HomeMy WebLinkAboutM2022-0059 - Misc (7)CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION
Final Project Report
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):____________________________________________________________________
This is to certify that I performed special inspection on the following portions of the work at the above address which required
continuous inspection, and which I was employed to inspect:
Based upon my personal observation and written reports of this work, it is my judgment that the inspected work was
performed, to the best of my knowledge, in accordance with the approved plans, specifications, and the applicable
workmanship provisions of the Uniformed Building Code.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionFinalProjectReport 8-24-15
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):_______________________________________ ( ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
List Tests Made:
Total Inspection Time Each Day:
Date:
Hours:
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionReport 8-24-15
201 East Coast Hwy
M2022-0059
Reinforced Concrete
09-05-2023
09-05-2023
NB0774Joshua Rock ICC#9632375
X
Observed the placement and mechanical consolidation of approximately 20 cubic yards of concrete, mix design
#68031, 1” MSA, type II/V, 5000 PSI supplied by Associated Ready Mixed Concrete Company into second section of
Footing.
All work observed was in compliance with approved contract documents and ACI Standards.
1 set of 5 4x8 cylinders were cast as recorded here:
Set 1: slump 4.5, ambient temperature 72, concrete temperature 85, load #1, ticket #45087798, plant #45
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):_______________________________________ ( ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
List Tests Made:
Total Inspection Time Each Day:
Date:
Hours:
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionReport 8-24-15
201 East Coast Hwy
M2022-0059
Reinforced Concrete
11-08-2023
11-08-2023
NB0774Joshua Rock ICC#9632375
X
Observed the placement and mechanical consolidation of approximately 40 cubic yards of concrete, mix design
#68031, 1” MSA, type II/V, 5000 PSI supplied by Associated Ready Mixed Concrete Company into Footing #5 of
Sea wall.
All work observed was in compliance with approved contract documents and ACI Standards.
1 set of 5 4x8 cylinders were cast as recorded here:
Set 1: slump 5, ambient temperature 66, concrete temperature 80, load #1, ticket #45089715, plant #45
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):_______________________________________ ( ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
List Tests Made:
Total Inspection Time Each Day:
Date:
Hours:
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionReport 8-24-15
201 East Coast Hwy
M2022-0059
Reinforced Concrete
11-08-2023
11-08-2023
NB0774Joshua Rock ICC#9632375
X
Observed the placement and mechanical consolidation of approximately 40 cubic yards of concrete, mix design
#68031, 1” MSA, type II/V, 5000 PSI supplied by Associated Ready Mixed Concrete Company into Footing #5 of
Sea wall.
All work observed was in compliance with approved contract documents and ACI Standards.
1 set of 5 4x8 cylinders were cast as recorded here:
Set 1: slump 5, ambient temperature 66, concrete temperature 80, load #1, ticket #45089715, plant #45
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):_______________________________________ ( ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
List Tests Made:
Total Inspection Time Each Day:
Date:
Hours:
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionReport 8-24-15
201 East Coast Hwy
M2022-0059
Reinforced Concrete
11-07-2023
11-07-2023
NB0774Joshua Rock ICC#9632375
X
Observed the reinforcing steel for Footing #5 of sea wall per detail C1 on sheet C-503 of the approved contract
documents, verified reinforcing steel for size, grade, lap, locations and clearances.
All work observed was in compliance with approved contract documents and ACI Standards.
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):_______________________________________ ( ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
List Tests Made:
Total Inspection Time Each Day:
Date:
Hours:
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionReport 8-24-15
201 East Coast Hwy
M2022-0059
Reinforced Concrete
11-13-2023
11-13-2023
NB0774Joshua Rock ICC#9632375
X
Observed the placement and mechanical consolidation of approximately 20 cubic yards of concrete, mix design
#68031 1” MSA, type II/V, 5000 PSI supplied by Associated Ready Concrete Mix Company into Tidal Wall #5.
Observed the reinforcing steel for Tidal Wall #5 per detail C1 on sheet C-503 of the approved contract
documents. Verified reinforcing steel for size, grade, lap, locations and clearances.
Superintendent stated that reinforcement has prior city of Newport Beach approval prior to placement of concrete
1 set of 5 4x8 cylinders were cast as recorded here:
Set 1: slump 5, ambient temperature 70, concrete temperature 75, load #1, ticket #45089846, plant #45
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):_______________________________________ ( ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
List Tests Made:
Total Inspection Time Each Day:
Date:
Hours:
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionReport 8-24-15
201 East Coast Hwy
M2022-0059
Reinforced Concrete
08-24-2023
08-24-2023
NB0774Joshua Rock ICC#9632375
X
Observed the placement and mechanical consolidation of approximately 10 cubic yards of concrete, mix design
#68031, 1” MSA, type II/V, 5000 PSI supplied by Associated Ready Mixed Concrete Company into first section of
wall. Observed the reinforcing steel for first section of wall per detail C1 on sheet C-503 of the approved contract
documents, verified reinforcing steel for size, grade, lap, locations and clearances.
1 set of 6 4x8 cylinders were cast as recorded here:
Set 1: slump 4, ambient temperature 68, concrete temperature 80, load #1, ticket #45087541, plant #45
All work observed was in compliance with approved contract documents and ACI Standards.
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658
www.newportbeachca.gov | (949) 644-3200
SPECIAL INSPECTION REPORT
Project Address:______________________________________________________________________
Permit Number:______________________________________________________________________
Inspection Type (s):____________________________________________________________________
Inspection Date (s):_______________________________________ ( ) Periodic ( ) Continuous
Describe Inspection, Including Location(s):
List Tests Made:
Total Inspection Time Each Day:
Date:
Hours:
List All Items Requiring Correction (Include Previously Listed Uncorrected Items):
Comments:
To the best of my knowledge, the work inspected was in accordance with the Building Division approved design drawings,
specifications and applicable workmanship provisions of the U.B.C. except as noted above.
Special Inspector Signature: Date:
Print Full Name: Newport Beach Registration No.:
SpecialInspectionReport 8-24-15
201 East Coast Hwy
M2022-0059
Reinforced Concrete
08-31-2023
08-31-2023
NB0774Joshua Rock ICC#9632375
X
Observed the placement and mechanical consolidation of approximately 10 cubic yards of concrete, mix design
#68031, 1” MSA, type II/V, 5000 PSI supplied by Associated Ready Mixed Concrete Company into second section of
Wall. Observed the reinforcing steel for second section of wall per detail C1 on sheet C-503 of the approved
contract documents, verified reinforcing steel for size, grade, lap, locations and clearances.
Aside from minor clearance & cleanliness issues considered to be pour watch duties, all work observed was in
compliance with approved contract documents and ACI Standards.
1 set of 5 4x8 cylinders were cast as recorded here:
Set 1: slump 4.5, ambient temperature 68, concrete temperature 80, load #1, ticket #45087676, plant #45