DATE / TIME: 02/28/22 RESPONSE – RFI #003R1
Please transmit the following pages to:
NAME: Chris Heim
E-MAIL: CHeim@WEOneil.com
COMPANY: W-E-O’Neil
PROJECT #: 15025.00
PROJECT: Clearwater at Newport Beach
We are transmitting 2 pages (including this cover page). If you do not receive all the pages, please call us at (949) 720-3850,
x310 as soon as possible. Neither the request nor the received response provides authorization for work that increases the
cost or time of the project.
Please find reply to Additional Information for RFI # 003 R1 – Title 24 U Value and VT Value
Requirements for Vinyl Windows
Question:
Reference sheet M7.01 Table G5 Fenestration Assembly Summary. It is assumed that the fixed window
requirements would also apply to fixed and operable vinyl windows.
Please confirm the minimum VT requirement for fixed and operable vinyl windows. One of the
proposed Milgard windows offers a maximum VT value of .45, and cannot meet the Table G5
requirement of 0.54.
Response:
Please see attached response from P2S (Mechanical Engineer).
Thank You,
Morgan Goei
INFORMATION
REVIEW
APPROVAL
REVISION
HARD COPY TO FOLLOW
FILE: 15025.00 RFI 003 R1 RESPONSE.DOC
Subject:Title 24 VT Value Requirements for Vinyl Windows Date:
Job:
Required:
Project:
Address:
Phone:
Estimated Cost Impact:
Estimated Days Impact:
02/24/22
Clearwater Harbor Point Senior Living
From:
1821203
03/03/22
Fax:
To:
101 Bayview Place
Newport Beach CA 92660
Thomas Le
Douglas Pancake Architects
W. E. O'Neil Const Co of CA
Nikki Saavedra
REQUEST FOR INFORMATION
0003.1
Page:1 of 1
Printed On:Feb 24, 2022
W. E. O'Neil Const Co of SD
201 Lomas Santa Fe Drive Suite 380
Solana Beach CA 92075
Co-Author:Contact:Co-Author RFI Number:null
Reference:
Spec. Section Drawing Ref.
Reference sheet M7.01 Table G5 Fenestration Assembly Summary. It is assumed that the fixed window requirements would also
apply to fixed and operable vinyl windows.
Please confirm the minimum VT requirement for fixed and operable vinyl windows. One of the proposed Milgard windows offers a
maximum VT Value of .45, and cannot meet the Table G5 requirement of .54.
Request:
Suggestion:
Answer:Accept Suggestion
Date:
Signed:
Answered By:
Distribution:
Visible Transmittance of 0.45 is acceptable for operable windows per the Energy Code.
