Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutPA2023-0076_20230803_Resubmittal PackageArcadis U.S., Inc.
445 South Figueroa
Street
Suite 3650
Los Angeles
California 90071
Phone: 213 486 9884
Fax: 213 486 9894
www.arcadis.com
1/7
David Lee
Senior Planner
City of Newport Beach
100 Civic Center Drive,
Newport Beach, CA 92658
Date: July 05, 2023
Subject: 250 East Coast Highway – Notice of Incomplete Filing
Dear Mr. Lee:
Thank you for your comments on the initial LCP and Development Permit
filing for the Orange County Sanitation District’s Bay Bridge Pump Station dated May 1, 2023. Specific
comments from the City are shown in bold and responded below. Comments from Fire, Building, and
Geotechnical departments are also included below. A list of attachments are provided at the end of this
document.
1. Project Description and Justification: Please provide the following project justification and
response to findings:
a. Site Development Review (20.52.080.F)
b. Back Bay Landing Site Development Review (PC 9 Section VII, Letter C)
c. Coastal Development Permit (21.52.015.F)
The Project Description and Justification submittal has been updated including the finding statements in
(a) Site Development Review (20.52.080.F), (b) Back Bay Landing Site Development Review (PC 9
Section VII, Letter C), and (c) Coastal Development Permit (21.52.015.F) per comments received. See
Attachment A - Project Description and Justification_Rev 1
d. Lot Line Adjustment (19.76.020.I). See Comment No. 2, below for more additional details.
The information for (d) Lot Line Adjustment (19.76.020.I) is provided in response to No. 2 below.
e. Include information as provided in emails to the City on April 21, 2023, regarding the status of
the Addendum to the EIR and the exemption from City-issued building permits.
Per California Code, 53091 d, as a local wastewater agency OC San is exempt from building
ordinances for wastewater facilities. The Addendum to the EIR is planned to be adopted at a future
Board of Directors Meeting. The addendum will include additional clarification on project staging
areas and does not change the project description or analysis.
2. Lot Line Adjustment:
a. More information is required regarding the future lot lines of the project site. Provide a
written narrative regarding the existing and proposed property lines and the status of the
Responses to Notice of Incomplete Filing
July 2023
www.arcadis.com 2/7
eminent domain. Preliminarily, the City has determined that Lot Line Adjustment (LLA) is
required for the project. However, more details and background would help City Departments
solidify that determination (for example, to determine that it is an LLA instead of a lot
merger).
A Lot line Adjustment (LLA) is not required. The Subdivision Map Act does not apply to property
conveyed to or from a governmental agency or public entity. (Gov. Code §66428(a)(2).) Here, OC
San owns the property where the existing pump station is located (Parcel 1 of Document recorded in
Book 7661, Page 741 of Official Records-4,879 sf) and is acquiring from adjacent property (APN
440-132-60) 9,713 square feet of land for the expansion of OC San’s existing facility. The land
being acquired is the subject of an eminent domain case (OC San v. Bayside Village Marina LLC, et.
al., OCSC Case No.: 30-2022-01251890) wherein OC San has secured an order of immediate
possession. At the conclusion of the eminent domain case, OC San will record a final order of
condemnation (Code of Civil Procedure section 1268.030), which will have the effect of creating the
new parcel boundaries. The recorded final order of condemnation will be provided to the County
Assessor’s office, who will revise the assessor parcel maps accordingly.
Attachment B includes a figure illustrating the existing property and the property being acquired.
b. Provide any proposed maps and plans in accordance to the requirements of the Lot Line
Adjustment/Lot Merger information sheet.
As discussed in connection with Comment a above, a lot line adjustment is not required. The
revised boundaries of the properties will be created by the recording of the final order of
condemnation at the conclusion of the eminent domain case. The County Assessor will revise the
assessor parcel maps upon receipt of the final order of condemnation in accordance with the final
order of condemnation. Attachment C includes the legal description and plat map of the property
being acquired in fee for the expansion of the pump station.
3. Site Development Review: Please review and provide all of the required submittal contents for a
Site Development Review, as required by the Back Bay Landing Planned Community Text (PC 9)
under Section VII, Letter D. The following documents need to be provided:
a. (10) A comprehensive, cohesive and coordinated lighting plan of exterior and parking
structure lighting, including locations, fixture height, fixture product type and technical
specifications.
The requested lighting information has been included in Attachment D, Lighting Plan, Datasheet,
and Specification.
b. (14) A statement that the proposed new structure is consistent with the goals, policies, and
actions of the General Plan and Planned Community Development Plan.
The statement has been included in Attachment A, Project Description and Justification_Rev 1. Also
see response to Comment No. 1.
Responses to Notice of Incomplete Filing
July 2023
www.arcadis.com 3/7
c. Please review the linked list to ensure all documents are accounted for.
The requirements identified in the Back Bay Landing Planned Community (PC 9) Site Development
Review under Section VII, Letter D have been reviewed and verified. All the applicable documents
are provided either through the original application and/or this response letter.
4. Coastal Hazards Report (PDF Page 65):
a. The report addresses the finished floor elevation of the entrance to the underground station
and how it is safe from sea-level rise impacts. However, please address the underground
pumps, which is shown to be approximately -22.0 feet on the provided Section Plans. Are the
underground elements of the project safe from sea-level rise (SLR)? Please address within
the Coastal Hazards Report.
Yes, the underground pump station is also safe from the sea-level rise (SLR) since the entrance to
the underground pump station is at the same elevation as the electrical room at 15.50 feet NAVD88.
The following sentence has been included in the Coastal Hazardous Report, “The entrance to the
underground pump station dry well is elevated to the same elevation of the electrical building
finished floor at 15.5 feet NVAD88.”
b. The Report’s projected SLR numbers for H++ scenario do not match the State of California’s
Sea Level Rise Guidance (see Table 28). Please verify all SLR projection numbers and
provide a table which outlines the projected SLR and demonstrate that the proposed facility
is protected.
The Bay Bridge Pump Station is designed considering a more conservative SLR reference from the
State of California’s Sea Level Rise Guidance and Critical Infrastructure at Risk: Sea Level Rise
Planning Guidance for California’s Coastal Zone. Final Adopted Guidance. November 17, 2021 as
shown in the table below. The State of California’s Sea Level Rise Guidance reference has also
been included in the updated Coastal Hazardous Report in Attachment E.
Year
Critical Infrastructure at Risk: Sea
Level Rise Planning Guidance for
California’s Coastal Zone
State of California’s Sea Level Rise
Guidance – Table 28
2050 2.7 2.6
2080 6.6 6.4
5. Water Quality Management Plan: As a part of the Coastal Development Permit requirements,
please submit a Water Quality Management Plan (WQMP) for City review.
A Water Quality Management Plan has been developed and included as Attachment F.
Responses to Notice of Incomplete Filing
July 2023
www.arcadis.com 4/7
6. Visual Impact Analysis (PDF Page 351):
a. Please remove the “Potential Future Coastal Public View Tower” from all plans, as it is no
longer a part of the Back Bay Landing project.
The “Potential Future Coastal Public View Tower” has been removed from all plans. See the
updated Visual Impact Analysis_Rev 1 included in Attachment G.
b. For all view simulations, please provide an existing vs. proposed (side by side) for effective
comparisons.
Existing vs. proposed (side by side) visual simulation comparisons are included in the Visual Impact
Analysis_Rev 1 in Attachment G.
7. Construction Management Plan (PDF Page 372):
a. Please note that the use of Lower Castaways Park for construction staging is still being
discussed and subject to change.
It is noted that the use of Lower Castaways Park for construction staging is still being discussed and
subject to change.
8. Notice of Application Filing: Please provide verification that a completed Notice of Application
Filing has been posted to the project site. This can be in the form of a photo of the notice posted on
site. See page 8 of linked document for the notice template.
Notice of Application Filing has been posted on the project site. See Attachment H – Site Photos for Notice
of Application Filing.
9. Public Noticing Materials: Please note that public noticing materials are required. Per previous
discussions, this will be provided once certain project details are resolved (construction staging).
Noted. The public noticing materials are under development and will be provided when ready.
10. Department Reviews: Please see linked reviews from Building, Fire, Geotechnical, and Municipal
Operations. Please note that additional comments from Public Works and Utilities Departments are
pending and will be provided when ready. FYI, these comments may further affect the project
resubmittal.
Fire Comments:
1) Provide premise identification per NBFD guideline.
The premise identification of 250 address ID has been included in the design. The detail of the
address ID has been included in Attachment I - Updated Architectural Drawings.
2) Provide Knox box for emergency access.
Knox boxes are provided near the north and south gates of the project site. See the updated
Architectural Drawings in Attachment I.
3) Provide NFPA 704 placarding for onsite hazards.
NFPA 704 signs will be installed where required.
Responses to Notice of Incomplete Filing
July 2023
www.arcadis.com 5/7
Building Comments:
1) A second means of egress will be required from the basement and roof levels if the exit
access travel distance exceeds 75 feet (100 feet if the building is equipped with an NFPA 13
fire sprinkler system) from the most remote location in on each level to the exit door at the
ground floor level (CBC 1006.3.4). The occupancy classification for the pump station is F-1
(CBC 306).
Means of Egress comment: The project site is exempted from the requirement of the second means
of egress per the following CBC code sections:
405.1 General
“Exceptions: 6. Pumping stations and other similar mechanical spaces intended only for limited
periodic use by service or maintenance personnel.”
1006.2.1 Egress Based on Occupant Load and Common Path of Egress Travel Distance
“Exceptions: 3. Unoccupied mechanical rooms and penthouses are not required to comply with
the common path of egress travel distance measurement.”
The proposed occupancy classification for the pump station is Factory Industrial F-2 Low Hazard
Occupancy. This is in line with other pump stations OC San owns throughout the City including the
Rocky Point and Bitter Point Pump Stations.
2) The proposed project is in a Soils Liquefaction Seismic Hazard Area. The soils report shall
include the analyses described in City of Newport Beach Building Code Policy CBC
1803.5.11-12 and recommendations for the mitigation of the effects of soils liquefaction.
The soils report submitted with the original application included evaluation of liquefaction potential
and mitigation measures.
Geotechnical Comments:
1) The site is located in a Liquefaction Seismic Hazard Zone, for purposes of Geotechnical and
Structural design of the building the Project is assumed to be in Seismic Risk Category IV per
Table 1604.5 of the 2022CBC. To reduce the Risk to Category III the project engineer must
prove that the building will not exceed the maximum allowable quantities per control area as
given in Table 307.1(2) of the 2022CBC. The Geotechnical Engineer must determine Site
Classification per ASCE7-16 Chapter 20, Table 20-3-1 with supporting blow count or shear
wave velocities. Soils vulnerable to potential failure due to liquefaction, sensitive clays and
collapsible weakly cemented soils are required to perform a Site-Specific Ground Motion for
Seismic Design with exception of buildings having a fundamental period of vibration equal to
or less than 0.5 seconds. If the exception is stablished the site class is permitted to be
determined in accordance with section 20.3 and the corresponding values of Fa and Fv
determined from Tables 11-4-1 and 11-4-2.
The Bay Bridge Pump Station is designed based on Risk Category IV for all structures.
Responses to Notice of Incomplete Filing
July 2023
www.arcadis.com 6/7
2) The geotechnical report must also provide estimated differential settlement for the proposed
structure and proposed 30”-inch and 24”-inch sewer lines along with remedial
recommendations to prevent damage.
Differential settlement is provided in the project Geotechnical Report provided with the original
submittal:
6.9.1 Pump Station and Pipeline Differential Settlement
Some materials encountered in the pump station area indicate that liquefaction could occur during a
seismic event. Based on our analyses, settlement up to about 4 inches at the ground surface and
up to about 6 inches of lateral spreading could occur. Foundations extending more than about 25
feet bgs (elevation -13 ft or deeper) could experience about 1 inch of post-liquefaction settlement.
Although the probability of liquefaction occurring in all layers susceptible to liquefaction should be
considered small, if the resulting differential movements from post-earthquake liquefaction
movement cannot be tolerated, flexible pipe connections should be considered to reduce the risk of
damage resulting from soil movement, and mitigation of underlying soils (e.g., grout injection, over
excavation) should be considered to help lessen the magnitude of potential soil movement.
To mitigate the differential settlement associated with utilities and shallow foundations, soil
improvements will be completed.
3) Provide specifications for the construction and removal of existing lines.
The existing pipelines will not be removed, rather they will be filled with 1-sack slurry and abandoned
in place.
Following review of the above responses and associated attachments, please feel free to reach out with any
questions. Furthermore, we are eager to schedule the Zoning Administrator Hearing with the City and
Orange County Sanitation District, if one is deemed necessary. Please reach out with your preferred timing
and location and how we can be of further assistance.
Sincerely,
Arcadis U.S., Inc.
Harmik Aghanian
Project Manager
Email: Harmik.Aghanian@arcadis.com
Direct Line: 213-797-5285
CC. Cindy Murra, Orange County Sanitation District
Responses to Notice of Incomplete Filing
July 2023
www.arcadis.com 7/7
Enclosures:
Attachment A – Project Description and Justification_Rev 1
Attachment B – Lot Lines and Easements
Attachment C – Legal Descriptions for Acquisition Parcels
Attachment D – Lighting Plan, Datasheet, and Specification
Attachment E – Coastal Hazardous Report_Rev 1
Attachment F – Water Quality Management Plan
Attachment G – Visual Impact Analysis_Rev 1
Attachment H – Site Photos for Notice of Application Filing
Attachment I – Updated Architectural Drawings
Attachment A
Project Description Justification
_Rev 1
Bay Bridge Pump Station Replacement
Project No. 5-67
Project Description and Justification
Orange County Sanitation District (OC San) owns, operates, and maintains the wastewater pump stations
and Newport Force Main (NFM) network along the Pacific Coast Highway (PCH) in the City of Newport
Beach (City), California. The network conveys wastewater to the Plant No. 2 wastewater treatment facility
in Huntington Beach. The existing Bay Bridge Pump Station (BBPS) conveys approximately half the
wastewater flow generated in the City and the wastewater will eventually be treated at OC San Plant
No.2. The locations of the existing and proposed pump stations are shown on Figure ES-1 and Figure
ES-2.
The existing BBPS was constructed in 1966 (Project No. 5-12) and upgraded in 1995 with new pumps,
piping and ventilation modifications, structural upgrades, architectural revisions, and a standby generator
(Project 5-33). In 2014, another pump was added for increased capacity and reliability (under Project 5-
60). The existing BBPS has been over 50 years and requires replacement.
The Bay Bridge Pump Station Replacement Project (Project 5-67) includes the replacement of both the
pump station and the associated force mains. The work includes demolition of the existing pump station
building, construction of a new underground pump room (approximately. 2,500 sf), and above grade
facilities consisting of an electrical room, an odor control facility, and a generator room (three buildings;
totaling approximately 3,630 sf). The new dual force main alignment is approximately 1,300 linear feet
and is located adjacent to the existing force mains.
The project is in compliance of the following requirements as stated in Site Development Review
(20.52.080.F), Back Bay Landing Site Development Review (PC 9 Section VII, Letter C), Coastal
Development Permit (21.52.015.F):
1) Allowed within the subject zoning district;
2) Compliance with the Site Development Review, the General Plan, the Zoning Code, Coastal Land
Use Plan, Back Bay Landing Planned Community Development Plan, any applicable specific
plan, and other applicable criteria and policies related to the use or structure;
3) The efficient arrangement of structures on the site and the harmonious relationship of the
structures to one another and to other adjacent developments; and whether the relationship is
based on standards of good design;
4) The compatibility in terms of bulk, scale, and aesthetic treatment of structures on the site and
adjacent developments and public areas;
5) The development shall be sited and designed to maximize the aesthetic quality of the project as
viewed from surrounding roadways, properties, and waterfront, with special consideration given to
providing a variety of building heights, massing, and architectural treatments to provide public
views through the site;
6) The adequacy, efficiency, and safety of pedestrian and vehicular access, including drive aisles,
driveways, and parking and loading spaces;
7) The adequacy and efficiency of landscaping and open space areas and the use of water efficient
plant and irrigation materials;
8) The protection of significant views from public right(s)-of-way and compliance with
Section 20.30.100 (Public View Protection);
Bay Bridge Pump Station Replacement
Project No. 5-67
9) Not detrimental to the harmonious and orderly growth of the City, nor endangers, jeopardizes, or
otherwise constitutes a hazard to the public convenience, health, interest, safety, or general
welfare of persons residing or working in the neighborhood of the proposed development; and
10) Conforms to all applicable sections of the certified Local Coastal Program;
Per California Code, 53091 d, as a local wastewater agency OC San is exempt from building ordinances
for wastewater facilities.
An EIR was prepared for the Bay Bridge Pump Station Replacement Project in August 2020 and the
document can be accessed via https://ceqanet.opr.ca.gov/Project/2016111031.
REGIONAL VICINITY MAP
NO
R
T
H
\\n
a
.
a
e
c
o
m
n
e
t
.
c
o
m
\
l
f
s
\
A
M
E
R
\
O
r
a
n
g
e
-
U
S
O
R
A
1
\
D
C
S
\
P
r
o
j
e
c
t
s
\
W
T
R
\
6
0
5
5
8
5
5
0
_
B
a
y
B
r
i
d
g
e
\
5
0
0
-
D
e
l
i
v
e
r
a
b
l
e
s
\
5
0
9
-
D
e
s
i
g
n
M
e
m
o
6
-
2
0
2
1
\
F
i
g
u
r
e
s
a
n
d
T
a
b
l
e
s
\
D
W
G
s
\
F
i
g
u
r
e
E
S
-
1
.
d
w
g
L
A
Y
O
U
T
:
F
I
G
U
R
E
1
S
A
V
E
D
:
8
/
1
3
/
2
0
2
1
1
1
:
1
8
A
M
A
C
A
D
V
E
R
:
2
3
.
1
S
(
L
M
S
T
E
C
H
)
P
A
G
E
S
E
T
U
P
:
-
-
-
-
P
L
O
T
S
T
Y
L
E
T
A
B
L
E
:
-
-
-
-
PL
O
T
T
E
D
:
8
/
2
6
/
2
0
2
1
7
:
3
8
A
M
B
Y
:
P
R
O
C
T
O
R
,
A
L
A
N
FIGURE
ES-1
LEGEND
PROJECT LOCATION
COUNTY BOUNDARY
N BAYSIDE
PROPOSED
PUMP STATION
EXISTING PUMP
STATION
P A C I F I C COAST HWY
PROJECT LOCATION MAP
Scale: 1 in = 200 ft
0 200'400'
NO
R
T
H
FIGURE
ES-2
Attachment B
Lot Lines and Easements
ENTRANCE & EXIT
ON BAY SIDE DRIVE
4,879 SF
9,713 SF
Attachment C
Legal Descriptions for Acquisition
Parcels
Page 1 of 2
EXHIBIT “A-1” 1
2
LEGAL DESCRIPTION 3
PARCEL 5-67-01 (FEE) 4
5
ORANGE COUNTY SANITATION DISTRICT 6
BAY BRIDGE PUMP STATION 7
8
That certain parcel of land situated in the City of Newport Beach, County of Orange State of 9
California, being that portion of Parcel 3 of Parcel Map No. 93-111 filed in Book 278, Pages 10
40 through 45 of Parcel Maps in the Office of the County Recorder of said Orange County, 11
described as follows: 12
13
COMMENCING at the easterly terminus of that certain course in the centerline of the East 14
Coast Highway shown as “North 87°36’58” West 160.15 feet” on said Parcel Map No. 93-111, 15
said point also being marked with a “spike and washer tagged DOH per Caltrans F.B. SR. 16
81-115/11” per said Parcel Map No. 93-111; 17
thence along said centerline North 87°36’58” West 160.15 feet to the northwesterly terminus 18
thereof, said point also being marked with a “spike and washer tagged DOH per Caltrans F.B. 19
SR. 81-115/11” per said Parcel Map No. 93-111; 20
thence leaving said centerline at right angles North 02°23’02” East 85.94 feet to a line shown 21
as “North 87°36’16” West 123.34 feet” in the southerly boundary of said Parcel 3, said line 22
also being the northerly Right-of-Way line of the East Coast Highway as shown on said Parcel 23
Map No. 93-11 and also shown on a Caltrans Right-of-Way Map No. 25491-C for 07-ORA-1 24
18.3; 25
thence along said southerly line of Parcel 3 North 87°36’16” West 65.10 feet to the intersection 26
of the southerly boundary of said Parcel 3 and the easterly line of Parcel 1 Dedicated to the 27
Orange County Sanitation District in a document recorded September 10, 1965 in Book 7661, 28
Page 741 of Official Records, in the Office of said Orange County Recorder, said point also 29
being the TRUE POINT OF BEGINNING; 30
thence North 13°39'41" East 71.32 feet; 31
thence North 76°24'23" West 173.32 feet; 32
thence South 13°39'46" West 79.83 feet to a line shown as “North 66°24’24” West 284.74 33
feet” in said southerly boundary of Parcel 3; 34
thence along said southerly boundary of Parcel 3 the following six (6) courses: 35
(1) South 66°24'24" East 8.72 feet to an angle point therein; 36
(2) South 73°06'54" East 43.65 feet to an angle point therein; 37
(3) South 83°06'23" East 60.83 feet to an angle point therein; 38
(4) North 01°46'10" West 60.00 feet to an angle point therein; 39
(5) North 88°13'14" East 60.00 feet to an angle point therein; 40
ORANGE COUNTY SANITATION DISTRICT
BAY BRIDGE PUMP STATION
PARCEL 5-67-01 (FEE)
Page 2 of 2
(6) South 01°46'46" East 70.87 feet to an angle point therein to the TRUE POINT OF 41
BEGINNING. 42
43
CONTAINING: 9,713 Square Feet more or less. 44
45
EXHIBIT “A-2” attached and by this reference made a part hereof. 46
47
48
49
50
51
52
53
54
Steven C. Slocum, P.L.S. 9044 Date 55
56
Michael Baker International 57
5 Hutton Centre Drive, Suite 500 58
Santa Ana, California 92707 59
Project No. 163755 60
H:\pdata\163755\CADD\Mapping\Exhibits\Pump Station Legals and Exhibits\Legal\163755-00A1 - Legal Fee Parcel.docx 61
08/17/2021
5 Hutton Centre Drive, Suite 500
Santa Ana, CA 92707
(949) 472-3505 ·MBAKERINTL.COM
5 Hutton Centre Drive, Suite 500
Santa Ana, CA 92707
(949) 472-3505 ·MBAKERINTL.COM
Attachment D
Lighting Plan, Datasheet, and
Specification
TRANSFORMER
ACCESS HATCH
GENERATOR
ROOM
RAISED
PLATFORM
ELECTRICAL
ROOM
ODOR CONTROL
AREA
PUMP STATION
(BELOW GRADE)
NORTH GATE
24' WIDE SWING GATE
SOUTH GATE
24' WIDE SWING GATE
WEST GATE
18' WIDE CANTILEVER
SLIDING GATE
MANHOLE COVERS, TYP.
SEE STRUCTL DWGS
RAISED
PLATFORM
45.57'
16.23'
9.52'
TOW = 29.33'
PEDESTRIAN GATE
8' HIGH WALL
10' HIGH WALL
8' HIGH WALL
F U T U R E A C C E S S R O A D
P A C I F I C
C O A S T H I G H W A Y
(E) BUILDING
STRUCTURE
OUTLINE
10' HIGH WALL
8' HIGH WALL
10' HIGH WALL
15' HIGH WALL
15' HIGH WALL
A2001
1
A20012
A2001 3
A2001
4
173.84'
57.26'
18.00'
4.44'
EXTERIOR WALL
BOUNDARY
SWITCHBOARD
106.32'
133.53'
39.48'
24.00'
43.99'
LANDSCAPE AREA
(SEE LANDSCAPE DWGS)
6' - 5 1/8"
LANDSCAPE AREA
(SEE LANDSCAPE DWGS)
TOW = 24.00'
TOW = 24.00'
TOW = 24.00'
TOW = 24.83'
TOW = 22.83'
TOW = 21.50'
TOW = 21.50'
6' - 10"
23' - 7 5/8"
41' - 7 7/8"
TOW = 21.50'
9
TOW = 24.83'
TOW = 29.33'
5.07'
TOW = 22.83'
TOW = 22.83'
TOW = 29.33'
TOW = 29.33'
SWITCHBOARD
PLATFORM
(REMOVABLE)
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2 3 4 5 6 7 8 9 10
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 4/20/2023 6:17:34 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt
A1001
BAY BRIDGE PUMP STATION
REPLACEMENT
SITE PLAN
30259
JOHN ERIC CHUNG
RUOTIAN CAI
SIEGFREDO LOPEZ
SCALE: 1/8" = 1'-0"
SITE PLAN
MARK DESCRIPTION DATE APPR.
E3 CITIZEN LED, 17W,
APPROXIMATE 10 FT AFG.
TYP OF 10. (GENERATOR
AND ELECTRICAL ROOM
AREA)
E3 CITIZEN LED, 17W,
APPROXIMATE 10 FT AFG.
TYP OF 10. (GENERATOR
AND ELECTRICAL ROOM
AREA)
WE-EF PLS420 LED, 18W,
APPROXIMATE 8 FT AFG.
TYP OF 4. (INSIDE
PERIMETER WALL)
E3 CITIZEN LED, 17W,
APPROXIMATE 10 FT AFG.
TYP OF 10. (GENERATOR
AND ELECTRICAL ROOM
AREA)
WE-EF PLS420 LED, 18W,
APPROXIMATE 8 FT AFG.
TYP OF 4. (INSIDE
PERIMETER WALL)
VIGILANT LED AREA LIGHT
ALU7AC26DWNNGN, 40W, AFG
APPROXIATE 10-11 FT. TYP OF
5. (ELECTRICAL ROOM AREA)
ALU7AC26DWNNGN, 40W,
APPROXIMATE 9 FT AFG.
TYP OF 4. (ODOR
CONTROL AREA)
LIGHT FIXTURE SCHEDULE
TYPE WATTS MOUNT DESCRIPTION MANUFACTURER
AW PENDANT%RAC.ETWALL MULTI9OLT LED LINEAR FIXTURE INCHES IN LENGTH WITH A MINIMUM LIGHT OUTPUT OF LUMENS
COLOR RENDERING INDEX AND LED COLOR TEMPERATURE %E . FIXTURE SHALL %E ENCLOSED
GAS.ETED AND SUITA%LE FOR USE IN WET LOCATIONS PRO9IDE FIXTURE WITH U9STA%ILI=ED HIGHIMPACT
FROSTED ACRYLIC LENS FOR UNIFORM LIGHT OUTPUT AND HIGH IMPACT RESISTANCE FIXTURE SHALL %E
PRO9IDED WITH HIGH EFFICIENCY LEDS 9 DIMMING STANDARD FOR A DIMMING RANGE OF TO
FIXTURE SHALL HA9E SURGE PROTECTION SINGLE FUSE AND AN IP RATING FIXTURE SHALL %E SUITA%LE
FOR WET LOCATIONS WITH AM%IENT TEMPERATURE UP TO DEGREES FAHRENHEIT FIXTURE SHALL %E A
DESIGNLIGHTS CONSORTIUM 4UALIFIED PRODUCT AND SHALL %E UL LISTED
HOLOPHANE LIGHTING
EMS SERIES
OR E4UAL
AEM W PENDANT%RAC.ETWALL MULTI9OLT LED LINEAR FIXTURE INCHES IN LENGTH WITH A MINIMUM LIGHT OUTPUT OF LUMENS
COLOR RENDERING INDEX AND LED COLOR TEMPERATURE %E . FIXTURE SHALL %E ENCLOSED
GAS.ETED AND SUITA%LE FOR USE IN WET LOCATIONS PRO9IDE FIXTURE WITH U9STA%ILI=ED HIGHIMPACT
FROSTED ACRYLIC LENS FOR UNIFORM LIGHT OUTPUT AND HIGH IMPACT RESISTANCE FIXTURE SHALL %E
PRO9IDED WITH HIGH EFFICIENCY LEDS 9 DIMMING STANDARD FOR A DIMMING RANGE OF TO
FIXTURE SHALL HA9E SURGE PROTECTION SINGLE FUSE AND AN IP RATING FIXTURE SHALL %E SUITA%LE
FOR WET LOCATIONS WITH AM%IENT TEMPERATURE UP TO DEGREES FAHRENHEIT FIXTURE SHALL %E A
DESIGNLIGHTS CONSORTIUM 4UALIFIED PRODUCT AND SHALL %E UL LISTED FIXTURE SHALL INCLUDE EM
SELFDIAGNOSTICS %ATTERY PAC.
