HomeMy WebLinkAboutX2012-0349 - CalcsX-2o 12-- o -54q
4b5q co f-Hand Or
Kenneth Cz. Brown # Co.
ARCHITECTURE - SPACE PLANNING
25401 Cabot Rd. 0201, Laguna Hllla, CA. ffi653
DOCUMENT MUST BE STAMPED AND SIGNED TO BE VALID
STRUCTURAL CALCULATIONS FOR RESIDENTIAL REMODEL PROJECT FOR:
Nowparast Residence
4839 Cortland Dr.
Corona Del Mar, CA.
LOADING CONDITIONS:
Roof Loads:
Floor loads:
Wall loads:
Live roof load = 20 psf
Dead roof load = 20 psf
TOTAL roof load = 40 psf
Live floor load = 40 psf
Dead floor load = 15 psf
TOTAL floor load =55 pet
Interior wall load = 8 psf
Exterior wall load =14 psf
DF&rAI CRITERIA: 2010 CALIFORNIA RESIDENTIAL CODE
West coast Douglas Fir Larch
Rafters, ceiling joists, floor joists: #2 Douglas Fir Larch
Beams and posts: #1 Douglas Fir - ASTM A53-S Std. wt. pipe
6x FB=1350 PSI: FV=85 PSI: E=1,600,000 PSI
Roof deck, floor deck and exterior wall sheathing:
Douglas Fir plywood, structural grade
Glue Laminated members: Douglas Fir Larch, 240OF grade
24F-V3 or as otherwise noted
25401 Cabot Rd, 0201, Laguna H1115, CA., 92653 Phone (949) 110-8550 Fax (949) 110-9510
Project: nowparast
Location: RRA
Roof Rafter
(2010 California Building Code(2005 NDS)]
1.5 IN x 7.251N x 13.0 FT(11+2)@24 O.C.
#2 - Douglas -Fir -Larch - Dry Use
Section Adequate By: 30.2%
Controlling Factor: Moment
DEFLECTIONS
Centsr
Richt
Live Load
0.19 IN U724 0.02
IN 2L/3012
Dead Load
0.19 in 0.00
in
Total Load
0.38 IN U368 0.00
IN 21JInFlnity
Live Load Deflection Criteria: U240 Total Load Deflection Criteria: L/180
RAFTER REACTIONS
LOADS
REACTIONS
Upper Live Load @ A
110
pit
220
Ito
Upper Dead Load @ A
112
plf
224
lb
Upper Total Load @ A
222
plf
444
lb
Lower Live Load @ B
154
pit
307
lb
Lower Dead Load @ B
162
plf
324
Ito
Lower Total Load @ B
316
pit
631
to
RAFTER SUPPORT DATA
A B
BearingLength 0.47 in 0.67 in
Span Length 11 ft 2 it
Rafter Pitch
4 :12
Roof sheathing applied to top of joists -top of rafters fully braced.
Roof Duration Factor
1.15
Peak Notch Depth
0.00
Base Notch Depth
0.00
#2 - Douglas -Fir -Larch
Base Values
Adiusted
Bending Stress: Flo = 900, psi
Fb' = 1428 psi
Cd=1.15CF=1.20 Cr-1.15
Shear Stress: Fv = 180 psi
Fv' = 207 psi
C&1.15
Modulus of Elasticity: E = 1600 ksi
E' = 1600 ksi
Min. Mod. of Elasticity: E_min = 580 ksi
E_min' = 580 ksi
Comp.-L to Grain: Fc --L= 625 psi
Fc --L= 625 psi
Controlling Moment: 1201 ft-lb
5.389 Ft from left support of span 2 (Center Span)
Created by combining all dead loads and live loads on span(s) 2
Controlling Shear: 400 lb
At a distance d from right support of span 2 (Center
Span)
Created by combining all dead loads and live loads on span(s) 2, 3
Comparisons with required sections: Rec'd
Provided
Section Modulus: 10.09 in3
13.14 in3
Area (Shear): 2.9 in2
10.88 in2
Moment of Inertia (deflection): 23.32 in4
47.63 in4
Moment: 1201 ft-Ito
1554 ft-lb
Shear: -4001b
1501 lb
page
Kenneth Brown
Kenneth Brown and Co.
25401 Cabot Rd. #207 er
Laguna Hills, CA. 92653
Uniform Roof Loading
Roof Live Load:
ILL =
20
psf
Roof Dead Load:
DL =
20
psf
Non -Snow Roof Loaded Area:
RLA =
0
sf
Slope Adjusted Spans And Loads
Interior Span:
L-adj =
11.6
ft
Eave Span:
L-Eave-adj =
2.11
ft
Rafter Live Load:
wL-adj =
36
plf
Eave Live Load:
wL-Eave-adj =
36
plf
Rafter Dead Load:
wD-adj =
38
plf
Rafter Total Load:
wT-adj =
74
plf
Eave Total Load:
wT-Eave-adj =
74
plf
Project: nowparast
Location: RB-I
Roof Beam
[2010 California Building Code(2005 NDS)]
2.688 IN x 9.25 IN x 10.0 FT
2.0E Parallam - iLevel Trus Joist
Section Adequate By: 90.8%
Controlling Factor: Moment
DEFLECTIONS Center
Live Load 0.14
IN U860
Dead Load 0.15
in
Total Load 0.29
IN L/411
Live Load Deflection Criteria: U240 Total Load Deflection Criteria: U180
REACTIONS A_
B
Live Load 1100
lb 1100 lb
Dead Load 1198
Ib 1198 lb
Total Load 2298
lb 2298 lb
Bearing Length 1.14
in 1.14 in
BEAM DATA
Span Length
10 ft
Unbraced Length -Top
0 ft
Unbraced Length -Bottom 0 ft
Roof Pitch
4 :12
Roof Duration Factor
1.15
MATERIAL PROPERTIES
2.0E Parallam - iLevel Trus Joist
Base Values
Ad'us ed
Bending Stress:
Fb = 2900 psi
Fb' = 3433 psi
Cd=1. 15 CF=1.03
Shear Stress:
Fv = 290 psi
Fv' = 334 psi
Cd=1. 15
Modulus of Elasticity:
E = 2000 ksi
E' = 2000 ksi
Comp..L to Grain:
Fc-1= 750 psi
Fc --L'= 750 psi
Controlling Moment: 5746 ft-lb
5.0 ft from left support
Created by combining all dead and live loads.
