50± MATCH EX.FS=13.25± MATCH EX. FG=11.65 TW=16.95 MATCH EX. FG=16.65 PAD=14.00FS=12.45 FS=12.70 G. B . FL=12.82 FL=12.98 FL=12.06 FL=12.14 FS=14.00 FS=12.00 FS=11.80 FS=11.50 EX. 18" RCP INV(S)=8.03 INV(E)=8.53 FS=13.50 FS=13.40 FS=13.50 FS=13.60 FL=13.15 FL=13.05 FS=13.00 FS=13.60 FS=13.15 FS=12.85 FL=12.46 MATCH EX. FS=13.50 FS=13.25 FS=13.25 FS=13.25 FG=15.00 FS=11.70 PROTECT EXISTING CATCH BASIN IN PLACE INV=8.00 FS=14.13 FS=13.55 FS=13.35 FS=12.60 FS=12.30 HPFL=13.30 2.7 % 1% 2% FS=13.15 RIM=13.75± INV(E)=10.50 INV(S)=9.00 INV=10.89± MATCH EX. INV=8.00 FS=13.50 FG=14.00 FS=12.22 1% FS=13.67 FS=13.67 FS=13.67 FL=13.24 MATCH EX. STORM DRAIN C PROFILE 6"HDPE (SD) 6"HDPE (SD) 8"HDPE (SD) 3 C5005 5 C3004 STORM DRAIN D PROFILE6"HDPE (SD) 1/2"CU (POTW) 8"HDPE (SD) 3 C3004 STORM DRAIN B PROFILE FL=11.78 8"HDPE (SD) 8"HDPE (SD) STORM DRAIN E PROFILE 6"HDPE (SD) FS=13.96 2 C3003 STORM DRAIN A PROFILE 2 C3003 STORM DRAIN A PROFILE STORM DRAIN A PROFILE 1 C3003 4 C3004 18"RCP (SD) FS=13.95 6"HDPE (SD)6 C3004 6"HDPE (SD) FS=13.10 FS=11.60± MATCH EX. ACCESS ROAD - BY OTHERS MH-1 N:2172040.57 E:6058631.75 RIM=13.15 INV IN=10.52 INV OUT=10.42 CB-1 N:2172025.01 E:6058699.66 GRATE=13.20 INV IN=11.25 INV OUT=11.15 FS=13.10 CB-5 N:2171970.24 E:6058615.60 RIM=11.40 INV=9.00 CB-2 N:2171966.44 E:6058613.04 GRATE=11.50 INV IN=9.73 INV OUT=9.63 CB-3 N:2171942.25 E:6058705.02 GRATE=13.50± INV(W)=8.78 INV(S)=8.68 CB-4 N:2172001.70 E:6058721.68 GRATE=12.90 INV=8.50 MH-2 (SOLID) N:2171963.84 E:6058740.37 RIM=13.40 INV (W)=7.64 INV (N)=7.35 INV (E)=7.00 3 C3003 - M3008 3 C3004 STORM DRAIN B PROFILEFL=13.17 FL=13.02 FL=12.22 FL=11.42 FS=15.46 FS=15.46 TYP. TYP. FS=13.25 G.B . DEMO EXISTING GRAVITY WALL (SEE D1001), STRAIGHTEN SIDEWALK EDGE AS SHOWN. FS=11.55 G.B. FS=13.70 FS=13.40 REMOVE AND REPLACE EXISTING LIGHT POLE IN-KIND, AS NECESSARY DURING CONSTRUCTION, PER PUBLIC WORKS REQUIREMENTS - C5003 CB-6 (GRATE INLET) N:2171952.08 E:6058766.92 GRATE=13.25 INV 6" IN (N)=7.80 INV 6" IN (SW)=6.96 INV 6" IN (NW)=5.77 INV 8" OUT (S)=2.50 FS=13.67 GRATE=13.45 INV=11.73 FS=13.35 0.7 % 0.7 % FS=15.36 FS=15.46 FS=15.36 2% 0.5% 2.7% 2.7% FS=13.10 FS=15.36 FS=15.36 FS=13.52 FS=13.15 FS=13.38 FS=13.70 FS=13.30 14 17 1 2 3 4 3 7 4 18 9 9 5 12 13 16 11 7 19 5 1 17 3 7 16 2 12 10 8 16 2 15 16 18 6 13 10 13 21 21 21 21 21 21 21 22 22 21 21 3 20 20 PROPOSED BACK OF SIDEWALK EDGE GRATE=13.20 INV=11.25 A 5007 A B 5007 B C 5007 C C1003 18 GRADING AND DRAINAGE PLAN ALAN PROCTOR PRAVEEN YERRA JESUS LOPEZ 10'20'0'10' SCALE: 1" = 10' A 1 2 3 4 5 6 7 8 9 10 B C D E F MARK DATE APPR.DESCRIPTION DW G : C : \ U s e r s \ a l a n . p r o c t o r \ A C C D o c s \ A r c a d i s \ A U S - 3 0 0 0 1 6 8 7 - O C S D – 5 - 6 7 B a y B r i d g e P u m p S t a t i o n \ F D S \ A u t o C A D \ S H E E T S \ C I V I L \ 5 - 6 7 - C 1 0 0 3 . d w g DA T E : A p r 2 4 , 2 0 2 3 1 1 : 0 8 a m U S E R : A l a n . P r o c t o r DRAWING NO. (IF NOT 2"-SCALE ACCORDINGLY) AT FULL SIZE LINE IS 2 INCHES ORANGE COUNTY SANITATION DISTRICT FDS APRIL 2023 NOT FOR CONSTRUCTION DRAWN BY: DESIGNED BY: CHECKED BY: BAY BRIDGE PUMP STATION REPLACEMENT 5-67 302OFSHEET NO.: Underground Service Alert TWO WORKING DAYS BEFORE YOU DIG Call:811 CONSTRUCTION NOTES: 1 CONSTRUCT 4" AC ON 6" ABC ON 12" COMPACTED SUBGRADE (PER FINAL GEOTECH REPORT - DATED: TBD). 2 REMOVE AND REPLACE EXISTING SIDEWALK IN KIND ANY PORTIONS THAT ARE DAMAGED OR REMOVED DURING CONSTRUCTION. REPLACE SIDEWALK TO THE NEAREST FULL SECTION, PER CALTRANS STD DWG A87A, SEE SHEET C5002. 3 CONSTRUCT 9" PCCP ON 4" ABC ON 12" COMPACTED SUBGRADE SUBGRADE (PER FINAL GEOTECH REPORT - DATED: TBD). 4 CONSTRUCT 9" THICK PCC VALLEY GUTTER PER DETAIL 2 ON SHEET C5005. 5 CONNECT TO BUILDING FLOOR DRAIN SEE SHEET M1011 FOR CONTINUATION. 6 18" RCP (D2000) STORM DRAIN, SEE PROFILE 3 ON DWG C3003. 7 FURNISH AND INSTALL 6" STORM DRAIN CLEAN OUT PER OC SAN STD. DWG S-073 AND S-015. 8 CONSTRUCT CONCRETE COLLAR, REFER TO SPPWC STANDARD PLAN 380-4. 9 FURNISH AND INSTALL 30" DRAIN BASIN (NYLOPLAST DWG # 7001-110-193 OR EQUAL) WITH H-20 RATED SOLID COVER OR STANDARD GRATE INLET, AS NOTED ON PLAN. 10 FURNISH AND INSTALL 12" DRAIN BASIN (NYLOPLAST DWG # 7001-110-189 OR EQUAL) WITH H-20 RATED STANDARD GRATE INLET. 11 18" RCP STORM DRAIN, SEE PROFILE 1 ON DWG C3003. 12 FURNISH AND INSTALL STORM DRAIN MANHOLE JUNCTION STRUCTURE PER SPPWC STANDARD PLAN 321-2 WITH SOLID COVER. 13 FURNISH AND INSTALL DRAINAGE STRUCTURE WITH GRATED INLET TYPE G1 PER CALTRANS STD. DET. D73B, SEE SHEET C5004. 14 INSTALL 18" RCP STORM DRAIN PENETRATION THROUGH BASE OF WALL, MATCH EXISTING OFFSITE GUTTER FLOW LINE. 15 FURNISH AND INSTALL GRATED LINE DRAIN WITH DUCTILE IRON HEEL PROOF GRATE INLET WIDTH 6.1 INCH, 2% MIN. SLOPE TO CB-1. 16 CONTRACTOR SHALL REMOVE INTERFERING PORTIONS OF EXISTING SIDEWALK, CURB AND GUTTER AND DRIVEWAY. MATCH EXISTING ELEVATIONS TO MAINTAIN DRAINAGE. CONSTRUCT ROLL CURB AND GUTTER TYPE E PER CALTRANS STD. DET A87A, SEE DETAIL ON SHEET C5002. 17 UNDERGROUND CONCRETE STRUCTURE, SEE STRUCTURAL SHEET S1004 FOR CONCRETE ROOF SLAB PLANS. 18 CONSTRUCT CONCRETE PAD, SEE STRUCTURAL PLANS. 19 CONSTRUCT 8"X8" WALL OPENING AT LOW POINT FOR DRAINAGE. 20 CONSTRUCT RETAINING WALL, SEE STRUCTURAL PLANS. 