HOLOPHANE LIGHTING
EMS SERIES
OR E4UAL
AW PENDANT%RAC.ETWALL SAME AS LIGHT FIXTURE TYPE A EXCEPT WITH A MINIMUM LIGHT OUTPUT OF LUMENS HOLOPHANE LIGHTING
EMS SERIES
OR E4UAL
AEM W PENDANT%RAC.ETWALL SAME AS LIGHT FIXTURE TYPE AEM EXCEPT WITH A MINIMUM LIGHT OUTPUT OF LUMENS HOLOPHANE LIGHTING
EMS SERIES
OR E4UAL
%W WALL 9 LED WALLPAC. LED COLOR TEMPERATURE OF . AND CRI TYPE I9 MEDIUM LIGHT DISTRI%UTION
HOUSING SHALL %E HEA9Y GRADE A CAST ALUMINUM WITH IP RATING FOR USE IN WET LOCATIONS
CONTROLS SHALL CONSIST OF AN INTEGRAL %UTTON STYLE PHOTOCONTROL PRO9IDE WITH SINGLE FUSE
INTEGRAL SURGE PROTECTION AND TAMPER RESISTANT HARDWARE
WEEF PLS LED
OR E4UAL
C W WALLCEILING 9 LED TYPE HA=ARDOUS AREA LIGHTING FIXTURE HEA9Y DUTY UL LISTED CLASS DI9ISION GROUP D
LOCATIONS IP RATED LENGTH LUMENS DIMMA%LE . WALLCEILING MOUNTING
HOLOPHANE HXPL
SERIES
D W RECESSED E CITI=EN LED ER ELEMENT ROUND DEGREE %EAM TILT CRI . 9 FLANGED
HEA9YGAUGE HOUSING DIECAST ALUMINUM TRIM ANTI4UE %RON=E FINISH %E9EL STYLE ETL LISTED WET
LISTED
TECH LIGHTING
ELEMENT LED FIXED
DOWNLIGHT
EMW WALL 9 TWO WATT LED LAMPS INDUSTRIAL EMERGENCY LIGHT WET LOCATION AND NEMA X RATED FIXTURE
SHALL PRO9IDE SAME LE9EL OF LUMEN OUTPUT FOR FULL MINUTES OF %ATTERY DISCHARGE WITH NO
LIGHT DEGRADATION EMERGENCY LIGHT FIXTURE SHALL %E PRO9IDED WITH SELFDIAGNOSTICS TO
MONITOR LED STATUS LED DRI9ER CIRCUIT %ATTERY CAPACITY AND CHARGER FUNCTION AND SHALL
DISPLAY ANY FAULT DETECTION %Y MEANS OF FLASHING CODE FLAMERATED U9 STA%LE THERMOPLASTIC
HOUSING FULLY GAS.ETED AND CORROSION RESISTANT LED %ASED LAMPHEADS CONSTRUCTED OF HIGH
STRENGTH DIECAST ALUMINUM WITH POLYCAR%ONATE LENS %ATTERY SHALL %E MAINTENANCEFREE
LITHIUM IRON PHOSPHATE TYPE AND SHALL PRO9IDE MINUTES OF EMERGENCY POWER UL LISTED FOR
CLASS DI9ISION GROUP D HA=ARDOUS LOCATIONS LED COLOR TEMPERATURE SHALL %E .
PRO9IDE %RAC.ETS FOR SURFACE MOUNT AS RE4UIRED
HU%%ELL LIGHTING
DUAL LITE DYNAMO
DYN SERIES
OR E4UAL
EEMW WALL WALL MOUNT 9 W EXIT SIGN WITH TWIN W HALOGEN LAMP EMERGENCY LIGHT COM%INATION
CONSTRUCTED OF IMPACTRESISTANT FI%ERGLASS REINFORCED POLYESTER HOUSING ONEPIECE FORMED
GAS.ET AND CORROSIONRESISTANT HARDWARE LAMP HEADS SHALL %E POLYCAR%ONATE PAR SEALED
%EAM FIXURE SHALL %E PRO9IDED WITH SELFDIAGNOSTICS TO MONITOR LAMPS %ATTERY AND CHARGER
%ATTERY SHALL %E MAINTENANCEFREE SEALED NIC.ELMETAL HYDRIDE TYPE AND SHALL PRO9IDE
MINUTES OF EMERGENCY POWER LETTERS SHALL %E RED INCHES HIGH WITH INCH STRO.E WITH
FEET 9IEWING DISTANCE RATING UL LISTED UL LISTED FOR CLASS DI9ISION GROUP D
HA=ARDOUS LOCATIONS
MULE LIGHTING S9XH
SERIES
OR E4UAL
EW WALL M9OLT LED LAMP INDUSTRIAL AND SUITA%LE FOR DAMP LOCATIONS EXIT SIGN SHALL MEET UL NFPA
CURRENT LIFE SAFETY CODE NEC AND OSHA ILLUMINATION STANDARDS ALUMINUM HOUSING
UNI9ERSAL DIRECTIONAL INDICATOR .NOC.OUTS AND MOUNTING LETTERS SHALL %E INCHES HIGH
INCH STRO.E WITH FEET 9IEWING DISTANCE RATING %ASED ON UL STANDARD
LITHONIA LIGHTING LE
SERIES
OR E4UAL
F W %RAC.ETWALL MULTI9OLT LOW PROFILE AREA LED LIGHT WITH MINIMUM LIGHT OUTPUT OF LUMENS COLOR
RENDERING INDEX LED COLOR TEMPERATURE . AND 9 DIMMING FOR A DIMMING RANGE OF
TO FIXTURE HOUSING SHALL %E COPPERFREE ALUMINUM WITH DUAL SEALED POLYESTER GRAY COLOR
TOPCOAT FINISH FIXTURE LENS SHALL %E CLEAR IMPACT RESISTANT TEMPERED GLASS WITH DEGREES
%EAM DISTRI%UTION PRO9IDE FIXTURE WITH INDI9IDUAL WIRE LEADS FOR TERMINATION IN FXTURE HOUSING
AND A DEGREE MOUNTING %RAC.ET FOR MOUNTING ON STEEL COLUMN FIXTURE SHALL %E FACTORY
SEALED UL LISTED FOR OUTDOOR LOCATIONS
VIGILENT LED
AREA LIGHT SERIES
OR EQUAL
G W DEGREE STANCHION 9OLT LED AREA LED LIGHT WITH MINIMUM LIGHT OUTPUT OF LUMENS COLOR RENDERING INDEX
LED COLOR TEMPERATURE . FIXTURE HOUSING SHALL %E COPPERFREE ALUMINUM WITH DUAL
SEALED POLYESTER GRAY COLOR TOPCOAT FINISH FIXTURE LENS SHALL %E POLYCAR%ONATE LENS
DEGREES %EAM DISTRI%UTION PRO9IDE FIXTURE WITH INDI9IDUAL WIRE LEADS FOR TERMINATION IN
FXTURE HOUSING AND A DEGREE MOUNTING %RAC.ET FOR MOUNTING ON CONDUIT FIXTURE SHALL %E
FACTORY SEALED UL LISTED FOR CLASS DI9ISION GROUP D LOCATIONS
DIALIGHT
SAFESITE SERIES
OR EQUAL
E0005
LIGHTING FIXTURE SCHEDULE
-EFF SO.OL
CHRISTINA LAN=EL
%RIAN YOUNG
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
MARK DATE APPR.DESCRIPTION
DW
G
C
?
U
V
H
U
V
?
C
L
D
Q
]
H
O
?
A
C
C
D
R
F
V
?
A
U
F
D
G
L
V
?
A
U
S
O
C
S
D
²
%
D
\
%
U
L
G
J
H
P
X
P
S
S
W
D
W
L
R
Q
?
P
U
R
M
H
F
W
F
L
O
H
V
?
F
D
S
?
A
X
W
R
C
A
D
?
S
H
E
E
T
S
?
E
L
E
C
?
E
G
Z
J
DA
T
E
A
S
U
S
P
U
S
E
R
C
L
D
Q
]
H
O
DRAWING NO
IF NOT SCALE ACCORDINGLY
AT FULL SI=E
LINE IS INCHES
ORANGE COUNTY SANITATION DISTRICT
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
DRAWN %Y
DESIGNED %Y
CHEC.ED %Y
BAY BRIDGE PUMP STATION REPLACEMENT 5-67
OFSHEET NO
MC
CB
CB
W(
B
)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)
J
J
JJ
J
E
(
B
)
E(
B
)
E(
B
)
E(
B
)
E(B)
E(B)
T
(
B
)
T(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)
J
J
J
CB
W(
B
)
ST(B)
ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)
J
J
E
(
B
)
E(
B
)
E(
B
)
E(
B
)
E(B)
E(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B)T(B)
TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)
J
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
MARK DATE APPR.DESCRIPTION
DW
G
:
C
:
\
U
s
e
r
s
\
C
L
a
n
z
e
l
\
A
C
C
D
o
c
s
\
A
r
c
a
d
i
s
\
A
U
S
-
3
0
0
0
1
6
8
7
-
O
C
S
D
–
5
-
6
7
B
a
y
B
r
i
d
g
e
P
u
m
p
S
t
a
t
i
o
n
\
P
r
o
j
e
c
t
F
i
l
e
s
\
F
D
S
\
A
u
t
o
C
A
D
\
S
H
E
E
T
S
\
E
L
E
C
\
5
-
6
7
-
E
1
0
0
1
.
d
w
g
DA
T
E
:
A
p
r
1
9
,
2
0
2
3
6
:
0
4
p
m
U
S
E
R
:
C
L
a
n
z
e
l
DRAWING NO.
(IF NOT 2"-SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ORANGE COUNTY SANITATION DISTRICT
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
DRAWN BY:
DESIGNED BY:
CHECKED BY:
BAY BRIDGE PUMP STATION REPLACEMENT 5-67
302OFSHEET NO.:
10'20'0'10'
SCALE: 1" = 10'
Underground Service Alert
TWO WORKING DAYS BEFORE YOU DIG
Call:811
E1001
165
ELECTRICAL SITE PLAN
CHRISTINA LANZEL
BRIAN YOUNG
JEFF SOKOL
IRRIGATION CONTROLLER
EXISTING SOUTHERN CALIFORNIA EDISON
(SCE) UNDERGROUND PULLBOX FOR
ACQUISITION OF TEMPORARY CIRCUIT.
COORDINATE ALL WORK WITH SCE.
EXISTING TELEPHONE COMPANY UNDERGROUND
PULLBOX FOR ACQUISITION OF NEW
COMMUNICATIONS CIRCUIT. COORDINATE ALL
WORK WITH TELEPHONE COMPANY.
NOTES:
1.JUNCTION BOX SHALL BE 12"Hx12"Wx6"D, NEMA 4X WITH
TOP AT 72" AFF.
2.FURNISH AND INSTALL 3/4" CONDUIT WITH 2-#12, 1-#12G
BETWEEN LIGHT FIXTURES AND ROUTE A HOMERUN TO
LIGHTING CONTROL PANEL 1 INSIDE OF THE ELECTRICAL
ROOM.
3.INSTALL UNDERGROUND DUCTANKS IN ACCORDANCE
WITH OCSAN STANDARD DETAIL S-400 AND RESPECTIVE
DUCTBANK SECTIONS.
4.JUNCTION BOX FOR FUTURE ACCESS CONTROL DEVICES
AND CABLES AT PERSONNEL GATE. SEE DRAWING D6014
FOR REQUIREMENTS.
METERING SWITCHBOARD
SCE UTILITY TRANSFORMER
PROVIDE CONCRETE PAD,
PRIMARY DUCTBANK AND
SECONDARY DUCTBANK IN
ACCORDANCE WITH SCE
REQUIREMENTS.
ELECTRICAL ROOM
SEE E1002 TO E1009
GENERATOR
ROOM
SEE E1016, E1017,
E1018
ODOR CONTROL
AREA
SEE E1019, E1020, E1021
8'-0" AFG
(NOTE 2)
8'-0" AFG
(NOTE 2)
18
B
18
B
8'-0" AFG
(NOTE 2)
18
B
55JSWB126
UTILITY POWER HIGH RESISTANCE
GROUNDING SYSTEM
55JLE035
S55J035
S55J050
55JAE050
55JLE038
S55J941
S55J038
N55JTTBA
55JSJB8022
S55J8022A
55JZSC634
N55J036RI
N55J036MI
N55J036PI
P55J696B S55J8022B
(NOTE 1)
11
E3
0
0
8
2
E3
0
0
8
22
E3
0
0
8
1
E3008
2
1
E
3
0
0
8
8'-0" AFG
(NOTE 2)
18
B PNL-A
CKT 38
PNL-A
CKT 38 PNL-A
CKT 38
PNL-A
CKT 38
EXISTING SCE TRANSFORMER
TEMPORARY UNDERGROUND
PRIMARY CIRCUIT FOR EXISTING SCE
TRANSFORMER DURING
CONSTRUCTION. PROVIDE
UNDERGROUND DUCTBANK PER
SCE REQUIREMENTS.
EXISTING PUMP STATION
TEMPORARY POWER PLAN
SECURITY
CAMERA #5
SECURITY
CAMERA #1
SECURITY
CAMERA #3
SECURITY
CAMERA #4
SECURITY
CAMERA #2
SECURITY
CAMERA #7
C55J634C
55JZSC634A
METERING SWITCHBOARD
TVSS UNIT
EXISTING SOUTHERN CALIFORNIA EDISON
(SCE) UNDERGROUND PULLBOX FOR
ACQUISITION OF NEW PRIMARY CIRCUIT.
COORDINATE ALL WORK WITH SCE.
NOTE 3
(TYP)
SECURITY
CAMERA #8
NOTE 4
ZSC062H
NOTE 4
INTRINSICALLY SAFE
RELAY PANEL COMBUSTIBLE GAS
CALIBRATION PANEL
S55J942
N55JTTBB
S55J943
IS55J040
55JLSH040
EF
WALL MOUNT WITH 45 DEGREE
ANGLE BRACKET 9'-0" AFF
EEM1
36
MOUNT ABOVE DOOR
D
17
MOUNT RECESSED IN CANOPY
D
17
MOUNT RECESSED IN CANOPY
E1
5
MOUNT ABOVE DOOR
D
17
MOUNT RECESSED IN CANOPY
A1/EM
50
E1
5
MOUNT ABOVE DOOR
PHOTOCELL
F
40
EXTERIOR FIXTURES SHOWN IN
APPROXIMATE LOCATION. SEE
ARCHITECTURAL DRAWINGS FOR EXACT
LOCATION. (TYP)
WALL MOUNT WITH 45
DEGREE ANGLE BRACKET
9'-0" AFF
WALL MOUNT WITH 45
DEGREE ANGLE BRACKET
9'-0" AFF
SWITCH FOR
RESTROOM LIGHTS
0-30 MINUTE TIMER SWITCH
FOR EXHAUST FAN
A1/EM
50
A1
50
3
3
PNL A
CKT 16
NL/EM
PNL A
CKT 16
PNL A
CKT 16
PNL A
CKT 16
NL/EM
PNL A
CKT 16
NL/EM
PNL A
CKT 16
PNL A
CKT 16
PNL A
CKT 16
NL/EM
GFCI
PNL A
CKT 14
NOTE 1
PNL A
CKT 18
PNL A
CKT 18
EM
CONTINUE TO FIXTURE IN STAIRWELL
SEE E1003
PNL A
CKT 20
EM
PNL A
CKT 16
PNL A
CKT 16
PNL A
CKT 42
PNL A
CKT 40
PNL A
CKT 40
PNL A
CKT 40
PNL A
CKT 40
PNL A
CKT 40
PNL A
CKT 42
PNL A
CKT 42
PNL A
CKT 4
PNL A
CKT 4
WP/GFCI
PNL A
CKT 8
PNL B
CKT 12
PNL A
CKT 1
PNL A
PNL A
PNL A
LIGHTING
CONTROL
PANEL 1
PNL A
CKT 26
PNL A
CKT 26
PNL A
PNL A
PNL A
LIGHTING
CONTROL
PANEL 1
LIGHTING
CONTROL
PANEL 1
LIGHTING
CONTROL
PANEL 1
CONTINUE TO
FIXTURES AT
MEZZANINE LEVEL
SEE E1013
MEZZANINE LEVEL LIGHT SWITCH
LOWER LEVEL LIGHT SWITCH
WALL SWITCH
PNL A
CKT 18
PANELBOARD A
55JBCP034
P55J322A
TPC1000
480V RECEPTACLE
(36" AFG)
PNL B
CKT 1
PNL B PNL A
PNL A
A1/EM
50
9'-0" AFF (TYP)
WP/GFCI
PNL A
CKT 8
WP/GFCI
PNL A
CKT 8PNL A
PNL B
CKT 10
PNL B
A1
50
9'-0" AFF (TYP)
C
74
WALL MOUNT
7'-0" AFF
DATA OUTLET
WITH (4) RJ45 JACKS
NETWORK
RACK
PNL A
D
17
MOUNT RECESSED IN CANOPY
PNL A
CKT 42
D
17
MOUNT RECESSED IN CANOPY
PNL A
CKT 42
F
40
F
40
F
40
F
40 F
40
PNL A
CKT 40
PNL A
CKT 42
PNL A
CKT 42
D
17
MOUNT RECESSED IN CANOPY
D
17
MOUNT RECESSED IN CANOPY
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2 3 4 5 6 7 8 9 10
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/7/2023 3:57:42 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-E-BBPS.rvt
E1008
BAY BRIDGE PUMP STATION
REPLACEMENT
ELECTRICAL ROOM
LIGHTING AND RECEPTACLE PLAN
302172
JEFF SOKOL
CHRISTINA LANZEL
BRIAN YOUNG
SCALE: 3/8" = 1'-0"
ELECTRICAL ROOM LIGHTING AND RECEPTACLE PLAN
0'2'6'4'
NOTES:
1.MOUNT RECEPTACLE 18" AFF FOR INSTANT
WATER HEATER.
MARK DESCRIPTION DATE APPR.
MOUNT RECESSED IN CANOPY
MOUNT ABOVE DOOR
9'-0" AFF
A1
50
9'-0" AFF
A1
50
E1
5
A1/EM
50
D
17
6
MOUNT ABOVE TRANSOM
CKT 25
GFCI
WP
PNL A
CKT 25
GFCI
PNL A
CKT 25
GFCI
PJB55J8000
PJB55J8000
LIGHTING
CONTROL
PANEL 1
PNL A
CKT 27
PNL A
CKT 27
EM
PNL A
CKT 27
PNL A
CKT 27
EM
PNL A
CKT 27
PNL A
CKT 27
EM
PNL A
CKT 27
PNL A
CKT 42
POWER JUNCTION BOX
PJB55J8000
9'-0" AFF
A1/EM
50
9'-0" AFF
A1
50
9'-0" AFF
A1/EM
50
MOUNT RECESSED IN CANOPY
D
17
PNL A
CKT 42
MOUNT RECESSED IN CANOPY
D
17
PNL A
CKT 42
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2 3 4 5 6 7 8 9 10
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/7/2023 4:05:09 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-E-BBPS.rvt
E1017
BAY BRIDGE PUMP STATION
REPLACEMENT
GENERATOR ROOM LIGHTING AND
RECEPTACLE PLAN
302181
JEFF SOKOL
CHRISTINA LANZEL
BRIAN YOUNG
SCALE: 1/2" = 1'-0"
GENERATOR ROOM LIGHTING AND RECEPTACLE PLAN
0'2'4'1'
MARK DESCRIPTION DATE APPR.
8'-10" AFG
9'-0" AFF
B
18
A2
62
8'-0" AFF
A2
62
8'-10" AFG
B
18
MOUNT ABOVE DOORE1
5
8'-10" AFG
B
18 8'-0" AFF
A2
62
8'-0" AFF
A2
62
8'-0" AFF
A2
62
9'-0" AFF
A2
62
9'-0" AFF
A2
62
8'-0" AFF
A2
62
NL/EM
MOUNT ON
EQUIPMENT RACK
A2
62
55JBCP696
CKT 1
GFCI\WP
55JBCP696
MOUNT ON
EQUIPMENT RACK
A2
62
LIGHTING
CONTROL
PANEL 2
55JBCP696
CKT 1
GFCI\WP
55JBCP696
CKT 1
GFCI/WP
55JBCP696
55JBCP696
8'-10" AFG
B
18
LIGHTING CONTROL PANEL 2
55JBCP696
240/120V PANELBOARD
55JBCP696
CKT 3
GFCI
WP
55JBCP696
CKT 4
55JBCP696
CKT 4
55JBCP696
CKT 4
EM
55JBCP696
CKT 4
55JBCP696
CKT 2
55JBCP696
CKT 2
55JBCP696
CKT 2
55JBCP696
CKT 4
55JBCP696
CKT 4
55JBCP696
CKT 4
55JBCP696
CKT 4
EM
55JBCP696
CKT 4
55JBCP696
CKT 4
EM
55JBCP696
LIGHTING
CONTROL
PANEL 2
55JBCP696
CKT 2
PHOTOCELL
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2 3 4 5 6 7 8 9 10
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 4/20/2023 9:36:41 AM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-E-BBPS.rvt
E1020
BAY BRIDGE PUMP STATION
REPLACEMENT
ODOR CONTROL AREA LIGHTING
AND RECEPTACLE PLAN
302184
JEFF SOKOL
CHRISTINA LANZEL
BRIAN YOUNG
SCALE: 3/8" = 1'-0"
LIGHTING AND RECEPTACLE PLAN
0'2'6'4'
MARK DESCRIPTION DATE APPR.
BBPS SITE PHOTOMETRIC PLAN
BA
Y
B
R
I
D
G
E
P
U
M
P
S
T
A
T
I
O
N
SI
T
E
P
H
O
T
O
M
E
T
R
I
C
P
L
A
N
Designer
C. LANZEL
Date
06/07/2023
Scale
Not to Scale
Drawing No.
Summary
1 of 1
Schedule
Symbol Label Quantity Catalog Number Description
Number
Lamps
Lumens
Per Lamp
Light Loss
Factor Manufacturer Wattage
B
8 131-9631_us PLS420 LED, Wall Luminaires / Surface
Mounted PLS420 [M] IP66:LED-
6/26W/2.7K;PLS420 LED, Wall Luminaires
/ Surface Mounted
6 374 1 WE-EF USA 30
F
6 ALU7AC26-XXXXX-
N_Simulated
VIGILANT AREA LIGHT 1 5501 1 DIALIGHT
CORPORATION
40
D
10 E3SFF-LH8306AI ELEMENT E3 ADJUSTABLE HOUSINGW/ 60
DEGREE OPTICS
1 1560 1 TECH LIGHTING 18.1
Statistics
Description Symbol Avg Max Min
Calc Zone #1 4.7 fc 60.6 fc 0.0 fc
Bay Bridge Pump Station Replacement LIGHTING
Project No. 5-67
FDS 16500-1
Section 16500
LIGHTING
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. CONTRACTOR shall furnish and install lighting fixtures, and accessories for all lighting
systems, complete and operable, all in accordance with the requirements of the Contract
Documents.
B. In case of conflict between this specification and the Contract Drawing Fixture
Schedule, the latter shall take precedence.
1.2 LIGHTING
A. General
1. Fixtures shall include mounting hardware, reflectors, lenses, globes, etc. and shall
be supplied as complete operating units.
2. Lighting system installation shall meet the specified seismic requirements.
3. Lighting System shall be easily maintainable.
1.3 RELATED WORK SPECIFIED ELSEWHERE
A. The requirements of the following sections and divisions apply to the Work of this
section. Other sections and divisions of the Specifications, not referenced below, shall
also apply to the extent required for proper performance of this Work.
1. Section 01332, Seismic Design Criteria
2. Section 09800, Protective Coating
3. Section 16010, Electrical General Provisions
4. Section 16050, Basic Materials and Methods
5. Section 16130, Raceway Systems and Pull Boxes
6. Section 16080, Electrical Testing
1.4 REFERENCE SPECIFICATIONS, CODES, AND STANDARDS
A. All Work specified herein shall conform to or exceed the applicable requirements of the
referenced portions of the following publications to the extent that the provisions thereof
are not in conflict with other provisions of these Specifications.
B. Comply with the applicable editions of the following codes, regulations, and standards:
LIGHTING Bay Bridge Pump Station Replacement
Project No. 5-67
16500-2 FDS
1. Codes and Regulations:
29 CFR 1910 Code of Federal Regulations, Title 29, Part
1910, U.S. Occupational Safety and Health
Standards (OSHA)
CCR California Code of Regulations, Title 8, Div. 1,
Chap. 4, Subchap. 5, Electrical Safety Orders
CCR California Code of Regulations, Title 24, Part 2,
California Building Code (CBC)
CCR California Code of Regulations, Title 24, Part 3,
California Electrical Code
NFPA 70 National Electrical Code (NEC)
2. Industry Standards:
ANSI C82.1 For Lamp Ballast - Line Frequency Fluorescent
Lamp Ballast
ANSI C82.4 For Lamp Ballast - Ballasts for High-Intensity-
Discharge and Low-Pressure Sodium Lamps
(Multiple-Supply Type)
ANSI C82.11 High-Frequency Fluorescent Lamp Ballasts
IESNA RP-7 Lighting Industrial Facilities
UL 924 Emergency Lighting and Power Equipment
3. Other Standards:
ANSI American National Standards Institute
ETL Intertek ETL SEMKO
IESNA Illuminating Engineering Society of North
America
NEMA National Electrical Manufacturers Association
UL Underwriters Laboratories
C. Comply with the applicable reference Specifications as directed in the General
Requirements and the Additional General Requirements.
1.5 CONTRACTOR SUBMITTALS
A. Submittals shall be in accordance with the General Requirements, the Additional
Requirements, and as specified herein.
1. Catalog literature for each fixture specified including description of materials, type
of diffuser, hardware, reflector, finish, mounting/support details, weight, electrical,
photometric data, and ballast. The submittal shall also show evidence of UL listing or
other testing laboratory acceptable to the ENGINEER.
2. If substitution fixtures are proposed, the submittal shall have sufficient information
for complete comparison of the proposed fixture to the originally specified fixture.
Photometric data shall include coefficients of utilization, average brightness,
candlepower distribution curves, and lumen output chart.
3. Pole-mounted fixtures shall include complete data on the pole material, finish,
handholes, anchoring, dimensions, structural loading data, and fixture attachment
details.
Bay Bridge Pump Station Replacement LIGHTING
Project No. 5-67
FDS 16500-3
4. Ballast catalog data shall include lamp wattage, ballast efficiency factor (BEF),
input watts, sound rating, power factor, and type of ballast. Data for outdoor ballast
shall include low-temperature starting characteristics.
5. Photocell submittal shall include voltage and wattage ratings, ambient light level
switching control means, and enclosure rating.
6. Lighting Control Panel submittal shall include detail lighting contactor schedule and
wiring diagram. The lighting contactor schedule shall include, but not be limited to, all
lighting contactors, along with associated lighting circuit number, and load description.
7. Provide lighting calculation based on selected and submitted lighting fixtures.
Photometric data, including zonal lumen data, average and minimum ratio, aiming
diagram, and computerized candlepower distribution data shall accompany shop
drawings.
1.6 QUALITY ASSURANCE
A. General:
1. Comply with the requirements specified herein and the applicable reference
Specifications of the General Requirements, and the Additional General
Requirements.
2. Exterior lighting system operation shall be demonstrated during the hours of
darkness to indicate that fixtures are properly focused and aimed, photocell operation
is correct, and that fixture switching functions as intended. Similar requirements shall
apply to interior lighting. The CONTRACTOR shall also demonstrate that the light
fixtures are properly circuited and the panel schedules and the panel directories are
correctly documented.
3. Lighting system functionality test shall occur within 2 weeks prior to start of
Reliability Acceptance Tests (RAT).
4. Fixture Appearance
a. Fixture lenses, diffusers, and reflectors shall be cleaned just prior to system
demonstrations.
b. Fixture trim, including poles and support brackets, where finish has been
damaged, shall be refinished or replaced.