Controlling Shear: -1977 lb
At a distance d from support.
Created by combining all dead and live loads.
Comparisons with required sections:
Read
Provided
Section Modulus:
20.09 in3
38.32 in3
Area (Shear):
8.89 in2
24,86 in2
Moment of Inertia (deflection):
77.56 in4
177.25 in4
Moment:
5746 ft-lb
10964 ft-lb
Shear:
-1977 lb
5527 lb
Page
Kenneth Brown /
Kenneth Brown and Co.
25401 Cabot Rd. #207
Laguna Hills, CA. 92653
StruCalc Version 8.0.111.0 2/13/2012 9:52:22 AM
LOADING DIAGRAM
Taft
ROOF LOADING
-
Side One:
Roof Live Load:
LL =
20 psf
Roof Dead Load:
DL =
20 psf
Tributary Width:
TW =
5.5 ft
Side Two:
Roof Live Load:
LL =
20 psf
Roof Dead Load:
DL =
20 psf
Tributary Width:
TW =
5.5 It
Wall Load:
WALL
= 0 plf
Non -Snow Roof Loaded Area: RLA =
110 plf
SLOPE/PITCH ADJUSTED LENGTHS
AND LOADS
Adjusted Beam Length:
Ladj =
10 It
Beam Self Weight:
BSW =
8 plf
Beam Uniform Live Load:
wL =
220 plf
Beam Uniform Dead Load:
wD_adj =
240 plf
Total Uniform Load:
wT= `
460 plf
project: nowparast
Location: RB-2
Roof Beam
[2010 California Building Code(2005 NDS)]
3.51N x 9.251N x 16.0 FT
2.0E Parallam -!Level Trus Joist
Section Adequate By: 91.5%
Controlling Factor: Deflection
DEFLECTIONS Center
'. Live Load 0.26
IN U752
Dead Load 0.30
in
Total Load 0.56
IN U345
Live Load Deflection Criteria: U240 Total Load Deflection Criteria: U180
REACTIONS A_
B
Live Load 640
Ito 640 lb
Dead Load 756
Ito 756 lb
Total Load 1396
It, 1396 Ito
Bearing Length 0.53
in 0.53 in
BEAM DATA
Span Length
16 ft
Unbraced Length -Top
0 ft
Unbraced Length -Bottom 0 ft
.. Roof Pitch
4 :12
Roof Duration Factor
1.25
MATERIAL PROPERTIES
2.0E Parallam - !Level Trus Joist
Base Values
Adiusted
Bending Stress:
Fb = 2900 psi
Fb' = 3731 psi
Cd=1. 25 CF=1.03
Shear Stress:
Fv = 290 psi
Fv' = 363 psi
Cd=1. 25
Modulus of Elasticity:
E = 2000 ksi
E' = 2000 ksi
Comp.-Lto Grain:
Fc--L= 750 psi
Fc--L= 750 psi
Controlling Moment: 5582 ft-lb
8.0 ft from left support
Created by combining all dead and live loads.
Controlling Shear: 1284 lb
At a distance d from support.
Created by combining all dead and live loads.
Comparisons with required sections:
Reo'd
Provided
Section Modulus:
17.95 !n3
49.91 in3
Area (Shear):
5.31 in2
32.38 in2
Moment of Inertia (deflection):
120.56 in4
230.84 in4
Moment:
5582 ft-lb
15520 ft-lb
Shear:
1284 lb
78241b
page
Kenneth Brown
Kenneth Brown and Co.
25401 Cabot Rd. #207 or
Laguna Hills, CA. 92653
StruCalc Version 8.0.111.0 2/13/2012 9:54:45 AM
LOADING DIAGRAM
ROOF LOADING
-
Side One:
Roof Live Load:
LL =
20
psf
Roof Dead Load:
DL =
20
psf
Tributary Width:
TW =
2
ft
Side Two:
Roof Live Load:
LL =
20
psf
Roof Dead Load:
DL =
20
psf
Tributary Width:
TW =
2
ft
Wall Load:
WALL =
0
plf
Non -Snow Roof Loaded Area: RLA =
64
pif
SLOPEIPITCH ADJUSTED
LENGTHS AND LOADS
Adjusted Beam Length:
Ladj =
16
it
Beam Self Weight:
BSW =
10
plf
Beam Uniform Live Load:
wL =
80
plf
Beam Uniform Dead Load:
wD_adj =
94
plf
Total Uniform Load:
wT = `
174
plf
Project: nowparast
Location: RB-3
Multi -Loaded Multi -Span Beam
[2010 California Building Code(2005 NDS)]
5.25 IN x 11.875 IN x 22.0 FT
2.0E Parallam - iLevel Trus Joist
Section Adequate By: 63.9%
Controlling Factor: Deflection
DEFLECTIONS Center
Live Load 0.29 IN
U917
Dead Load 0.38 in
Total Load 0.67 IN L/393
live Load Deflection Criteria: U360 Total Load Deflection Criteria: U240
REACTIONS A_
B
Live Load 550 Ito
550 Ib
Dead Load 813 lb
813 lb
Total Load 1363 lb
1363 lb
Bearing Length 0.35 in
0.35 in
BEAM DATA
Center
�I Span Length
22 ft
Unbraced Length -Top
0 ft
Unbraced Length -Bottom
22 ft
Live Load Duration Factor
1.00
Notch Depth
0.00
2.0E Parallam - iLevel Trus Joist
Base Values
Adjusted
Bending Stress:
Fb = 2900 psi
Fb' = 2903 psi
Cd=1. 00 CF=1. 00
Shear Stress:
Fv = 290 psi
Fv' = 290 psi
Cd=1.00
Modulus of Elasticity:
E = 2000 ksi
E' = 2000 ksi
Comp.-Lto Grain:
Fc-1= 750 psi
Fc --L = 750 psi
Controlling Moment: 13818 ft-lb
11.0 Ft from left support of span 2 (Center Span)
Created by combining all dead loads and live loads on span(s) 2
Controlling Shear: 1346 It,
At a distance d from left support of span 2 (Center Span)
Created by combining all dead loads and live loads on span(s) 2
Comparisons with required sections:
Read
Provided
Section Modulus:
57.11 in3
123.39 in3
Area (Shear):
6.96 in2
62.34 in2
Moment of Inertia (deflection):
447.03 in4
732.62 in4
Moment:
13818 ft-lb
29854 ft-lb
Shear:
1346 lb
120531b
page
Kenneth Brown
Kenneth Brown and Co.