Stephen Kazim, PE
STATE OF CALIFORNIA
FENESTRATION ACCEPTANCE
CEC-NRCA-ENV-02-F (Revised 01/20) CALIFORNIA ENERGY COMMISSION
X2021-2737Clearwater Senior Living City of Newport Beach
101 Bayview Pl Newport Beach 92660
MIL-A-153-13306-00001 MIL-A-178-08040-00001 MIL-A-153-04996-00001 MIL-A-178-05945-00002
MIL-A-178-05945-00001
STATE OF CALIFORNIA
FENESTRATION ACCEPTANCE
CEC-NRCA-ENV-02-F (Revised 01/20) CALIFORNIA ENERGY COMMISSION
X2021-2737
Sean Carroll
W.E. O'Neil Construction 02/05/24
201 Lomas Santa Fe Dr.
Solana Beach, CA 92075 (310) 970-2869
Bill Rucker
Hardy Window Company Director of New Construction
1639 E. Miraloma Ave
Placentia, CA 92870 714-996-1807 02/05/24
Sean Carroll
W.E. O'Neil Construction Senior Project Engineer
201 Lomas Santa Fe Dr. 484031
Solana Beach, CA 92075 (310) 970-2869 02/05/24
Clearwater Senior Living City of Newport Beach
101 Bayview Pl Newport Beach 92660
Sean Carroll Digitally signed by Sean Carroll
DN: C=US, E=scarroll@weoneil.com, O=W.E. O'Neil,
OU=Clearwater Harbor Pointe, CN=Sean Carroll
Date: 2024.02.05 14:40:58-08'00'
Digitally signed by Bill Rucker
DN: cn=Bill Rucker, c=US, o=Hardy Window Company,
email=bill@hardywindows.com
Date: 2024.02.05 14:04:17 -08'00'Bill Rucker
Sean Carroll Digitally signed by Sean Carroll
DN: C=US, E=scarroll@weoneil.com, O=W.E. O'Neil,
OU=Clearwater Harbor Pointe, CN=Sean Carroll
Date: 2024.02.05 14:40:46-08'00'
STATE OF CALIFORNIA
ENVELOPE
CEC-NRCI-ENV-01-E (Revised 01/20) CALIFORNIA ENERGY COMMISSION
Clearwater Senior Living City of Newport Beach X2021-2737
101 Bayview Pl Newport Beach 92660
X2021-2737
X
X
Title 24 M7.01, M7.02, M7.03 08/23/22
Window Drawings A10.1 08/23/22
08/23/22
08/23/22
Exterior Drawings 08/23/22A8.1 &A8.2
STATE OF CALIFORNIA
ENVELOPE
CEC-NRCI-ENV-01-E (Revised 01/20) CALIFORNIA ENERGY COMMISSION
Clearwater Senior Living City of Newport Beach X2021-2737
101 Bayview Pl Newport Beach 92660
W.E. O'Neil Construction
201 Lomas Santa Fe Drive
Solana Beach, CA 92075
Sean Carroll
Engineer
(310) 970-2769 2/2/24
484031
W.E. O'Neil Construction
201 Lomas Santa Fe Drive
Solana Beach, CA 92075
Sean Carroll
(310) 970-2769
2/2/24
Sean Carroll Digitally signed by Sean Carroll
DN: C=US, E=scarroll@weoneil.com, O=W.E. O'Neil,
OU=Clearwater Harbor Pointe, CN=Sean Carroll
Date: 2024.02.05 13:50:00-08'00'
Sean Carroll
Digitally signed by Sean Carroll
DN: C=US, E=scarroll@weoneil.com, O=W.E.
O'Neil, OU=Clearwater Harbor Pointe,
CN=Sean Carroll
Date: 2024.02.05 13:50:30-08'00'
AAMA/WDMA/CSA 101/I.S.2/A440-08
CSA A440S1-09
TEST REPORT SUMMARY
Rendered to:
MILGARD MANUFACTURING
1010 54th Avenue East
Fife, WA 98424
PRODUCT TYPE: XO – Horizontal Sliding Window
SERIES/ MODEL: 6110
Title Summary of Results
Primary Product Designator Class LC-PG30:Size tested 1511 x 1511 mm (60 x 60 in)-Type HS*
Design Pressure ± 1440 Pa (30.08 psf)
Operating Force (in motion max) 38 N (8.5 lbf)
Air Infiltration 0.2 L/s/m2 (0.03 cfm/ft2)*
Canadian Air
Infiltration/Exfiltration A3 Level
Water Penetration Resistance
Test Pressure 220 Pa (4.59 psf)
Uniform Load Structural Test
Pressure ± 2160 Pa (45.11 psf)
Forced Entry Resistance ASTM F588-07 - Grade 20 – Pass*
CAWM 1-79, CMBSO 301 – Pass*
*Reference NCTL Report #310-2484 for Original Gateway Performance and Air Leakage and Forced Entry Resistance Test results.
Test Completed: 04/09/13
Reference must be made to Report No. NCTL-310-3316 dated 06/05/13 for complete test specimen
description and data.
For National Certified Testing Laboratories
Jim Clarke
Structural Performance Technician
AAMA/WDMA/CSA 101/I.S.2/A440-08
CSA A440S1-09
STRUCTURAL TEST REPORT
NCTL-310-3316
REPORT TO:
MILGARD MANUFACTURING
1010 54TH AVENUE EAST
FIFE, WA 98424
REPORT NUMBER: NCTL-310-3316
REPORT DATE: 06/05/13
PRODUCT:
XO – 1511 x 1511 mm (60 x 60 in)
Horizontal Sliding Window
Report Number NCTL-310-3316
Report Date 06/05/13
Report To MILGARD MANUFACTURING
1010 54th Avenue East
Fife, WA 98424
Test Start Date 04/0913
Test End Date 04/09/13
Specification AAMA/WDMA/CSA 101/I.S.2/A440-08
NAFS North American Fenestration Standard/Specification for windows,
doors, and skylights
CSA A440S1-09
Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440,
NAFS - North American Fenestration Standard/Specification for
windows, doors, and skylights
Performance Results Class LC-PG30:Size tested 1511 x 1511 mm (60 x 60 in)-Type HS*
*Reference NCTL Report #310-2484 for Original Gateway Performance
Description of Specimen Tested
Note: All dimensions are in the order (Width x Height x Thickness) unless otherwise noted.