21 FURNISH AND INSTALL HDPE PIPE (SSPWC 207-18, MIN. PS-50), LENGTH, SIZE, AND SLOPE AS NOTED ON PLAN AND PROFILE 22 CONSTRUCT BOLLARDS PER OC SAN STD. DET. S-120 AND S-121. SEE SHEET C1002 FOR BOLLARD LAYOUT AND SPACING. NOTES: ·GROUND SURFACE ELEVATIONS AND COORDINATES ARE PROVIDED FOR CONTRACTOR'S REFERENCE ONLY, AND REPRESENT THE DESIGN INTENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO LAY OUT THE SITE SO THAT A SMOOTH AND CONTINUOUS GROUND SURFACE WITH ADEQUATE DRAINAGE IS PROVIDED. ·CONTRACTOR TO VERIFY ALL EXISTING GRADE ELEVATIONS. - S1004 1 C5002 1 C5004 2 C5005 1 C3003 - C1002 3 S5303 1 C5006 FOR CONTINUATION SEE M1011 FOR CONTINUATION SEE M1011 DISCHARGE TO UPSTREAM MANHOLE AND THEN TO WET WELL CONNECTED TO CITY'S EXISTING STORM DRAIN SYSTEM CONNECTED TO CITY'S EXISTING STORM DRAIN SYSTEM OFFSITE DRAINAGE ONSITE DRAINAGE O1 OA OB O2 PEDESTRIAN DOORS ROLL-UP DOOR HOSE BIBB SHUT-OFF VALVE BY OTHERES MAGNESIUM HYDROXIDE CHEMICAL TANK BY OTHERS CALCIUM NITRATE CHEMICAL TANK BY OTHERS PUMP SKID BY OTHERS TO WET WELL 3" CAP3" CAP HOSE BIBB 18' - 9"18' - 9" 1 1/4" Cu (POTW) 1-1/4" TEE 1 1/4" Cu (POTW) 1 1/4" Cu (POTW) 1-1/4" X 1" REDUCER 1" (POTW) 1" Cu (POTW) 1-1/4" X 1" REDUCER 1" CPVC (CA(NO3)2) 3" CPVC (MG(OH)2) 1" CPVC (MG(OH)2) 3" CPVC (CA(NO3)2) 1" CPVC (CA(NO3)2) 1" CPVC (MG(OH)2) 8' - 1 " BY OTHERS BY OTHERS SEE SHEET C1004 FOR CONTINUATION FROM WET WELL WALL CLAMP, TYP. HOSE RACK TYP. HOSE RACK 55JSFS638 55JSFS639 HOSE RACK HOSE BIBB BACKFLOW PREVENTER SCRUBBER FOUL AIR FAN DUCT BUTTERFLY DAMPER 55JFAN170 55JFV870 10" FRP (FA) DUCT EXPANSION JOINT MAGNESIUM HYDROXIDE FILL STATION WITH SPILL CONTAINMENT CALCIUM NITRATE FILL STATION WITH SPILL CONTAINMENT 55JSFS634 4' - 0 " A M3007 B M3008 C M3008 7' - 3"7' - 3" 7' - 3" 5' - 9 " 4' - 0" 1/2" TRAP PRIMER SEE SHEET C1003 FOR CONTINUATION TO CONNECTION TO THE 8" P-TRAP 1 1/2" CPVC (POTW) 1 1/2" X 1 1/4" REDUCER 11' - 6" TO WET WELL MAGNESIUM HYDROXIDE EYEWASH STATION CALCIUM NITRATE EYEWASH STATION ELECTRICAL PANELS CHEMICAL LOADOUT EYEWASH STATION 8" FRP (FA)16" FRP (FA) 9' - 0" 2' - 6" AIR FLOW METER 6 M5003 6 M5003 1"CAP O1 OA O2 TO MANHOLE 18' - 9"18' - 9" TO MANHOLE 6" PLUG VALVE WITH POST INDICATOR FOR CONTINUATION SEE SHEET C1003 TO CATCH BASIN SEE SHEET C1003 FOR CONTINUATION ED 1/2" CONDENSATE DRAIN WITH BALL VALVE ED 1/2" CONDENSATE DRAIN WITH BALL VALVE 6" DI (D) AD AD AD6" CPVC (CHEMD) 2" DI (D) 2" DI (D) 2" DI (D) 1" DI (D) 3' - 7"7' - 7" CONNECT TO 1" NPT DRAIN VALVE AT THE CARBON SCRUBBER CONNECT TO 1" NPT DRAIN VALVE AT THE FOUL AIR FAN 4" DI (D) 4" DI (D) 55JPV540A 55JPV540B 7' - 8" 3' - 6" 10 " 9' - 