25401 Cabot Rd. #207 or
Laguna Hills, CA. 92653
StruCalc Version 8.0.111.0 2/13/2012 9:58:06 AM
LOADING DIAGRAM
7
)
22 fl —
UNIFORM LOADS Center
Uniform Live Load 0
pif
Uniform Dead Load 0
plf
Beam Self Weight 19
plf
Total Uniform Load 19
pif
POINT LOADS - CENTER
SPAN
Load Number One
Live Load 1100 lb
Dead Load 1198 Ito
Location 11 ft
Project: nowparast
Location: RB-4
Multi -Loaded Multi -Span Beam
[2010 California Building Code(2005 NDS))
7.0 IN x 11.875 IN x 22.0 FT
2.0E Parallam - iLevel Trus Joist
Section Adequate By: 49.3%
Controlling Factor: Deflection
DEFLECTIONS Center
Live Load 0.32 IN U816
Dead Load 0.41 in
Total Load 0,74 IN U358
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: U240
REACTIONS A B
Live Load 990 to 990 lb
Dead Load 1325 lb 1325 lb
Total Load 2315 lb 2315 lb
Bearing Length 0.44 in 0.44 in
BEAM DATA Cents
Span Length 22 It
Unbraced Length -Top 0 ft
Unbraced Length -Bottom 22 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
MATERIAL PROPERTIES
2.0E Parallam - iLevel Trus Joist
Base Values
Adiusted
Bending Stress:
Fb =
2900 psi
Fb' = 2903 psi
Cd=1.00
CF=1.00
Shear Stress:
Fv =
290 psi
Fv' = 290 psi
Cd=1.00
Modulus of Elasticity:
E =
2000 ksi
E= 2000 ksi
Comp.-Lto Grain:
Fc-
750 psi
Fc --L= 750 psi
Controlling Moment: 19051 ft-lb
11.0 Ft from left support of span 2 (Center Span)
Created by combining all dead loads and live loads on span(s) 2
Controlling Shear: -2221 lb
At a distance d from right support of span 2 (Center Span)
Created by combining all dead loads and live loads on span(s) 2
Comparisons with required sections:
Rec'd
Provided
Section Modulus:
78.74 in3
164.52 in3
Area (Shear):
11.49 in2
83.13 in2
Moment of Inertia (deflection):
654.22 in4
976.83 in4
Moment:
19051 ft-lb
39805 ft-lb
Shear:
-2221 lb
16071 lb
page
Kenneth Brown /
Kenneth Brown and Co.
25401 Cabot Rd. #207 m
Laguna Hills, CA. 92653
Uniform Live Load
40
plf
Uniform Dead Load
40
plf
Beam Self Weight
26
plf
Total Uniform Load
106
plf
POINT LOADS - CENTER SPAN
Load Number One
Live Load 1100 Ito
Dead Load 1198 Ito
Location 11 ft
Project: nowparast
Location: RB-5
Roof Beam
[2010 California Building Code(2005 NDS)]
3.51N x 9.251N x 12.5 FT
2.0E Parallam - iLevel Trus Joist
Section Adequate By: 173.0%
Controlling Factor: Deflection
DEFLECTIONS Center
Live Load 0.14 IN U1051
Dead Load 0.16 in
Total Load 0.31 IN U491
Live Load Deflection Criteria: U240 Total Load Deflection Criteria: U180
:: REACTIONS A_ B
Live Load 750 lb 750
lb
Dead Load 854 lb 854
Ito
' Total Load 1604 lb 1604
lb
Bearing Length 0.61 in 0.61
in
BEAM DATA
Span Length 12.5
ft
Unbraced Length -Top 0
ft
Unbraced Length -Bottom 0
ft
Roof Pitch 4 :12
Roof Duration Factor 1.15
2.0E Parallam - iLevel Trus Joist
Base Values
Adjusted
Bending Stress:
Fb = 2900 psi
Fb' = 3433 psi
Cd=1. 15 CF=1. 03
Shear Stress:
Fv = 290 psi
Fv' = 334 psi
Cd=1. 15
Modulus of Elasticity:
E = 2000 ksi
E' = 2000 ksi
Comp.-L to Grain:
Fc-1= 750 psi
Fc-L'= 750 psi
Controlling Moment: 5012 ft-lb
6.25 ft from left support
Created by combining all dead and live loads.
Controlling Shear: -1411 lb
At a distance d from support.
Created by combining all dead and live loads.
Comparisons with required sections:
Read
Provided
Section Modulus:
17.52 in3
49.91 in3
Area (Shear):
6.35 in2
32.38 in2
Moment of Inertia (deflection):
84.56 In4
230.84 in4
Moment:
5012 ft-lb
14278 ft-lb
Shear:
-1411 Ito
7198 lb
page
Kenneth Brown
Kenneth Brown and Co.