1.7 SITE CONDITIONS
A. Seismic requirements shall be in accordance with Section 01332, Seismic Design
Criteria and this Specification section.
PART 2 - PRODUCTS
2.1 LIGHTING SYSTEMS GENERAL
A. Lighting system material shall be UL-listed or listed by an OSHA-recognized testing
agency acceptable to the ENGINEER.
LIGHTING Bay Bridge Pump Station Replacement
Project No. 5-67
16500-4 FDS
B. Lighting systems for occupied building spaces shall conform to the latest edition of
IESNA requirements.
2.2 FIXTURES
A. General: Provide fixtures as shown in fixture schedule, with proper hangers, pendants,
canopies, lamps, etc., necessary for complete installation. Provide fixtures having "feed
thru" or separate junction boxes. Provide two lamp ballasts wherever possible. Provide
fixtures with wire leads not smaller than 18 AWG and with all electrical components easily
accessible and replaceable without removing the fixture from the ceiling.
B. Special Requirements:
1. Fixtures shall be rated for the locations where they are installed. Refer to
Specification section 16010, Electrical General Provisions and the Drawings for area
designation. Fixtures installed in wet and corrosive locations shall have a removable
prewired driver.
2. Where designated for emergency lighting service provide fixtures containing
integral battery module, charger, and control module to illuminate one-half of the lamps
in the fixture to a value of approximately 40 percent output for 90 minutes in case of
power failure. Furnish unit that automatically recharges the battery on return of normal
line voltage.
3. For exterior fixtures with photocells, provide the fixture manufacturer's standard
design. Adjust photocells to switch light ON at dusk and OFF at dawn. All exterior light
fixtures shall be full-cutoff.
4. Provide pendant type fixtures with a safety cable attached to the structure and the
fixture at each support capable of supporting four times the vertical load.
2.3 REFLECTORS
A. Reflectors and reflecting cones or baffles shall be as follows:
1. Free of any tooling marks, indentations caused by riveting or other assembly
techniques.
2. No rivets, springs, or other hardware visible after installation.
3. First quality polished, buffed, and anodized finish.
4. Low iridescence for fluorescent sources.
5. Finish color as indicated in the Contract Documents.
6. All reflectors and baffles of modified elliptical contour, with no apparent brightness
from above 40 degrees above the nadir, with no lamp image or any part of the lamp
visible from above 40 degrees above the nadir.
7. Cone flange formed as an integral part of the cone and with identical color and
finish, unless specified otherwise. Width of the flange covers all ceiling opening without
light leaks or hardware visible.
Bay Bridge Pump Station Replacement LIGHTING
Project No. 5-67
FDS 16500-5
2.4 LENSES
A. All lenses shall be secured by positive means with neoprene or silicone gasket or
washers, as required to hold the lens tight within a frame or attaching to the housing.
1. All glass lenses shall be heat treated (tempered) or sealed with a clear acrylic
laminate layer to provide a "safety glass" rating. All lenses which require removal for
relamping or normal maintenance shall be attached to the fixture housing by a minimal
length of safety chain to prohibit the lens from falling and striking surrounding surfaces.
Glass edges exposed during the relamping process shall be gasketed to prevent
chipping or cracking.
2. Acrylic lenses shall be 100 percent virgin acrylic polymer, colorless.
2.5 LOUVERS (NOT USED)
2.6 FIXTURE MANUFACTURERS
A. Fixture manufacturers shall be as called out in the fixture schedule shown on the
Drawings, or equal.
2.7 LAMPS (NOT USED)
2.8 BALLASTS (NOT USED)
2.9 LIGHTING CONTROL
A. General: Provide lighting control system as indicated in the Contract Documents.
B. Lighting Controllers shall be of the non-combination lighting contactor type similar to
combination motor starters without overload relays. Circuit breakers shall be of the molded
case, thermal-magnetic type.
1. Provide a detailed lighting contactor schedule and wiring diagram. The lighting
contactor schedule shall include, but not be limited to, all lighting contactors, along with
associated lighting circuit number, and load description.
C. Time Switch: Provide a time switch as shown on Contract Drawings with a plain 4-
hour dial.
D. Photocells:
1. Outdoor lighting shall be controlled by a photoelectric cell in accordance with the
Contract Documents. The photocell shall be rated 120 V, 2000 W, 3-wire service,
single-pole, single-throw (SPST).
2. The photocell shall be completely self-contained in NEMA 4 housing, ON at dusk
and OFF at dawn; time delay feature to prevent false switching; and field adjustable to
control operating levels. Photocell shall be Tork Model No. 2101, or equal.
E. Dimming System: (NOT USED)
F. Motion Sensors: (NOT USED)
LIGHTING Bay Bridge Pump Station Replacement
Project No. 5-67
16500-6 FDS
2.10 LIGHTING FIXTURE SCHEDULE: SEE DRAWINGS
2.11 EMERGENCY LIGHTING
A. Emergency lighting units shall be as specified on the fixture schedule. The two lighting
heads shall consist of sealed beam lamps. The unit shall be able to accommodate
additional remotely located fixtures when specified in the Contract Documents. Batteries
shall be the sealed nickel cadmium, maintenance-free type rated for a minimum of 90
minutes. An integral battery charger shall automatically provide a high-rate charge
immediately upon restoration of normal power to the unit. When float voltage is reached,
the charge level shall be maintained continuously. Time delay shall be provided to maintain
emergency lighting for 15 minutes after normal power restoration. The fixtures shall be
UL-listed, and shall be in accordance with UL 924.
B. Test Push Button: The emergency lighting units shall have push-to-test button as part
of the unit to simulate loss of power and demonstrates unit operability.
C. Integral Self-Test: Factory- installed electronic device automatically initiates code-
required test of unit emergency operation at required intervals. Test failure is annunciated
by an integral audible alarm and a flashing red LED.
2.12 EXIT SIGNS
A. Exit signs shall be red, light-emitting diode (LED) type. LEDs shall be provided to
illuminate letters from within the exit sign. They shall be designed to remain illuminated
upon failure of the normal power supply via an internal nickel cadmium battery. An integral
battery charger shall automatically provide a high-rate charge immediately upon restoration
of normal power to the unit. When float voltage is reached, the charge level shall be
maintained continuously. The number of faces, arrow signage, and enclosure type shall be
as shown on the Drawings. The exit signs shall be Chloride Systems, Dual-Lite, Lithonia
Lighting, or equal.
B. Test Push Button: The exit sign shall have push-to-test button as part of the unit to
simulate loss of power and demonstrates unit operability.
C. Integral Self-Test: Factory- installed electronic device automatically initiates code-
required test of unit emergency operation at required intervals. Test failure is annunciated
by an integral audible alarm and a flashing red LED.
2.13 LED LUMINAIRES AND DRIVERS
A. All Luminaires
1. Comply with IES LM-79-08 Approved Method for measuring lumen maintenance
of LED light sources.
2. Comply with IES LM-80-08 Approved Method for electrical and photometric
measurement of SSL product.
3. Luminaire shall be mercury and lead free, and (RoHS) compliant.
4. LED arrays shall be sealed, high performance, long life type; minimum 70% rated
output at 50,000 hours.
Bay Bridge Pump Station Replacement LIGHTING
Project No. 5-67
FDS 16500-7
5. Drivers shall be solid state and accept 120 through 277VAC at 60Hz input.
6. LED light source shall be fully dimmable with the use of compatible dimmers switch
designated for low voltage loads.
7. Luminaire shall have a maximum Total Harmonic Distortion (THD) of 20% at full
power and across specified voltage range.
8. Luminaire shall operate normally for input voltage fluctuation of plus or minus 10
percent.
9. Luminaires shall be accessible from below ceiling plane for all maintenance work.
10. Luminaire Color Rendering Index (CRI) shall be a minimum CRI of 85 for interior
luminaires and 70 for exterior luminaires.
11. LED driver shall have a minimum power factor (pf) of 0.9 and a maximum crest
factor (cf) of 1.5 at full power and across specified voltage range.
12. LED driver shall be compatible with dimming controls where dimming is indicated
on the contract documents.
13. Wiring connection to LED drivers shall utilize polarized quick-disconnects for field
maintenance.
14. The LED luminaire shall carry a limited 5-year warranty minimum for LED light
engine(s)/board array, and driver(s).
15. Provide all of the following data on the submittals:
a. Delivered lumens
b. Input watts
c. Efficacy
d. Color Rendering Index
16. Luminaire manufacturers shall adhere to device manufacturer guidelines,
certification programs, and test procedures for thermal management.
2.14 HARDWARE
A. Hardware for fixtures located outdoors, in wet and corrosive areas shall be Type 316
stainless steel. Lighting pole hardware including nuts, bolts and washers for anchoring
shall be Type 316 stainless steel.
PART 3 - EXECUTION
3.1 FIXTURES
A. General
LIGHTING Bay Bridge Pump Station Replacement
Project No. 5-67
16500-8 FDS
1. Install each fixture as recommended by the fixture manufacturer, per National
Electrical Code and California Electrical Code requirements and as shown on the
Drawings.
2. Install fixtures plumb, level, straight, and true with reference to adjacent walls.
3. Where fixtures height is indicated on the Drawings, the height shall be as
measured from the bottom of the fixture to finished floor or finished grade, whichever
is applicable.
4. After construction of total Project is completed, clean fixtures and lenses. Replace
all lamps used for lighting during construction.
5. Circuit directories in panelboard door pockets shall be typewritten to identify all
circuits.
6. All flood and spotlights shall be aimed as shown on the Drawings.
7. Install all recessed fixtures tight with the finished surface so that no spill light shall
show between the ceilings and the sealing rings, and furnish plaster frames when
required by ceiling construction.
8. Provide each fluorescent recessed fixture with two safety chains or two 12 AWG
soft-annealed galvanized steel wire of length needed to secure fixture to building
structure independent of ceiling structure. Tensile strength of chain or wires and
fastening to structure shall be adequate to support weight of fixture. Fasten a chain or
wires to each end of fixture.
9. Coordinate fixture locations with other utility systems (e.g., Plumbing, HVAC).
Relocate fixtures to avoid conflict with these other systems and to avoid blockage of
fixture light output. Obtain ENGINEER’s acceptance on the new locations.
10. Provide lighting calculation based on selected and submitted lighting fixtures.
Photometric data, including zonal lumen data, average and minimum ratio, aiming
diagram, and computerized candlepower distribution data shall accompany shop
drawings.
3.2 BALLASTS (NOT USED)
3.3 LIGHTING CONTROL
A. Install lighting control as shown on Drawings.
B. Provide ballasts compatible with the dimming system.
3.4 FIXTURE MOUNTING
A. Surface-mounted and flush-mounted fixtures shall be solidly connected to a junction
box.
* * * * * *
Equipment Data and Catalog Cuts
Electrical
VFD
MCC
Switchboard
480/120 V Transformer
SCE Requirements
Overvoltage Protection
High Resistance Grounding – Low Voltage
Cam Locks and Cabinet
Automatic Transfer Switch
Reduced Voltage Soft Starters (RVSS)
Lighting Fixtures
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice.
EMS LED
Page 1 of 6
Catalog Number
Notes Type
Capable Luminaire
This item is an A+ capable luminaire, which has been designed and
tested to provide consistent color appearance and out-of-the-box control
compatibility with simple commissioning.
• All configurations of this luminaire meet the Acuity Brands’
specification for chromatic consistency
• This luminaire is part of an A+ Certified solution for nLight® or
XPoint™ Wireless control networks marked by a shaded background*
To learn more about A+, visit www.acuitybrands.com/aplus.
*See ordering tree for details
FEATURES & SPECIFICATIONS
INTENDED USE — A general purpose and energy-efficient surface-mounted or suspended LED
fixture, suitable for wet, damp and/or cold locations. For vapor-tight demanding environments where
moisture or dust is a concern and where relatively low fixture mounting heights and wide fixture
spacing are common. Typical applications include industrial facilities, parking garages, retail malls,
multi-purpose rooms, garden centers, and food processing. Certain airborne contaminants can
diminish the integrity of acrylic and/or polycarbonate. Click here for Acrylic-Polycarbon-
ate Compatibility table for suitable use.
Certain airborne contaminants may adversely affect the functioning of LEDs and other
electronic components, depending on various factors such as concentrations of the
contaminants, ventilation, and temperature at the end-user location. Click here for a
list of substances that may not be suitable for interaction with LEDs and other electronic
components.
CONSTRUCTION — One-piece 5VA fiberglass housing with integral perimeter channel utilizing
continuous poured-in-place NEMA 4X gasket. Approved as a wireway and for through wiring. Captive
polymeric latches are standard. Stainless steel latches (#316) available as an option for food process-
ing or more demanding applications.
Power connection is easily accomplished through pre-drilled holes. Fixture easily mounts to ceilings
and other solid structures, or can be suspended with chain, cable or rod using stainless steel mount-
ing brackets (included).
OPTICS — Injection molded, acrylic lens (.080” thick) provides high impact-resistance comparable
to 100% DR. A UV stabilized polycarbonate diffuser is available (.080" thick) in clear or frosted for
additional impact strength where vandal protection is desired.
Expected service life of 60,000 hours at 80% lumen maintenance (L80); predicted life of more than
100,000 hours.
ELECTRICAL — Utilizes high-efficiency LEDs mounted to core circuit boards. High-efficiency drivers
operate 120-277 (MVOLT) and 347-480 (HVOLT) offered with 0-10 volt dimming. Standard Luminaire
Surge Protection Level: 6kV/3kA Surge Rated per ANSI C82.77-5-2015.
INSTALLATION — Fixture can be surface or suspended mounted. Pre-punched stainless steel
mounting brackets are included (two per luminaire) for easy field-attachment of bolts, screws and
other mounting hardware. A covered ceiling is not required to maintain wet location listing or IP
rating.
LISTINGS — CSA Certified to UL and C-UL Standards. Suitable for wet location. Covered ceiling not
required to maintain wet location listing or IP ratings. IP65,IP66, IP67 rated and certified to meet
NSF Splash Zone 2. NEMA 4X rated. Sensors maintain IP65 and IP66 only. See chart on page 5 for
Ambient Temperatures.
DesignLights Consortium® (DLC) Premium qualified product and DLC qualified product. Not all ver-
sions of this product may be DLC Premium qualified or DLC qualified. Please check the DLC Qualified
Products List at www.designlights.org/QPL to confirm which versions are qualified.
WARRANTY — 5-year limited warranty. Complete warranty terms located at:
www.acuitybrands.com/support/customer-support/terms-and-conditions
NOTE: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.
Low-Profile Enclosed and Gasketed Industrial
EMS LED
SURFACE/ SUSPENDED MOUNT
Deep Lens
Low profile with sensor
Low profile
AA1, A2, A1/EM, A2/EM
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice.
EMS LED
Page 2 of 6
EMS LED
Low-Profile Enclosed and Gasketed
ORDERING INFORMATION Lead times will vary depending on options selected. Consult with your sales representative.Example: EMS L48 4000LM IMAFL WD MVOLT GZ10 40K 80CRI
Series Length Nominal Lumens Diffuser Distribution Voltage Driver Color temperature CRI
EMS L24 24" ‡
L48 48" ‡
L96 96" ‡
2000LM 2,000 lumens
3000LM 3,000 lumens
4000LM 4,000 lumens
6000LM 6,000 lumens
3000LM 3,000 lumens
4000LM 4,000 lumens
6000LM 6,000 lumens
8000LM 8,000 lumens
10000LM 10,000 lumens
12000LM 12,000 lumens
9000LM 9,000 lumens
12000LM 12,000 lumens
15000LM 15,000 lumens
18000LM 18,000 lumens
20000LM 20,000 lumens
24000LM 24,000 lumens
IMAFL Acrylic, lineal ribbed frosted lens
IMACD Acrylic, clear deep lens
IMAFD Acrylic, deep frosted lens
LPAFL Acrylic, low profile frosted lens
LPACL Acrylic, low profile clear lens
LPPCL Polycarbonate, low profile clear lens
LPPFL Polycarbonate, low profile frosted lens
MD Medium
WD Wide
PGD Parking garage
MVOLT MVOLT
HVOLT 347-480 ‡
120 120V
277 277V
347 347V
480 480V
GZ10 0 - 10V dimming 30K 3000K
35K 3500K
40K 4000K
50K 5000K
80CRI 80 CRI
90CRI 90 CRI
Options
E10WMCP EM Self-diagnostics battery pack, MVOLT, 10W, Constant Power Certified in the California Title 20 Modernized Appliance Efficiency Database (MAEDBS) ‡
BE6WCP Cold Weather EM battery pack, 120/277V, 6W, Constant Power Certified in the California Title 20 Modernized Appliance Efficiency Database (MAEDBS) ‡
BGTD Generator transfer device
SPD Surge protection device, additional 10kV/6kA
WLF Wet location fitting (two outboard, top(L24 - 20 inches off-center, L48 - 48 inches off-center, L96 95.7 inches off-center))
WLFEND Wet location fitting (one end)
WLFEND2 Wet location fitting (both ends) ‡
WLFPMP Wet location pendant monopoint ‡
ANGBKT Angle bracket shipped with fixture
CPSB16YWLBH 6' Brad Harrison 16/3 cord and straight blade plug set ‡
CPSB16YWL12FTBH 12' Brad Harrison 16/3 cord and straight blade plug set ‡
CRSB16YWLBH Brad Harrison receptacle ‡
CNP16WWL 6' white cord, 16/3, no plug, wet location
CNP16WWL12FT 12' white cord, 16/3, no plug, wet location
CNP164CWWL 6' white cord, 16/4, no plug, wet location (for use when unswitched circuit is required with battery pack)
TRS Tamper Resistant Torx® T10 screws
DPMB Dual pendant mounting bracket
STSL Stainless steel latches
Individual Controls:
SBOR10 Low mount 360° integral motion sensor, wet location, On/Off operation
SBOR10 HL 3V Low mount 360° integral motion sensor, wet location, High/Low operation (bi-level)
SBOR10 P Low mount 360° integral motion sensor, wet location, On/Off operation for motion sensing, override Off due to daylight
Xpoint Wireless:
XPA SBOR10 Xpoint wireless integral motion sensor, On/Off operation for motion sensing, override Off due to daylight ‡
XAD XPoint™ wireless controller, 0-10V dimming ‡
nLight Air:
NLTAIR2 RSBOR10 nLight AIR generation 2 enabled 306 low mount motion sensor
NLTAIR2 RIO nLight (wireless) gen 2 dimming & switching module
NOTE: ‡ indicates option chosen has ordering restrictions. Please reference ordering restrictions chart, page 3. Options are sorted alphanumerically.
A+ Capable options indicated
by this color background.
See Accessories and ordering restrictions on next page.
ELE/GEN ROOM -
ODOR CONTROL -
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice.
EMS LED
Page 3 of 6
EMS LED
Low-Profile Enclosed and Gasketed
‡ Option Value Ordering Restrictions
Option value Restriction
L24 Not available with BE6WCP.
L48 Not available with WLFPMP.
L96 Not available with WLFPMP
HVOLT When ordered with L24 available with 6000LM only. When ordered with L48 not avaialble with 3000LM or 4000LM. Not available with XAD or XPA SBOR10.
BE6WCP Not available with L24 length.
Order with CNP164CWWL when unswitched hot is required for battery.
E10WMCP Order with CNP164CWWL when unswitched hot is required for battery.
WLFEND Available with cord or sensor option. Choose only one.
WLFEND2 Not available with sensor or cord options.
WLFPMP Available only with L24.
CNP16WWL Not available with BE6WCP or E10WMCP.
CNP16WWL12FT Not available with BE6WCP or E10WMCP.
CPSB16YWLBH Not available with BE6WCP or E10WMCP.
CPSB16YWL12FTBH Not available with BE6WCP or E10WMCP.
CRSB16YWLBH Not available with BE6WCP or E10WMCP.
XPA SBOR6 Not available with HVOLT.
XAD Not available with HVOLT.
Accessories: Order as separate catalog number.
MHCH 36 Jack chain 36" (pair)
MHHK120 10' single leg air craft cable (ships as pair)
MHHK120SS 10' single leg air craft cable, stainless steel (ships as pair)
RK1 T10BIT W/PIN U Hex-base driver bit, Torx TX10, for tamper resistant screws with center reject pin
FEMDPMB Dual pendant mounting bracket (ships as a pair)
FEMANGBKT Angle bracket (ships as pair)
FEMSMB Surface mount bracket (ships as pair)
MOUNTING OPTIONS
FEMSMB
(304 stainless steel)
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice.
EMS LED
Page 4 of 6
EMS LED
Low-Profile Enclosed and Gasketed
OPERATIONAL DATA (80 CRI*, MD**, MVOLT***)
Length Package Input Wattage CCT Frosted Lens' Lumens (LPW)Clear Lens' Lumens (LPW)
IMAFL IMAFD LPAFL LPPFL IMACD LPACL LPPCL
L24
2000LM 13.4
30K 1962 (147)2083 (156)2076 (155)1861 (139)2112 (158)2105 (158)1890 (142)
35K 2002 (150)2126 (159)2118 (159)1899 (142)2155 (161)2147 (161)1929 (144)
40K 2099 (157)2228 (167)2220 (166)1991 (149)2259 (169)2251 (169)2022 (151)
50K 2122 (159)2252 (169)2244 (168)2013 (151)2284 (171)2276 (170)2044 (153)
3000LM 19.9
30K 2869 (144)3046 (153)3035 (153)2721 (137)3088 (155)3077 (155)2764 (139)
35K 2927 (147)3108 (156)3096 (156)2777 (140)3151 (158)3139 (158)2820 (142)
40K 3069 (154)3258 (164)3246 (163)2911 (146)3303 (166)3291 (166)2956 (149)
50K 3102 (156)3293 (166)3281 (165)2942 (148)3339 (168)3327 (167)2988 (150)
4000LM 26.0
30K 3676 (142)3903 (150)3889 (150)3487 (134)3957 (152)3943 (152)3541 (136)
35K 3751 (145)3982 (153)3968 (153)3558 (137)4037 (156)4023 (155)3613 (139)
40K 3932 (152)4174 (161)4159 (160)3730 (144)4232 (163)4217 (162)3788 (146)
50K 3975 (153)4219 (163)4204 (162)3770 (145)4278 (165)4263 (164)3829 (148)
6000LM 39.2
30K 5287 (135)5613 (143)5593 (143)5015 (128)5691 (145)5671 (145)5093 (130)
35K 5395 (138)5727 (146)5707 (145)5117 (130)5806 (148)5786 (147)5196 (132)
40K 5655 (144)6004 (153)5982 (153)5364 (137)6087 (155)6065 (155)5447 (139)
50K 5717 (146)6069 (155)6047 (154)5422 (138)6153 (157)6131 (156)5506 (140)
L48
3000LM 18.0
30K 2689 (149)2855 (158)2844 (158)2551 (141)2894 (160)2884 (160)2590 (144)
35K 2743 (152)2912 (161)2902 (161)2602 (144)2953 (164)2942 (163)2643 (146)
40K 2876 (159)3053 (169)3042 (169)2728 (151)3095 (172)3084 (171)2770 (154)
50K 2907 (161)3086 (171)3075 (170)2758 (153)3129 (173)3118 (173)2800 (155)
4000LM 23.8
30K 3543 (149)3762 (158)3748 (157)3361 (141)3814 (160)3800 (160)3413 (143)
35K 3615 (152)3838 (161)3824 (161)3429 (144)3891 (163)3877 (163)3482 (146)
40K 3790 (159)4023 (169)4009 (168)3595 (151)4079 (171)4064 (171)3650 (153)
50K 3831 (161)4067 (171)4052 (170)3634 (153)4123 (173)4109 (173)3690 (155)
6000LM 37.8
30K 5284 (140)5609 (149)5589 (148)5012 (133)5687 (151)5667 (150)5090 (135)
35K 5391 (143)5723 (152)5703 (151)5114 (135)5802 (154)5782 (153)5193 (138)
40K 5651 (150)6000 (159)5978 (158)5361 (142)6083 (161)6061 (161)5444 (144)
50K 5713 (151)6065 (161)6043 (160)5419 (144)6149 (163)6127 (162)5503 (146)
8000LM 50.5
30K 6952 (138)7380 (146)7354 (146)6594 (131)7482 (148)7456 (148)6696 (133)
35K 7093 (141)7530 (149)7503 (149)6728 (133)7634 (151)7607 (151)6832 (135)
40K 7435 (147)7894 (156)7865 (156)7053 (140)8003 (159)7975 (158)7162 (142)
50K 7516 (149)7979 (158)7950 (158)7129 (141)8090 (160)8061 (160)7240 (144)
10000LM 62.0
30K 8646 (140)9179 (148)9146 (148)8201 (132)9306 (150)9273 (150)8328 (134)
35K 8822 (142)9365 (151)9332 (151)8368 (135)9495 (153)9461 (153)8497 (137)
40K 9248 (149)9817 (158)9782 (158)8772 (142)9953 (161)9918 (160)8908 (144)
50K 9348 (151)9924 (160)9888 (160)8867 (143)10061 (162)10026 (162)9004 (145)
12000LM 75.0
30K 10406 (139)11047 (147)11007 (147)9871 (132)11200 (149)11160 (149)10024 (134)
35K 10617 (141)11271 (150)11231 (150)10071 (134)11427 (152)11387 (152)10227 (136)
40K 11130 (148)11816 (157)11773 (157)10557 (141)11979 (160)11937 (159)10721 (143)
50K 11251 (150)11944 (159)11901 (159)10672 (142)12109 (161)12066 (161)10837 (144)
L96
9000LM 53.4
30K 7962 (149)8452 (158)8422 (158)7552 (141)8570 (160)8539 (160)7669 (144)
35K 8124 (152)8624 (161)8593 (161)7706 (144)8743 (164)8713 (163)7825 (146)
40K 8516 (159)9040 (169)9008 (169)8078 (151)9166 (172)9133 (171)8203 (154)
50K 8608 (161)9138 (171)9106 (170)8165 (153)9265 (173)9232 (173)8292 (155)
12000LM 75.5
30K 10570 (140)11221 (149)11181 (148)10026 (133)11377 (151)11337 (150)10182 (135)
35K 10785 (143)11449 (152)11408 (151)10230 (135)11608 (154)11567 (153)10388 (138)
40K 11306 (150)12002 (159)11959 (158)10724 (142)12168 (161)12125 (161)10890 (144)
50K 11428 (151)12132 (161)12089 (160)10840 (144)12300 (163)12257 (162)11008 (146)
15000LM 94.3
30K 13399 (142)14225 (151)14174 (150)12710 (135)14422 (153)14371 (152)12907 (137)
35K 13671 (145)14513 (154)14461 (153)12968 (138)14714 (156)14662 (156)13169 (140)
40K 14331 (152)15214 (161)15160 (161)13594 (144)15425 (164)15370 (163)13805 (146)
50K 14487 (154)15379 (163)15324 (163)13741 (146)15592 (165)15537 (165)13954 (148)
18000LM 103.4
30K 15901 (154)16881 (163)16820 (163)15083 (146)17114 (165)17054 (165)15317 (148)
35K 16224 (157)17223 (167)17161 (166)15389 (149)17462 (169)17400 (168)15627 (151)
40K 17007 (164)18055 (175)17990 (174)16132 (156)18305 (177)18240 (176)16382 (158)
50K 17192 (166)18251 (176)18185 (176)16307 (158)18503 (179)18438 (178)16560 (160)
20000LM 125.5
30K 17549 (140)18630 (148)18564 (148)16646 (133)18888 (150)18822 (150)16904 (135)
35K 17906 (143)19008 (151)18940 (151)16984 (135)19272 (154)19204 (153)17247 (137)
40K 18770 (150)19927 (159)19855 (158)17804 (142)20202 (161)20131 (160)18080 (144)
50K 18974 (151)20143 (160)20070 (160)17997 (143)20421 (163)20349 (162)18276 (146)
24000LM 149.5
30K 21142 (141)22445 (150)22364 (150)20055 (134)22756 (152)22675 (152)20365 (136)
35K 21571 (144)22900 (153)22818 (153)20461 (137)23217 (155)23135 (155)20779 (139)
40K 22613 (151)24006 (161)23920 (160)21450 (143)24339 (163)24253 (162)21782 (146)
50K 22858 (153)24266 (162)24179 (162)21682 (145)24602 (165)24516 (164)22018 (147)
* For 90CRI, reduce lumen output by 17.1%** For WD reduce output by 4.7%, PGD reduce output by 5.4%*** For HVOLT use scale factor in HVOLT SCALE FACTOR TABLE
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice.
