HomeMy WebLinkAbout15 - Amendment to Services Agreement for Heating, Ventilation and Air Conditioning of City Facilities (Contract No. 9669-1)Q �EwPpRT c 9C/FOR TO: FROM: CITY OF NEWPORT BEACH City Council Staff Report October 28, 2025 Agenda Item No. 15 HONORABLE MAYOR AND MEMBERS OF THE CITY COUNCIL Mark Vukojevic, Utilities Director - 949-644-3011, mvukojevic@newportbeachca.gov PREPARED BY: Kyle Brodowski, Equipment and Facilities Maintenance Superintendent - 949-718-3464, kbrodowski@newportbeachca.gov TITLE: Amendment No. Three to Services Agreement with Harbor Pointe Air Conditioning & Control Systems for Heating, Ventilation and Air Conditioning of City Facilities (Contract No. 9669-1) ABSTRACT: The City of Newport Beach (City) has over 100 separate heating, ventilation and air conditioning systems (HVAC) located throughout the City facilities (i.e. City Hall, Recreation Facilities, Fire Stations, etc.) that require regular preventive maintenance, testing and as -needed repair services. The HVAC systems are managed by the Public Works Municipal Operation Division with the assistance of a specialty contractor. Recently Public Works assumed the direct responsibility for nine additional City recreation and library facilities. For the City Council's consideration is a third amendment to the existing service agreement with Harbor Pointe Air Conditioning & Control Systems. The amended agreement will allow up to $700,000 in additional services through the remaining agreement term which expires July 24, 2029. RECOMMENDATIONS: a) Determine this action is exempt from the California Environmental Quality Act (CEQA) pursuant to Sections 15060(c)(2) and 15060(c)(3) of the CEQA Guidelines because this action will not result in a physical change to the environment, directly or indirectly; and b) Approve Amendment No. Three to On -Call Maintenance/Repair Services Agreement with Harbor Pointe Air Conditioning & Control Systems, Inc. for On -Call HVAC Maintenance and Repair Services to increase the contract amount by $700,000, and authorize the Mayor and City Clerk to sign the amendment. DISCUSSION: The Public Works Department utilizes the assistance of contractors to service and repair HVAC systems at various City facilities, including the Civic Center, corporation yards, police and fire stations, community centers and library branches. These systems require quarterly and annual preventive maintenance to ensure they remain in good working order. 15-1 Amendment No. Three to Services Agreement with Harbor Pointe Air Conditioning & Control Systems for Heating, Ventilation and Air Conditioning of City Facilities (Contract No. 9669-1) October 28, 2025 Page 2 On June 23, 2024, following a competitive selection process, an agreement for HVAC Maintenance and Repair Services was awarded to Harbor Pointe for a five-year $600,000 term. During the first year of the agreement, two amendments were required: • October 2024: The agreement was amended by $75,000 to include the Junior Lifeguard Headquarters. • May 2025: A second amendment was approved to add the Balboa Library, Corona del Mar Library and Jetty Restaurant. Beginning in July 2025, Public Works Maintenance Operations Division assumed the additional responsibility of nine Recreation and Senior Services Department buildings. Harbor Pointe worked with staff to visit each site, develop an inventory of equipment, assess overall system conditions, and provide a proposal for scheduled maintenance and regular inspections. The proposed annual cost for HVAC