25401 Cabot Rd. #207 m
Laguna Hills, CA. 92653
StruCalc Version 8.0.111.0 2/13/2012 10:34:21 AM
LOADING DIAGRAM
-
12.5 k
-
ROOF LOADING
Side One:
Roof Live Load:
LL =
20
psf
Roof Dead Load:
DL =
20
psf
Tributary Width:
TW =
6
ft
Side Two:
Roof Live Load:
LL =
20
psf
Roof Dead Load:
DL =
20
psf
Tributary Width:
TW =
0
ft
Wall Load:
WALL =
0
plf
Non -Snow Roof Loaded Area:
RLA =
75
plf
SLOPEIPITCH ADJUSTED LENGTHS AND LOADS
Adjusted Beam Length:
Ladj =
12.5
ft
Beam Self Weight:
BSW =
10
plf
Beam Uniform Live Load:
wL =
120
pit
Beam Uniform Dead Load:
wD_adj =
137
pif
Total Uniform Load:
wT= ,
257
plf
LATERAL
SEISMIC ANALYSIS
Site location is : Latitude 33.588 / Longitude -117:855
-------------- Ss = 1.744g ; S1 = 0.638g
Site Class type D:
-------------- Fa = 1.0 =_> Sms = Fa* Ss = 1.744
-------------- Fv = 1.5 __> Srni = Fv* S1 = 0.957
Acceleration Parameters:
Sds = 0.667* Sms = 0.667* 1.744= 1.163
Sdi = 0.667* Smi = 0.667* 0.957 = 0.638
Numerical coefficient R = 6.5 (Bearing wall system with plywood shear panels)
Importance factor I = 1.0---------> R/I = 6.5/1 = 6.5
Approximate fundamental period = T = Ct*(h)A3/4 = 0.020 (30)A3/4 = 0.256 second
< 0.5 ---- k = 1.0
Design Base Shear: Vs = Cs*W
Where Cs = Sds/(R/1) = 1.163/6.5 = 0.178 <------ Govern
Cs (max) = Sdi/(R/I)*T = 0.638/(6.5*0.256) = 0.384
Cs (min) = 0.044*Sds*I = 0.044*1.163*1 = 0.051
or = 0.5*Si/(R/1) = 0.5*0.638/6.5 = 0.049
>> Vs = 0.178*W-------- Strength Design
>> Vs = 0.178*W/1.4 = 0.127*W ------ Allowable Stress Design (ASD)
Redundancy: p = 1.30 >>> Vs = 0.178*W*1.3 = 0.231*W (ASD)
Rdl Part Fdl Part
Vs = 0.231 *( 20 + 8 + 0 + 0 ) = 6.46 psf
WIND ANALYSIS: Basic Wind Speed = 85 mph --- 3 second gust
Assume transverse load direction at 20 govern: Use conservative loads
Horizontal loads: Wall end and interior zone = 15.9 psf
Vertical loads: Roof end and interior zone = -13.8 psf -- Ignore
(less than roof dead load)
Overhang end S interior ?one = -19.3 psf -- May reduce by
roof dead load
Conterminous 48 States
2003 NEHRP Seismic Design Provisions
Latitude = 33.588
Longitude =-117.855
Spectral Response Accelerations Ss and S1
Ss and S1 = Mapped Spectral Acceleration Values
Site Class B - Fa = 1.0 ,Fv = 1.0
Data are based on a 0.01 deg grid spacing
Period Sa
(sec) (g)
0.2 1.744 (Ss, Site Class B)
1.0 0.638 (SI, Site Class B)
Conterminous 48 States
2003 NEHRP Seismic Design Provisions
Latitude = 33.588
Longitude =-117.855
Spectral Response Accelerations SMs and SM1
SMs = Fa x Ss and SM1 = Fv x S1
Site Class D - Fa = 1.0 ,Fv = 1.5
Period Sa
(sec) (g)
0.2 1.744 (SMs, Site Class D)
1.0 0.957 (SM1, Site Class D)
Conterminous 48 States
2003 NEHRP Seismic Design Provisions
Latitude = 33.588
Longitude =-117,855
Design Spectral Response Accelerations SDs and SDI
SDs = 2/3 x SMs and SDI = 2/3 x SM1
Site Class D - Fa = 1.0 ,Fv = 1.5
Period Sa
(sec) (g)
0.2 1.163 (SDs, Site Class D)
1.0 0.638 (SDI, Site Class D)
,S ov 1
Diaphram:
Ww = 15.9 psf (9) = 143 psf Gov
Ws = 6.46 psf (12.5') = 81 psf
Ud = 143 (12.5/2) = 893#/16 = 55 plf
sw� use 3/4" T&G plywd w/ 10d@6,6,10
Chord:
Shearwall Roof:
C=T= 143 (25"25/9)/16 = 620#
#of 16d = 620/93(1.33) = 8.8 nails
use 10 - 16d@ dbl top plate splice
Line SW1 Vs = 6.46 psf (7)(23) = 1040#
Vw = 15.9 (7)(9) = 1001#
Wall =1040/6=173plf 14
T/C = 173 (9) = 1557# HDU2-SDS2.5
Line SW2 Vs = 6.46 psf (10)(23) = 1485#
Vw = 15.9 (10)(9) = 1431#
Wall = 1485 plf Simp StrgWall (2) SW16x7x4
Line SW3 Vs = 6.46 psf (11.5)(7) = 520#
Vw = 15.9 (11.5)(9) = 1645#
Wall = 1645 / 6 = 274 plf 14
T/C = 274 (9) = 2466# HDU2-SDS2.5
Line SW4 Vs = 6.46 psf (11.5)(7) = 520#
Vw = 15.9 (11.5)(9) = 1645#
Wall =1645/6=274plf 14
T/C = 274 (9) = 2466# HDU2-SDS2.5
Line SW5 GIs = 6.46 psf (11.5)(10) = 742#
Vw = 15.9 (11.5)(9) = 1645#
Wall = 1645 / 6 = 274 plf 14
T/C = 274 (9) = 2466 HDU2-SDS2.5
Line SW6 Vs = 6.46 psf (11.5)(10) = 742#
Vw = 15.9 (11.5)(9) = 1645#
Wall = 1645 / 6 = 274 plf 14
T/C = 274 (9) = 2466 HDU2-SDS2.5
Prescriptive Certificate of Compliance: CF-1 R ADD
Residential Additions (Page 1 of 5
Site Address: Enforcement Agency: Date:
i v 3'� God U Jr , Z as
General Information
Project Name
Climate Zone q i
# of Stl ries
W
4'
Building Type% Single Family ❑
ulti Family
Circle the Front Orientation: E S, W or Degrees
Conditioned Floor Area of Addition
New Addition Size: ❑ Less than or equal to 100 ft- W Less than or equal to 1000 it
(CFA):
(Do not use this form for additions greater than 1000 )
-
NOTE: For Alterations to an existing home, submit a completed CF-IR-ALT Form.
Exception: Existing HVAC systems that are re laced or altered to serve the addition may be included on the CF-IR -ADD Form.
Prescriptive Envelope Re uirements for Additions
Option 1: Use Option I for standard wood and assemblies meetine the Cavity R-value only. For all other use Option 2.
. For 100 ft' additions, the Proposed values must be equal or greater than the Standard column or when indicated when using Package D,
"Pkg D ". Enter all values in the Proposed Columns.