EMS LED
Page 5 of 6
EMS LED
Low-Profile Enclosed and Gasketed
CSA LISTED AMBIENT RATING*
HVOLT SCALE FACTOR
CONFIGURATION WEIGHTS
Standard**
(surface)"
Standard**
(suspended)"
E10WMCP
(surface)
E10WMCP
(suspended)
BE6WCP
(surface)
BE6WCP
(suspended)
XAD
(surface)
XAD
(suspended)
L24
2000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
3000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
4000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
6000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
L48
3000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
4000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
6000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
8000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
10000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
12000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
L96
9000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
12000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
15000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
18000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
20000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
24000LM 35°C 50°C 5°C - 25°C 5°C - 35°C -20°C - 25°C -20°C - 35°C 30°C 45°C
Factor
2000LM 0.814
3000LM 0.814
4000LM 0.814
6000LM 0.835
8000LM 0.845
9000LM 0.850
10000LM 0.850
12000LM 0.845
15000LM 0.860
18000LM 0.880
20000LM 0.845
24000LM 0.865
Standard w/ Sensor w/ Battery
L24 8 9 9
L48 11 12 12
L96 23 24 24
*Minimum Ambient is -30°C unless noted, **All options not specifically listed in this table are considered standard
NUMBER OF BOARDS AND DRIVERS
Lumen
package
Fixture
length
Number of
boards
Number of
drivers
2000LM
L24
1 1
3000LM 1 1
4000LM 1 1
6000LM 1 1
3000LM
L48
2 1
4000LM 2 1
6000LM 2 1
8000LM 2 1
10000LM 2 1
12000LM 2 1
9000LM
L96
4 1
12000LM 4 2
15000LM 4 2
18000LM 4 2
20000LM 4 2
24000LM 4 2
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2016-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/05/20 Specifications subject to change without notice.
EMS LED
Page 6 of 6
EMS LED
Low-Profile Enclosed and Gasketed
PHOTOMETRICS
See www.holophane.com for photometry reports.
51-3/4(131.4)
100-1/4(254.6)
DIMENSIONS
Specifications subject to change without notice.
All dimensions are inches (centimeters) unless otherwise indicated.
[10.6]4.2 [11.1]4.4 [14.5]5.7
[17.2]6.8 [17.2]6.8 [17.2]6.8
Diffuser Type:
LPAFL
LPACL
LPPFL
LPPCL
Weight (may vary with options or accessories)
EMS L48: 11.9 lbs (5.397kg)
EMS L96: 24.3 lbs (11.022kg)
Diffuser Type:
IMAFL
Diffuser Type:
IMAFD
IMACD
2734"
(703.26)
Description
IP66. Class I. IK08. Marine-grade, die-cast aluminum alloy. 5CE superior
corrosion protection including PCS hardware. Silicone CCG® Controlled
Compression Gasket. CAD-optimized optics for superior illumination and glare
control. Integral driver. Advanced thermal management protects LEDs while
optimizing lumens output. 0-10V Dimming comes standard with luminaire.
Luminaire is factory-sealed and does not need to be opened during
installation. Luminaire can be mounted for up or down lighting. Specify
product with 7 Digit product code – Finish Color. Accessories, such as
mounting, optical, and electrical, must be specified separately. Example: XXX-
XXXX-9004 (Black) + XXX-XXXX (Accessory 1)
PLS420 LED
Surface Mounted Wall Luminaires
1/7
WE-EF LIGHTING USA LLC
Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42
Technical modifications and errors excepted
TYPE B
Material Specification
Body:Marine-grade, die-cast aluminium alloy
Lens:Safety glass lens
Colours: RAL9004 Black
RAL9007 Grey Metallic
RAL9016 White
RAL8019 Dark Bronze
Quick Ship Quickship features a one week ship time for Steplights and two week ship time for the
rest of our Core products. All applicable information must be included for orders to be
processed and colors must be in one of our 4 standard finishes. A maximum order
quantity of 30 pieces applies.
Gasket:Silicone CCG® Controlled Compression Gasket
Fasteners:PCS hardware
Ingress protection:IP66
Impact protection:IK08
Corrosion protection:5CE
Listings:ETL listed. Suitable for wet locations.
Specifications
Electrical Specification
Power supply:Integral [ECG] electronic driver 120V-277V. 0-10V dimmable, to be specified with order.
Driver / Ballast:Integral EC electronic converter
Lifetime
Ta=25°/40° L90B10 > 90000h
PLS420 LED
Surface Mounted Wall Luminaires
2/7
WE-EF LIGHTING USA LLC
Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42
Technical modifications and errors excepted
Choices
Light Distributions Nominal Lumen Nominal Watt Colour Temperatures Colours
[S70] Type II Short
[A60] Type IV Very Short
[R65] Type IV Medium
symmetric, medium beam [M]
symmetric, narrow beam [N]
1398
1476
2220
2340
2700
2839
2993
3453
12
18
26
2700 K
3000 K
4000 K
RAL9004 Black
RAL9007 Grey Metallic
RAL9016 White
RAL8019 Dark Bronze
PLS420 LED
Surface Mounted Wall Luminaires
3/7
WE-EF LIGHTING USA LLC
Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42
Technical modifications and errors excepted
Configurations
Light Distributions Part ID Light Source Delivered Lumens Rated Input Power CRI Weight Link
131-9629 LED-6/12W / 700 mA - 2700 K 1122.5 15 80 9.30
131-9581 LED-6/12W / 700 mA - 3000 K 1185.1 15 80 9.30
131-9582 LED-6/12W / 700 mA - 4000 K 1185.1 15 80 9.30
131-9630 LED-6/18W / 1050 mA - 2700 K 1755.1 21 80 9.30
131-9583 LED-6/18W / 1050 mA - 3000 K 1850 21 80 9.30
131-9584 LED-6/18W / 1050 mA - 4000 K 2134.6 21 80 9.30
131-9631 LED-6/26W / 1400 mA - 2700K 2244.5 30 80 9.30
131-9585 LED-6/26W / 1400 mA - 3000 K 2366.2 30 80 9.30
131-9586 LED-6/26W / 1400 mA - 4000 K 2729.9 30 80 9.30
symmetric, medium beam [M]
131-9632 LED-6/12W / 700 mA - 2700 K 1055.6 15 80 9.30
131-9587 LED-6/12W / 700 mA - 3000 K 1114.5 15 80 9.30
131-9588 LED-6/12W / 700 mA - 4000 K 1114.5 15 80 9.30
131-9633 LED-6/18W / 1050 mA - 2700 K 1779.9 21 80 9.30
131-9589 LED-6/18W / 1050 mA - 3000 K 1876.1 21 80 9.30
131-9590 LED-6/18W / 1050 mA - 4000 K 2164.7 21 80 9.30
131-9634 LED-6/26W / 1400 mA - 2700K 2276.2 30 80 9.30
131-9591 LED-6/26W / 1400 mA - 3000 K 2399.7 30 80 9.30
131-9592 LED-6/26W / 1400 mA - 4000 K 2768.5 30 80 9.30
symmetric, narrow beam [N]
131-9620 LED-6/12W / 700 mA - 2700 K 835.5 15 80 9.30
131-9562 LED-6/12W / 700 mA - 3000 K 882.1 15 80 9.30
131-9564 LED-6/12W / 700 mA - 4000 K 882.1 15 80 9.30
131-9621 LED-6/18W / 1050 mA - 2700 K 1290.6 21 80 9.30
131-9565 LED-6/18W / 1050 mA - 3000 K 1360.4 21 80 9.30
131-9566 LED-6/18W / 1050 mA - 4000 K 1569.7 21 80 9.30
131-9622 LED-6/26W / 1400 mA - 2700K 1650.5 30 80 9.30
131-9567 LED-6/26W / 1400 mA - 3000 K 1740 30 80 9.30
131-9568 LED-6/26W / 1400 mA - 4000 K 2007.5 30 80 9.30
[S70] Type II Short
131-9626 LED-6/12W / 700 mA - 2700 K 811.4 15 80 9.30
131-9575 LED-6/12W / 700 mA - 3000 K 856.7 15 80 9.30
131-9576 LED-6/12W / 700 mA - 4000 K 856.7 15 80 9.30
131-9627 LED-6/18W / 1050 mA - 2700 K 1216.5 21 80 9.30
131-9577 LED-6/18W / 1050 mA - 3000 K 1282.3 21 80 9.30
131-9578 LED-6/18W / 1050 mA - 4000 K 1479.6 21 80 9.30
131-9628 LED-6/26W / 1400 mA - 2700K 1555.7 30 80 9.30
131-9579 LED-6/26W / 1400 mA - 3000 K 1640.1 30 80 9.30
131-9580 LED-6/26W / 1400 mA - 4000 K 1892.2 30 80 9.30
[A60] Type IV Very Short
131-9623 LED-6/12W / 700 mA - 2700 K 759.5 15 80 9.30
131-9569 LED-6/12W / 700 mA - 3000 K 801.9 15 80 9.30
131-9570 LED-6/12W / 700 mA - 4000 K 801.9 15 80 9.30
131-9624 LED-6/18W / 1050 mA - 2700 K 1183.1 21 80 9.30
131-9571 LED-6/18W / 1050 mA - 3000 K 1247 21 80 9.30
131-9572 LED-6/18W / 1050 mA - 4000 K 1438.9 21 80 9.30
[R65] Type IV Medium
PLS420 LED
Surface Mounted Wall Luminaires
4/7
WE-EF LIGHTING USA LLC
Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42
Technical modifications and errors excepted
Configurations
Light Distributions Part ID Light Source Delivered Lumens Rated Input Power CRI Weight Link
131-9625 LED-6/26W / 1400 mA - 2700K 1513 30 80 9.30
131-9573 LED-6/26W / 1400 mA - 3000 K 1595 30 80 9.30
131-9574 LED-6/26W / 1400 mA - 4000 K 1840.2 30 80 9.30
[R65] Type IV Medium
Related Families / PLS400
Family Dimensions Wattage Nominal Lumen Links
Links Download Data Sheet
PLS420 LED 10.43 x 8.86 12 -26 W 1398 -3453
PLS430 LED 13.78 x 8.86 24 -52 W 2796 -6907
PLS420 LED
Surface Mounted Wall Luminaires
5/7
WE-EF LIGHTING USA LLC
Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42
Technical modifications and errors excepted
Bird deterrent
131-9600 Bird deterrent BD
Mounting Accessories
Light shield
430-0029 LS180
430-0038 LS180-[A60]
Honeycomb louvre
C1 H1
131-9596 Honeycomb louvre IW 8.82 2.80
Optical Accessories
Electrical Accessories
PLS420 LED
Surface Mounted Wall Luminaires
6/7
WE-EF LIGHTING USA LLC
Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42
Technical modifications and errors excepted
Emergency Lighting Package
620-7400 _LS420/430 LED Emergency Lighting Package
Photocell
620-8001 PLS420 Button Photocell Kit
Control
PLS420 LED
Surface Mounted Wall Luminaires
7/7
WE-EF LIGHTING USA LLC
Spec Support Hotline: +1 724 278 3855 | 410-D Keystone Drive | Warrendale PA 15086 U.S.A. | Tel +1 724 742 0030 | info.usa@we-ef.com | www.we-ef.com | 16-06-2022 13:42
Technical modifications and errors excepted
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice.
HXPL
Page 1 of 4
HXPL Series
Hazardous Area Lighting Fixtures
Catalog Number
Notes Type
Dimensions: Inches (millimeters) unless otherwise noted.
See individual fixture dimensions and weight specifications on page 2.
• Paint Spray Booth
• Coal & Dust Storage
• Petroleum Refineries
• Ethanol Facilities
• Chemical Plants
• Waste Water & Water Treatment Plants
• Power Generation Plants
Typical Applications
Description• Versatile heavy-duty, explosion-proof LED fixture designed for hazardous environments where flammable gases or vapors, flammable liquids, combustible dust and/or ignitable fibers may exist.
• Suitable for wet locations and marine environments where saltwater spray is an issue.
• Also suitable for indoor and outdoor areas where corrosive chemicals exist.
• Certain airborne contaminants may adversely affect the functioning of LEDs and other electronic components, depending on various factors such as concentrations of the contaminants, ventilation, and temperature at the end-user location. Click here for a list of substances that may not be suitable for interaction with LEDs and other electronic components.
Optics• Explosion-proof, impact and heat resistant glass tubes, provide LED protection.• Optional wire guard and/or clear polycarbonate shield available for additional security.• Heavy gauge extruded aluminum reflectors (2.5 millimeters thick), with high gloss reflective finish. Resists dents and corrosion. Easy, quick removal for cleaning.• 84CRI is standard.
Electrical• 0-10 Volt driver.• Driver has 1.5kV surge protection, for additional surge protection against power line transient surges, installer will need to provide remote surge protection.
Mechanical• Factory sealed. • Fixture constructed of corrosion-resistant, copper-free aluminum alloy (less than 0.4% copper). • Over-sized, finned driver housing provides greater heat dissipation and extended driver life.• Maintenance can be done quickly from either end of the fixture. All access covers are screw type and interchangeable with O-ring seals. Easily accessible and externally mounted.
Listings• UL Listed to US and Canadian standards.• Suitable for use in Hazardous Locations. • Class I, Division 1, Groups C and D• Class I, Division 2, Groups C and D• Class II, Division 1, Groups E, F, and G• Class II, Division 2, Groups E, F, and G• Class III• Simultaneous presence• Zone Equivalency Markings (See chart on page 5)• -4°F (-20°C) to 131°F (55°C) (see chart on page 4)• Marine Rated.• NEMA 4X, 7CD & 9EFG Rated.• IP66 Rated.• Paint Spray Booth
Warranty5-year limited warranty on the fixture. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions
Note: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.
C
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice.
HXPL
Page 2 of 4
HXPL Series
Hazardous Area Lighting Fixtures
ORDERING INFORMATION Example: HXPL L24 2 3000LM AS DM 30K
Series Fixture Length Number of Tubes Lumens Voltage Dimming Color Temperature Options
HXPL L24 2 foot
L48 4 foot
2 2 tubes
3 3 tubes ‡
4 4 tubes
3L 3000 nominal lumens (2ft, 2 tube)
4L 4000 nominal lumens (2ft, 3 tube)
5L 5000 nominal lumens (4ft, 2 tube)
8L 8000 nominal lumens (4ft, 3 tube)
10L 10000 nominal lumens (4ft, 4 tube)
AS 120-277V, 50/60Hz
120 120V, 50/60Hz
208 208V, 50/60Hz
240 240V, 50/60Hz
277 277V, 50/60Hz
DM Dimmable (0-10V DC) ‡
NDM Non-Dimming Driver
30K 3000K
40K 4000K
50K 5000K
EM10WCP EM battery backup, 10W, Certified in CA Title 20 MAEDBS ‡
EMO Emergency operation only ‡
DS Outboard option
IF In-line Fusing ‡
Accessories: Order as separate catalog number.
HXPL22TSSG Stainless steel guards (L24 2 3L only)
HXPL42TSSG Stainless steel guards (L48 2 5L only)
HXPL43TSSG Stainless steel guards (L48 3 8L only)
HXPL44TSSG Stainless steel guards (L48 4 10L only)‡
HXPL23TPS Polycarb shield (L24 3 4L only)
HXPL22TPS Polycarb shield (L24 2 3L only)
HXPL42TPS Polycarb shield (L48 2 5L only)
HXPL43TPS Polycarb shield (L48 3 8L only) ‡
HXPL44TPS Polycarb shield (L48 4 10L only) ‡
HXPLWCMK Wall/ceiling mounting kit ‡
HXPLSMK Shock mounting kit ‡
HXPLDMK Drop mounting kit ‡
HXPLBMK Beam mounting kit ‡
HXPLUMK Unistrut mounting kit ‡
‡ Option Value Ordering Restrictions & Notes
Option value Restriction
3 tubes The 3 tube option does not have an available accessory mounting kit available. See page 2 for drawing detailing the 3/4" NPT hubs used to mount the fixture.
DM Not available with EM10WCP or EMO.
EM10WCP Available with L48, 4 foot versions of the fixture only. Not available with DM option. Nameplate label on the fixture will show EM to indicate a battery is included.
EMO Available with the L24 2 3L (3000 lumen) version of the fixture only. Not available with DM option. Fixture operation: Under normal power conditions, battery will charge and fixture will be OFF. If Power is lost then battery will power the LEDs until the power is restored or a min of 90 minutes has elapsed.
HXPL44TSSG Will ship with a qty of 2 HXPL42TSSG guards.
HXPL44TPS Will ship with a qty of 2 HXPL42TPS guards.
HXPL43TPS 3 tube fixtures with polycarb shields require a qty of 1 HXPL43TSSG stainless steel guard.
HXPLWCMK, HXPLSMK, HXPLDMK, HXPLBMK Available with 2 tube fixtures only.
HXPLUMK Available with 4 tube fixtures only.
IF External Fusing. Not marine listed. Must specify voltage at time of order. Nameplate label on the fixture will show AS to indicate the voltage.
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice.
HXPL
Page 3 of 4
DIMENSIONAL DATA
HXPL Series
Hazardous Area Lighting Fixtures
Package A B C D E Boxed Weight
Two-tube, four-foot 53"48.5"6.5"7"11.5"65 lbs.
Two-tube, two-foot 29"24.5"6.5"7"11.5"40 lbs.
Package A B C D Boxed
Weight
Three-tube, four-foot 53"48.5"8.9"16.3"78 lbs.
Three-tube, two-foot 29"24.5"8.9"16.3"47 lbs.
2 tube fixture dimensions
3 tube fixture dimensions
4 tube fixture dimensions
Package A B C D E Boxed
Weight
Four-tube, four-foot 53"49.4"6.8"11.3"23.2"138 lbs.
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice.
HXPL
Page 4 of 4
HXPL Series
Hazardous Area Lighting Fixtures
OPERATIONAL DATA
Operating Characteristics
Package Ambient Rating
(120V - 277V)
Delivered Lumens
4000 K CCT @ 25C ‡Wattage @ 120V LPW @ 4000 K
HXPL L24 2 3L AS -4°F to 131°F
(-20°C to 55°C)2783 26.6 104.6
HXPL L24 3 4L AS -4°F to 131°F
(-20°C to 55°C)4110 36.75 111
HXPL L48 2 5L AS -4°F to 131°F
(-20°C to 55°C)5450 46.9 116.2
HXPL L48 3 8L AS -4°F to 131°F
(-20°C to 55°C)8220 73.5 111.8
HXPL L48 4 10L AS -4°F to 131°F
(-20°C to 55°C)10918 93.6 116.6
Operating Temperature Code for Hazardous Locations:
Package ‡Max Ambient
Range
Class I Division 1
Groups C, D
Class II Division 1,
Groups E, F, G, Class III
Simultaneous Presence
Class I & Class II
HXPL L24 2 3L 55°C T6 T4A T4A
HXPL L24 3 4L 55°C T6 T5 T5
HXPL L48 2 5L 55°C T6 T4A T4A
HXPL L48 3 8L 55°C T6 T5 T5
HXPL L48 4 10L 55°C T6 T4A T4A
Package ‡0 Hours 15,000
Hours
30,000
Hours
45,000
Hours
60,000
Hours
HXPL L48 4 10L AS @ 25°C 1.0 0.95 0.91 0.87 0.83
HXPL L48 4 10L AS @ 40°C 1.0 0.94 0.89 0.85 0.80
HXPL L48 4 10L AS @ 55°C 1.0 0.92 0.86 0.80 0.74
Projected Lumen Maintenance (TM-21)
‡ Notes
Delivered Lumens 4000 K CCT @ 25C Absolute photometry calculated in accordance with IESNA LM-79-08.
‡ Notes
Package Project lumen maintenance factors at max. ambient temperature per lumen package.
‡ Notes
Package Supply wire temperature is 75°C.
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE | www.holophane.com
© 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/06/22 Specifications subject to change without notice.
HXPL
Page 5 of 4
How to Estimate Delivered Lumens in Emergency Mode
Use the formula below to estimate the delivered lumens in emergency modeDelivered Lumens = P x LPW
P = Output power of emergency driver
LPW = Lumen per watt rating of the luminaire. (See charts on page 7)
The LPW rating is also available at Designlight Consortium
P = 10 watts for E10WCP
Emergency Lumen Output Example - 10 Watt Battery
Approximate Luminaire Efficacy
Approximate Lumens at 1 Minute
Approximate Lumens at 45 Minutes
Approximate Lumens at 90 Minutes
100 LPW 1000 1000 1000
110 LPW 1100 1100 1100
120 LPW 1200 1200 1200
130 LPW 1300 1300 1300
140 LPW 1400 1400 1400
150 LPW 1500 1500 1500
Emergency Lumen Output
HXPL Series
Hazardous Area Lighting Fixtures
Zone Equivalency Markings
NEC Protections
Area Protection Techniques Zone Equivalency Markings
Class I
Division 1 Intrinsic Safety CLASS I, DIV 1, GROUP D CLASS I, ZONE 1 GROUP IIA
Explosion Proof CLASS I, DIV 1, GROUP C CLASS I, ZONE 1 GROUP IIB
Division 2 Hermetically-sealed CLASS I, DIV 2, GROUP D CLASS I, ZONE 2 GROUP IIA
Nonincendive CLASS I, DIV 2, GROUP C CLASS I, ZONE 2 GROUP IIB
Class II
Division 1
Intrinsic Safety
CLASS II, DIV 1 GROUP E, F, OR G CLASS II ZONE 20 AND ZONE 21Dust-ignitionproof
Pressurized
Division 2
Dust tight
CLASS II, DIV 2, GROUP F OR G CLASS II, ZONE 22
Hermetically-sealed
Nonincendive
Pressurized
Any Class II, Division 1 technique
Class III
Division 1
Intrinsic Safety
N/A N/ADust tight
Hermetically-sealed
Division 2 Nonincendive N/A N/AAny Class III, Division 1 technique
1
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
The ELEMENT 3" Next Generation Fixed recessed downlight features a patented high/low lamp positioning
which allows the LED to be positioned closer to the aperture for maximum light output and efficiency or
higher in the ceiling to minimize glare and flash on the trim. LED options include premium Warm Dimming,
Tunable White, Xicato and Xicato Artist Series. Trim options include Flanged or Flangeless and Flangeless
in Wood Ceiling.
• Housing reduced by 60%
• Patented high/low lamp positioning
• 2-step standard
• Standard dimming down to 1%
• Trim reflector options
• Solite Soft Focus lens option
LUMEN MULTIPLIER (CRI/CCT)
CCT
80 CRI
MULTIPLIER
90 CRI
MULTIPLIER
2700K 0.95 0.80
3000K 1.00 0.85
3500K 1.05 0.90
Lumen output will vary by CCT and CRI.
See photometric charts for output information.
SPECIFICATIONS
STATIC WHITE XICATO WARM DIM TUNABLE WHITE
HIGH
OUTPUT
LOW
OUTPUT
STANDARD
SERIES
ARTIST
SERIES
HIGH
OUTPUT
LOW
OUTPUT
HIGH OUTPUT
(5000K)
HIGH OUTPUT
(4000K)
DELIVERED LUMENS 1800/1450 1319/1124 1129 945 1300 900 1272 1150
WATTS 17 12 15 15 17 12 18 18
EFFICACY 106/85 110/94 75 63 76 75 72 64
CRI 80+/90+80+95+90+90+
CBCP
10° - 19,414 | 18° - 5,848
25° - 5,416 | 40° - 3,230
60° - 2,305
21° - 3,184
43° - 2,733
60° - 1,014
18° - N/A | 25° - N/A | 40° - 1,622 | 60° - N/A
CCT 2700K, 3000K, or 3500K 2700K, 3000K, or 3500K3 3000K - 1800K 5000K - 2700K 4000K - 1800K
COLOR CONSISTENCY 2-step 1 X 2-step 3-step 2-step
VOLTAGE 120V or 277V
DIMMING1
Standard reverse-phase, forward-phase, TRIAC, and 0-10V dimming (down to 1%)
Lutron Hi-lume EcoSystem (down to 0.1%)
Lutron Hi-lume 2-Wire (down to 1%) | eldoLED 0-10V or Dali (down to 0.1%)
eldoLED 0-10V or Dali
(down to 0.1%)
POWER SUPPLY Constant current driver with +.9 power factor and +80% efficiency
OPTICS Field changeable:
10°, 18°, 25°, 40°, or 60° TIR
Field changeable:
21°, 43°, or 60° Reflector
Field changeable:
18°, 25°, 40°, or 60° TIR
ADJUSTABILITY High/low lamp positioning; 45° collar rotation
CEILING APPEARANCE Flanged, Flangeless or Flangeless in Wood Ceiling
CEILING THICKNESS
Flanged: Up to 2-1/2"
Flangeless: No ceiling thickness limitations | Flangeless in Wood Ceiling: 1/2" to 2"
Note: Thicker ceilings impact light cutoff
CEILING APERTURE 3-7/8" ceiling cutout
HOUSING IC Airtight, Non-IC Airtight, Chicago Plenum. IC suitable up to R60 spray foam insulation.
Sauna/Steam-room use available only with combination of H Shower trim, LO Low Output housing, and I IC housing rating.
CONSTRUCTION Housing: Heavy-Gauge, Cold-Rolled Steel | Trim: Die-Cast Aluminum
FINISH Housing: Black Powder Coat | Trim: Antique Bronze, Black, Satin Nickel, White (paintable)
GENERAL LISTINGS ETL listed. Damp listed. Shower version Wet listed.
CALIFORNIA TITLE 24 Registered CEC Appliance Database. Can be used to comply with CEC 2019 Title 24 Part 6 (JA8-2016, JA8-2019) (for 90 CRI versions).
L70 50,000 hours min
WARRANTY2 5 years
Data in chart reflect 3000K/80 CRI values unless noted.
Custom Output/Custom RAL/Custom CCT available, Contact Quotes Department
Ordering grids available on page 2.
Accepts two optical controls and an optional trim-mounted lens.
1See ELEMENT-Lighting.com for dimmer compatibility.
2Visit ELEMENT-Lighting.com for specific warranty limitations and details.
33500K Xicato module not available for Artist series.
SHOWN IN FLANGELESS BEVEL SQUARE
UPDATED 3/11/21
TYPE D
2
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
ORDERING GRIDS
TRIM
PRODUCT CEILING APPEARANCE STYLE APERTURE FINISH
E3R ELEMENT 3" ROUND
E3S ELEMENT 3" SQUARE
L FLANGELESS
F FLANGED UP TO 1" CEILING THICKNESS
F15 FLANGED 1.1"-1.5" CEILING THICKNESS
F20 FLANGED 1.6"-2.0" CEILING THICKNESS
F25 FLANGED 2.1"-2.5" CEILING THICKNESS
B BEVEL
F FLAT
-O NO LENS
-H SHOWER1
-L LENSED
Z ANTIQUE BRONZE
B BLACK
S SATIN NICKEL
W WHITE
-
Wood Ceiling option accommodates Flangeless trims only.
1H - Sauna/Steam-room use available only with combination of H Shower trim, LO Low Output housing, and I IC housing rating.
REPLACEMENT OPTICS
PRODUCT BEAM SPREAD
353E4LEDCOPT 18 18°25 25°40 40°60 60°
353E4LEDCOPT
REPLACEMENT REFLECTORS1
PRODUCT BEAM SPREAD
352LEDXREF 21 21°43 43°60 60°
352LEDXREF
1For use with Xicato modules only.