services at these nine buildings is approximately $100,000. In addition to routine maintenance, Harbor Pointe will continue to support unexpected repair needs and provide installation of replacement HVAC units when required. In previous years, annual costs for unplanned repairs ranged between $22,000 and $48,000. The expected service life of industrial HVAC equipment is 10-15 years. The City's marine environment contributes to the corrosion of our HVAC systems. As systems age and reach the end of their useful life, staff anticipate an increase in both unforeseen repairs and replacement of critical components such as electronics, compressors, high-pressure lines and blower fans. Staff estimate these additional costs at approximately $50,000 annually. The Fire Department has also requested additional service capacity to address various repair needs for its eight stations and two lifeguard facilities. Recent examples include the replacement of corroded HVAC system lines at Fire Station 3, evaporator coil repairs at Fire Station 8, and planned replacements of rusted exhaust fans and ducts at the Lifeguard headquarters building. The department has also temporarily increased preventative maintenance efforts at several facilities to mitigate recurring HVAC system issues. The existing agreement with Harbor Pointe has a remaining term of 3.75 years. Staff recommends the existing term remain and requests City Council approval to increase the agreement's expenditure allowance by $700,000. This would bring the total not -to -exceed compensation amount to $1,375,000. 15-2 Amendment No. Three to Services Agreement with Harbor Pointe Air Conditioning & Control Systems for Heating, Ventilation and Air Conditioning of City Facilities (Contract No. 9669-1) October 28, 2025 Page 3 FISCAL IMPACT: The adopted budget includes sufficient funding for this service. It will be expensed to the Maintenance and Repair Building accounts in the Public Works Department, 0108041-851031 and 0108041-851016. Additional funding for this contract may be expensed to the department(s)' facility maintenance and repairs budgets. ENVIRONMENTAL REVIEW: Staff recommends the City Council find this action is not subject to the California Environmental Quality Act (CEQA) pursuant to Sections 15060(c)(2) (the activity will not result in a direct or reasonably foreseeable indirect physical change in the environment) and 15060(c)(3) (the activity is not a project as defined in Section 15378) of the CEQA Guidelines, California Code of Regulations, Title 14, Chapter 3, because it has no potential for resulting in physical change to the environment, directly or indirectly. NOTICING: The agenda item has been noticed according to the Brown Act (72 hours in advance of the meeting at which the City Council considers the item). ATTACHMENT: Attachment A — Amendment No. Three to the Maintenance and Repair Services Agreement 15-3 ATTACHMENT A AMENDMENT NO. THREE TO ON -CALL MAINTENANCEIREPAIR SERVICES AGREEMENT WITH HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. FOR ON -CALL HVAC MAINTENANCE AND REPAIR SERVICES THIS AMENDMENT NO. THREE TO ON -CALL MAINTENANCE/REPAIR SERVICES AGREEMENT ("Amendment No. Three") is made and entered into as of this 28th day of October, 2025 ("Effective Date"), by and between the CITY OF NEWPORT BEACH, a California municipal corporation and charter city ("City"), and HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC., a California corporation ("Contractor"), whose address is 720 South Richfield Road, Placentia, CA 