. For less than 1,000 flt additions must comply with 'Pkg D" requirements unless indicated in the Standard Column. To meet "Pkg D" minimum
encrly compliance re uirements, see RCHAppender B, Table 151-C. Or §151 (b in the RCM Enter all values in the Proposed Columns.
Size of Addition
100 ft2 or less
Less than 1,000 W
Component
Standard
Comment
Standard
Comment
Ceiling Insulation
R-19
Minimum
Pkg D
9
Table 151-C
Wall Insulation
R-13
Minimum
R-13
Minimum
Floor Insulation
R-13
Minimum
Pkg D
Table 151-C
U-
U-
Fill out
Fenestration
factor
SHGC
Enter Proposed
P
factor
SHGC
Fenestration
Proposed Areas
0.40
Pkg D
0.40
Pkg D
, 4,10
, Ll o
values then
Skip Over
Below
Fill out
To Roofing
Package D (20%
Additional
Maximum Glazing
z
50 ft
z
ft
Products
Q
g'd WAllowed
Area
�
BelowofCFA)+Glass
Removed
a
Fenestration
Areas Below
Radiant Barrier
N/A
Pkg D
Table 151-C
Roofing
Pkg D
See Roofing Products Below
Pkg D
See Roofing Products Below
O ague Surface Details For the furred portioned of Mass Walls see Furring Strips Construction Table below.
A B C D
E
F G H I J
Proposed Ni,U
Standard
Values From JA4 Table
Framing
Thickness,
Framed
Continuous
JA4
Proposed
Tag/
Assembly Name
Material
Spacing,
U-
JA4 Table
Cavity
insulation
Assembly
Assend d
ID'
or T el
and Size
or Other"
factor°
Numbers
R-value'
R-Valuet
Cell Values
U-factor
'Z
�
en
G
k
Note: Far furred assemblies, accountingfor Continuous Insulation R-value, see Page JA4-3 and Equation 4-1. For calculatingfurred walls use the Mass and
Furring Construction table below.
1. For Tag/ID indicate the identification name that matches the building plans. _
1. Indicate the Assembly Name or type: Roof/Ceiling, Walls, Floors, Slabs, Crawl Space, Doors and etc... indicate the Frame type and Size: For
Wood, Metal, Metal Buildings, Mass, enter 2x4, 1x6, or etc... see JA4for other possible frame type assemblies.
3. Enter the thickness for mass in inches or Spacing between framing members enter, 16 "or 14 "OC; or Other for all other assembly description
such as Concrete Sandwich Panel, Spandrel Panel, Logs, Straw Bale Panel and etc....
4. Based on the Climate Zone; enter the Standard U factor from Table 151- Cfor each different assembly Name or type.
5. Enter- the Table number that closely resembles the proposed assembly.
6. Enter the R-value that is being installed in the wall cavity or between the framing; otherwise, enter "0 ".
'. Enter the Continuous Insulation R-value for the proposed assembly,- otherwise, enter "0 ".
,i. Fnier the row and columm of the U factor value has on Column F Table Number and enter due Assembly U factor in Column J.
9. The Proposed .4.ssemb/y U floor, Column J, must he equal to or less than the Standard G facto in Column E to comply.
Registration Number: Regisa'alion Dare/Tlow
200R Residevinal Compliance Founts
HERS Provider.
Atntaust 2009
Prescriptive Certificate of Compliance' CF-I R ADD
Residential Additions (Page 2 of 5
Site Address: Enforcement Agency: Date:
f I cm Z'v)-P�.—v I of
Furring Strips Construction Table for Mass Walls O 31
A 6 C D E
F G H I J K
L
M
Proposed Properties of Masonry and Concrete
Added Interior or Exterior Insulation
Walls From Reference
in Furring Space from Reference
Joint Appendix Table 4.3.5, 4.3.6, 4.3.7
Joint A endix Table 4.3.13
U
T
j
C
;
v
�
T
y
Assembly
iY
�
G
2.�
L
u
T
u v�
c ?
.E
?��
"N'
Final
Assembly
Mass
Name or
JA4 Table
'
m d a
o
i
v —'
Q>
u>
U-factorb''
Comment
Thickness
Type'
Number'
I
1. Indicate the Mass Thickness from Reference Joint Appendix JA.
.Indicate the Assembly Name or type: Roof/Ceiling, fValls, Floors, Stabs, Crawl Space, Doors and etc_.Indicate the Frame type and Size: For
Wood, Metal, Metal Buildings, Mass, enter 2x4, 2x6, or etc... see J44 for other possible frame type assemblies.
. Enter the Table number that closely resembles the proposed assembly.
4. Enter the row and column of the Ufactor value.
. Enter the Effective R-value listed in the JA4 Table Number.
6. The Final Assembly is calculated by using Equation 4-1 or Equation 4-4 of the Reference Joint Appendix JA4. Enter the value in Column L.
7. Thethe Final Assembly U- actor value back on to the Opaque Surface Details table in Column J.
FENESTRATION PROPOSED AREAS
'
Fenestration Type and Frame
Window, Glass Door or S li t
Orientation
(North, East,
South, West
PropsedArea�
fl U-factorZ'
Maximum
Maximum
SHGC' '
NFRC or s
Default Values
-YVC
b '
L10
0
Total
%
1. Fenestration area is the area of total glazed product (i.e. glass plus frame). Exception: When a door is less than 50% glass, the fenestration
area may be the glass area plus a "2 inch frame" around the glass.
2. Enter valuefrom Component Package D Requirements in Table 151-C p
3. Actual fenestration products installed and as indicated in CF-6R-ENV Form shall be equivalent to or have a lower U-factor and/or a lower
SHGC value than that specified on the CF-I R ADD Form.
4. Submit a completed WS-31? Form if a reduced SHGC is calculated with exterior shading.
S.applicable at this stage enter "NFRC" or NFRC Certified windows or CEC "Default" valuesfound in Table 116-A or B.