8 " 6' - 7 " FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2 3 4 5 6 7 8 9 10 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 4/20/2023 9:27:41 AM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-M-BBPS.rvt M1011 BAY BRIDGE PUMP STATION REPLACEMENT ODOR CONTROL AREA MECHANICAL & PLUMBING PLAN 302142 CATHERINE WOO ROSHANI SHRESTHA HARMIK AGHANIAN SCALE: 1/4" = 1'-0" ODOR CONTROL AREA MECHANICAL PLAN SCALE: 1/4" = 1'-0" ODOR CONTROL AREA DRAINAGE PLAN 0'4'8'2'0'4'8'2' 6 M5003 MARK DESCRIPTION DATE APPR. OFFSITE DRAINAGE ONSITE DRAINAGE Attachment G Visual Impact Analysis_Rev 1 SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2345678910 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:13 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt A9001 BAY BRIDGE PUMP STATION REPLACEMENT VISUAL IMPACT ANALYSIS - 01 302 JOHN ERIC CHUNG RUOTIAN CAI SIEGFREDO LOPEZ EXISTING PUMP STATION PROPOSED NEW PUMP STATION EAST COAST HIGHWAY VIEW CORRIDORS PER BACK BAY LANDING PLANNED COMMUNITY DEVELOPMENT PLAN (PC-9) VIEW CORRIDOR IDENTIFIED IN 2014 VIEW CORRIDOR IDENTIFIED IN 2016 VIEW CORRIDOR COMPARISON THE PROPOSED NEW PUMP STATION MAINTAINED THE VIEW CORRIDOR IDENTIFIED IN 2014. THE FUTURE COASTAL PUBLIC VIEW TOWER AND BLUFF IS UNOBSTRUCTED ON THE VIEW CORRIDOR. IN RESPECT TO THE BACK BAY LANDING DEVELOPMENT, A LANDSCAPE SETBACK IS PROVIDED IN FRONT OF PCH PERIMETER WALL. THE BUILDING MASSING AND MATERIALS ARE ADDRESSED TO INTEGRATE WITH SURROUNDING SITE CONTEXT AND NATURAL ENVIRONMENT. NOTES: THIS DRAWING CONTAINS COLOR DIGITAL PHOTOGRAPHS AND/OR COLOR RENDERINGS. SEE THE ELECTRONIC VERSION OF THIS SHEET FOR MAXIMUM CLARITY. MARK DESCRIPTION DATE APPR. 1 LCP RESUBMITTAL 06/2023 1 SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2345678910 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:46 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt A9002 BAY BRIDGE PUMP STATION REPLACEMENT VISUAL IMPACT ANALYSIS - 02 302 JOHN ERIC CHUNG RUOTIAN CAI SIEGFREDO LOPEZ V1 V2 V3 V4 V5 V6 EXISTING NOTES: THIS DRAWING CONTAINS COLOR DIGITAL PHOTOGRAPHS AND/OR COLOR RENDERINGS. SEE THE ELECTRONIC VERSION OF THIS SHEET FOR MAXIMUM CLARITY. MARK DESCRIPTION DATE APPR. 1 LCP RESUBMITTAL 06/2023 V1 -VIEW FROM NORTH OF CASTAWAYS PARK V2 -VIEW FROM SOUTH OF CASTAWAYS PARK V3 -VIEW FROM WEST OF PACIFIC COAST HIGHWAY PROPOSED EXISTING PROPOSED EXISTING PROPOSED 1 V1 V2 V3 V4 V5 V6 NOTES: THIS DRAWING CONTAINS COLOR DIGITAL PHOTOGRAPHS AND/OR COLOR RENDERINGS. SEE THE ELECTRONIC VERSION OF THIS SHEET FOR MAXIMUM CLARITY. SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2345678910 