92870, and is made with reference to the following: RECITALS A. On July 23, 2024, City and Contractor entered into an On -Call Maintenance/Repair Services Agreement (Contract No. C-C-9669-1) ("Agreement") to perform on -call HVAC maintenance and repair services for City ("Project"). B. On October 25, 2024, City and Contractor entered into Amendment No. One to the Agreement ("Amendment No. One") to reflect additional services not included in the Agreement, to increase the total compensation, and to update the billing rates. C. On May 6, 2025, City and Contractor entered into Amendment No. Two to reflect additional Services not included in the Agreement, as amended, and to update the billing rates. D. The parties desire to enter into this Amendment No. Three to reflect additional Services not included in the Agreement, as amended, to increase the total compensation, update the billing rates, and update the insurance requirements. NOW, THEREFORE, it is mutually agreed by and between the undersigned parties as follows: 1. SERVICES TO BE PERFORMED Exhibit A to the Agreement shall be supplemented to include the Scope of Services, attached hereto as Exhibit A and incorporated herein by reference ("Services" or "Work"). Exhibit A to Amendment No. One, Exhibit A to Amendment No. Two, and, Exhibit A to this Amendment No. Three shall collectively be known as "Exhibit A." The City may elect to delete certain Services within the Scope of Services at its sole discretion. 2. COMPENSATION TO CONTRACTOR As of the Effective Date of this Amendment No. Three, Exhibit B to the Agreement shall be deleted in its entirety and replaced with the Schedule of Billing Rates, attached hereto as Exhibit B and incorporated herein by reference. 15-4 Section 4.1 of the Agreement is amended in its entirety and replaced with the following: "City shall pay Contractor for the Services on a time and expense not -to -exceed basis in accordance with the provisions of this Section and the Letter Proposal and the Schedule of Billing Rates attached hereto as Exhibit B and incorporated herein by reference. Except as otherwise provided herein, no rate changes shall be made during the term of this Agreement without the prior written approval of City. Contractor's compensation for all Services performed in accordance with this Agreement, including all reimbursable items, . shall not exceed One Million Three Hundred Seventy Five Thousand Dollars and 001100 ($1,375,000.00), without prior written amendment to the Agreement." The total amended compensation reflects Contractor's additional compensation for additional Services to be performed in accordance with this Amendment No. Three, including all reimbursable items and subconsultant fees, in an amount not to exceed Seven Hundred Thousand Dollars and 001100 ($700,000.00). 3. INSURANCE As of the Effective Date of this Amendment No. Three, Exhibit C of the Agreement shall be deleted in its entirety and replaced with Exhibit C, attached hereto and incorporated herein by reference. Any reference to Exhibit C in the Agreement shall hereafter refer to Exhibit C attached hereto. 