Model/ Series 6110 Series Horizontal Sliding Window
Configuration XO
Overall Frame Size 1511 mm x 1511 mm (59.5” x 59.5”)
Active Sash Size 742.95 mm x 1466.85 mm (29.25” x 57.75”)
Fixed Daylight Opening 695.33 mm x 1450.98 mm (27.375” x 57.125”)
Frame & Sash Type Extruded polyvinyl chloride (PVC)
Joint Construction All corners were mitered and welded, the fixed interlock was fitted and
double screw-connected to the head and sill extrusions
Glazing Components
Overall 19 mm (0.75”) nominal
Glass Thickness Two (2) panes of 2.4 mm (0.09375”) nominal annealed
Spacer Type/Size 14.3 mm (0.5625”) nominal steel U-channel (SU-D)
Glazing System Exterior glazed with a foam tape back-bedding and a snap-in extruded
vinyl glazing bead
Weatherstrip
Type Woolpile with integral center fin(s)
Size 5.6 mm (0.220”) high
Location 1. Along the exterior face of the active sash jamb stile and top and bottom
rails
2. Along the interior face of the fixed interlock
Filler Bars Not Applicable
Operating Hardware
Locks
Type Positive action lock
Location Single screw-connected to the edge face of the active interlock at the
midpoint
Note: The lock mount screws continued into or through a leg of the internal
reinforcement
Keeper
Type Zinc strike
Location Single screw-connected to the interior face of the fixed interlock at the
corresponding location
Rollers
Type Dual wheel adjustable nylon
Location Snap-fit onto the bottom face of the active sash bottom rail near each
end. The rollers rested on an extruded vinyl sill track, snap-fit into the
interior sill channel. The sill track was cut approximately 9.5 mm (0.375”)
short at each end to allow for water drainage.
Pull Handle
Type Integral vinyl
Location Full length on the interior face of the active interlock
Auxiliary
Type Extruded vinyl antilifts
Location Snap-fit into the interior head channel, within the active sash opening
near each end, two (2) total
Reinforcement
Type Extruded aluminum
Location 1. Internal hollow of the fixed interlock
2. Internal hollow of the active interlock
Weep Description
Size 6.35 mm (0.25”) diameter hole
Location Below the active I.G. unit, through the glazing pocket floor, draining
completely through the bottom rail into the interior sill channel at each
end and at 101.6 mm (4”) from each end, four (4) total
Size 17.46 mm x 4.76 mm (0.6875” x 0.1875”)
Location From the interior sill channel, through the sill floor, draining into the
internal sill hollow at 44.45 mm (1.75”) from each end, two (2) total
Size 15.88 mm x 4.76 mm (0.625” x 0.1875”)
Location From the exterior sill/screen channel, through the sill floor, draining into
the internal sill hollow at 41.28 mm (1.625”) from each end, two (2) total
Size 9.53 mm x 4.76 mm (0.375” x 0.1875”)
Location From the internal sill hollow, draining out the exterior sill face at 44.45
mm (1.75”) from each end, two (2) total
Interior/ Exterior
Surface Finish White vinyl (PVC)
Sealant
Location Glazing corners
Material Silicone
Insect Screen
Corner Construction Pressure fitted plastic corner keys
Material Fiberglass mesh with solid spline, two (2) stile retainer springs and (2)
pull tabs.
Installation Method The window was installed in a 50.8 mm x 152.4 mm (2” x 6”) wood buck
and the window was fastened through the nail fin with #8 x 31.7 mm
(1.25”) washer head screws located at 101.6 mm (4”) from each corner
and 203.2 mm (8”) on center thereafter at the frame perimeter.
This space left intentionally blank
Test Results - AAMA/WDMA/CSA 101/I.S.2/A440-2008
Paragraph Test
5.2 Operating Force and Force to Latch - Method B (Force Gauge)
ASTM E2068-00(08)
Initiate Motion = 69 N (15.5 lbf)
Allowed (Normal Use) = Report Only
Maintain Motion - Opening = 38 N (8.5 lbf)
Maintain Motion - Closing = 36 N (8 lbf)
Allowed (Normal Use) = 115 N (25.85 lbf)
Latches (Unlatch/Positive action lock)= 9 N (2 lbf)
Allowed = 100 N (22.5 lbf)
NOTE: The results above represent the maximum force among all sash tested.