1
Re+istralion NumberRe isi"Mon Dul"Time: HERS Pros irlcr:
'DOb Re iderm rl Compliance Furors August 2009
Prescriptive Certificate of Compliance: CF-I R ADD
Residential Additions (Page 3 of 5)
Site Address: Enforcement Agency: Date
Ccs
ADDITION ALLOWED FENESTRATION AREAS
A
B
C
D
E
P
CFA of
Allowed%
Allowed Area
Area
z
Removed
Total Area
Allowed
Proposed Area '°
P
Addition
oCCFA
(A x B)
ftz
+ D
(Table .46ove)
ftz
(C
Total Fenestration Area
Zs
L>
L O
West Fenestration Area
.05
>
(Required In CZ's 2, 4 & 7 -15
1. West Fenestration Area includes west -sloping skylights and any skylights with a pitch less than 1: 12.
2. West facing glazing area removed cannot be "counted" ooice. " In order to distribute the west glazing area removed to the other orientations,
input the west glazing area removed in the Total Fenestration Area row, column D.
3. Include the Proposed Area of the West facing fenestration in both Area columns below.
4. To meet compliance, the Proposed Area must be less than or equal to the Total Allowed Area for BOTH the Total and West Fenestration Areas.
ROOFING PRODUCTS (COOL ROOFS) §151(011
Check applicable box below if the roof addition is exempt from the roofing product "Cool Roof' requirements. Note: if any one of the boxes are
checked below, the Aged Solar Reflectance and Thermal Emithince requirements for roofing products in §118(i) are not applicable. Do not fill
table below.
❑ Roofing compliance Not Required in Climate Zones 1-12, 14, and 16 with a Low Slope. Less or 2:12 pitch.
,Roofing compliance Not Required in Climate Zones I through 9 and 16 with a Low -Sloped. Roofs pitch greater than 2:12 and product weight
less than 5lb/ft2.
❑ Roofing area covered by building integrated; photovoltaic panels and solar thermal panels are exempt from the above Cool Roof criteria
❑ Roof constructions that have thermal mass over the roof membrane with at least 25 Ib/ft' is exempt from the above Cool Roof criteria.
)te: If no CRRC-1 label is available, this compliance method cannot be used, use the Performance Approach to show compliance, otherwise, check
ate applicable box below if Exempt from the Roofing Products "Cool Roof' Requirement:
Roof Slope
Product Weight
Product
Aged Solar
Thermal
CRRC Product ID Number
< 2:12 > 2:12
_❑
< 5lb/ft> 51b/ft2
—
z
Refectance3'4
Emittance
SRIS
❑
i
❑
❑4
❑
❑
❑
❑
❑4
❑
❑
❑
❑
❑4
❑
❑
❑
❑
❑4
1. The CRRC Product ID Number can be obtained from the Cool Roof Rating Council's Rated Product Directory at www coolroo(s ore/nroductslsearch vho
2. Indicate the type of product is being used for the roof top, i.e. single -ply roof, asphalt roof, metal roof, etc.
. If the Aged Reflectance is not available in the Cool Roof Rating Council's Rated Product Directory then use the Initial Reflectance value from the same
directory and use the equation (0.240.7(pMatvt-0,2) to obtain a calculated aged value. Where p is the Initial Solar Reflectance.
. Check box if the Aged Reflectance is a calculated value using the equation above.
5. Calculate the SRI value by using the SRI- Worksheet at him 11www energy ca govlude,24/ and enter the resulting value in the SRI Column above and attach acopy of
the SRI- Worksheet to the CF-IR.
o apply Liquid Field Applied Coatings, the coating must be applied across the entire roof surface and meet the dry mil thickness or coverage
recommended by the coatings manufacturer and meet minimum performance requirements listed in §118(i)4. Select the applicable coating:
❑ Aluminum -Pigmented Asphalt Roof Coating
❑ Cement -Based Roof Coating
❑ Other
Re niranun Number _ RcQ,,I,,ni i OW, '1 irn, 111iKS Provider': _
_004 RcsId, 'nn 1/ (brnp(i,mt r I otlnv :lll,Rlal 1009
Prescriptive Certificate of Compliance: CF-1R ADD
Residential Additions (Page 4 of 5
Site Address: Enforcement Agency: Date:
HVAC SYSTEMS - HEATING G
Du t or
Configuration
Heating Equipment
Type and Capacity""'
Minimum
Efficiency
AFUE or HSPF
Distribution
Type and
Location°
Piping
Insulation
R-Value
Thermostat
Type
(Central, Split,
Space, Package or
H dronic
1. Indicate Heating Tvpe (Central Furnace, Wall Furnace, Heat pump, Boiler, Electric Resistance, etc.)
2. Electric resistance heating is allowed only in Component Package C, or except where electric heating is supplemental (i. e., if total capacity
< 2 KW or 7,000 Btu/hr electric heating is controlled by a time -limiting device not exceeding 30 minutes). See §151(b)3 exception.
3. Refer to the HERS Verification section on Pages 3 and 4 of the CF-IR-ADD Form for additional requirements and check applicable boxes.
4. Indicate Type or Location (Ducts, H dronic in Floor, Radiators, etc.
HVAC SYSTEMS - COOLING [i
Configuration
Cooling Equipment
Type and Capacity"
Minimum
Efficiency
(SEERIEER or COP)
Distribution
Type and
Location'
Duct or Piping
Insulation
R-Value
Thermostat
Type
(Central, Split,
Space, Package or
H dronic)
1. Indicate Cooling Type (A/C, Heat pump, Evap. Cooling, etc).
2. Refer to the HERS Verification section on Pages 3 and 4 of the CF-I R-ADD Form for additional requirements and check applicable boxes.
3. Indicate Type or Location (Ducts, H dronic in Floor, Radiators, etc.
WATER HEATING , /. W� NJ glj %� 07
dronic heating. Individual dwelling DHW heaters must be
List water heaters and boilers for both damesu of water (D ) hea rs and h space
gas or propane fired, and may not exceed 50 gallons. Hot water pipe insulation from the DHW heater to the kitchens) and on all underground
hot water pipes is required in all com onent acka es in all climate zones.
External Tank
Water Heater Type/Fuel
Distribution Type
Number In
Tank
Energy Factor or
Insulation
T
Standard, ReeinailatingfSystem
Capacity al
Thermal Efficient
R-Value'
L Indicate Type (Storage Gas, Heat Pump, Instantaneous, etc.)
2. Recirculating systems serving multiple dwelling units shall meet the recirculation requirements of§150(n). The Prescriptive requirements do
not allow the installation of a recirculating water heating systemfor single dwelling units.
