HomeMy WebLinkAboutX2021-2033 - Misc66. The spacing for general receptacle outlets must be located so that no point on any wall,
fixed glass, or cabinets is over 6 feet from a receptacle outlet. (CEC 210.52(A)(1))
67. Hallways 10 feet or more must have at least one receptacle outlet. (CEC 210.52(H))
68. Garages shall have at least one receptacle for each car space on the interior. The branch
circuit supplying the receptacles shall not serve outlets outside of the garage. (CEC 210.52
(G) (1)).
69. Laundry rooms must have at least one dedicated 20 amp receptacle circuit. (CEC
210.11(C) (2)).
70. Provide 120V receptacle within 3 feet of water heater. (Cal Energy Code 150.0 (n) 1 A.)
FOUNDATION:
71. Weep screed for stucco at the foundation plate line shall be a minimum of 4 inches above
the earth or 2 inches above paved areas. (CRC R703.7.2.1, CBC 2512.1.2)
72. Fasteners and connectors (nails, anchor bolts, etc.) in contact with preservative -treated
wood shall be of hot -dipped zinc -coated galvanized steel, stainless steel, silicon bronze
or copper. (CRC R317.3, CBC 2304.10.5.1)
73. Anchor bolts shall include steel plate washers, a minimum of 0.229" x 3" x 3" in size,
between sill plate and nut. (CRC R602.11.1, CBC 2308.3, Acceptable alternate SDPWS
4.3.6.4.3)
2019 CorrList\RESIDENTIALConstructionMinimumReq 11/2020 7