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:39:19 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt A9003 BAY BRIDGE PUMP STATION REPLACEMENT VISUAL IMPACT ANALYSIS - 03 302 Designer Author Checker MARK DESCRIPTION DATE APPR. 1 LCP RESUBMITTAL 06/2023 V4 -VIEW FROM EAST OF PACIFIC COAST HIGHWAY V5 -VIEW FROM COAST HIGHWAY & N BAYSIDE DR V6 -VIEW FROM N BAYSIDE DR EXISTING PROPOSED EXISTING PROPOSED EXISTING PROPOSED 1 Attachment H Site Photos for Notice of Application Filing Attachment H – Site Photos for Notice of Application Filing 250 E Coast Highway, Newport Beach, CA 92660 arcadis.com 1 Site Photos for Notice of Application Filing Location: 250 E Coast Highway, Newport Beach, CA 92660 Photograph taken by: Xintong Qiu Date: 5/25/2023 Photograph Number Photograph Description 1 Notice on Existing Bay Bridge Pump Station Gate Facing PCH 2 Notice on Existing Bay Bridge Pump Station Gate Facing PCH Attachment H – Site Photos for Notice of Application Filing 250 E Coast Highway, Newport Beach, CA 92660 arcadis.com 2 Photograph Number Photograph Description 3 Notice on Existing Bay Bridge Pump Station Gate Facing PCH 4 Notice on Fence of Existing Valve Vault West of the Channel Attachment H – Site Photos for Notice of Application Filing 250 E Coast Highway, Newport Beach, CA 92660 arcadis.com 3 Photograph Number Photograph Description 5 Notice on Fence of Existing Valve Vault West of the Channel Attachment I Updated Architectural Drawings TRANSFORMER ACCESS HATCH GENERATOR ROOM RAISED PLATFORM ELECTRICAL ROOM ODOR CONTROL AREA PUMP STATION (BELOW GRADE) NORTH GATE 24' WIDE SWING GATE SOUTH GATE 24' WIDE SWING GATE WEST GATE 18' WIDE CANTILEVER SLIDING GATE MANHOLE COVERS, TYP. SEE STRUCTL DWGS RAISED PLATFORM 45.57' 16.23' 9.52' TOW = 29.33' PEDESTRIAN GATE 8' HIGH WALL 10' HIGH WALL 8' HIGH WALL F U T U R E A C C E S S R O A D P A C I F I C C O A S T HI G H WA Y (E) BUILDING STRUCTURE OUTLINE 10' HIGH WALL 8' HIGH WALL 10' HIGH WALL 15' HIGH WALL 15' HIGH WALL A2001 1 A20012 A2001 3 A2001 4 173.84' 57.26' 18.00' 4.44' EXTERIOR WALL BOUNDARY SWITCHBOARD 106.32' 133.53' 39.48' 24.00' 43.99' LANDSCAPE AREA (SEE LANDSCAPE DWGS) 6' - 5 1/8" LANDSCAPE AREA (SEE LANDSCAPE DWGS) TOW = 24.00' TOW = 24.00' TOW = 24.00' TOW = 24.83' TOW = 22.83' TOW = 21.50' TOW = 21.50' 6' - 10" 23' - 7 5/8" 41' - 7 7/8" TOW = 21.50' 9 TOW = 24.83' TOW = 29.33' 5.07' TOW = 22.83' TOW = 22.83' TOW = 29.33' TOW = 29.33' SWITCHBOARD PLATFORM (REMOVABLE) RECESSED KNOXBOX. LOCATION TO BE APPROVED BY THE FIRE DEPT. MOUNT 5' ABOVE FINISHED GRADE. RECESSED KNOXBOX. LOCATION TO BE APPROVED