3. The water heating tank and i es shall be insulated to meet the requirements o 150 ' .
SPECIAL FEATURES The enforcement agency should pay special attention to the Special Features specified in this checklist below. These
items may require written justification and documentation and special verification.
Radiant Barrier (Roof) '0 YES ❑ NO
YES: Required in Climate Zones 2, 4, and 8-15 for additions larger than 100 ft.
Slab Edge (Perimeter) Insulation ❑ YES F9 NO
YES: In Climate Zone 16 under Component Packa a D, R-7 insulation is required.
Heated Slab Insulation ❑ YES NO
YES: Slab edge insulation required for heated slabs in all Climate Zones. See details in Table 118-A of the standards.
Raised Slab Insulation ❑ YES M NO
YES: In Climate Zones 1, 2, 11, 13, 14 & 16 R-8 insulation is required, and in Climate Zones 12 & 15 R-4 insulation is required under
Component Package D.
Thermal Mass - To obtain Compliance Credit for the installation of thermal mass, use the Performance Approach.
Re is(ration Nurnbe,, Regi,oation Dun,Timr- IIERSP,,mder:
004 Residential Compliant Fnrrns. tugma 7009
Prescri tive Certificate of Compliance: CF-1 R ADD
Residential Additions _ _(Page 5 of 5)
Site Address: Enfm-cemenf Agency: Dale: '
HERS VERIFICATION SUMMARY - The enforcement agency should pay special attention to the HERS Measures specified in this
checklist below. A completed and signed CF-4R Form for all the measures specified shall be submitted to the building inspector before final
inspection.
Duct Sealing & Testing HERS verification is required for oils measure.
❑ YES ($ NO YES: In all Climate Zones, if a new space -conditioning system (HVAC equipment and ducting) is installed to serve
the addition alone, the ducts are to be sealed and tested per § 151(I)10.
❑ YES 4l NO YES: in Climate Zones 2 and 9-16, if more than 40 linear feet of new or replacement ducts are installed in unconditioned
space to serve the addition, the ducts are to be sealed and tested per § 152(b)I D.
❑ EXCEPTION: Existing duct systems that are extended, which are constructed, insulated or sealed with asbestos.
❑ YES iW NO YES: In Climate Zones 2 and 9-16, if the existing HVAC equipment is replaced (including replacement of the air handler,
outdoor condensing unit of a split system, cooling or heating coil, or the furnace heat exchanger) and will serve the
addition, the ducts are to be sealed and tested per § 152(b)1 E.
- ❑ EXCEPTION: Duct systems that are documented to have been previously sealed confirmed through HERS
verification in accordance with procedures in the Reference Residential Appendix RA3.
❑ EXCEPTION: Duct systems with less than 40 linear feet in unconditioned space.
❑ EXCEPTION: Existing ducts stems constructed, insulated or sealed with asbestos.
Refrigerant Charge - Split System HERS verification is required for this measure.
❑ YES gd NO YES: In Climate Zones 2 and 8-15, if newly ducted split A/C or heat pump is installed to serve the addition alone, a
refrigerant charge measurement shall be verified per § 151(07A.
�-�/
❑ qI YES NO YES: in Climate Zones 2 and 8-15, if the existing HVAC equipment is replaced (including replacement of the air handler,
outdoor condensing unit of a split system, cooling or heating coil, or the furnace heat exchanger) and will serve the
addition, a refrigerant charge measurement shall be verified per 152(b)I F.
Central Fan Integrated Ventilation System - Airflow and Fan Watt Draw - do not apply for additions 1,000 fe or less.
Ducted Split Systems - Air Conditioners and Heat Pumps: Airflow and Fan Watt Draw HERS verification is required.
❑ YES 9 NO YES: In Climate Zones 10 through 15, if a new space -conditioning system (HVAC equipment and ducting) is installed to
serve the addition alone, the airflow, and fan watt draw shall be verified per § 151(f)7B.
3 YES '6 NO YES: In Climate Zones 10 through 15, if the existing space -conditioning system (HVAC equipment and ducting) is replaced
and will serve the addition, the airflow, and fan watt draw shall be verified per § I52(b)1 F.
Documentation Author's Declaration Statement '
• I certify that this Certificate of Compliance documentatio accurate lete.
Name:
NET
Sign
Company: �
�
14
Da S U � N
Address:
Zrgq ��"`:4
CEA r ❑ CEPE
If Applic ble #)
(Certific tion
:30"asCR9ZG53
City/state/zip:
(9?-- So
49
Responsible Building Designer's Declaration Statement
• 1 am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the building design identified on
this Certificate of Compliance.
• I certify that the energy features and performance specifications for the building design identified on this Certificate of Compliancereonforrn
to the requirements of Title 24, Parts I and 6 of the California Code of Regulations.
• The building design features identified on this Certificate of Compliance are consistent with the information provided to document this
building design on the other applicable compliance forms, worksheets, calculations, plans and sp cific submitted to the enforcement
agency for approval with this building ermit application.
Name:�//�,������ �.,,,\
r�N�� U. BqOV-)
Sig lure:
Company:
KF NN�T11 (4. FLt,00 Comp
Date:
U
Address:
License:
City/State/Zip:
c� az�53
Phone: o48sso
l c�o VU
For assistance or questions regarding the Energy Standards, contact the Energy f/otline at: 1-800-772-3.100.
ltc >eetralion Ahrmber-; Kcpirrrariun (7we%l�imc _._ 11E2S'I'rurrc cr:
ZOOS Rrcidrrvr rl <,mipli rnt c Fw m, .drrt u.el 2009
Mandatory Measures Summary MF-1R
Residential (Pa e 1 of 3)
Site Address: Enforcement Agency: Date:
NOTE. Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed,
regardless of the compliance approach used. More stringent energy measures listed at the Certificate of Compliance (CF-IR,
CF-IR-ADD, or CF-IR-ALT Form) shall supersede the items marked with an asterisk(*) below. This Mandatory Measures
Summary shall be incorporated into the permit documents and the applicablefeatures shall be considered by all parties as minimum
component performance specifications whether they are shown elsewhere in the documents or in this summary. Submit all
applicable sections of the MF-IR Form with plans.
DESCRIPTION
Building Envelope Measures:
116(a) I: Doors and windows between conditioned and unconditioned s aces are manufactured to limit air leakage.