4. INTEGRATED CONTRACT Except as expressly modified herein, all other provisions, terms, and covenants set forth in the Agreement shall remain unchanged and shall be in full force and effect. [SIGNATURES ON NEXT PAGE] HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page 2 15-5 IN WITNESS WHEREOF, the parties have caused this Amendment No. Three to be executed on the dates written below. APPROVED AS TO FORM: CITY ATTORNEY'S OFFICE Date: By: ar . n Harp it Attorney ATTEST: Date CITY OF NEWPORT BEACH, a California municipal corporation Date: Joe Stapleton Mayor CONTRACTOR: HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS. INC., a California corporation Date: 93 Lena Shumway Gregory Howard Perez City Clerk Chief Executive Officer Date: By: Sammi Dee Perez Chief Financial Officer/Secretary [END OF SIGNATURES] Attachments: Exhibit A — Scope of Services Exhibit B — Schedule of Billing Rates Exhibit C — Insurance Requirements HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page 3 15-6 EXHIBIT SCOPE OF SERVICES HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page A-1 15-7 Harbor P®inte --"`---�.-- s, rr`o�rii�crCnrttrof595tee CITY OF NEWPORT BEACH JOB LOCATION: CITY OF NEWPORT BEACH - POLICE DEPARTMENT 870 SANTA BARBARA AVE NEWPORT BEACH, CA 92660 Site: POLICE DEPARTMENT HEADQUARTERS JOB SUBJECT: PREFORM QUARTERLY MAINTENANCE ON THE REFRIGERATION EQUIPMENT SERVING THE POLICE STATION. EQUIPMENT COVERED: UNIT REACH IN REACH IN REACH IN REACH IN REACH IN WALK IN UNIT EVAPORATOR WALK IN UNIT EVAPORATOR WALK IN UNIT CONDENSER WALK IN UNIT CONDENSER SCOPE OF WORK: MANUFACTURER MODEL# SERIAL VOLTAGE TRAULSEN G22010 T5103OF16 115 TRAULSEN G22010 T53321L13 115 TRAULSEN DHT 232 NUT T449460 5M 115 TRAULSEN G20010 T16455806 115 TRUE MANUFACTURERING STG2DT-2S 9779944 115 LRC SLE-1065 143400-901 2081230 1 PH HEATCRAFT LCE6120BMC6B D04GO2139 208/2301PH TECUMSEH AVA2512ZXTHN 16K2913913099 208/230 3PH HEATCRAFT MOH0261-63 T04F 06492 208/230 3PH 1 15-8 1 ' Hari6D9` �, Pb to oi l C���%[io�iinJ e+s�Cnntrol S�}Sty ¢. REACH IN UNITS: VISUALLY INSPECT OVERALL UNIT CONDITION. INSPECT DOOR GASKETS, HINGES FOR WEAR AND PROPER SEAL. INSPECT THE COMPRESSOR FOR INCONSISTANT NOISE OR VIBRATION. CHECK ELECTRICAL CONNECTIONS FOR SIGNS OF CORROSION, DAMAGE, OR LOOSE WIRES. INSPECT FAN MOTOR AND BLADE FOR PROPER OPERATIONS. TEST THERMOSTAT CALIBRATION TO ENSURE ACCURATE TEMPERATURE CONTROL. INSPECT THE EVAPORATOR AND CONDENSER COIL FOR SIGNS OF OIL. USE NITROGEN TO BLOW OUT COILS AND VACUUM THE REMAINING DIRT AND DEBRIS. VERIFY PROPER DEFROST CYCLE OPERATIONS. INSPECT TXV AND CAPILLARY TUBE FOR FOR RESTRICTIONS OR ICING. WIPE DOWN EXTERIOR AND INTERIOR SURFACES. CLEAN DOOR GASKET TO ENSURE PROPER SEAL. POWER UNIT ON AND ALLOW UNIT TO CYCLE. CONFIRM UNIT SATISFIES AND MAINTAINS PROPER TEMPERATURE. CHECK DEFROST OPERATION AND TIMING FOR ABNORMAL CYCLING. LOG TEMPERATURES OF BEFORE AND AFTER MAINTENANCE. WALK IN UNIT: INSPECT FOR SIGNS OF CORROSION ON EVAPORATOR COIL, COPPER PIPING, AND SOLDER JOINTS. CONFIRM EVAPORATOR FAN MOTORS AND BLADES ARE OPERATING CORRECTLY. LUBRICATE MOTORS IF APPLICABLE. VISUALLY INSPECT WIRING FOR SIGNS OF AN ELECTRICAL SHORT. INSPECT DRAIN PAN TO CONFIRM THERE ARE NO OBSTRUCTIONS OR ICE BUILD UP AND THAT WATER IS FLOWING PROPERLY. CHECK OPERATION / CALIBRATION OF ALL FAN CYCLE AND DEFROST CONTROLS. LOOK FOR ABNORMAL ACCUMULATUTION OF ICE PATTERNS AND ADJUST DEFROST CYCLES ACCORDINGLY. INSPECT LINESET FROM THE EVAPORATOR COIL TO ROOF TOP CONDENSER FOR SIGNS OF DETERIORATION OR ICE BUILD UP. INSPECT CONDENSER FOR SIGNS OF OIL OR A REFRIGERANT LEAK WITHIN THE COIL. VERIFY ALL ELECTRICAL COMPONENTS ARE OPERATING PROPERLY. WASH CONDENSER COIL. 15-9 �C 6or Pd rote � ����Eln �inJ rr CartL�oi 5'jSY��t15� CHECK UNIT SUPERHEAT AND COMPARE READING AGAINST MANUFACTURER CALL OUT. LOG TEMPERATURES OF THE WALK IN BOX BEFORE AND AFTER MAINTENANCE. 