Reference NCTL Report #310-2484 for Air Leakage Resistance Test results. For convenience, the results are
repeated here.
Paragraph Test
5.3.2.1 Air Leakage Resistance
ASTM E283-04(12)
The tested specimen meets or exceeds the performance levels specified in AAMA/WDMA/CSA
101/I.S.2/A440- 2008 for air infiltration at 75 Pa (1.57 psf).
Maximum Allowable = 1.5 L/s/m2 (0.3 cfm/ft2)
Infiltration
Extraneous Air Leakage = 9.96 L/s (21.10 cfm)
Total Air Leakage = 0.42 L/s (0.89 cfm)
Air Infiltration Rate = 0.2 L/s/m2 (0.03 cfm/ft2)
Exfiltration
Extraneous Air Leakage = 19.79 L/s (41.93 cfm)
Total Air Leakage = 0.70 L/s (1.48 cfm)
Air Infiltration Rate = 0.3 L/s/m2 (0.05 cfm/ft2)
Paragraph Test
5.3.3 Water Penetration Resistance
ASTM E547-00(09) and ASTM E331-00(09)
No Leakage after 4 cycles of 5 minutes at 220 Pa (4.59 psf)
NOTE:Tested with and without insect screen
Paragraph Test
5.3.4.2 Uniform Load Deflection at Design Pressure
ASTM E330-02(10)
No damage after positive 1440 Pa (40.10 psf) held for 10 seconds
No damage after negative 1440 Pa (40.10 psf) held for 10 seconds
Measured Deflection Positive = 26.64 mm (1.049 inches)
Measured Deflection Negative = 28.28 mm (1.114 inches)
Paragraph Test
5.3.4.3 Uniform Load Structural Test
ASTM E330-02(10)
No damage after positive 2160 Pa (45.11 psf) held for 10 seconds
No damage after negative 2160 Pa (45.11 psf) held for 10 seconds
Measured Permanent Set Positive = 1.52 mm (0.060 inches)
Measured Permanent Set Negative = 1.80 mm (0.071 inches)
Maximum Allowed (0.4%) = 5.87 mm (0.231 inches)
NOTE:Deflection and Permanent Set measurements taken on the active interlock over a 1467
mm (57.75”) span.
Reference NCTL Report #310-2484 for Forced Entry Resistance Test results. For convenience, the results are
repeated here.
Paragraph Test
5.3.5 Forced Entry Resistance
ASTM F588-07
Type A Window Assembly/ Grade 20: Pass
Test Results Allowed
Disassembly No Entry No Entry
Test A1 No Entry No Entry
Test A2 No Entry No Entry
Test A3 No Entry No Entry
Test A4 No Entry No Entry
Test A5 No Entry No Entry
Test A7 No Entry No Entry
Hardware Manipulation Test No Entry No Entry
Sash Manipulation Test No Entry No Entry
NOTE:1. T1 = 5 minutes, L1 = 150 lbf, L2 = 75 lbf, L3 = 25 lbf
2. Loads were held for 60 seconds.
Paragraph Test
5.3.5 Forced Entry Resistance
CMBSO 1-79, CAWM 301
Type I Window Assembly Pass
Test Results Allowed
Disassembly No Entry No Entry
Hand/Tool Manipulation No Entry No Entry
Test A No Entry No Entry
Test B No Entry No Entry
Test C No Entry No Entry
Hand/Tool Manipulation No Entry No Entry
Test D No Entry No Entry
Hand/Tool Manipulation No Entry No Entry
Note:Each Concentrated Load was maintained from the exterior side whenever possible and
maintained for a period of one (1) Minute.
The disassembly sequence and the hand and tool manipulation tests were each
conducted continuously for a period of five (5) minutes.