HOUSING
PRODUCT CEILING APPEARANCE OUTPUT LAMP BEAM SPREAD FUNCTION HOUSING RATING DRIVER
E3R ELEMENT 3" ROUNDE3S ELEMENT 3" SQUARE
LF FLANGELESSFF FLANGEDWC WOOD CEILING1
-LH HIGH OUTPUT, 17W2
-LO LOW OUTPUT, 12W3
-X XICATO, HIGH OUTPUT, 14W9
827 80 CRI, 2700K, 2-STEP830 80 CRI, 3000K, 2-STEP835 80 CRI, 3500K, 2-STEP927 90 CRI, 2700K, 2-STEP930 90 CRI, 3000K, 2-STEP935 90 CRI, 3500K, 2-STEPWD 90 CRI, 3000-1800K, WARM DIM, 3-STEPTW52 90 CRI, 5000K-2700K, TUNABLE WHITE, 2-STEP4
TW41 90 CRI, 4000K-1800K, TUNABLE WHITE, 2-STEP4
I27 80 CRI, 2700K, 1X2-STEP, XICATOI30 80 CRI, 3000K, 1X2-STEP, XICATOI35 80 CRI, 3500K, 1X2-STEP, XICATOA27 95 CRI, 2700K, 1X2-STEP, XICATO ARTISTA30 95 CRI, 3000K, 1X2-STEP, XICATO ARTIST
0 10°5
1 18°2 25°4 40°6 60°
21 21° XICATO43 43° XICATO60 60° XICATO
D DOWNLIGHT I IC AIRTIGHTN NON-IC AIRTIGHTC CHICAGO PLENUM
INTEGRATED DRIVERS 120V/277V UNIVERSAL PHASE/0-10V 1% (LEAVE BLANK)6
-ELD0 ELDOLED 0.1% 0-10V LINEAR7
-ELD0A ELDOLED 0.1% 0-10V LOGARITHMIC7
-ELDD ELDOLED 0.1% DALI7
-ELT0 ELDOLED TUNABLE WHITE 0.1% 0-10V LINEAR4,7
-ELTD ELDOLED TUNABLE WHITE 0.1% DALI4,7
-HLECO LUTRON HI-LUME 0.1% ECOSYSTEM8
INTEGRATED DRIVERS 120V-HL2W LUTRON HI-LUME 1% 2-WIRE7
-D
Trims are required and must be ordered separately.
For dimming details, refer to Dimmer Compatibility Chart.
1WC - Wood Ceiling option accommodates Flangeless trims only.
2LH - High Output available for Wet applications. Not available for Sauna/Steam-room.
3LO - Sauna/Steam-room use available only with combination of H Shower trim, LO Low Output housing, and I IC housing rating.
4TW52/TW41/ELT0/ELTD - Tunable White only available in High Output, only available with ELT0 (0-10V, linear), or ELTD (Dali). For 0-10V logarithmic dimming consult Quotes Department.
50 - 10° optic has a unique LED module not available with Warm Dim or Tunable White. Changing optics to 18°, 25°, 40° or 60°, will require a new LED module.
6Universal dimming is reverse-phase, forward-phase, and TRIAC.
7Lutron Hi-lume and eldoLED drivers not compatible with Round Flangeless (E3RLF) or Round Wood Ceiling (E3RWC) housings.
8HLECO - Lutron has put their entire 0.1% ECO drivers on indefinite hold which impacts all -HLECO item numbers. Please consult factory for alternatives. This does not impact -HL2W.
9X - XICATO housings utilize dedicated Standard Phase, 0-10V, 120V and 277V drivers. If ordering Xicato with Standard Drivers (non-Lutron or eldoLED), at the end of the item number please specify:
-010 for 0-10V 120V, -277 for Phase 277V or -010-277 for 0-10V 277. For example: E3RLF-XA2743DI-010 or E3RLF-XA2743DI-277 or E3RLF-XA2743DI-010-277.
PREMIUM LENS HOLDER
PRODUCT LENSES
240E3LENSHLDR 1 ONE LENS
2 TWO LENSES
240E3LENSHLDR
The premium, threaded lens holder provides more
secure mounting of additional lenses as compared to
the standard lens holder that ships with each fixture.
LENSES / LOUVERS1
PRODUCT
140MR16SF SOLITE SOFT FOCUS LENS
140MR16SB SANDBLASTED LENS
140MR16LL LINEAR SPREAD LENS
140MR16DF DIFFUSER SPREAD LENS
140UVMR16 CLEAR GLASS LENS
EL2RHCBK EGGCRATE/HEXCELL LOUVER
1For additional lenses, louvers, optical controls and accessories,
reference ELEMENT-lighting.com/Products/Accessories.
ELEMENT allows up to two Lenses or Louvers per fixture.
3
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
IC AIRTIGHT / NON-IC AIRTIGHT / CHICAGO PLENUM
HOUSING
4"102 mm
9.5"
241 mm
12.5"318 mm
5.2"132 mm
COLLAR HEIGHT 0.75" (19 MM) (SEE INSTRUCTIONS FOR CEILING THICKNESS < 0.75")
TRIMS
ROUND BEVEL SQUARE BEVELROUND BEVEL
ROUND FLATROUND FLAT
SQUARE BEVEL
SQUARE FLATSQUARE FLAT
FLANGED FLANGELESS
3.2"81 mm
1.7"43 mm 1.7"43 mm
3.2"81 mm
3.2"81 mm
1.7"43 mm
4.3"109 mm
1.7"43 mm 1.7"43 mm
3.2"81 mm
1.7"43 mm
4.3"109 mm
4.3"109 mm
3.2"81 mm
1.7"43 mm 1.7"43 mm
4.3"109 mm
3.2"81 mm
FINISH
ANTIQUEBRONZE
BLACK
SATIN NICKEL
WHITE(PAINTABLE)
FLANGELESS IN WOOD CEILING LENS OPTION
ROUND BEVEL (ANTIQUE BRONZE)
ROUND FLAT (ANTIQUE BRONZE)
3.2"81 mm
1.7"43 mm 1.7"43 mm
3.2"81 mm
3.2"81 mm
1.7"43 mm 1.7"43 mm
3.2"81 mm
SQUARE BEVEL (SATIN NICKEL)
SQUARE FLAT (SATIN NICKEL)
SHOWN WITH AND WITHOUT A LENS (SQUARE FLANGED BEVEL)
SHOWN WITH AND WITHOUT A LENS (ROUND FLANGELESS BEVEL)
4
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
FLANGELESS IN WOOD CEILING TRIM ADAPTER
Wood Ceiling housings (“WC” designation in the ordering grid) ship with an adjustable trim
adapter that inserts into the housing aperture and allows standard ELEMENT 3" Flangeless
trims to achieve a truly flangeless, flush ceiling appearance in special applications such as
wood or stone installation. For use in new construction. Consult installation instructions
regarding plenum requirements and ceiling thickness ratios.
TRIM ADAPTER INSTALLED
INSTALL BEFORE CEILING
TRIM ADAPTER
HOUSINGCOLLAR
HOUSING
TRIM ADAPTER FLUSH
HOUSING
COLLAR.85"22 mm
HOUSING
TRIM ADAPTER EXTENDED
HOUSING
COLLAR
.625"
16 mm
1.5"38 mm
5
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
ELEMENT Specular Reflectors reduce glare while creating a clean, quiet ceiling appearance.
Available finishes include Anodized Gold and Silver for a decorative accent or Anodized Black for
an ultimate quite ceiling aesthetic. These beautiful trim accessories have been specifically designed
to minimize any effect on light performance, color and output. Specular Reflectors are available for
both Adjustable and Fixed downlights and are compatible with ELEMENT 3" trims and housings.
• Can be easily installed or removed
• Assembles to existing trim
• Compatible with Fixed and Adjustable Housings
• Finish Options: Anodized Gold (G), Anodized Black (B) or Anodized Silver (S)
SHOWN IN ANODIZED BLACK (REFLECTOR ONLY)
SHOWN IN ANODIZED BLACK (BELOW CEILING VIEW)
E3 TRIM-MOUNTED REFLECTORS
PRODUCT STYLE FINISH
E3TREF NS1 NON-SLOTTED
NS2 NON-SLOTTED
NS3 NON-SLOTTED
NS4 NON-SLOTTED
NS5 NON-SLOTTED
NS6 NON-SLOTTED
B ANODIZED BLACK
G ANODIZED GOLD
S ANODIZED SILVER
E3TREF
Reflectors are placed on top of the inside of the trim or affixed
via screws (only if provided).
ORDERING GRID
SHOWN IN ANODIZED GOLD (BELOW CEILING VIEW)
SHOWN IN ANODIZED SILVER (BELOW CEILING VIEW)
SHOWN IN ANODIZED GOLD (TRIM MOUNTED)
COMPATIBLE TRIMS NON-SLOTTED
(FOR FIXED)
3" round, flanged, bevel
2.6"66 mm2.6"66 mm
1.9"48 mm
1.3"33 mm
E3TREFNS1
(B, G, S)
3" square, flanged, bevel
3.2"81 mm2.7"69 mm3.2"81 mm
1.6"41 mm
1.3"33 mm
E3TREFNS5
(B, G, S)
3" round, flanged, flat
2.6"66 mm2.6"66 mm
1.9"48 mm
1.3"33 mm
E3TREFNS1
(B, G, S)
3" square, flanged, flat
2.8"71 mm2.8"71 mm
1.9"48 mm
1.2"30 mm
E3TREFNS3
(B, G, S)
3" round, flangeless, bevel
2.1"53 mm2.1"53 mm
1.9"48 mm
1.3"33 mm
E3TREFNS2
(B, G, S)
3" square, flangeless, bevel
2.9"74 mm2.9"74 mm
1.9"48 mm
1.2"30 mm
E3TREFNS6
(B, G, S)
3" round, flangeless, flat
2.1"53 mm 2.1"53 mm
1.9"48 mm
1.3"33 mm
E3TREFNS4
(B, G, S)
3" square, flangeless, flat
2.8"71 mm2.8"71 mm
1.9"48 mm
1.2"30 mm
E3TREFNS3
(B, G, S)
May require lamp to be placed in high position.
Not compatible with lensed trims.
SPECIFICATIONS
4.3"109 mm
1.7"43 mm
1.7"43 mm
4.3"109 mm
4.3"109 mm
3.2"81 mm
1.7"43 mm
4.3"109 mm
3.2"81 mm
1.7"43 mm
1.7"43 mm
4.3"109 mm
3.2"81 mm
1.7"43 mm
3.2"81 mm
1.7"43 mm
3.2"81 mm
3.2"81 mm
1.7"43 mm
3.2"81 mm
1.7"43 mm
TRIM-MOUNTED REFLECTORS
6
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
Description: 3" LED Module
25° Beam - 0° Tilt,
80 CRI, 3000K
Model: E3 Citizen LED
Input Power (Watts): 18.3
Input Power Factor: 0.98
Absolute Luminous
Flux (Lumens): 1754
Lumen Efficacy
(Lumens per Watt): 95.5
Description: 3" LED Module
18° Beam - 0° Tilt,
80 CRI, 3000K
Model: E3 Citizen LED
Input Power (Watts): 18.1
Input Power Factor: 0.98
Absolute Luminous
Flux (Lumens): 1598
Lumen Efficacy
(Lumens per Watt): 88.1
Description: 3" LED Module
10° Beam - 0° Tilt,
80 CRI, 3000K
Model: E3 Citizen LED
Input Power (Watts): 16.3
Input Power Factor: 0.98
Absolute Luminous
Flux (Lumens): 1337
Lumen Efficacy
(Lumens per Watt): 82
Output difference between CCTs ~ 5%, CRIs ~ 15%.
ANGLE 0°45°90°
0°19414 19414 19414
5°10254 10254 10254
10°3511 3511 3511
15°1342 1342 1342
20°383 383 383
25°126 126 126
30°84 84 84
35°54 54 54
40°31 31 31
45°22 22 22
50°18 18 18
55°11 11 11
60°6 6 6
65°3 3 3
70°2 2 2
75°0 0 0
80°0 0 0
85°0 0 0
90°0 0 0
ANGLE 0°45°90°
0°5848 5848 5848
5°5500 5478 5491
10°3919 3944 3905
15°2103 2212 2149
20°1058 1199 1075
25°507 548 508
30°250 237 250
35°148 140 141
40°93 98 94
45°51 69 61
50°33 46 37
55°21 27 24
60°4 15 10
65°2 3 2
70°2 2 2
75°0 0 0
80°0 0 0
85°0 0 0
90°0 0 0
ANGLE 0°45°90°
0°5422 5416 5427
5°4916 4872 4888
10°3800 3718 3721
15°2040 2115 2016
20°870 979 900
25°400 441 414
30°190 190 196
35°103 103 105
40°60 65 61
45°27 43 31
50°16 25 17
55°7 12 7
60°2 5 2
65°2 2 2
70°1 1 2
75°0 0 0
80°0 0 0
85°0 0 0
90°0 0 0
PHOTOMETRICS
6718fc
1783fc
777fc
432fc
282fc
1.7'
3.3'
5'
00.9'
8.3'
6.7'
0
3333
6667
10,000
13,333
16,667
20,000
90˚
80˚
70˚
60˚
50˚
40˚30˚20˚10˚0˚
0˚ 0˚45˚
90˚45˚
90˚
1899fc
504fc
220fc
122fc
78fc
1.7'
3.3'
5'
02.8'4.6'
8.3'
6.7'
2024fc
537fc
234fc
130fc
85fc
1.7'
3.3'
5'
02.2'3.7'
8.3'
6.7'
0
917
1833
2750
3667
4583
5500
90˚
80˚
70˚
60˚
50˚
40˚30˚20˚10˚0˚
0˚ 0˚45˚
90˚45˚
90˚
0
983
1967
2950
3933
4917
5900
90˚
80˚
70˚
60˚
50˚
40˚30˚20˚10˚0˚
0˚ 0˚45˚
90˚45˚
90˚
7
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
Description: 3" LED Module
60° Beam - 0° Tilt,
80 CRI, 3000K
Model: E3 Citizen LED
Input Power (Watts): 18.4
Input Power Factor: 0.98
Absolute Luminous
Flux (Lumens): 1536
Lumen Efficacy
(Lumens per Watt): 83.5
Description: 3" LED Module
40° Beam - 0° Tilt,
80 CRI, 3000K
Model: E3 Citizen LED
Input Power (Watts): 16.9
Input Power Factor: 0.98
Absolute Luminous
Flux (Lumens): 1774
Lumen Efficacy
(Lumens per Watt): 104.6
Output difference between CCTs ~ 5%, CRIs ~ 15%.
ANGLE 0°45°90°
0°3230 3230 3230
5°3107 3126 3159
10°2824 2830 2871
15°2415 2407 2463
20°1863 1866 1937
25°1111 1125 1128
30°490 521 479
35°221 232 205
40°115 114 110
45°65 64 59
50°30 38 22
55°14 22 11
60°6 9 4
65°1 3 1
70°1 1 1
75°1 1 1
80°0 0 0
85°0 0 0
90°0 0 0
ANGLE 0°45°90°
0°2305 2305 2305
5°2313 2298 2268
10°2295 2248 2155
15°2219 2116 1938
20°1964 1876 1714
25°1548 1544 1330
30°1113 1176 1013
35°749 835 704
40°450 511 428
45°230 283 221
50°94 140 91
55°38 69 35
60°18 31 16
65°8 13 6
70°0 4 0
75°0 0 0
80°0 0 0
85°0 0 0
90°0 0 0
PHOTOMETRICS
0
396
791
1187
1584
1979
2375
90˚
80˚
70˚
60˚
50˚
40˚30˚20˚10˚0˚
0˚ 0˚45˚
90˚45˚
90˚
576fc
144fc
64fc
36fc
2'
4'
6'
04.1'8.1'
8'
1118fc
297fc
129fc
72fc
47fc
1.7'
3.3'
5'
04'6.7'
8.3'
6.7'
0
550
1100
1650
2200
2750
3300
90˚
80˚
70˚
60˚
50˚
40˚30˚20˚10˚0˚
0˚ 0˚45˚
90˚45˚
90˚
8
©2022 Tech Lighting, L.L.C. All rights reserved. The Tech Lighting logo is a registered trademark of Tech Lighting.
Tech Lighting reserves the right to change specifications for product improvements without notification.
ELEMENT™ 3" LED
FIXED DOWNLIGHT
8
7400 Linder Ave., Skokie, IL 60077
T 847.410.4400
www.techlighting.com
PROJECT INFORMATION
JOB NAME AND INFORMATION
FIXTURE TYPE AND QUANTITY
NOTES
Series Face type Housing color Number of faces Letter color Input voltage Operation Options
LE LED, surface mount
LRE LED, re-cessed
S Stencil
P Panel 1
(blank)Matte black, brushed aluminum face
BZ Dark bronze
W White
B Matte black
1 Single face
2 Double face 2
R Red
G Green
(blank)Universal input voltage (120-277V, 50 or 60 HZ)
(blank)AC only
EL N Nickel-cadmium battery back-up
X2 Lamp wired on two separate AC circuits 3
(blank)None
TP Two tamper proof Torx-head screws
VR Vandal-resistant shield (1/8” thick polycarbonate) 4
FI FA Field selectable fire alarm interface or flashing emergency operation with intermittent audible alarm (one flash per minute) 5
FI Fire alarm flashing interface 6
FA Flashing emergency operation and intermittent audible alarm 7
SD Self-diagnostics 7
BAA BAA Buy America(n) Act Compliant 8
ORDERING INFORMATION For shortest lead times, configure products using bolded options. Example: LE S 1 R EL N SD
EMERGENCY LE-LRE
Die-Cast Aluminum Exits
LE and LRE
FEATURES & SPECIFICATIONS
INTENDED USE — Ideal for applications requiring attractive die-cast aluminum signage, superior il-
lumination and low energy consumption.
CONSTRUCTION — Precision-molded, die-cast aluminum construction — ultra-slim, compact housing.
Fine-grain brushed aluminum faceplate with matte black electrostatic polymeric trim. Clear lacquer finish
on brushed face inhibits fingerprints and other surface contaminants.
All electronics located inside housing.
Fully overlapping light seal prevents light leaks. Universal directional chevron knockouts are completely
concealed and easily removed. Hinged faceplate and spring latches for easy lamp compartment access,
no exposed hardware.
Letters 6" high with 3/4" stroke, with 100 ft viewing distance rating, based upon UL924 standards.
U.S. Patent No. 5,739,639, 5,954,423 and 6,502,044. Canada Patent No. 2,204,218. Other
patents pending.
OPTICS — Lamp is constructed using new LED technology. Provides perfectly uniform illumination to
meet 3/4" letter stroke required by code.
The typical life of the exit LED lamp is 10 years, based on continuous operation. Unique LED lamp platform
accommodates both single-face and double-face exits.
Low energy consumption — red exit consumes std .81W, 1.3W (120V), green exit consumes std is 1W, 1.5W
(120V). Universal input voltage capabilities (120V through 277V, 50 or 60 HZ).
ELECTRICAL — Solid-state electronic elements to eliminate risk of electromechanical failures.
Surge protection meets ANSI/IEEE C62.41 category B and IEC 1000 immunity standards for high voltage
surges, electrostatic discharges, high frequency electrical fast transients and line voltage dips/swells.
Emergency Operation (for EL N option only): Battery: Sealed, maintenance-free nickel-cadmium
battery delivers 90 minutes capacity to lamp.
Self-diagnostics (SD option only): Two-state constant-current charger maximizes battery life and
automatically recharges after battery discharge. Test switch provided for manual testing.
Self-diagnostic testing for five minutes every 30 days, 30 minutes at 180-day interval, and 90 minutes
annually.
Diagnostic evaluation of LED light source, AC to DC transfer, charging and battery condition.
Continuously monitors AC functionality.
Low voltage disconnect prevents excessive deep discharge that can permanently damage the battery.
Single-point microcomputer control for all electronic features.
Crystal oscillator timing system with watchdog protection for precision accuracy.
AC/LVD reset allows battery connection before AC power is applied and prevents battery damage from
deep discharge.
Brownout protection is automatically switched to emergency mode when supply voltage drops below
80% of nominal.
Single multi-chromatic LED indicator to display two-state charging, test activation and three-state
diagnostic status.
Test switch provides manual activation of 30-second diagnostic testing for on-demand visual inspection.
INSTALLATION — Universal mounting (top, end or back). Double face available with top or end mounting
only. LRE: Trim ring has 3/4” depth adjustment to ensure a flush fit against the surface. Protrudes 1/10”
from the surface. No exposed hardware.
Die-cast aluminum canopy provided for surface mount only.
LISTINGS — UL damp location listed 50°F - 104°F (10°C - 40°C). Meets UL 924, NFPA 101 (current Life Safety
Code), NEC and OSHA illumination standards. North Carolina Department of Insurance.
BUY AMERICAN — Product with the BAA option is assembled in the USA and meets the Buy America(n)
government procurement requirements under FAR, DFARS and DOT.
Please refer to www.acuitybrands.com/buy-american for additional information.
WARRANTY — 5-year limited warranty. (Battery is prorated.) This is the only warranty provided and
no other statements in this specification sheet create any warranty of any kind. All other express and
implied warranties are disclaimed. Complete warranty terms located at:
www.acuitybrands.com/support/warranty/terms-and-conditions
Note: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.
Notes
1 Panel face available for special wording only (see Custom Signage spec sheet).
2 Not available with LRE models.
3 UL Listed as emergency lighting.
4 VR contains tamper proof screws.
5 Available with SD option only.
6 Available with AC only or EL N operation only.
7 Available with EL N option only.
8 BAA only available for LE.
9 Add W for white.
Catalog
Number
Notes
Type
LE surface
LRE recessed
Accessories: Order as separate catalog number.
ELA US12 12” stem kit (see spec sheet ELA-StemKits) 2,9
ELA WG1 Back-mount wire guard (see spec sheet ELA-WG) 2
ELA WGEXT Top-mount wire guard (see spec sheet ELA-WG) 2
ELA WGEXE End-mount wire guard (see spec sheet ELA-WG) 2
ELA ERK Recess mounting rough-in kit for LRE only
(see spec sheet ELA-ERK)
† Small Battery Chargers Certified in the CA Title 20 Appliance Efficiency Database.
†
Buy American
E1
SPECIFICATIONS
LE-LRE LED, Signature
MOUNTING
All dimensions are in inches (centimeters). For VR option, add 1/4" to height
and width. Add 1/8" depth for single face; 1/4" depth for double face.
Shipping weight: LE - 4 lbs (1.8 kgs)
LE EL N- 5 lbs (2.3 kgs)
LRE - 4 lbs (1.8 kgs)
LRE EL N - 5 lbs (2.3 kgs)
SELF-DIAGNOSTICS
(SD option only)
The typical life of the exit LED lamp is 10 years.
KEY FEATURE
LE - End Mounting LE - Top Mounting
LE - Back Mounting
1-5/8(4.1)
1-3/4(4.4)
9-1/2(24.0)
4-1/2(11.4)
6(15.2)
5-3/4(14.4)
13(33.0)
7-7/8(20.0)
7-7/8(20.0)4(10.2)
11-3/8(28.9)
11-3/8(28.9)
• Five-minute test every 30 days
• 30-minute test every six months
• 90-minute test annually
• Diagnostics evaluate the battery, lamp, charger and
AC to DC transfer.
Condition Indication
Normal mode Steady green
Self-testing Flashing green
Emergency mode Off
Hi-charge Steady red
Battery failure Single-flash red
Lamp failure Double-flash red
Circuit failure Triple-flash red
Notes
1 The typical life of the exit LED lamp is 10 years, based on continuous operation.
2 At 77°F (25°C).
3 All life safety equipment, including emergency lighting for path of egress must be maintained, serviced, and
tested in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the
required maintenance, service, or testing could jeopardize the safety of occupants and will void all warranties.
4 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower
temperatures affect life and capacity.
ELECTRICAL
Primary circuit
Type
Typical LED
life1
Supply
voltage Input watts Max. amps
Red LED AC only 10 Years 120 0.81 0.05
277 1.2 0.06
Green LED AC only 10 Years 120 1.05 0.05
277 1.32 0.06
Red LED emergency 10 Years 120 1.3 0.06
277 1.4 0.07
Green LED emergency 10 Years 120 1.5 0.07
277 1.7 0.07
BATTERY
Sealed Nickel-Cadmium
Shelf life2 Typical life2 Maintenance3 Temperature range 4
3 years 7-9 years none 50°F – 104°F
(10°C – 40°C)
LE-LRE
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone:800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 1994-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/08/22
9-7/16(24.0)
12-3/8(31.4)
8-7/8(22.5)
4(10.2)
12-15/16(32.9)
STANDARD MOUNTING
Trim ring brackets(provided)
Trim ring
(provided)
J-box(contractor furnished)
Wall opening dimensions: 8-3/4” H x 12-3/8” W x 1-3/4” D
MOUNTING WITH OPTIONAL ROUGH-IN KIT (ELA ERK)
Contractorfurnishedsupports
Wall opening dimensions: 8-7/8” H x 12-3/8” W x 4” D
Mule Lighting , Inc. 46 Baker Street Providence, RI 02905 800 556-7690 P 401 941-2929 F www.mulelighting.com
SVXH CLASS 1 DIVISION 2 LED EXIT SIGN COMBO
HAZARDOUS LOCATION SERIES
LED ILLUMINATION SPECIFICATIONS
Red or green LED (Light Emitting Diode) light strips provide
brilliant and powerful EXIT illumination while consuming
less than 5 watts of electricity at all times.
The SVXH Class 1 Division 2 Exit Sign & Emergency Lights Combo is designed for use in hazardous locations that feature flammable and explosive gases, vapors, and dust. Such environ-ments include power plants, chemical processing facilities, and oil refineries. This Class 1 Div 2 exit sign is waterproof and weatherproof, it can be installed both indoors and out, including in freezing environments.
The body of the SVXH is made from aluminum and features a vandal proof polycarbonate faceplate that protects the unit from moisture and abuse. The polycarbonate faceplate is fully gasketed and and fastened with stainless steel tamper resistant screws.
A poly-vinyl chloride frame features a built-in gasket that seals out moisture. This hazardous location exit sign is corrosion and and flame resistant. 120 or 277V dual voltage operation. UL 924 Listed, Class 1 Division 2, Groups A, B, C, and D.
Two 10-watt, bottom-mounted MR16 Halogen lamps (LED also) provide powerful egress illumination. The lamps are easily positions and protected by a polycarbonate shield. The nickel cadmium exit sign emergency light battery backup system operates the fixture for at least 90 minutes after AC power loss.
• Rated for Class 1 Division 2 Groups A, B, C and D• 2 for 1 exit sign and emergency light solution• Push-to-test button with LED charging indicator• NEMA 3, 4, 4x, and 12 Rated• UL 924 Listed for the USA• 3 year warranty
OVERVIEW
FEATURES
DIMENSIONS
ORDERING INFORMATION
SERIES
H (6V 20W NiCad)
H12N (12V 24W NiCad)
R (red)
G (green)
D (self-diagnostic)
AD (audible SD)
0 (0 heads)
2 (2 heads)
LETTER COLOR OPTIONS # OF HEADS
LA (6V 4W LED)
LG (12V 4W LED)
LI (12V 5W LED)
LJ (12V 6W LED)
LAMP TYPEOPERATION
SVX
TYPE EEM1
BATTERY
INTERNAL HEATER OPTION
ELECTRICAL SPECIFICATIONS
Mule Lighting , Inc. 46 Baker Street Providence, RI 02905 800 556-7690 P 401 941-2929 F www.mulelighting.com
EXTERNAL SPECIFICATIONS
This Class 1 Division 2 exit sign and emergency lights combo is composed of an aluminum housing paired with a polycarbonate faceplate that cover the LED exit sign and halogen emergency lamps. The housing and faceplate are sealed together to prevent fluids, vapors, and gases from entering the inside of the SVXH exit sign combo with emergency lights.
The housing is tamper-resistant and features a hermetically sealed magnetic test switch that allows for easy testing of the nickel cadmi-um battery backup system. The entire housing is vandal resistant and approved for use in high abuse areas such as schools and prisons.These types of fixtures are known as explosion proof exit signs, because the housing is hermetically sealed to prevent the intrusion of any type of gas, vapor, or liquid which could ignite a fire or explo-sion.
Class 1 Division 2 exit signs are designed for hazardous locations and are thus designed and built under the strictest quality control standards. If you need a model that has emergency lights attached to it.
UL924 Listed for the U.S. and Canada, CS860, NFPA, Life Safety 101, UL Listed for Damp Locations. UL Listed for Wet Locations.
CODE COMPLIANCE
Standard Self-Diagnostic circuitry continuously monitors every
critical function of the unit. If a problem occurs, a single fault
indicator on the outside of the fixture flashes immediately.
A detailed diagnostic display is located internally. The detailed
display will further indicate the nature of the fault as either a battery
fault, load fault or a charger fault. Audible self-diagnostics
available.