BY THE FIRE DEPT. MOUNT 5' ABOVE FINISHED GRADE. FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2345678910 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:06 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt A1001 BAY BRIDGE PUMP STATION REPLACEMENT SITE PLAN 30259 JOHN ERIC CHUNG RUOTIAN CAI SIEGFREDO LOPEZ SCALE: 1/8" = 1'-0" SITE PLAN MARK DESCRIPTION DATE APPR. 1 LCP RESUBMITTAL 06/2023 1 1 A B ST-01 STU-02 MTL-01 STU-01 SITE GRADING LINE BEHIND SITEWALK PT-02 4' - 0 " 18' - 0"14' - 0"14' - 0"18' - 0"14' - 0"14' - 0" STU-02 STU-01 ST-01 2' - 1 0 " 8' - 6 " 3' - 6 " 4' - 6 " OA OB 9 AVG. SITE LEVEL EL 13.50' MTL-01 SWING GATE PROP. LINE SITEWALK RAILING (TO MATCH EXISTING OR PUBLIC WORK REQ.) PROP. LINE A4005 6 SIM. STU-01 MTL-01 6' - 1 0 " 4' - 6 " CONTROL JOINT, TYP. 4" H METAL COPING, TYP. 1' - 0 " 7' - 0 " STUCCO TO STONE VENEER TRANSITION, TYP. TOW = 24.83' TOW = 22.83'TOW = 21.50'TOW = 21.50' 1' - 0"1' - 0 " A4005 9 SIM. ABC ODOR CONTROL TOW EL 29.33' 18' - 0"18' - 0"18' - 0"19' - 2" ST-01 STU-01 STU-02 MTL-01 STU-01 ST-01 4' - 0 " 6' - 6 " 4' - 1 0 " 8" MTL-01 10 ' - 6 " OAOB AVG. SITE LEVEL EL 13.50' 19' - 8"19' - 8"18' - 5"18' - 0" 16 ' - 0 " 12 ' - 1 0 " SWING GATE PROP. LINE PROP. LINE A4005 5 1' - 6" 4" H METAL COPING, TYP. CONTROL JOINT, TYP. 2" W METAL REVEAL, BRONZE MTL-01 CONTROL JOINT, TYP. 2' - 4 " 10 ' - 6 " 8" H METAL COPING TYP. 4' - 0" STUCCO TO STONE VENEER TRANSITION, TYP. TOW = 24.00'TOW = 24.00' 1' - 6 " 2' - 0" 5' - 0 " RECESSED KNOXBOX. LOCATION TO BE APPROVED BY THE FIRE DEPT. MOUNT 5' ABOVE FINISHED GRADE. A4005 9 MATERIAL LEGEND ( SEE DETAILS IN MATERIAL SCHEDULE ) CODE DESCRIPTION COLOR STU-01 ST-01 PT-02 CMU-01 GL-01 STONE VENEER, STACKED STONE STUCCO PAINTING EXPOSED CMU, TAN/ PRECISION LAMINATED, FRITTED GLAZING OFF WHITE LIGHT BROWN BRONZE CREAM BRONZE STU-02 STUCCO MEDIUM BROWN MP-01 METAL PANEL, ANODIZED BRONZE MTL-01 METAL COATING BRONZE ODOR CONTROL TOW EL 29.33' ST-01 MTL-01STU-02 TYP. 4' - 0" O1O2 AVG. SITE LEVEL EL 13.50' PROP. LINE 15 ' - 1 0 " 3' - 6 " 11 ' - 1 0 " 8" 3' - 6 " TOW = 29.50'TOW = 29.50' STU-01 8" H METAL COPING 4" H METAL COPING, TYP. 2" W METAL REVEAL, BRONZE 16' - 4"14' - 8"16' - 0"14' - 8" CONTROL JOINT, TYP. STUCCO TO STONE VENEER TRANSITION, TYP. 5' - 0 " RECESSED KNOXBOX. LOCATION TO BE APPROVED BY THE FIRE DEPT. MOUNT 5' ABOVE FINISHED GRADE. 