Paragraph Test
5.3.6.2 Thermoplastic Corner Weld Test (PVC products only) - Pass
Paragraph Test
5.3.6.3 Deglazing Test
ASTM E987-88(09)
Rails – 230 N (51.71 lbf)Results Allowed
Top Rail 20.5% <90% (<100%)
Bottom Rail 18.0% <90% (<100%)
Stiles – 320 N (71.94 lbf) Results Allowed
Jamb Stile 10.5% <90% (<100%)
Meeting Stile 12.5% <90% (<100%)
NOTE:The glass bite was approximately 12.7 mm (0.5”)
This space left intentionally blank
Test Results - CSA A440S1-09
Paragraph Test
5.1 Insect Screen Serviceability Test
ASTM E1748-95(01)
60 N (13.5 lbf)= Pass/ No disengagement
Paragraph Test
5.2 Operating Force and Force to Latch - Method B (Force Gauge)
ASTM E2068-00(08)
Initiate Motion = 69 N (15.5 lbf)
Allowed (Normal Use) = 90 N (20 lbf)
Maintain Motion - Opening = 38 N (8.5 lbf)
Maintain Motion - Closing = 36 N (8 lbf)
Allowed (Normal Use) = 45 N (10 lbf)
Latches (Unlatch/Positive action lock)= 9 N (2 lbf)
Allowed = 100 N (22.5 lbf)
NOTE: The results above represent the maximum force among all sash tested.
Paragraph Test
5.3 Canadian Air Infiltration/Exfiltration
ASTM E283-04(12)
The tested specimen meets or exceeds the performance levels specified in CSA A440S1-09 for
air infiltration at 75 Pa (1.57 psf)
A3 Level Maximum Allowable = 0.5 L/s/m2 (0.1 cfm/ft2)
Infiltration
Extraneous Air Leakage Tare = 9.96 L/s (21.10 cfm)
Total Air Leakage = 0.42 L/s (0.89 cfm)
Air Infiltration Rate = 0.2 L/(s•m2) (0.03 cfm/ft2)
Exfiltration
Extraneous Air Leakage Tare = 19.79 L/s (41.93 cfm)
Total Air Leakage = 0.70 L/s (1.48 cfm)
Air Exfiltration Rate = 0.3 L/(s•m2) (0.05 cfm/ft2)
Paragraph Test
5.4 Water Penetration Resistance
ASTM E547-00(09)
No Leakage after 4 cycles of 5 minutes at 220 Pa (4.59 psf)
NOTE:Tested with and without insect screen
All testing was performed at Milgard Manufacturing, 1010 54th Ave East, Fife WA, 98424.
This test report was prepared by National Certified Testing Laboratory NW Inc. (NCTL), for the exclusive
use of the above named client and it does not constitute certification of this product. The results are for the
particular specimen tested and do not imply the quality of similar or identical products manufactured or
installed from specifications identical to the tested product. The test specimen was supplied to NCTL NW by
the above named client. No conclusions of any kind regarding the adequacy or inadequacy of the glass in
the test specimen are to be drawn from the ASTM E330 test. Forced entry resistance test equipment used
is in compliance with Section 7 of the ASTM F588-07 test method.NCTL NW is a testing lab and assumes
that all information provided by the client is accurate and does not guarantee or warranty any product tested
or installed. The results in this report are actual tested values and are applicable to the specimen tested
only, using the components and construction methods described herein.
Detailed drawings were available for laboratory records and compared to the test specimen at the time of
this report. Component drawings were reviewed for product verification. The bill of materials contains
details with any deviations noted. Ambient conditions during the referenced testing are available upon
request. A copy of this report along with representative sections of the test specimen will be retained by
NCTL NW. This report does not constitute certification or approval of the product, which may only be
granted by a certification program validator or recognized approval entity. All tests were conducted in full
compliance with the referenced specifications and/or test methods. This report is the joint property of
National Certified Testing Laboratories North West Inc. and the Client to whom it is issued. Permission to
reproduce this report by anyone other than National Certified Testing Laboratories North West Inc and the
Client must be granted in writing by both of the above parties. This report may not be reproduced, except
its entirety, without the written consent of NCTL NW.
National Certified Testing Laboratories
Jim Clarke
Structural Performance Technician
Jeffrey M. Douglas
Lab Manager
Attachments
Appendix A – Revision Summary
Appendix B – Drawings
Appendix A
Section 1:
Component Drawings, with Applicable Part Numbers, Manufacturing and Modeling Details, were
Reviewed (as submitted) for Product Verification
(Reference: NCTL-310-3316)
See Attached Documentation;
any deviations noted.
Note: The above referenced component drawings (if applicable) along with representative sections of the test specimen will be
retained per procedure by NCTL. This testing facility assumes that all information provided by the client is accurate.
Section 2:
Identification Date Page & Revision
Original Issue 06/05/13 Not Applicable
Appendix B
Drawings