I 1 a 4: Fenestration pro ucts except re - a near a winows aveeaMel listing Lne ceruilea U-IIHUMT'
Certified
SHGC), and infiltration that meets the requirements of § 10-11 I la).
§ 117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
§ 118(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on CF-6R For.
§I 18(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of § 118(1) when the installation of
a Cool Roof is specified on the CF-I R Form.
*§ 150(a): Minimum R-19 insulation in wood -frame ceiling or equivalent U-factor.
§150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R-Value.
*§ 150(c): Minimum R-13 insulation in wood -frame wall or equivalent U-factor.
*§150(d): Minimum R-13 insulation in raised wood -frame floor or equivalent U-Factor.
§ 150(f): Air retarding wrap is tested, labeled, and installed according to ASTM E 1677-95(2000) when specified on the CF-1 R Form.
§ 150(g): Mandatory Vapor barrier. installed in Climate Zones 14 or 16.
§ 150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance rate is no
eater than 2.0 permlinch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§ 150(e)IA: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§ 150(e)1B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped
with a with a readily accessible, o rable, and tight -fitting dam er and or a combustion -air control device.
§ I50(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor au is vented to the outside of the
building, are prohibited -
Space Conditioning, Water Heating and Plumbing System Measures:
§ 1 l0-§ 113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release valve,
backflow -prevention, pump isolation valve, and recirculation 1002 connection requirements of § 113(c)5. -
§ 115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appliances with an
electrical supply voltage connection with pilot li bts that consume less than 150 Btuflu are exempt , and pool ands a heaters.
§ 150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
§ 150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§ 1500)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with
insulation having an installed thermal resistance of R-12 or greater.
§1500)IB: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water tanks have R-12
external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.
§ 1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of recirculating sections
of hot water pipes are insulated per Standards Table 150-B.
§ 1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot water tank
shall be insulated to Table 150-B and Equation 150-A.
§ 1506)2: Pipe insulation for steam hydronic heating systems or hot water systems > 15 psi, meets the requirements of Standards Table 123-A.
§ 1500)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§ 150Q)3A: Insulation for chilled water piping and reftieerant suction lines includes a vapor retardant or is enclosed entirely in conditioned space_
3005 Residential Compliance Fors Au'ctr'r -,,,
Mandatory Measures Summary MF-1R
Residential (Pare 2 of 3)
Site Address: Enforcement Agency: Date:
J-/
150604: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation. I
Ducts and Fans Measures:
§ 150(m) I: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602,
603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-4.2 or
enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the applicable
requirements of UL 181, UL 181A, or UL 181B or aerosol sealant that meets the requirements of UL 723. if mastic or tape is used to
seal openings reater than 1/4 inch, the combination of mastic and either mesh or toe shall be used
§ 150(m) I : Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal,
duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts.
Ducts installed in cavities and support platforms shall not be coin ressed to cause reductions in the cross -sectional area of the ducts.
150 m 2D: Joints and seams of duct systems and [ heir components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape
is used in combination with mastic and draw ban s.
§ I50(m)7: Exhaust fan systems have back draft or automatic dampers.
§ I50(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers.
§ 150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam
insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that
can cause degradation of the material.
§ I50(m)l0: Flexible ducts cannot have porous inner cores.
§ 150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air Quality in
Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in
Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§ 114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations;
an on -off switch mounted outside of the heater, a permanent weatherproof plate or card with operating instructions; and shall not use
electric resistance heating or a pilot light.
§ 114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction and remm
lines, or built-up connections for future solar heating
§ 114(b)2: Outdoor pools or spas that have a heat punr or gas heater shall have a cover.
§ 114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to rnn only during off-peak electric demand ptiriods.
§150(p): Residential pool systems or equipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150(p).
Residential Lighting Measures:
§150(k)l: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies contained in
Table 150-C and is not a low efficacy lunamaire as specified by § 150(k)2.
§ 150(k)3: The wattage of permanently installed luminaires shall be determined as specified by § 130(d).
§ I50(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
§ 150(k)5: Permanently installed night lights and night lights integral to a permanently installed lummaure or exhaust fan shall contain only high
efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -voltage
lamp holder; OR shall be rated to consume no more than five watts of power as determined by § 130(d), and shall not contain a medium
screw -base socket.
§ 150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of § 150(k).
§150(k)7: All switching devices and controls shall meet the requirements of §d50(k)7. -
§ I50(k)8: A minimum of 50 percent of the total rated wattage of permaaently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft or 100 watts for dwelling units larger than 2,500 ti' may be exempt
from the 5091. high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§ 150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§ 150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms shall be high
efficacv.
August 100`
200,b Residentialr Compliance Foms r
Mandatory Measures Summary MF-1R
Residential (Page 3 of 3)
Site Address: Enforcement Agency: Date:
EXCEPTION I: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupant sensor.
§ 150(k)1 I: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility
rooms shall be high efficacy luminaires.
EXCEPTION I: Permanently installed low efficacy luminaires shall be allowed provided they are controlled by either a dimmer switch
that complies with the applicable requirements of § 119, or by a manual -on occupant sensor that complies with the
applicable requirements of §119.
EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site is not required to comply
with §I50(k)]1.
§ I50(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or
other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air leakage less then
at 75 Pascals when tested in actor ante wtt ; an a sea een e ummaae housing
t etw
and ceiling,
§ I50(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more dwelling
units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the same lot
shall be high efficacy.
EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that they are controlled by a manual
on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, and one of the
following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an
energy management control system (EMCS) not having an override or bypass switch that allows the luminaire to be
always on
EXCEPTION 2: Outdoor luminaires used to comply with Exception to §150(k)13 may be controlled by a temporary override switch
which bypasses the motion sensing function provided that the motion sensor is automatically reactivated within six
hours.
EXCEPTION 3: Permanently installed luminaires in or around swimming pool, water features, or other location subject to Article 680 of
the California Electric Code need not be high efficacy luminaires.
§ 150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no more than five
watts of power as determined according to § 130(d).
§ 150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable requirements in
Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable requirements of
Sections 130, 131, 134, and 146
§ 150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more dwelling units
shall be high efficacy luminaires.
EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by an occupant sensor(s)
certified to comply with the applicable requirements of § 119.
2008 Reeidewiol ( onplimrcc Furors
August 2001.