SELF-DIAGNOSTIC TESTING
• LA - 6V 4W MR16 LED• LG - 12V 4W MR16 LED• LI - 12V 5W MR16 LED• LJ - 12V 6W MR16 LED
LAMP SELECTION GUIDE
The SVXH Series comes with a 3-year factory warranty. The lamps
are not covered. Deliberate damage, misuse, or improper installa-
tion effectively cancel the warranty. Battery features a 20% per year
pro-rata warranty.
Class 1 Div 2 exit sign combos feature a maintenance-free Nickel Cadmium exit sign battery provides 90 minutes of emergency support and lasts for 5-7 years.
The SVXH Class 1 Division 2 Exit Sign Combo can be upgraded to a Nickel-Metal Hydride battery which lasts up to 10 years long and features a 12V 40W capacity.
The unit can be outfitted with an internal heater that keeps battery
backup system ready for emergency mode operation for applications
that feature freezing temperature environments (up to -4o F)
120/277V AC dual-voltage operation is standard. Other voltages
available upon request such as 220v and 240v.
T6 (maximum 85°C/185°F). Evaluated to UL 924 and UL1598
standards.
WARRANTY
SVXH CLASS 1 DIVISION 2 LED EXIT SIGN COMBO
HAZARDOUS LOCATION SERIES
Application
The “Dynamo” DYN Series is a highly versatile superior lumen output, industrial
application emergency lighting unit, designed to provide a minimum of 90
minutes illumination when primary power is lost. The DYN Series provides the
same level of lumen output with no light degradation for the full 90 minutes of
battery discharge. It has a flame-rated, UV stable thermoplastic housing which is
fully gasketed and corrosion resistant with a gray finish. LED based lamp-heads
are made of high strength die-cast aluminum with polycarbonate lens. Includes
micro-controller based 3-stage charger and Lithium Iron Phosphate(LiFePO4)
battery. The DYN Series accepts 120 through 277VAC input at 50 or 60Hz. Not
designed for self-diagnostic operation at 220-240VAC input. Universal mounting
plate made of painted stamped steel. The Dynamo is specifically designed for
demanding environments, high reliability operation in industrial settings such as
wet location or hose-down, food processing, food storage, production facilities,
chemical plant and wastewater treatment. Hazardous location emergency
lighting units with optional C1D2 listed for use in NEC Class I, Division 2, Groups
A, B, C and D and Class 1, Zone 2, Groups IIA, IIB, IIB+H2, IIC. Hazardous
Location Emergency Lighting Units with optional C2D1 listed for use in NEC
Class II, Division 1, Groups E, F and G, and Zone 20, 21 and Class 3.
Construction
The DYN series housing, covers, remote housing and shield are made of
polycarbonate. Lamp-heads are made of die-cast aluminum for thermal
dissipation. LED lenses are made of polycarbonate. The Food Processing(FP) and
Class 2, Division 1(C2D1) optioned DYN includes a clear polycarbonate shield
which fully covers the lamp-heads.
Installation
The unit includes a universal mounting plate which facilitates mounting to a
truss or I-beam, pole, column, or wall. Included is a special bracket to ensure
positive pole gripping when using bands. In wet or NEMA 4X applications, use
UL listed water tight conduit fittings that meet the requirements of the UL 514B
Standard for Conduit Tubing and Cable Fittings when using knockouts on the
side or top of unit. All fittings supplied by others. C1D2 and C2D1 listed models
include 2 each hazardous location rated conduit hubs with ground provision.
Illumination
The DYN series provides bright and uniform illumination and is specifically
designed for higher mounting heights above 9’. Coverage provided by 2 sealed
aluminum lamp-heads using 3 high power LEDs each. The LEDs are located in
a specially designed heat dissipating lamp-head which is fully adjustable and
can be locked into position. The DYN is designed for full lumen output across
the entire 90 minutes of operation. This ensures maximum visibility of the egress
path over the full 90 minute discharge period.
Warranty
LED Lifetime Warranty
DYN Standard Model- 3 Year Full
DYN Spectron Model- 5 Year Full
FEATURES
Dynamo DYN Series
NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light
Catalog Number
Comments Type
ACCESSORIES
DYNRS-4X NEMA 4X Rated
Single Head Remote
DYNRD-4X NEMA 4X Rated
Double Head Remote
DYNRS-4X-FP Food Processing rated Single Head Remote
(Includes Polycarbonate Shield)
DYNRD-4X-FP Food Processing rated Double Head Remote
(Includes Polycarbonate Shield)
WGA2 Wire Guard (Does not include Food Processing
option)
15”H x 14”L x 7”D
DYNRD-C1D2 Class 1, Div. 2 Remote, 3W heads, 1 conduit
hub included
DYNRD-C2D1 Class 2, Div. 1 Remote, 3W heads with shield,
1 conduit
hub included
ORDERING GUIDE
Model
DYN
Blank Wet Location 4X NEMA 4X/IP66 Rated FP Food Processing Rated 4
HTR Heater for Cold Temp 5
C1D2 Class 1 Div. 2 6
C2D1 Class 2 Div. 1 7
Application
1. Only available on DYN with 12 watt capacity
2. DYN6 only available in the following configurations-DYN6, DYN6I, DYN6-4X, DYN6I-4X, DYN6I-4X-HTR, DYN6I-4X-FP, DYN6I-4X-HTR-FP
3. DYN12 only available in the following configurations-DYN12, DYN12I, DYN12-4X, DYN12-4X-FP, DYN12I-4X, DYN12I-4X-HTR, DYN12I-4X-FP, DYN12I-4X- HTR-FP, DYN12-06L, DYN12I-06L, DYN12-4X-06L, DYN12-4X-FP-06L, DYN12I-4X-06L, DYN12I-4X-HTR-06L, DYN12I-4X-FP-06L, DYN12I-4X-HTR-FP-06L
4. FP option must be ordered with 4X option. Example: DYN6I-4X-FP
5. HTR option only available with Spectron®
6. C1D2 Option only available with DYN6I-C1D2, DYN12I-C1D2, and DYN12I-C1D2-06L
7. C2D1 Option only available with DYN6I-C2D1, DYN12I-C2D1, and DYN12I-C2D1-06L which includes shield
Patent Pending
Capacity
6 6 Watt 2
12 12 Watt 3 Blank Wet Location I Spectron® Self Diagnostics
Self-Diagnostics Lamp
Blank 3 Watt LED lamps 06L 6 Watt LED lamps 1
Compliances
Listed to UL924 Standard, NFPA 101, NFPA 70
Wet Location, NEMA 4, 4X rated
UL Sanitation Certified with FP Option
IP66 rated for 4X models only
C1D2 and C2D1 optioned products;
Listed to Standard 924 and Standard 844 (Hazardous Location)
NEC Class 1 Division 2 Groups A, B, C, D
NEC Class 2, Division 1 Groups E, F and G
NEC Class 3
CEC T20 Compliant
EM2
Electronics
Upon failure of the normal utility power, a LED driver is automatically activated to power the emergency LED lamp-heads. At resumption of normal utility
power, the LED driver is turned off. The battery is recharged through a micro-controller based 3-stage charger. The battery is a maintenance-free Lithium
Iron Phosphate (LiFePO4) type. The EVHC series accepts dual-voltage input of 120 through 277VAC at 50 or 60 Hz. A low voltage battery disconnect(LVD)
feature protects the battery from severe damage during prolonged power failures. Manual testing is available at any time using the push-to-test button.
The optional heater features a heating wrap and thermostat to maintain optimal battery temperature during charge or discharge. The DYN remote can be
located up to 100’ from the source unit using 12 gage wire.
Number of Lamps: 2 lamp-heads with 3 high-power LEDs per head
Lamp Color: Cool White, 5000K
Total Lamp Output: Standard Model, 331 lumens per lamp-head
Optional 6W Lamps, 514 lumens per lamp-head
Rated LED Lifecycle: Greater than 100,000 hrs
Standard Features Include:
• Wet location operation with lock-down head positioning(no shield)
• Sealed external push-to-test switch and AC-on indicator
• Battery re-charge within 24 hours
• AC Lock-out circuit
• Low voltage battery disconnect
• Conduit entry knock-out located at the top center and upper half of each side
• Micro-controller based 3-stage charger
• Flashing service alert code for “Battery Disconnect” or “Charger Fault” in compliance with UL 924
Optional Feature Include:
• 4X -NEMA4, 4X option fully sealed and gasketed for indoor/outdoor use, splash and hose-down environments and corrosion resistance • FP- Food processing option is UL Sanitation certified for use in food preparation and storage, and in food service establishments
• HTR- Includes a heating wrap and thermostat to maintain optimal battery temperature in cold environments to -22°F(-30°C)
Optional Spectron Includes:
• Self-diagnostics monitors LED status, LED driver circuit, battery capacity and charger function and displays any fault detection by means of a flashing code
• Self-Test feature automatically runs a 1 minute test once a month and an alternating 30-60 minute test once every 6 months. Multi-color LED indicator provides visible fault detection and charging status
• User initiated 1, or 90-minute system test feature
• 15 minute re-transfer delay
• Automatic unit transfer in brown-out conditions (below 80% of nominal AC input voltage)
SPECIFICATIONS
INPUT POWER CONSUMPTION
Photometrics available for download at www.dual-lite.com
Maintenance Mode Power Consumption 120VAC- 0.33W
Maintenance Mode Power Consumption 277VAC- 0.36W
Battery Capacity Lamp(W)Lumens per Lamp Remote Lamp Watts Run-Time Extended Runtime Remote Capable Remote Part Number
DYN6 LiFePO4 6 watts 3 watts 331 0 90 min No No N/A
DYN6I LiFePO4 6 watts 3 watts 331 0 90 min No No N/A
DYN12 LiFePO4 12 watts 3 watts 331 6 90 min Yes Yes DYNR
DYN12I LiFePO4 12 watts 3 watts 331 6 90 min Yes Yes DYNR
DYN12-06L LiFePO4 12 watts 6 watts 514 0 90 min No No N/A
DYN12I-06L LiFePO4 12 watts 6 watts 514 0 90 min No No N/A
Operating Temperature:
Wet/NEMA 4X Location Listed: 50° to 122°F(10° to 50°C)
Heater Option Models: -22° to 122°F(-30° to 50°C)
Additional Product Information
Input Voltage Amps.Max. Watts
DYN6 120 0.03 3.40
277 0.04 3.49
DYN6 with heater 120 0.18 20.94
277 0.08 21.13
DYN12 120 0.05 5.98
277 0.04 6.52
DYN12 with heater 120 0.21 25.30
277 0.09 25.60
Dynamo DYN Series
NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light
Operating Temperature in °C
Ambient °C CLASS 1 DIV. 2 A, B, C, D CLASS 2 DIV. 1 E, F, G Supply Wire Temp. °C Min.
40 T6 T6 75
50 T5 T6 75
Temperature Codes and Maximum Temperature Ratings
APPLICATION INFORMATION
* Multiple unit spacing based on 6’ path
Ceiling Mount
6’ Path
SPACING (SEE CHART)
MOUNTING HEIGHT (SEE CHART)
Industrial Parameters CH=30’, R=10/10/10, Ceiling mounted (Multiple Unit Spacing), 6’ Path
DYN12-06L (6 watt lamp option)DYN6 (3 watt lamps)
Mounting Height 20’18’16’14’12’10’7.5’Mounting Height 20’18’16’14’12’10’7.5’
Max Spacing @ 1
FC Avg 62’65’68’71’74’77’81’Max Spacing @ 1
FC Avg 43’45’48’51’53’56’59’
Max Spacing @ 1
FC Min 35’34’34’33’32’31’29’Max Spacing @ 1
FC Min 28’28’27’27’26’24’22’
Meets Life Safety Code minimum illuminance of 0.1 fc and average illuminance of 1.0 fc. Photometry files available on the Dual-Lite
web site (www.dual-lite.com).
Dynamo DYN Series
NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light
DIMENSIONS
5.15”
4.34”
4.25”
11.25”11.61”
9.78”9.78”
1.24”
5.15”
6.04”
3.54”
6.3”
10.54”
3.72”
4.94”
9.75”
11.04”
10.54”
3.72”
4.94”
9.75”
11.04”
6.11”
Web: www.dual-lite.com • Tech Support: (866)-313-3909701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright © Dual-Lite, a division of Hubbell Lighting, Inc., All Rights Reserved
Specifications subject to change without notice. • Printed in U.S.A.0603637 A 03/18
5.15”
4.34”
4.25”
11.25”11.61”
9.78”9.78”
1.24”
5.15”
6.04”
3.54”
6.3”
10.54”
3.72”
4.94”
9.75”
11.04”
10.54”
3.72”
4.94”
9.75”
11.04”
6.11”
Dynamo DYN Series
NEMA 4X / C1D2 / C2D1 Industrial LED Emergency Light
Industrial Applications | Area Light
44 www.dialight.com
Vigilant® LED Area Light
100-277 VAC, 120-250 VDC
Dimensions in inches [mm]
Mechanical Information:
Fixture weight: 10 lb (4.5 kg) - Polycarbonate lens
12 lb (5.5 kg) - Tempered glass lens
with stainless steel bracket: 13 lb (5.9 kg) - Polycarbonate lens
15 lb (6.8 kg) - Tempered glass lens
Shipping weight: Add 2 lb (0.91 kg) to weights above
Impact rating: IK10 - Polycarbonate lens
IK07 - Tempered glass lens
Cabling: 10’ STOOW 1.02 mm 18 AWG
Mounting: Secondary retention standard
Electrical Specifications:
Operating voltage: 100-277 VAC 50/60Hz, 120-250 VDC
Operating temperature: -40°F to +149°F (-40°C to +65°C)
EMC: FCC Title 47, Subpart B, Section 15,
Class A device
CISPR-15
RF Immunity 20V/m 80MHz-1GHz.
Transient protection: 6 kV, 2 Ohm line-line and line-ground
Harmonics: IEC 61000-3-2, Class C
THD: < 20%
Power factor: > 0.9
Construction:
Housing: Copper-free aluminum
Finish: Superior dual coat finish
- Sealed polyester topcoat
Lens: Hard-coated polycarbonate
Tempered glass
Photometric Information:
CRI: 80
CCT: 5000K (cool white)
4000K (neutral white)
Optics: 360°
180° forward throw for 45° mounting
Wide for 0° mounting
All values typical unless otherwise stated (tolerance +/- 10%)
*ETL listed
Tempered Glass Lens
Polycarbonate Lens
Certifications & Ratings*
• 10 year warranty
• UL 1598/A
• CSA C22.2 No. 250
• IP66 / 67 / 69
• NEMA 4X
WARNING: INSTALLATION & SECONDARY RETENTION: The use of this product without proper installation and inspections, including secondary safety retention/securing, could cause severe injury or death. Dialight recommends that all installations should use secondary retention (appropriate to the installation environment) where applicable. It is the exclusive responsibility of
the contractor, installer and/or end customer to: (a) determine the suitability of the product for its intended application; and, (b) ensure that the product is installed safely (with secondary retention
where appropriate) and in compliance with all applicable laws and regulations. To the extent permissible under the relevant law, Dialight disclaims all responsibility for personal injury and/or other
damage resulting from any dislodgement or other dislocation of this product.
TYPE F
Industrial Applications | Area Light
www.dialight.com 45
Vigilant® LED Area Light
100-277 VAC, 120-250 VDC with Mounting Adapters
Mechanical Information:
Fixture weight:
UMA models: 12 lb (5.5 kg) - Polycarbonate lens
15 lb (6.8 kg) - Tempered glass lens
Wall mount models: 15 lb (6.8 kg) - Polycarbonate lens
18 lb (8.2 kg) - Tempered glass lens
45° wall mount models: 14 lb (6.4 kg) - Polycarbonate lens
17 lb (7.7 kg) - Tempered glass lens
45° stanchion mount: 15 lb (6.8 kg) - Polycarbonate lens
18 lb (8.2 kg) - Tempered glass lens
Shipping weight: Add 2 lb (0.91 kg) to weights above
Impact rating: IK10 - Polycarbonate lens
IK07 - Tempered glass lens
Cabling: 14” leads 1.02 mm 18 AWG
Mounting: Secondary retention standard
Electrical Specifications:
Operating voltage: 100-277 VAC 50/60 Hz, 120-250 VDC
Operating temperature: -40°F to +149°F (-40°C to +65°C)
EMC: FCC Title 47, Subpart B, Section 15,
Class A device
CISPR-15
RF Immunity 20V/m 80MHz-1GHz.
Transient protection: 6 kV, 2 Ohm line-line and line-ground
Harmonics: IEC 61000-3-2, Class C
THD: < 20%
Power factor: > 0.9
Construction:
Housing: Copper-free aluminum
Finish: Superior dual coat finish
- Sealed polyester topcoat
Lens: Hard-coated polycarbonate
Tempered glass
Photometric Information:
CRI: 80
CCT: 5000K (cool white)
4000K (neutral white)
Optics: 360°
180° forward throw for 45° mounting
Wide for 0° mounting
All values typical unless otherwise stated (tolerance +/- 10%)
*ETL listed
Certifications & Ratings*
• 10 year warranty
• UL 1598/A
• CSA C22.2 No. 250
• IP66 / 67 / 69
• NEMA 4X
Universal Mounting Adapter
Wall Mount
45o Stanchion Mount
45o Wall Mount
For use with HZXW01, HZXW45 or
HZXS45 brackets sold separately
HZXW01 HZXS45 HZXW45
WARNING: INSTALLATION & SECONDARY RETENTION: The use of this product without proper installation and inspections, including secondary safety retention/securing, could cause
severe injury or death. Dialight recommends that all installations should use secondary retention (appropriate to the installation environment) where applicable. It is the exclusive responsibility of the contractor, installer and/or end customer to: (a) determine the suitability of the product for its intended application; and, (b) ensure that the product is installed safely (with secondary retention
where appropriate) and in compliance with all applicable laws and regulations. To the extent permissible under the relevant law, Dialight disclaims all responsibility for personal injury and/or other
damage resulting from any dislodgement or other dislocation of this product.
46 www.dialight.com
Industrial Applications | Area Light
AL 2 D G N
Product
Code Cert.Lens
Material
Beam
Dist.
CCT &
CRI
Oper.
Voltage
Lumen
Type Controls Mounting
Options
HW
Access.
Elect.
Access.Coatings
Product Code
AL Area Light
Certification
U UL 1598/A CSA 22.2 No. 250.0
Lens Material
5 Polycarbonate - Diffused
7 Glass - Clear
Beam Distribution
A 180°
B 360°
W Wide
CCT & CRI
C Cool White 5000K - 80 CRI
N Neutral White 4000K - 80 CRI
Operating Voltage
2 100-277 VAC, 120-250 VDC
Lumen Type
3 3,001 - 4,000 Lumens
4 4,001 - 5,000 Lumens
6 5,001 - 6,000 Lumens
7 6,001 - 7,000 Lumens
9 8,001 - 9,000 Lumens
Controls
D Dimming (0-10V)
Mounting Options
A Appleton Mercmaster III
B Swivel Bracket, Locking 0°- 90°
316 Stainless Steel
C Crouse-Hinds - Champ
G GE Filtr-Gard
H Thomas & Betts Hazlux
K Killark Certilite & Certilite V
M Appleton Mercmaster II
N 3/4” NPT
S 45° Stanchion Mount
U UMA - Mounting Hub
V 0° Wall Mount
W 45° Wall Mount
Coatings
G Gray (RAL 7040)
Universal Mounting Adapter
(UMA)
Notes
1) When ordering Beam Distribution W - Wide: Lumen Type = 7.
2) When ordering Mounting Options “UMA” or “Retro-fit”: Hardware Accessories = N.
3) When ordering Mounting Option U - UMA Mounting Hub HZXW01, HZXW45, HZXS45 or HZXCV34 are required. See page 37 for details.
U
Hardware Accessories
N For Mounting Options -
A, C, G, H, K, M, S, U, V, W, Y
(individual wire leads are terminated
in adapter housing)
W 10 ft (3 meter) Power Cable for
Mounting Options - B, N
Electrical Accessories
N No Option
Retro-fit Adapter
Battery
Battery
N No Option
*For lumen output see page 10
Specifications
Vigilant® LED Area Light
100-277 VAC, 120-250 VDC
Project Information
Part Number:
Project:
Fixture Type: Date:
Ordering Information
N
DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract
with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and
conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does
not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail.
7 A C 6 W N
www.dialight.com 47
Industrial Applications | Area Light
Ordering Information
Vigilant® LED Area Light - 100-277 VAC, 120-250 VDC
100-277 VAC, 120-250 VDC Model
Part Number Lumens Wattage lm/W CCT CRI Lens Beam Distribution Controls Option Mounting
ALU-7BC2-9DNW-NGN 9,000 66 136 CW 80 Glass 360° Dimming 3/4" Conduit
ALU-5BC2-9DNW-NGN 8,300 66 126 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit
ALU-7BC2-7DNW-NGN 7,300 52 140 CW 80 Glass 360° Dimming 3/4" Conduit
ALU-5BC2-7DNW-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit
ALU-5AC2-7DNW-NGN 6,600 52 127 CW 80 Polycarbonate Diffused 180° Dimming 3/4" Conduit
ALU-7BC2-6DNW-NGN 5,700 40 143 CW 80 Glass 360° Dimming 3/4" Conduit
ALU-5BC2-6DNW-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit
ALU-5AC2-6DNW-NGN 5,100 40 128 CW 80 Polycarbonate Diffused 180° Dimming 3/4" Conduit
ALU-7BC2-4DNW-NGN 4,200 30 140 CW 80 Glass 360° Dimming 3/4" Conduit
ALU-5BC2-4DNW-NGN 3,900 30 130 CW 80 Polycarbonate Diffused 360° Dimming 3/4" Conduit
ALU-7BC2-4DNW-NGN 4,200 30 140 CW 80 Glass 360 Dimming 3/4" Conduit
100-277 VAC, 120-250 VDC Model with Retro-fit Adapters
Part Number Lumens Wattage lm/W CCT CRI Lens Beam Distribution Controls Option Mounting
ALU-7BC2-9DCN-NGN 9,000 66 136 CW 80 Glass 360° Dimming Crouse-Hinds Retro-fit
ALU-5BC2-9DCN-NGN 8,300 66 126 CW 80 Polycarbonate Diffused 360° Dimming Crouse-Hinds Retro-fit
ALU-5BC2-7DAN-NGN 6,700 69 97 CW 80 Polycarbonate Diffused 360° Dimming Appleton M III Retro-fit
ALU-5BC2-7DCN-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming Crouse-Hinds Retro-fit
ALU-5BC2-7DGN-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming GE H2 Retro-fit
ALU-7BC2-6DCN-NGN 5,700 40 143 CW 80 Glass 360° Dimming Crouse-Hinds Retro-fit
ALU-5BC2-6DAN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Appleton M III Retro-fit
ALU-5BC2-6DCN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Crouse-Hinds Retro-fit
ALU-5BC2-6DGN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming GE H2 Retro-fit
ALU-7AC2-4DAN-NGN 4,100 30 137 CW 80 Glass 180° Dimming Appleton M III Retro-fit
All values typical unless otherwise stated (tolerance +/- 10%).
See ordering chart for additional options.
All values typical unless otherwise stated (tolerance +/- 10%).
See ordering chart for additional options.
DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract
with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and
conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does
not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail.
Ordering Information
Vigilant® LED Area Light - 100-277 VAC, 120-250 VDC
with Mounting Adapters
HZXW01 HZXS45 HZXW45
100-277 VAC, 120-250 VDC Model with Mounting Adapters
Part Number Lumens Wattage lm/W CCT CRI Lens Beam Distribution Controls Option Mounting
ALU-7BC2-9DUN-NGN 9,000 66 136 CW 80 Glass 360° Dimming Universal Mounting Adapter
ALU-5BC2-9DUN-NGN 8,300 66 126 CW 80 Polycarbonate Diffused 360° Dimming Universal Mounting Adapter
ALU-5BC2-7DSN-NGN 6,700 68 99 CW 80 Polycarbonate Diffused 360° Dimming Stanchion 45°
ALU-5BC2-7DWN-NGN 6,700 52 129 CW 80 Polycarbonate Diffused 360° Dimming Wall Mount 45°
ALU-5AC2-7DSN-NGN 6,600 52 127 CW 80 Polycarbonate Diffused 180° Dimming Stanchion 45°
ALU-5AC2-7DWN-NGN 6,600 52 127 CW 80 Polycarbonate Diffused 180° Dimming Wall Mount 45°
ALU-7BC2-6DUN-NGN 5,700 40 143 CW 80 Glass 360° Dimming Universal Mounting Adapter
ALU-5BC2-6DSN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Stanchion 45°
ALU-5BC2-6DUN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Universal Mounting Adapter
ALU-5BC2-6DVN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Wall Mount 0°
ALU-5BC2-6DWN-NGN 5,300 40 133 CW 80 Polycarbonate Diffused 360° Dimming Wall Mount 45°
ALU-5AC2-6DSN-NGN 5,100 40 128 CW 80 Polycarbonate Diffused 180° Dimming Stanchion 45°
ALU-5BC2-4DSN-NGN 3,900 30 130 CW 80 Polycarbonate Diffused 360° Dimming Stanchion 45°
48 www.dialight.com
Industrial Applications | Area Light
DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract
with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and
conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does
not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail.
All values typical unless otherwise stated (tolerance +/- 10%).
See ordering chart for additional options.
www.dialight.com 49
Industrial Applications | Area Light
Vigilant® LED Area Light
Lumen Tables
100-277 VAC, 120-250 VDC
Output Family Beam Distribution Lens Wattage
Lumens
5000 CCT
5000
CCT lm/W
Lumens
4000 CCT
4000
CCT lm/W
Lumens
2700 CCT
2700
CCT lm/W
9,000
360°
1/4" AR Glass
66
9000 136 8800 134 8200 124
Class I, Div 1 Glass 8600 131 8400 128 7900 120
Polycarbonate 8300 127 8100 123 7600 115
180°
1/4" AR Glass 8800 134 8600 131 8000 121
Class I, Div 1 Glass 8400 128 8200 125 7700 117
Polycarbonate 8100 124 7900 120 7400 112
7,300
360°
1/4" AR Glass
52
7300 140 7100 138 6700 129
Class I, Div 1 Glass 7000 135 6800 132 6400 123
Polycarbonate 6700 131 6500 126 6100 117
180°
1/4" AR Glass 7100 138 6900 134 6500 125
Class I, Div 1 Glass 6800 132 6600 128 6200 119
Polycarbonate 6600 128 6400 124 6000 115
Wide
1/4" AR Glass
64
7300 114 7100 112 6700 105
Class I, Div 1 Glass 7000 110 6800 107 6400 100
Polycarbonate 6700 106 6500 103 6100 95
5,700
360°
1/4" AR Glass
40
5700 143 5500 140 5200 130
Class I, Div 1 Glass 5400 137 5200 132 4900 123
Polycarbonate 5300 133 5100 130 4800 120
180°
1/4" AR Glass 5500 140 5300 135 5000 125
Class I, Div 1 Glass 5300 134 5100 130 4800 120
Polycarbonate 5100 130 4900 125 4600 115
4,200
360°
1/4" AR Glass
30
4200 140 4100 137 3800 127
Class I, Div 1 Glass 4000 134 3900 131 3600 120
Polycarbonate 3900 130 3800 127 3900 130
180°
1/4" AR Glass 4100 137 4000 134 4100 137
Class I, Div 1 Glass 3900 132 3800 127 3900 130
Polycarbonate 3800 127 3700 124 3400 113
3,100
360°
1/4" AR Glass
24
3100 129 3000 127 2800 117
Class I, Div 1 Glass 2900 124 2900 121 2600 108
Polycarbonate 2800 120 2700 114 2500 104
180°
1/4" AR Glass 3000 127 2900 123 2700 113
Class I, Div 1 Glass 2900 121 2800 118 2600 108
Polycarbonate 2800 118 2700 114 2500 104
All values typical unless otherwise stated (tolerance +/- 10%).
For lighting layouts, please find IES files at www.dialight.com
DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract
with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and
conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does
not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail.
Polycarbonate Lens - Option 5
Glass Lens - Option 7
Industrial Applications | Area Light
50 www.dialight.com
Vigilant® LED Area Light
Beam Distribution & Dimensional Drawings
Beam Distribution
180o 360o Wide
DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract
with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and
conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does
not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail.
www.dialight.com
Industrial Applications | Area Light
Vigilant® LED Area Light
Accessories
51
Please reference spec sheet at www.dialight.com for all dimensional drawings of mounting options.