1 2 3 ST-01STU-01ST-01 MTL-01MTL-01 MTL-01 AVG. SITE LEVEL EL 13.50' SIDEWALK 2' - 4 " 10 ' - 6 " 10 ' - 0 " CANTILEVER SLIDE GATE SITEWALK RAILING (TO MATCH EXISTING) 12 ' - 1 0 " TOW = 24.00' TOW = 24.00' PROP. LINE 1' - 6 " 8' - 6 " TOW = 24.83' A4005 7 4"6' - 3"34' - 8"16' - 0"18' - 0"1' - 8" CONTROL JOINT, TYP. 4" H METAL COPING, TYP. STUCCO TO STONE VENEER TRANSITION, TYP. TOW = 22.00' TOW = 22.00' FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2345678910 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:11 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt A2001 BAY BRIDGE PUMP STATION REPLACEMENT SITE ELEVATIONS 30266 JOHN ERIC CHUNG RUOTIAN CAI SIEGFREDO LOPEZ SCALE: 1/8" = 1'-0" SITE -SOUTH ELEVATION SCALE: 1/8" = 1'-0" SITE -NORTH ELEVATION SCALE: 1/8" = 1'-0" SITE -EAST ELEVATION SCALE: 1/8" = 1'-0" SITE -WEST ELEVATION MARK DESCRIPTION DATE APPR. 1 LCP RESUBMITTAL 06/2023 1 1 1 1 8' - 0 " 4" PE R S T R U C T R L 3" MTL-01 6063 T6 AL 1"X6"-0.100" T&G SLAT INFILL MORTICE LOCKSET W/ CYBERKEY CYLINDAR & SS LEVER HANDLES (2) S.S. CANE BOLT MOUNT TO BASE OF GATE AND CORE STRIKE HOLES 3" DEEP ANCHOR INTO 12" SQ. CONCRETE POUR TYP. 6" 4"2"11' - 6"11' - 6"2"4"V.I.F. 24' - 0" MTL-01 1' - 6 " 1' - 0" 6" 6" (1) HEAVY DUTY GATE WHEEL (2) 4"X4"X1/4" STL GATE POST W/ 1/4" THK STL PLATE CAP. PAINT TO MATCH FRAME 6063 T6 AL 3"X2"X1/4" U- CHANNEL INFILL PANEL FRAME FACE-MOUNTED (6) WELD-ON HEAVY DUTY BARREL HINGE. PAINT TO MATCH FRAME PER CODE 3' - 0 " 6063 T6 AL 3"X2"X1/4" GATE FRAME BEHIND 3" 4" 10 ' - 0 " MTL-01 6063 T6 AL 1"X6"-0.100" T&G SLAT INFILL MORTICE LOCKSET W/ CYPERKEY CYLINDAR & SS LEVER HANDLES TY P . 6" (8) WELD-ON HEAVY DUTY BARREL HINGE. PAINT TO MATCH FRAME PE R S T R U C T R L 4"2"11' - 6"11' - 6"2"4"V.I.F. 24' - 0" 6" 6" 1' - 6 " 1' - 0" MTL-01 (2)S.S. CANE BOLT MOUNT TO BASE OF GATE AND CORE STRIKE HOLES 3" DEEP ANCHOR INTO 12" SQ. CONC POUR PE R C O D E 3' - 0 " (1)HEAVY DUTY GATE WHEEL (2)4"X4"X1/4" THK STL GATE POST W/ 1/4" THK STL PLATE CAP. PAINT TO MATCH FRAME 6063 T6 AL 3"X2"X1/4" U- CHANNEL INFILL PANEL FRAME FACE-MOUNTED 6063 T6 AL 3"X2"X1/4" GATE FRAME BEHIND 10' - 0" R.O. 18' - 0" 9' - 0 " 4" 28' - 0" CONC. FOUNDATION PER MANUF. SPECS ALUMN. FRAME SS BOTTOM TRACK MTL-01 STANDARD CARRIAGE WALL MOUNTED TOP GUIDE WALL-MOUNTED GATE RECEIVER WALL-MOUNTED BOTTOM END CUP 10 ' - 0 " GROUND FINISH PER CIVIL DWGS MORTICE LOCKSET W/ CYPERKEY CYLINDAR & SS LEVER HANDLES ADJ. WALL 6063 T6 AL 3"X2"X1/4" U- CHANNEL INFILL PANEL FRAME FACE-MOUNTED PE R C O D E 3' - 0 " TYP. 6" 6063 T6 AL 1"X6"-0.100" T&G SLAT INFILL 6063 T6 AL 3"X2"X1/4" GATE FRAME BEHIND V.I.F. 24' - 0" 4"X4"X1/4" THK STL GATE POST W/ 1/4" THK STL PLATE CAP. A4005 8 4"X4"X1/4" THK STL GATE POST W/ 1/4" THK STL PLATE CAP. A4005 8 R.O. 18' - 0"31' - 5" 2' - 0" 2' - 0 " 7' - 7" CONC. FOUNDATION PER MANUF. SPECS WALL-MOUNTED GATE RECEIVER & BOTTOM END CUP A4005 8 ALUM INFILL DETAIL SIM. OFF PROPERTY PROJECT SIDE 3" H ALUM COPING, BRONZE WATER REPELLENT ON EXPOSED 8X8X16 CMU BLOCK, TAN/ GROUND VA R I E S EARTH TOW EL VARIES PER SITE PLAN FG VARIES FG VARIES WEEP SCREED 18 " M I N PE R E N G . PER ENG. PROPPERTY LINE 2" MIN. TO CMU BLOCK VARIES CMU BLOCK GROUT SOLID , REINFORCING PER STRUCTRL CONCRETE FOOTING PER STRUCTRL RETAINING WALL PER STRUCTRL A4005 4 A4005 2 3-COAT CEMENT PLASTER FINISH (OR THIN STONE VENEER OVER SCRACH COAT WHERE OCCURS) OVER METAL LATH OVER CMU. WALL FINISH PER ELEVATIONS. A4005 3 4" T Y P . FRT WOOD BLOCKING ALUM. COPING W/ CONT. CLEAT, SLOPE TO DRAIN 3-COAT CEMENT PLASTER FINISH (OR THIN STONE VENEER OVER SCRACH COAT) OVER METAL LATH OVER CMU. SEE ELEVATIONS REINF. PER STRUCTRL J MOLDING 4" M I N . WEEP SCREED EARTH 3-COAT CEMENT PLASTER FINISH (OR THIN STONE VENEER OVER SCRACH COAT WHERE OCCURS) OVER METAL LATH OVER CMU. WALL FINISH PER ELEVATIONS. REINF. PER STRUCTRL UNFINISHED GRADE SRF. CONC. BASE IN PAINT FINISH TO MATCH ADJ. 3-COAT CEMENT PLASTER FINISH OVER METAL LATH ON CMU. REINF. PER STRUCTRL THIN STONE VENEER OVER SCRACH COAT OVER METAL LATH ON CMU. GSM FLASHING J MOLDING JOINT SEALANT 4"X4"X1/4" THK STL GATE POST W/ 1/4" THK STL PLATE CAP. PAINT TO MATCH FRAME 4"2"3" 4" 2" 2" 6063 T6 AL 3"X2"X1/4" GATE FRAME BEHIND 6063 T6 AL 3"X2"X1/4" U- CHANNEL INFILL PANEL FRAME FACE-MOUNTED 6063 T6 AL 1"X6"-0.100" T&G SLAT INFILL WELD-ON HEAVY DUTY BARREL HINGE. PAINT TO MATCH FRAME PROPERTY SIDE OFF PROPERTY NOTES: 1/2" THK FLAT-CUT ALUM NUMERIALS, PAINTING ON ALL SIDES. MOUNTED TO FACE OF EXTERIOR FACADE WITH 1/4" THICK STAND-OFFS APINTED TO MATCH NUMERALS AND THREADED INSERTS AS REQUIRED TO ATTACHMENT. MP-01 6" 1' - 2" 3/ 4 " FDS APRIL 2023 NOT FOR CONSTRUCTION SHEET NO.:OF DRAWING NO.: 1 F DESIGNED BY: DRAWN BY: CHECKED BY: 5-67 E D C B A 2345678910 LINE IS 2 INCHES AT FULL SIZE (IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:12 PM BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt A4005 BAY BRIDGE PUMP STATION REPLACEMENT ENLARGED SITEWORK & DETAILS 30277 JOHN ERIC CHUNG RUOTIAN CAI SIEGFREDO LOPEZ SCALE: 1/4" = 1'-0"A2001 6 SOUTH GATE -SWING SCALE: 1/4" = 1'-0"A2001 5 NORTH GATE -SWING SCALE: 1/4" = 1'-0"A2001 7 WEST GATE -CANTILEVER SLIDE SCALE: 3/4" = 1'-0"A3002 1 PERIMETER WALL, TYP. SCALE: 1 1/2" = 1'-0"A3001 4 TOP OF WALL SCALE: 1 1/2" = 1'-0"A4002 2 GRADE CONDITION SCALE: 1 1/2" = 1'-0"A4002 3 PLASTER/ STONE TRANSITION SCALE: 1" = 1'-0"A4005 8 GATE ASSEMBLY DETAIL MARK DESCRIPTION DATE APPR. 1 LCP RESUBMITTAL 06/2023 1 SCALE: 1 1/2" = 1'-0"A2001 9 ADDRESS ID