HomeMy WebLinkAboutF2025-0016 - Misc8/12124, 12:51 PM LicenseBMLLINGLISTNEW
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
16-33 Vdc/fwr
Candela 15 cd. 30cd, 75, 115 cd selectable
82 dB at 10 feet
INSTALLATION:
In accordance with listee's printed installation instructions, NFPA 72, applicable codes
and ordinances, and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating, and UL label.
Models beginning with G are marked Edwards.
Models beginning with E are marked for Kidde.
APPROVAL:
Listed as horn or horn/strobe when used with a separately listed compatible fire alarm
control unit. Units are suitable for indoor dry locations only. These units can generate a
distinctive 3-Pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation)
in accordance with NFPA72.
Listed as a strobe or horn/strobe for the hearing impaired when used with separately
listed electrically compatible fire alarm control units. The lights are only considered
synchronized when used in conjunction with Listed Model G1M-RM (CSFM listing No.
7300-1657:0201) or Model SIGA-CC1S (CSFM listing No. 7300-1657:0121).
'Models complies with the applicable requirements in UL 464, 10th Edition. Models
GCAV also complies with the applicable requirements in UL 1638, 5th Edition, and UL
1971. 3rd Edition.
Refer to listee's Installation Instruction Manual for details.
NOTES:
'Rev 3-1-23 DAL
This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test
results and/or other data but does not make an independent verification of any claims. This listing is not an
<O< endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: 05/03/2024
Authorized By: David Castillo, Program Coordinator
Fire Engineering & Investigations Division
Page 1 of 1
Listing Expires: 0613012025
https://calfire.govmotus.org/GOVFirePublicReportIPrintReportl?reportPath= / 2FGovFireReports°/ 2FLicenseBMLLI NGLISTNEW&UserName=&Report... 2/2