HZXW3
• 316 stainless steel bracket
HZXSTAN100S
• 1.00” (1.315” Pole OD) Slip-fit stanchion mount
HZXSTAN125S
• 1.25” (1.660” Pole OD) Slip-fit stanchion mount
HZXSTAN150S
• 1.50” (1.900” Pole OD) Slip-fit stanchion mount
HZXSTAN200S
• 2.00” (2.375” Pole OD) Slip-fit stanchion mount
HZXSTAN100T
• 1.00” (1.315” Pole OD) NPT threaded stanchion mount
HZXSTAN125T
• 1.25” (1.660” Pole OD) NPT threaded stanchion mount
HZXSTAN150T
• 1.50” (1.900” Pole OD) NPT threaded stanchion mount
HZXSTAN200T
• 2.00” (2.375” Pole OD) NPT threaded stanchion mount
HZXW4
• 316 stainless steel bracket with pipe clamp
HZXSAFECBLS
• Safety cable kit
Certified to: UL 50E • CSA C22.2 No. 94.2-07
HZXJB075
• 0.75” Ceiling / Wall / Pole mount junction box
HZXJB100
• 1.00” Ceiling / Wall / Pole mount junction box
HZXJB125
• 1.25” Ceiling / Wall / Pole mount junction box
HZXJB150
• 1.50” Ceiling / Wall / Pole mount junction box
HZXJB075PC1
• 0.75” Junction box with photocell
HZXJB100PC1
• 1.00” Junction box with photocell
HZXJB125PC1
• 1.25” Junction box with photocell
HZXJB150PC1
• 1.50” Junction box with photocell
Certified to: UL 50E • CSA C22.2 No. 94.2-07 Certified to: UL 50E • CSA C22.2 No. 94.2-07
HBXC1
• 0.75” NPT Ceiling mount
Certified to: UL 50E • UL 1203
ISA 12.12.01 • CSA C22.2 No. 94.2-07
Fixtures are available with a universal mounting adapter factory installed, see product N-chart for details.
Choose from one of the four available mounting options:
Wall Mount
HZXW01
45° Wall Mount
HZXW45
45° Stanchion Mount
HZXS45
ALxxxx2xDUNxGN 34mm Slip-fit Pole Mount
HZXCV34
HZXW7
• Aluminum bracket
HZXW8
• Aluminum bracket with pipe clamp
DISCLAIMER: All information provided is, to the best of Dialight’s knowledge, accurate as of the date of publication, but is subject to change without notice and does not form part of any contract
with Dialight. When ordering please refer to www.dialight.com for current versions of: (a) relevant product documentation (including the most up to date product data sheets); (b) Dialight terms and
conditions of sale; and, (c) the relevant product warranty. All information provided is, to Dialight’s knowledge, accurate at the date of publication, but is subject to change without notice and does
not form part of any contract with Dialight. In the event of any discrepancy between this document and information provided on our website, the latter shall prevail.
TYPE G
Attachment E
Coastal Hazardous Report_Rev 1
Memo
SUBJECT PROJECT
Coastal Hazards Analysis Bay Bridge Pump Station
Replacement Project (5-67)
TO DATE
Orange County Sanitation District June 2023
Introduction
This memorandum summarizes the analysis for coastal hazards for the Bay Bridge Pump Station (BBPS)
Replacement Project, Newport Beach, Orange County, California. The Orange County Sanitation District (OC
San) proposes to replace the existing BBPS with a new pump station and force main infrastructure. The existing
BBPS is over 50 years old, outdated, and no longer meets structural, electrical, and maintenance standards. The
Project includes replacing the existing pump station and force mains with a new pump station, replacement force
mains, a new electrical building, a new emergency generator building, and an odor control structure.
The new pump station will include a trench-type wet well and a dry well for housing the pumps, motors, and other
mechanical equipment. As shown on Figure 1, the pump station site also includes an electrical building, a
generator building, and an odor control structure. The proposed electrical building includes the electrical
equipment, instrumentation, control equipment, and restroom. The electrical building has a finished floor elevation
of 15.50 feet NAVD88 and is elevated from the grade level. The entrance to the underground pump station dry
well is also elevated to the same elevation of the electrical building finished floor at 15.5 feet NVAD88. The
generator room finished floor is 14.17 feet NAVD88 and the generator will be mounted on a 2-ft-high belly fuel
tank. The odor control structure finished floor is 14.00 feet NAVD88. The new force main will be installed beneath
the Newport Bay Channel and would not be affected by coastal processes and is not included in the analysis.
This memorandum summarizes the potential impacts on the BBPS resulting from anticipated sea level rise,
coastal geologic instability, and flooding per the requirements of the Newport Beach Local Coastal Plan Policies
LUPs 2.8.1-1, 2.8.-2 and 2.8.1-4 and per Section 30253 of the Coastal Act.
Site Characteristics and Land Use
The Project site is located within a fully developed and urbanized area north of East Coast Highway. The existing
BBPS is approximately 4,800 square feet, occupied by a single-story pump station building. The perimeter of the
pump station building is surrounded by concrete masonry walls on all sides with two entrance gates. The existing
facility is located on a parcel that is surrounded to the north, east, and west by a recreational vehicle storage area.
Seven acres of the site are planned for a mixed-use development. Surrounding land uses include residential,
commercial, and commercial recreational marine uses. Within the vicinity of the Project, East Coast Highway, also
known as State Route 1 is a 7 to 8 lane roadway including a bridge that crosses the Newport Bay Channel.
Bayside Drive is located to the east of the Project and is a 4 lane, designated secondary road.
Sea Level Rise Evaluation and Flooding
Several analyses have been conducted to understand the potential for anticipated Sea Level Rise (SLR) to impact
the BBPS and whether the facility is at risk.
In 2019, OC San prepared the Resiliency Study SP-152 (Resiliency Study) which examined the potential climate
change impact, including SLR on OC San facilities throughout its service area. The Resiliency Study used SLR
projections from the Rising Seas Report and California’s Fourth Assessment (Hall 2018) as representing the state
Orange County Sanitation District
Coastal Hazard Analysis
June 2022
www.arcadis.com
Coastal Hazards Analysis 2/3
of science for SLR for the Orange County area. Relying on Hall 2018, OC San used SLR increases of 1.54 feet
for 2050 and 3.71 feet for the year 2070 (Hazen 2019) to determine the potential risk of SLR in 2050 and 2070.
Using the 2050 and 2070 projections, the Resiliency study did not identify the BBPS site as having a significant
risk associated with SLR in Year 2050 or 2070 (Hazen 2019).
The design also considers the most conservative SLR reference from the State of California’s Sea Level Rise
Guidance (California Ocean Protection Council 2018) and Critical Infrastructure at Risk: Sea Level Rise Planning
Guidance for California’s Coastal Zone (California Coastal Commission 2021). According to the State of
California’s Sea Level Rise Guidance (California Ocean Protection Council 2018), the H++ scenario SLR for Los
Angeles are 2.6 feet by 2050, 6.4 feet by 2080, and 9.9 feet by 2100. According to the State Sea-Level Rise
Guidance, under the H++ SLR scenario, 2.7 feet of SLR can be expected by 2050, 6.6 feet by 2080, and 10.2 feet
by 2100 (California Coastal Commission 2021). The life expectancy of the new pump station will be around 50
years and the 6.6 feet SLR of Year 2080 based on California Coastal Commission 2021 will be used for
evaluation. The Our Coast Our Future (OCOF) map with projection of 6.6-ft SLR above mean high water (MHW)
is shown on Figure 2. A portion of the existing site is shown inundated based on the 2080 SLR of 6.6-ft SLR
Above MHW (11.15 feet NAVD88).
In developing the design for the new BBPS, the engineers used both SLR and potential tsunami run up elevations
when determining ground elevations for the Project. The BBPS design took a conservative approach of designing
to a minimum floor elevation of 14.00 feet NAVD88 as shown on Figure 1. Using this minimum floor elevation,
construction of the new BBPS would avoid SLR impacts for the anticipated life of the facility.
Flooding & Tsunami
According to the Federal Emergency Management Agency (FEMA) 2019 FIRM map, the Project is not located
within the 100 year flood hazard zones (Figure 3). As analyzed in the 2020 Recirculated Environmental Impact
Report (Michael Baker International 2020), less than significant impacts are anticipated in the event of the 100-
year flood.
The Project site is located within the designated tsunami zone (California Department of Conservation 2022).
During design of the BBPS, the engineers used the American Society of Civil Engineer’s (ASCE) Tsunami Design
Zone (TDZ) to determine the Maximum Considered Tsunami (MCT). In the event of a tsunami, the Project site
could be expected to see some minor flooding and the run up elevation at the Project site is 7.24 feet above MHW
or 11.74 feet NAVD88 (Figure 4 and 5). Figure 4 shows that in the event of tsunami, the parking areas may be
expected to see minor flooding. However, because the minimum floor elevation of the new BBPS would be 14.00
feet NAVD88, the new facilities would not be subjected to inundation.
Furthermore, onsite drainage is routed to the BBPS. The pump station is designed to operate even if the site is
inundated. Therefore, the risk of flooding the pump station is minimal.
Ground Improvements and Shoring
The Project site is located in an area of potential liquefaction. To mitigate the potential for liquefaction, static
settlement, and differential settlement, the new pump station will be excavated over 35 feet deep such that the
impacts from liquefaction are not anticipated. The ground improvement plan for the overall pump station site can
be referenced to the Geotechnical Design Report enclosed in the permitting package. Deep excavation will
require shoring and design is exploring several techniques including, but not limited to slurry diaphragm wall,
secant pile wall shoring, solid sheet pile wall, or a combination of shoring techniques.
Erosion and Shoreline Loss
Orange County Sanitation District
Coastal Hazard Analysis
June 2022
www.arcadis.com
Coastal Hazards Analysis 3/3
The location of the BBPS is located within a developed area and is not located at the shoreline or at the bank of
the Newport Bay Channel. The Project site is not subject to erosion and shoreline loss. The BBPS would not be
subjected to erosion or shoreline loss as a result of waves or wave run up. The Project does not include, and
does not require shoreline protection.
Summary and Conclusion
The BBPS Project has been analyzed with regards to postal coastal hazards, including SLR, flooding, tsunami,
and geologic stability. The new BBPS will be located in a developed area, including the location of the existing
BBPS. The new BBPS is designed to ensure that the facilities would not be subjected to the SLR and tsunami
impacts.
References:
Michael Baker International. 2020. Bay Bridge Pump Station and Force Mains Replacement Project (Project No.
5-67) 2020 Recirculated Environmental Impact Report. May 2020.
Arcadis. 2022. Preliminary Design Report Project No. 5-67 Bay Bridge Pump Station Replacement.
California Coastal Commission. 2021. Critical Infrastructure at Risk: Sea Level Rise Planning Guidance for
California’s Coastal Zone. Final Adopted Guidance. November 17, 2021.
California Department of Conservation. 2022. Orange County Tsunami Hazard Areas. Website located at
https://www.conservation.ca.gov/cgs/tsunami/maps/orange. Retrieved June 17, 2022
California Ocean Protection Council. 2018. State of California’s Sea Level Rise Guidance. March 14, 2018.
Hall, Alex, Neil Berg, Katharine Reich. (University of California, Los Angeles). 2018. Los Angeles Summary
Report. California’s Fourth Climate Change Assessment. Publication number: SUM-CCCA4-2018-007
Hazen. 2019. Climate Resiliency Study. Final Report. SP-152. November 27, 2019.
Our Coast Our Future Mapping Tool. 2022. Website located at: https://ourcoastourfuture.org/ retrieved June 10,
2022
Enc. [Enclosures]
Figure1
Site Plan
Orange County Sanitation District
Bay Bridge Pump Station Replacement Project
TRANSFORMER
ACCESS HATCH
GENERATOR
ROOM
RAISED
PLATFORM
ELECTRICAL
ROOM
ODOR CONTROL
AREA
PUMP STATION
(BELOW GRADE)
NORTH GATE
24' WIDE SWING GATE
SOUTH GATE
24' WIDE SWING GATE
WEST GATE
18' WIDE CANTILEVER
SLIDING GATE
MANHOLE COVERS, TYP.
SEE STRUCTL DWGS
RAISED
PLATFORM
45.57'
16.23'
9.52'
TOW = 29.33'
PEDESTRIAN GATE
8' HIGH WALL
10' HIGH WALL
8' HIGH WALL
F U T U R E A C C E S S R O A D
P A C I F I C
C O A S T HI G H W A Y
(E) BUILDING
STRUCTURE
OUTLINE
10' HIGH WALL
8' HIGH WALL
10' HIGH WALL
15' HIGH WALL
15' HIGH WALL
A2001
1
A20012
A2001 3
A2001
4
173.84'
57.26'
18.00'
4.44'
EXTERIOR WALL
BOUNDARY
SWITCHBOARD
106.32'
133.53'
39.48'
24.00'
43.99'
LANDSCAPE AREA
(SEE LANDSCAPE DWGS)
6' - 5 1/8"
LANDSCAPE AREA
(SEE LANDSCAPE DWGS)
TOW = 24.00'
TOW = 24.00'
TOW = 24.00'
TOW = 24.67'
TOW = 23.33'
TOW = 22.00'
TOW = 22.00'
6' - 10"
23' - 7 5/8"
41' - 7 7/8"
TOW = 22.00'
9
TOW = 24.67'
TOW = 29.33'
5.07'
TOW = 23.33'
TOW = 23.33'
TOW = 29.33'
TOW = 29.33'
SWITCHBOARD
PLATFORM
(REMOVABLE)
SCALE: 1/8" = 1'-0"
SITE PLAN
FF = 14.17
FF = 15.50
FF = 14.00
Figure2
6.6-Foot Sea Level Rise Map
Orange County Sanitation District
Bay Bridge Pump Station Replacement Project
Project Location
Source: Our Coast Our Future: https://ourcoastourfuture.org/hazard-map/
BAY BRIDGE PUMP STATION
PROJECT SITE
Figure3
FEMA Map
Orange County Sanitation District
Bay Bridge Pump Station Replacement Project
Legend
Offshore Tsunami Amplitude
Runup Elevation Point
Inundation Depth Point
Earthquake Induced Regional Ground
Subsidence (ft)
Tsunami Design Zone
World Imagery
Low Resolution 15m Imagery
High Resolution 60cm Imagery
High Resolution 30cm Imagery
Citations
60cm Resolution Metadata
Maxar | City of Newport Beach, County of Los Angeles, Esri, HERE, Garmin, INCREMENT P, USGS, Bu
Orange County Sanitation District
Bay Bridge Pump Station Replacement Project
GENERATOR BLDG
ELECTRICAL BLDG
ODOR CONTROL AREA
ASCE Tsunami Hazard Tool with Bay BridgePump Station
BAY BRIDGE
PUMP STATION
Source: ASCE Tsunami Hazard Tool - ASCE Tsunami Design Geodatabase Version 2016-1.0
Figure
4
Legend
Offshore Tsunami Amplitude
Runup Elevation Point
Inundation Depth Point
Earthquake Induced Regional Ground
Subsidence (ft)
Tsunami Design Zone
World Imagery
Low Resolution 15m Imagery
High Resolution 60cm Imagery
High Resolution 30cm Imagery
Citations
60cm Resolution Metadata
Maxar | City of Newport Beach, County of Los Angeles, Esri, HERE, Garmin, INCREMENT P, USGS, Bu
Runup Elevation Point
Latitude Longitude Runup Elevation (MHW) (ft.)Runup Elevation (NAVD88) (ft.)
33.61667 -117.90222 7.24 11.74
Earthquake Induced Regional Ground Subsidence (ft.): 0
Zoom to
ASCE Tsunami Hazard Tool with RunupElevation
Orange County Sanitation District
Bay Bridge Pump Station Replacement ProjectSource: ASCE Tsunami Hazard Tool - ASCE Tsunami Design Geodatabase Version 2016-1.0
Figure5
Attachment F
Water Quality Management Plan
Memo
1/1
SUBJECT
Water Quality Management Plan PROJECT
5-67 Bay Bridge Pump Station Replacement Project
TO
Orange County Sanitation District
FROM
Tim J. Rumbolz, CPESC, QSD, QISP
timothy.rumbolz@arcadis.com
408-797-2009
DATE
June 2023
This memo is to discuss the Water Quality Management Plan (WQMP) for the Bay Bridge Pump Station (BBPS)
Replacement project. Per the City of Newport Beach Coastal Development Permit application, Supplemental
Materials Checklist, this memo will present the WQMP as specified in Section 21.35.050.
The existing ground surface at the BBPS site (pre-construction) consists of impermeable surfaces, primarily
asphalt paving and some small structures. No significant changes to the ground surface type are planned for the
project. During construction, water quality will be controlled using an Erosion and Sediment Control Plan (ESCP)
designed by a QSD (Qualified SWPPP Developer). Note: the project disturbance area is under one acre, so a
SWPPP is not required.
Site grading is designed to direct stormwater flows within the paved area to onsite drainage inlets (drop inlets /
catch basins) and conveyed in a separate piping system. This system will consist of three exterior catch basins as
well as three floor drains located within the Odor Control Area, and the storm drain pipes are sized to capture 10-
year storm. The onsite drainage discharged to the pump station wet well will eventually be conveyed to the
Orange County Sanitation District (OC San) Treatment Plant No. 2 for treatment via the existing sanitary sewer
system. The onsite drainage system is shown as the orange-highlighted piping on Drawings C1003 and M1011.
The amount of onsite flow is summarized in Table 1.
Table 1 Onsite 10-Year Stormwater Runoff
Condition Onsite Drainage Area
Runoff Flow
ft3/s gpm
Existing Pump Station* 3,877 SF / 0.09 acres 0.22 99
Proposed Pump Station* 14,592 SF / 0.33 acres 0.82 368
*The pump station onsite drainage area does not include pump station rights within the Public Right of Way.
For the proposed pump station, over 90% of the onsite drainage will flow to the pump station wet well and less
than 10% of onsite drainage for the landscape and driveway will discharge to the existing Caltrans storm drain.
The project will also reroute the existing flows from areas that are not impacted by the project (offsite drainage).
The offsite drainage will be collected in a series of four stormwater catch basins located around the perimeter of
the BBPS. The catch basins will be connected via underground piping to the existing Caltrans storm drain system.
See the blue-highlighted piping on Drawing C1003 for details. Offsite drainage flows are not impacted by the
project.
Enc. Drawing C1003 – Grading and Drainage Plan
Drawing M1011 – Odor Control Area, Mechanical & Plumbing Plan
PB
PBPB
PB
CONC.
PCH
CONC.
CB DWY
24W(
D
)
24W(
D
)
24W(
B
)
24W(
B
)
24W(B
)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(B)
24W(D)24W(D)
21
S
E
W
(
C
)
21
S
E
W
(
C
)
24SD(C)
24SD(C)
24SD(C)
24SD(C)
24SD(C)
24SD(C)
18
S
D
(
C
)
18
S
D
(
C
)
18
S
D
(
C
)
30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)30SD(C)
18
S
D
(
C
)
18
S
D
(
C
)
CB
CB
30W
(
D
)
30W
(
D
)
30W
(
D
)
30W
(
D
)
30W
(
D
)
30W
(
D
)
30W(
D
)
30W
(
D
)
30W
(
D
)
30W
(
D
)
30W
(
D
)
ST(B)
ST(B)
ST(B
)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)
ST(B)ST(B)
ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)ST(B)
J
J
CTV
(
B
)
CTV
(
B
)
CTV(
B
)
CTV(
B
)
CTV(B
)
CTV(B
)
CTV(B
)
CTV(B)
CTV(B)
CTV(
B
)
CTV(
B
)
CT
V
(
B
)
CT
V
(
B
)
CTV(
B
)
CTV(B)
CTV(B)
CTV(B)
CTV(B)CTV(B)CTV(B)
CTV
(
B
)
CTV
(
B
)
CTV(B)CTV(B)CTV(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)
TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)TS(B)
D
S
ELECTRICAL ROOM
FF=15.50
ODOR CONTROL AREA
FF=14.00
1211
11
1
4
13
12
1
3
15
13
16
17
GENERATOR ROOM
FF=14.17
OC SA
N
PRIVAT
E
CALTRANS
CAL
T
R
A
N
S
PRIV
A
T
E
P
R
O
P
E
R
T
Y
PRIVATE
PRIVATE PROPERTY
PAD=15.50
FS=11.80±
MATCH EX.
FS=13.75
INV=8.00
FS=13.50
FS=13.50
FS=13.50±
MATCH EX.FS=13.25±
MATCH EX.
FG=11.65
TW=16.95
MATCH EX.
FG=16.65
PAD=14.00FS=12.45
FS=12.70
G.
B
.
FL=12.82
FL=12.98
FL=12.06
FL=12.14
FS=14.00
FS=12.00
FS=11.80
FS=11.50
EX. 18" RCP
INV(S)=8.03
INV(E)=8.53
FS=13.50
FS=13.40
FS=13.50
FS=13.60
FL=13.15
FL=13.05
FS=13.00
FS=13.60
FS=13.15
FS=12.85
FL=12.46
MATCH EX.
FS=13.50
FS=13.25
FS=13.25
FS=13.25
FG=15.00
FS=11.70
PROTECT EXISTING
CATCH BASIN IN PLACE
INV=8.00
FS=14.13
FS=13.55
FS=13.35
FS=12.60
FS=12.30
HPFL=13.30
2.7
%
1%
2%
FS=13.15
RIM=13.75±
INV(E)=10.50
INV(S)=9.00
INV=10.89±
MATCH EX.
INV=8.00
FS=13.50
FG=14.00
FS=12.22
1%
FS=13.67
FS=13.67
FS=13.67
FL=13.24
MATCH EX.
STORM DRAIN C
PROFILE
6"HDPE (SD)
6"HDPE (SD)
8"HDPE (SD)
3
C5005
5
C3004
STORM DRAIN D
PROFILE6"HDPE (SD)
1/2"CU (POTW)
8"HDPE (SD)
3
C3004
STORM DRAIN B
PROFILE
FL=11.78
8"HDPE (SD)
8"HDPE (SD)
STORM DRAIN E
PROFILE
6"HDPE (SD)
FS=13.96
2
C3003
STORM DRAIN A
PROFILE
2
C3003
STORM DRAIN A
PROFILE
STORM DRAIN A
PROFILE
1
C3003
4
C3004
18"RCP (SD)
FS=13.95
6"HDPE (SD)6
C3004
6"HDPE (SD)
FS=13.10
FS=11.60±
MATCH EX.
ACCESS ROAD - BY OTHERS
MH-1
N:2172040.57
E:6058631.75
RIM=13.15
INV IN=10.52
INV OUT=10.42
CB-1
N:2172025.01
E:6058699.66
GRATE=13.20
INV IN=11.25
INV OUT=11.15
FS=13.10
CB-5
N:2171970.24
E:6058615.60
RIM=11.40
INV=9.00
CB-2
N:2171966.44
E:6058613.04
GRATE=11.50
INV IN=9.73
INV OUT=9.63
CB-3
N:2171942.25
E:6058705.02
GRATE=13.50±
INV(W)=8.78
INV(S)=8.68
CB-4
N:2172001.70
E:6058721.68
GRATE=12.90
INV=8.50
MH-2 (SOLID)
N:2171963.84
E:6058740.37
RIM=13.40
INV (W)=7.64
INV (N)=7.35
INV (E)=7.00
3
C3003
-
M3008
3
C3004
STORM DRAIN B
PROFILEFL=13.17
FL=13.02
FL=12.22
FL=11.42
FS=15.46
FS=15.46
TYP.
TYP.
FS=13.25
G.B
.
DEMO EXISTING GRAVITY WALL
(SEE D1001), STRAIGHTEN
SIDEWALK EDGE AS SHOWN.
FS=11.55
G.B.
FS=13.70
FS=13.40
REMOVE AND REPLACE
EXISTING LIGHT POLE
IN-KIND, AS NECESSARY
DURING CONSTRUCTION,
PER PUBLIC WORKS
REQUIREMENTS
-
C5003
CB-6 (GRATE INLET)
N:2171952.08
E:6058766.92
GRATE=13.25
INV 6" IN (N)=7.80
INV 6" IN (SW)=6.96
INV 6" IN (NW)=5.77
INV 8" OUT (S)=2.50
FS=13.67
GRATE=13.45
INV=11.73
FS=13.35
0.7
%
0.7
%
FS=15.36
FS=15.46
FS=15.36
2%
0.5%
2.7%
2.7%
FS=13.10
FS=15.36
FS=15.36
FS=13.52
FS=13.15
FS=13.38
FS=13.70
FS=13.30
14
17
1
2
3
4
3
7
4
18
9
9
5
12
13
16
11
7
19
5
1
17
3
7
16
2
12
10
8
16
2
15
16
18
6
13
10
13
21
21
21
21
21
21
21
22
22
21
21
3
20
20
PROPOSED BACK OF SIDEWALK EDGE
GRATE=13.20
INV=11.25
A
5007
A
B
5007
B
C
5007
C
C1003
18
GRADING AND DRAINAGE PLAN
ALAN PROCTOR
PRAVEEN YERRA
JESUS LOPEZ
10'20'0'10'
SCALE: 1" = 10'
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
MARK DATE APPR.DESCRIPTION
DW
G
:
C
:
\
U
s
e
r
s
\
a
l
a
n
.
p
r
o
c
t
o
r
\
A
C
C
D
o
c
s
\
A
r
c
a
d
i
s
\
A
U
S
-
3
0
0
0
1
6
8
7
-
O
C
S
D
–
5
-
6
7
B
a
y
B
r
i
d
g
e
P
u
m
p
S
t
a
t
i
o
n
\
F
D
S
\
A
u
t
o
C
A
D
\
S
H
E
E
T
S
\
C
I
V
I
L
\
5
-
6
7
-
C
1
0
0
3
.
d
w
g
DA
T
E
:
A
p
r
2
4
,
2
0
2
3
1
1
:
0
8
a
m
U
S
E
R
:
A
l
a
n
.
P
r
o
c
t
o
r
DRAWING NO.
(IF NOT 2"-SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ORANGE COUNTY SANITATION DISTRICT
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
DRAWN BY:
DESIGNED BY:
CHECKED BY:
BAY BRIDGE PUMP STATION REPLACEMENT 5-67
302OFSHEET NO.:
Underground Service Alert
TWO WORKING DAYS BEFORE YOU DIG
Call:811
CONSTRUCTION NOTES:
1 CONSTRUCT 4" AC ON 6" ABC ON 12" COMPACTED SUBGRADE
(PER FINAL GEOTECH REPORT - DATED: TBD).
2 REMOVE AND REPLACE EXISTING SIDEWALK IN KIND ANY
PORTIONS THAT ARE DAMAGED OR REMOVED DURING
CONSTRUCTION. REPLACE SIDEWALK TO THE NEAREST FULL
SECTION, PER CALTRANS STD DWG A87A, SEE SHEET C5002.
3 CONSTRUCT 9" PCCP ON 4" ABC ON 12" COMPACTED SUBGRADE
SUBGRADE (PER FINAL GEOTECH REPORT - DATED: TBD).
4 CONSTRUCT 9" THICK PCC VALLEY GUTTER PER DETAIL 2 ON
SHEET C5005.
5 CONNECT TO BUILDING FLOOR DRAIN SEE SHEET M1011 FOR
CONTINUATION.
6 18" RCP (D2000) STORM DRAIN, SEE PROFILE 3 ON DWG C3003.
7 FURNISH AND INSTALL 6" STORM DRAIN CLEAN OUT PER OC SAN
STD. DWG S-073 AND S-015.
8 CONSTRUCT CONCRETE COLLAR, REFER TO SPPWC STANDARD
PLAN 380-4.
9 FURNISH AND INSTALL 30" DRAIN BASIN (NYLOPLAST DWG #
7001-110-193 OR EQUAL) WITH H-20 RATED SOLID COVER OR
STANDARD GRATE INLET, AS NOTED ON PLAN.
10 FURNISH AND INSTALL 12" DRAIN BASIN (NYLOPLAST DWG #
7001-110-189 OR EQUAL) WITH H-20 RATED STANDARD GRATE INLET.
11 18" RCP STORM DRAIN, SEE PROFILE 1 ON DWG C3003.
12 FURNISH AND INSTALL STORM DRAIN MANHOLE JUNCTION
STRUCTURE PER SPPWC STANDARD PLAN 321-2 WITH SOLID COVER.
13 FURNISH AND INSTALL DRAINAGE STRUCTURE WITH GRATED
INLET TYPE G1 PER CALTRANS STD. DET. D73B, SEE SHEET C5004.
14 INSTALL 18" RCP STORM DRAIN PENETRATION THROUGH BASE OF
WALL, MATCH EXISTING OFFSITE GUTTER FLOW LINE.
15 FURNISH AND INSTALL GRATED LINE DRAIN WITH DUCTILE IRON HEEL
PROOF GRATE INLET WIDTH 6.1 INCH, 2% MIN. SLOPE TO CB-1.
16 CONTRACTOR SHALL REMOVE INTERFERING PORTIONS OF
EXISTING SIDEWALK, CURB AND GUTTER AND DRIVEWAY. MATCH
EXISTING ELEVATIONS TO MAINTAIN DRAINAGE. CONSTRUCT ROLL
CURB AND GUTTER TYPE E PER CALTRANS STD. DET A87A, SEE
DETAIL ON SHEET C5002.
17 UNDERGROUND CONCRETE STRUCTURE, SEE STRUCTURAL
SHEET S1004 FOR CONCRETE ROOF SLAB PLANS.
18 CONSTRUCT CONCRETE PAD, SEE STRUCTURAL PLANS.
19 CONSTRUCT 8"X8" WALL OPENING AT LOW POINT FOR DRAINAGE.
20 CONSTRUCT RETAINING WALL, SEE STRUCTURAL PLANS.
21 FURNISH AND INSTALL HDPE PIPE (SSPWC 207-18, MIN. PS-50),
LENGTH, SIZE, AND SLOPE AS NOTED ON PLAN AND PROFILE
22 CONSTRUCT BOLLARDS PER OC SAN STD. DET. S-120 AND
S-121. SEE SHEET C1002 FOR BOLLARD LAYOUT AND SPACING.
NOTES:
·GROUND SURFACE ELEVATIONS AND COORDINATES ARE PROVIDED
FOR CONTRACTOR'S REFERENCE ONLY, AND REPRESENT THE
DESIGN INTENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO LAY
OUT THE SITE SO THAT A SMOOTH AND CONTINUOUS GROUND
SURFACE WITH ADEQUATE DRAINAGE IS PROVIDED.
·CONTRACTOR TO VERIFY ALL EXISTING GRADE ELEVATIONS.
-
S1004
1
C5002
1
C5004
2
C5005
1
C3003
-
C1002
3
S5303
1
C5006
FOR CONTINUATION
SEE M1011
FOR CONTINUATION
SEE M1011
DISCHARGE TO
UPSTREAM
MANHOLE AND THEN
TO WET WELL
CONNECTED TO
CITY'S EXISTING
STORM DRAIN
SYSTEM
CONNECTED TO
CITY'S EXISTING
STORM DRAIN
SYSTEM
OFFSITE DRAINAGE
ONSITE DRAINAGE
O1
OA OB
O2 PEDESTRIAN
DOORS
ROLL-UP DOOR
HOSE BIBB
SHUT-OFF VALVE
BY OTHERES
MAGNESIUM
HYDROXIDE CHEMICAL
TANK BY OTHERS
CALCIUM NITRATE
CHEMICAL TANK BY
OTHERS
PUMP SKID
BY OTHERS
TO WET WELL
3" CAP3" CAP
HOSE BIBB
18' - 9"18' - 9"
1 1/4" Cu (POTW)
1-1/4" TEE 1 1/4" Cu (POTW)
1 1/4" Cu (POTW)
1-1/4" X 1"
REDUCER
1" (POTW)
1" Cu (POTW)
1-1/4" X 1" REDUCER
1" CPVC (CA(NO3)2)
3" CPVC (MG(OH)2)
1" CPVC (MG(OH)2)
3" CPVC (CA(NO3)2)
1" CPVC (CA(NO3)2)
1" CPVC (MG(OH)2)
8'
-
1
"
BY OTHERS
BY OTHERS
SEE SHEET C1004
FOR CONTINUATION
FROM WET WELL
WALL CLAMP, TYP.
HOSE RACK TYP.
HOSE RACK
55JSFS638
55JSFS639
HOSE RACK
HOSE BIBB
BACKFLOW PREVENTER
SCRUBBER
FOUL AIR FAN
DUCT BUTTERFLY DAMPER
55JFAN170
55JFV870
10" FRP (FA)
DUCT EXPANSION
JOINT
MAGNESIUM HYDROXIDE
FILL STATION WITH SPILL
CONTAINMENT
CALCIUM NITRATE FILL
STATION WITH SPILL
CONTAINMENT
55JSFS634
4'
-
0
"
A
M3007
B
M3008
C
M3008
7' - 3"7' - 3"
7' - 3"
5'
-
9
"
4' - 0"
1/2" TRAP PRIMER SEE SHEET C1003
FOR CONTINUATION TO CONNECTION
TO THE 8" P-TRAP
1 1/2" CPVC (POTW)
1 1/2" X 1 1/4"
REDUCER
11' - 6"
TO WET WELL
MAGNESIUM HYDROXIDE
EYEWASH STATION CALCIUM NITRATE
EYEWASH STATION
ELECTRICAL PANELS
CHEMICAL LOADOUT
EYEWASH STATION
8" FRP (FA)16" FRP (FA)
9' - 0"
2' - 6"
AIR FLOW
METER
6
M5003
6
M5003 1"CAP
O1
OA
O2
TO MANHOLE
18' - 9"18' - 9"
TO MANHOLE
6" PLUG VALVE WITH
POST INDICATOR
FOR CONTINUATION
SEE SHEET C1003
TO CATCH BASIN
SEE SHEET C1003
FOR CONTINUATION
ED
1/2" CONDENSATE
DRAIN WITH BALL VALVE
ED
1/2" CONDENSATE
DRAIN WITH BALL VALVE
6" DI (D)
AD
AD AD6" CPVC (CHEMD)
2" DI (D)
2" DI (D)
2" DI (D)
1" DI (D)
3' - 7"7' - 7"
CONNECT TO 1" NPT
DRAIN VALVE AT THE
CARBON SCRUBBER
CONNECT TO 1" NPT
DRAIN VALVE AT THE
FOUL AIR FAN
4" DI (D)
4" DI (D)
55JPV540A
55JPV540B
7' - 8"
3' - 6"
10
"
9'
-
8
"
6'
-
7
"
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2 3 4 5 6 7 8 9 10
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 4/20/2023 9:27:41 AM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-M-BBPS.rvt
M1011
BAY BRIDGE PUMP STATION
REPLACEMENT
ODOR CONTROL AREA
MECHANICAL & PLUMBING PLAN
302142
CATHERINE WOO
ROSHANI SHRESTHA
HARMIK AGHANIAN
SCALE: 1/4" = 1'-0"
ODOR CONTROL AREA MECHANICAL PLAN
SCALE: 1/4" = 1'-0"
ODOR CONTROL AREA DRAINAGE PLAN
0'4'8'2'0'4'8'2'
6
M5003
MARK DESCRIPTION DATE APPR.
OFFSITE DRAINAGE
ONSITE DRAINAGE
Attachment G
Visual Impact Analysis_Rev 1
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2345678910
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:13 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt
A9001
BAY BRIDGE PUMP STATION
REPLACEMENT
VISUAL IMPACT ANALYSIS - 01
302
JOHN ERIC CHUNG
RUOTIAN CAI
SIEGFREDO LOPEZ
EXISTING PUMP STATION
PROPOSED NEW PUMP STATION
EAST COAST HIGHWAY VIEW CORRIDORS
PER BACK BAY LANDING PLANNED
COMMUNITY DEVELOPMENT PLAN (PC-9)
VIEW CORRIDOR IDENTIFIED IN 2014
VIEW CORRIDOR IDENTIFIED IN 2016
VIEW CORRIDOR COMPARISON
THE PROPOSED NEW PUMP STATION MAINTAINED THE VIEW CORRIDOR IDENTIFIED IN 2014. THE FUTURE COASTAL PUBLIC VIEW
TOWER AND BLUFF IS UNOBSTRUCTED ON THE VIEW CORRIDOR. IN RESPECT TO THE BACK BAY LANDING DEVELOPMENT, A
LANDSCAPE SETBACK IS PROVIDED IN FRONT OF PCH PERIMETER WALL. THE BUILDING MASSING AND MATERIALS ARE
ADDRESSED TO INTEGRATE WITH SURROUNDING SITE CONTEXT AND NATURAL ENVIRONMENT.
NOTES: THIS DRAWING CONTAINS COLOR DIGITAL PHOTOGRAPHS
AND/OR COLOR RENDERINGS. SEE THE ELECTRONIC VERSION OF
THIS SHEET FOR MAXIMUM CLARITY.
MARK DESCRIPTION DATE APPR.
1 LCP RESUBMITTAL 06/2023
1
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2345678910
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:46 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt
A9002
BAY BRIDGE PUMP STATION
REPLACEMENT
VISUAL IMPACT ANALYSIS - 02
302
JOHN ERIC CHUNG
RUOTIAN CAI
SIEGFREDO LOPEZ
V1
V2
V3 V4 V5
V6
EXISTING
NOTES: THIS DRAWING CONTAINS COLOR DIGITAL PHOTOGRAPHS
AND/OR COLOR RENDERINGS. SEE THE ELECTRONIC VERSION OF
THIS SHEET FOR MAXIMUM CLARITY.
MARK DESCRIPTION DATE APPR.
1 LCP RESUBMITTAL 06/2023
V1 -VIEW FROM NORTH OF CASTAWAYS PARK V2 -VIEW FROM SOUTH OF CASTAWAYS PARK V3 -VIEW FROM WEST OF PACIFIC COAST HIGHWAY
PROPOSED
EXISTING
PROPOSED
EXISTING
PROPOSED
1
V1
V2
V3 V4 V5
V6
NOTES: THIS DRAWING CONTAINS COLOR DIGITAL PHOTOGRAPHS
AND/OR COLOR RENDERINGS. SEE THE ELECTRONIC VERSION OF
THIS SHEET FOR MAXIMUM CLARITY.
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2345678910
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:39:19 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt
A9003
BAY BRIDGE PUMP STATION
REPLACEMENT
VISUAL IMPACT ANALYSIS - 03
302
Designer
Author
Checker
MARK DESCRIPTION DATE APPR.
1 LCP RESUBMITTAL 06/2023
V4 -VIEW FROM EAST OF PACIFIC COAST HIGHWAY V5 -VIEW FROM COAST HIGHWAY & N BAYSIDE DR V6 -VIEW FROM N BAYSIDE DR
EXISTING
PROPOSED
EXISTING
PROPOSED
EXISTING
PROPOSED
1
Attachment H
Site Photos for Notice of
Application Filing
Attachment H – Site Photos for
Notice of Application Filing
250 E Coast Highway,
Newport Beach, CA 92660
arcadis.com 1
Site Photos for Notice of Application Filing
Location: 250 E Coast Highway, Newport Beach, CA 92660
Photograph taken by: Xintong Qiu
Date: 5/25/2023
Photograph
Number Photograph Description
1
Notice on
Existing Bay
Bridge Pump
Station Gate
Facing PCH
2
Notice on
Existing Bay
Bridge Pump
Station Gate
Facing PCH
Attachment H – Site Photos for
Notice of Application Filing
250 E Coast Highway,
Newport Beach, CA 92660
arcadis.com 2
Photograph
Number Photograph Description
3
Notice on
Existing Bay
Bridge Pump
Station Gate
Facing PCH
4
Notice on
Fence of
Existing Valve
Vault West of
the Channel
Attachment H – Site Photos for
Notice of Application Filing
250 E Coast Highway,
Newport Beach, CA 92660
arcadis.com 3
Photograph
Number Photograph Description
5
Notice on
Fence of
Existing Valve
Vault West of
the Channel
Attachment I
Updated Architectural Drawings
TRANSFORMER
ACCESS HATCH
GENERATOR
ROOM
RAISED
PLATFORM
ELECTRICAL
ROOM
ODOR CONTROL
AREA
PUMP STATION
(BELOW GRADE)
NORTH GATE
24' WIDE SWING GATE
SOUTH GATE
24' WIDE SWING GATE
WEST GATE
18' WIDE CANTILEVER
SLIDING GATE
MANHOLE COVERS, TYP.
SEE STRUCTL DWGS
RAISED
PLATFORM
45.57'
16.23'
9.52'
TOW = 29.33'
PEDESTRIAN GATE
8' HIGH WALL
10' HIGH WALL
8' HIGH WALL
F U T U R E A C C E S S R O A D
P A C I F I C
C O A S T HI G H WA Y
(E) BUILDING
STRUCTURE
OUTLINE
10' HIGH WALL
8' HIGH WALL
10' HIGH WALL
15' HIGH WALL
15' HIGH WALL
A2001
1
A20012
A2001 3
A2001
4
173.84'
57.26'
18.00'
4.44'
EXTERIOR WALL
BOUNDARY
SWITCHBOARD
106.32'
133.53'
39.48'
24.00'
43.99'
LANDSCAPE AREA
(SEE LANDSCAPE DWGS)
6' - 5 1/8"
LANDSCAPE AREA
(SEE LANDSCAPE DWGS)
TOW = 24.00'
TOW = 24.00'
TOW = 24.00'
TOW = 24.83'
TOW = 22.83'
TOW = 21.50'
TOW = 21.50'
6' - 10"
23' - 7 5/8"
41' - 7 7/8"
TOW = 21.50'
9
TOW = 24.83'
TOW = 29.33'
5.07'
TOW = 22.83'
TOW = 22.83'
TOW = 29.33'
TOW = 29.33'
SWITCHBOARD
PLATFORM
(REMOVABLE)
RECESSED
KNOXBOX.
LOCATION TO BE
APPROVED BY THE
FIRE DEPT. MOUNT 5'
ABOVE FINISHED
GRADE.
RECESSED
KNOXBOX.
LOCATION TO BE
APPROVED BY THE
FIRE DEPT. MOUNT 5'
ABOVE FINISHED
GRADE.
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2345678910
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:06 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt
A1001
BAY BRIDGE PUMP STATION
REPLACEMENT
SITE PLAN
30259
JOHN ERIC CHUNG
RUOTIAN CAI
SIEGFREDO LOPEZ
SCALE: 1/8" = 1'-0"
SITE PLAN
MARK DESCRIPTION DATE APPR.
1 LCP RESUBMITTAL 06/2023
1
1
A B
ST-01
STU-02
MTL-01 STU-01
SITE GRADING LINE
BEHIND
SITEWALK
PT-02
4'
-
0
"
18' - 0"14' - 0"14' - 0"18' - 0"14' - 0"14' - 0"
STU-02 STU-01 ST-01
2'
-
1
0
"
8'
-
6
"
3'
-
6
"
4'
-
6
"
OA OB
9
AVG. SITE LEVEL
EL 13.50'
MTL-01
SWING GATE
PROP. LINE
SITEWALK RAILING
(TO MATCH EXISTING
OR PUBLIC WORK
REQ.)
PROP. LINE
A4005
6 SIM.
STU-01
MTL-01
6'
-
1
0
"
4'
-
6
"
CONTROL
JOINT, TYP.
4" H METAL
COPING, TYP.
1'
-
0
"
7'
-
0
"
STUCCO TO
STONE VENEER
TRANSITION, TYP.
TOW = 24.83'
TOW = 22.83'TOW = 21.50'TOW = 21.50'
1' - 0"1'
-
0
"
A4005
9 SIM.
ABC
ODOR CONTROL TOW
EL 29.33'
18' - 0"18' - 0"18' - 0"19' - 2"
ST-01 STU-01
STU-02
MTL-01 STU-01
ST-01
4'
-
0
"
6'
-
6
"
4'
-
1
0
"
8"
MTL-01
10
'
-
6
"
OAOB
AVG. SITE LEVEL
EL 13.50'
19' - 8"19' - 8"18' - 5"18' - 0"
16
'
-
0
"
12
'
-
1
0
"
SWING GATE
PROP. LINE
PROP. LINE
A4005
5
1' - 6"
4" H METAL
COPING, TYP.
CONTROL
JOINT, TYP.
2" W METAL
REVEAL, BRONZE
MTL-01
CONTROL
JOINT, TYP.
2'
-
4
"
10
'
-
6
"
8" H METAL
COPING
TYP.
4' - 0"
STUCCO TO
STONE VENEER
TRANSITION, TYP.
TOW = 24.00'TOW = 24.00'
1'
-
6
"
2' - 0"
5'
-
0
"
RECESSED
KNOXBOX.
LOCATION TO BE
APPROVED BY THE
FIRE DEPT. MOUNT 5'
ABOVE FINISHED
GRADE.
A4005
9
MATERIAL LEGEND ( SEE DETAILS IN MATERIAL SCHEDULE )
CODE DESCRIPTION COLOR
STU-01
ST-01
PT-02
CMU-01
GL-01
STONE VENEER, STACKED STONE
STUCCO
PAINTING
EXPOSED CMU, TAN/ PRECISION
LAMINATED, FRITTED GLAZING
OFF WHITE
LIGHT BROWN
BRONZE
CREAM
BRONZE
STU-02 STUCCO MEDIUM BROWN
MP-01 METAL PANEL, ANODIZED BRONZE
MTL-01 METAL COATING BRONZE
ODOR CONTROL TOW
EL 29.33'
ST-01
MTL-01STU-02
TYP.
4' - 0"
O1O2
AVG. SITE LEVEL
EL 13.50'
PROP. LINE
15
'
-
1
0
"
3'
-
6
"
11
'
-
1
0
"
8"
3'
-
6
"
TOW = 29.50'TOW = 29.50'
STU-01
8" H METAL
COPING
4" H METAL
COPING, TYP.
2" W METAL
REVEAL, BRONZE
16' - 4"14' - 8"16' - 0"14' - 8"
CONTROL
JOINT, TYP.
STUCCO TO
STONE VENEER
TRANSITION, TYP.
5'
-
0
"
RECESSED
KNOXBOX.
LOCATION TO BE
APPROVED BY THE
FIRE DEPT. MOUNT 5'
ABOVE FINISHED
GRADE.
1 2 3
ST-01STU-01ST-01 MTL-01MTL-01 MTL-01
AVG. SITE LEVEL
EL 13.50'
SIDEWALK
2'
-
4
"
10
'
-
6
"
10
'
-
0
"
CANTILEVER SLIDE GATE
SITEWALK RAILING
(TO MATCH EXISTING)
12
'
-
1
0
"
TOW = 24.00'
TOW = 24.00'
PROP. LINE
1'
-
6
"
8'
-
6
"
TOW = 24.83'
A4005
7
4"6' - 3"34' - 8"16' - 0"18' - 0"1' - 8"
CONTROL
JOINT, TYP.
4" H METAL
COPING, TYP.
STUCCO TO
STONE VENEER
TRANSITION, TYP.
TOW = 22.00'
TOW = 22.00'
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2345678910
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:11 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt
A2001
BAY BRIDGE PUMP STATION
REPLACEMENT
SITE ELEVATIONS
30266
JOHN ERIC CHUNG
RUOTIAN CAI
SIEGFREDO LOPEZ
SCALE: 1/8" = 1'-0"
SITE -SOUTH ELEVATION
SCALE: 1/8" = 1'-0"
SITE -NORTH ELEVATION
SCALE: 1/8" = 1'-0"
SITE -EAST ELEVATION
SCALE: 1/8" = 1'-0"
SITE -WEST ELEVATION
MARK DESCRIPTION DATE APPR.
1 LCP RESUBMITTAL 06/2023
1
1
1
1
8'
-
0
"
4"
PE
R
S
T
R
U
C
T
R
L
3"
MTL-01
6063 T6 AL 1"X6"-0.100" T&G
SLAT INFILL
MORTICE LOCKSET W/
CYBERKEY CYLINDAR &
SS LEVER HANDLES
(2) S.S. CANE BOLT
MOUNT TO BASE OF
GATE AND CORE STRIKE
HOLES 3" DEEP ANCHOR
INTO 12" SQ. CONCRETE
POUR
TYP.
6"
4"2"11' - 6"11' - 6"2"4"V.I.F.
24' - 0"
MTL-01
1'
-
6
"
1' - 0"
6"
6"
(1) HEAVY DUTY
GATE WHEEL
(2) 4"X4"X1/4" STL GATE
POST W/ 1/4" THK STL
PLATE CAP. PAINT TO
MATCH FRAME
6063 T6 AL 3"X2"X1/4" U-
CHANNEL INFILL PANEL
FRAME FACE-MOUNTED
(6) WELD-ON HEAVY DUTY
BARREL HINGE. PAINT TO
MATCH FRAME
PER CODE
3'
-
0
"
6063 T6 AL 3"X2"X1/4" GATE
FRAME BEHIND
3"
4"
10
'
-
0
"
MTL-01
6063 T6 AL 1"X6"-0.100"
T&G SLAT INFILL
MORTICE LOCKSET W/
CYPERKEY CYLINDAR
& SS LEVER HANDLES
TY
P
.
6"
(8) WELD-ON HEAVY
DUTY BARREL HINGE.
PAINT TO MATCH FRAME
PE
R
S
T
R
U
C
T
R
L
4"2"11' - 6"11' - 6"2"4"V.I.F.
24' - 0"
6"
6"
1'
-
6
"
1' - 0"
MTL-01
(2)S.S. CANE BOLT
MOUNT TO BASE OF
GATE AND CORE STRIKE
HOLES 3" DEEP ANCHOR
INTO 12" SQ. CONC POUR
PE
R
C
O
D
E
3'
-
0
"
(1)HEAVY DUTY
GATE WHEEL
(2)4"X4"X1/4" THK STL
GATE POST W/ 1/4" THK
STL PLATE CAP. PAINT
TO MATCH FRAME
6063 T6 AL 3"X2"X1/4" U-
CHANNEL INFILL PANEL
FRAME FACE-MOUNTED
6063 T6 AL 3"X2"X1/4"
GATE FRAME BEHIND
10' - 0"
R.O.
18' - 0"
9'
-
0
"
4"
28' - 0"
CONC.
FOUNDATION PER
MANUF. SPECS
ALUMN. FRAME
SS BOTTOM
TRACK
MTL-01
STANDARD
CARRIAGE
WALL MOUNTED
TOP GUIDE
WALL-MOUNTED
GATE RECEIVER
WALL-MOUNTED
BOTTOM END CUP
10
'
-
0
"
GROUND FINISH
PER CIVIL DWGS
MORTICE LOCKSET
W/ CYPERKEY
CYLINDAR & SS
LEVER HANDLES
ADJ. WALL
6063 T6 AL 3"X2"X1/4" U-
CHANNEL INFILL PANEL
FRAME FACE-MOUNTED
PE
R
C
O
D
E
3'
-
0
"
TYP.
6"
6063 T6 AL 1"X6"-0.100"
T&G SLAT INFILL
6063 T6 AL 3"X2"X1/4" GATE
FRAME BEHIND
V.I.F.
24' - 0"
4"X4"X1/4" THK STL GATE
POST W/ 1/4" THK STL
PLATE CAP.
A4005
8
4"X4"X1/4" THK STL GATE
POST W/ 1/4" THK STL
PLATE CAP.
A4005
8
R.O.
18' - 0"31' - 5"
2' - 0"
2'
-
0
"
7' - 7"
CONC. FOUNDATION
PER MANUF. SPECS
WALL-MOUNTED
GATE RECEIVER &
BOTTOM END CUP
A4005
8 ALUM INFILL DETAIL
SIM.
OFF PROPERTY PROJECT SIDE
3" H ALUM COPING,
BRONZE
WATER REPELLENT ON
EXPOSED 8X8X16 CMU
BLOCK, TAN/ GROUND
VA
R
I
E
S
EARTH
TOW EL VARIES
PER SITE PLAN
FG VARIES
FG VARIES
WEEP SCREED
18
"
M
I
N
PE
R
E
N
G
.
PER ENG.
PROPPERTY LINE
2" MIN. TO CMU BLOCK
VARIES
CMU BLOCK GROUT
SOLID , REINFORCING
PER STRUCTRL
CONCRETE FOOTING
PER STRUCTRL
RETAINING WALL
PER STRUCTRL
A4005
4
A4005
2
3-COAT CEMENT PLASTER FINISH
(OR THIN STONE VENEER OVER
SCRACH COAT WHERE OCCURS)
OVER METAL LATH OVER CMU.
WALL FINISH PER ELEVATIONS.
A4005
3
4"
T
Y
P
.
FRT WOOD
BLOCKING
ALUM. COPING W/
CONT. CLEAT, SLOPE
TO DRAIN
3-COAT CEMENT PLASTER FINISH
(OR THIN STONE VENEER OVER
SCRACH COAT) OVER METAL LATH
OVER CMU. SEE ELEVATIONS
REINF. PER STRUCTRL
J MOLDING
4"
M
I
N
.
WEEP SCREED
EARTH
3-COAT CEMENT PLASTER FINISH (OR
THIN STONE VENEER OVER SCRACH
COAT WHERE OCCURS) OVER METAL
LATH OVER CMU. WALL FINISH PER
ELEVATIONS.
REINF. PER STRUCTRL
UNFINISHED
GRADE SRF.
CONC. BASE IN PAINT
FINISH TO MATCH ADJ.
3-COAT CEMENT PLASTER FINISH
OVER METAL LATH ON CMU.
REINF. PER STRUCTRL
THIN STONE VENEER OVER SCRACH
COAT OVER METAL LATH ON CMU.
GSM FLASHING
J MOLDING
JOINT SEALANT
4"X4"X1/4" THK STL GATE
POST W/ 1/4" THK STL
PLATE CAP. PAINT TO
MATCH FRAME
4"2"3"
4"
2"
2"
6063 T6 AL
3"X2"X1/4" GATE
FRAME BEHIND
6063 T6 AL 3"X2"X1/4" U-
CHANNEL INFILL PANEL
FRAME FACE-MOUNTED
6063 T6 AL
1"X6"-0.100" T&G
SLAT INFILL
WELD-ON HEAVY
DUTY BARREL HINGE.
PAINT TO MATCH
FRAME
PROPERTY SIDE
OFF PROPERTY
NOTES:
1/2" THK FLAT-CUT ALUM
NUMERIALS, PAINTING ON ALL
SIDES. MOUNTED TO FACE OF
EXTERIOR FACADE WITH 1/4"
THICK STAND-OFFS APINTED
TO MATCH NUMERALS AND
THREADED INSERTS AS
REQUIRED TO ATTACHMENT.
MP-01
6"
1' - 2"
3/
4
"
FDS
APRIL 2023
NOT FOR
CONSTRUCTION
SHEET NO.:OF
DRAWING NO.:
1
F
DESIGNED BY:
DRAWN BY:
CHECKED BY:
5-67
E
D
C
B
A
2345678910
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT 2" - SCALE ACCORDINGLY) 6/6/2023 4:38:12 PM
BIM 360://AUS-30001687-OCSD–5-67 Bay Bridge Pump Station/5-67-A-BBPS.rvt
A4005
BAY BRIDGE PUMP STATION
REPLACEMENT
ENLARGED SITEWORK & DETAILS
30277
JOHN ERIC CHUNG
RUOTIAN CAI
SIEGFREDO LOPEZ
SCALE: 1/4" = 1'-0"A2001
6 SOUTH GATE -SWING
SCALE: 1/4" = 1'-0"A2001
5 NORTH GATE -SWING
SCALE: 1/4" = 1'-0"A2001
7 WEST GATE -CANTILEVER SLIDE
SCALE: 3/4" = 1'-0"A3002
1 PERIMETER WALL, TYP.
SCALE: 1 1/2" = 1'-0"A3001
4 TOP OF WALL
SCALE: 1 1/2" = 1'-0"A4002
2 GRADE CONDITION
SCALE: 1 1/2" = 1'-0"A4002
3 PLASTER/ STONE TRANSITION
SCALE: 1" = 1'-0"A4005
8 GATE ASSEMBLY DETAIL
MARK DESCRIPTION DATE APPR.
1 LCP RESUBMITTAL 06/2023
1
SCALE: 1 1/2" = 1'-0"A2001
9 ADDRESS ID