15-10 - Y. �C � ¢6or �i _ P®inte Cam' �rronir� cb Con ero C S�JS `m51 CITY OF NEWPORT BEACH UK JOB LOCATION: CITY OF NEWPORT BEACH - MARINA PARK 1600 WEST BALBOA BLVD NEWPORT BEACH, CA 92663 Site: MARINA PARK JOB SUBJECT: PERFORM QUARTERLY HVAC MAINTENACE EQUIPMENT LISTED: BUILDING FLOOR LOCATION UNIT MANUFACTURER MODEL# OUTDOOR # ID CONDENSER BALBOA SFC 1 1ST DAIKIN FXMQ36PVJU HRU-1 ROOM 1-3 BALBOA SFC 1 1ST DAIKIN FXMQ48MVJU HRU-1 ROOM 1-4 BOAT BAY SFC 1 1ST DAIKIN FXAQ07MVJU HRU-1 OFFICE 1 1-5 SF6C 1 2ND LINDA ISLE DAIKIN FXMQ36PVJU HRU-1 SFC 1 2ND LINDA ISLE DAIKIN FXMQ30PVJU HRU-1 UPPER SFC 1 2ND DAIKIN FXMQ48MVJU HRU-1 MEZZANINE 1-8 1 H +',bor P® to 16""ei�G+r cnnirv[ 51�St 1 2ND CONFERENCE S 9C DAIKIN FXZQ18PVJU HRU-1 HALLWAY TO SFC 1 2ND DAIKIN FXAQ24PVJU HRU-1 OFFICES 1-10 SFC 2ND FLOOR 1 2ND 1- DAIKIN FXAQ07PVJU HRU-1 OFFICES 11A SFC 2ND FLOOR 1 2ND 1- DAIKIN FXAQ07MVJU HRU-1 OFFICES 11B SFC 2ND FLOOR 1 2ND 1- DAIKIN FXAQ07MVJU HRU-1 OFFICES 11C 2ND FLOOR SFC 1 2ND CORNER DAIKIN FXAQ18MVJU HRU-1 1-12 OFFICE SFC 1 2ND MFD ROOM DAIKIN FXAQ24MVJU HRU-1 1-13 BOAT BAY 1 1 DAIKIN UNKNOWN OFFICE 2 NEWPORT 2 1ST ISLAND 21C DAIKIN FXMQ48PVJU HRU-2 ROOM NEWPORT SFC 2 1ST ISLAND DAIKIN FXMQ48PVJU HRU-2 2-2 ROOM ADMIN OFFICE ACROSS SFC 2 1ST DAIKIN FXMQ30PVJU HRU-2 FROM LIDO 2-3 ISLAND ROOM ADMIN OFFICE ACROSS SFC 2 1ST DAIKIN FXMQ30PVJU HRU-2 FROM LID0 2-4 ISLAND ROOM NEWPORT 2 1ST ISLAND 5 DAIKIN FXMQ18PVJU HRU-2 2C ROOM 2 15-12 Hail �ante �"`r`t�oairJ rh-CantroLS�%Ste 51 BAY ISLAND SFC 2 2ND DAIKIN FXMQ72MVJU HRU-2 ROOM 2-6 BAYISLAND SFC 2 2ND DAIKIN FXMQ48MVJU HRU-2 ROOM 2-7 WARMING SFC 2 2ND DAIKIN FXMQ48MVJU HRU-2 KITCHEN 2-8 WARMING SFC 2 2ND DAIKIN FXMQ36PVJU HRU-2 KITCHEN 2-9 WARMING SFC 2 2ND DAIKIN FXMQ36PVJU HRU-2 KITCHEN 2-10 BAY ISLAND SFC 2 2ND DAIKIN FXMQ18PVJU HRU-2 ROOM 2-11 CONDENSER INFORMATION BUILDING FLOOR LOCATION UNIT ID MANUFACTURER MODEL# # 1 2ND MEZZANINE HRU1 DAIKIN REYQ335PYDN MECHANICAL 2 1ST HRU2 DAIKIN REY0336PYDN YARD BRANCH SELECTOR BOXES QTY UNIT ID 12 BS 3 TONX-Y 6 BS 5 TON X-Y 3 BS B TON X-Y BUILDING FLOOR LOCATION MANUFACTURER MODEL# DAIKIN BSVQ36 DAIKIN BSVQ60 DAIKIN BSVQ96 EXHAUST FANS UNIT ID MANUFACTURER MODEL# CFM TYPE 3 15-13 1..g Haxbor �� Pointe, �"`riioai�ry di Cantrof Sri 5'" MECHANICAL CWB BELT 2 1ST EF2 GREENHECK 1300 YARD 141 HP DRIVEN BELT 1 ROOFTOP EF3 GREENHECK CUBE-141 1600 DRIVEN NOTE: THE EQUIPMENT BELOW WILL NOT BE SERVICED DURING THE MAINTENANCE PER LUKE MASON U OUTDO BRAN BUIL FLO LOCATI NI MANUFAC MODEL VOLTAG OR CH DING TYPE BTU OR ON T TURER # E CONDE SELE # ID NSER CTOR BOAT SF HORIZ BS 1-1 2ND BAY C FXMQ72 ONTAL 208VllP 1 DAIKIN 81000 HRU-1 (8 STORA 1- MVJU DISCHA H160HZ TON) GE 1 RGE SF HORIZ BS 1-2 RESTAU C FXMQ24 ONTAL 208VA P 1 1ST DAIKIN 27000 HRU-1 (3TON RANT 1- PVJU DISCHA H160HZ 2 RGE U BUIL FLO LOCATI NI MANUFAC MODEL DING CFM TYPE OR ON T TURER # # ID RO RESTAU EF PANASON FV- DIRECT 1 80 OAP RANT 1 IC O8VK1 DRIVE U BUIL FLO LOCATI NI MANUFAC MODEL HEATIN VOLTAG DING OR ON T TURER # G BTU E # ID BOAT R SPACE 120V/1P 1 1ST BAY CB 50 50000 H1 RAY HI60HZ GARAG 4 15-14 Haribor ['-P6inte h�kio�rer+g eii Ca ntro � 5�j E BOAT 1ST BAY R SPACE CB50 50000 120V/1P GARAG H2 RAY H160HZ E SCOPE OF WORK: CONDENSERS INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS. INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS. VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE. VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. BRANCH SELECTOR INSPECT REFRIGERANT PIPING FOR SIGNS OF LEAKS VERIFY SOLENOID OPERATION THROUGH SWITCHING FUNCTION AT THE CONTROLLER. CONTROLLER CONFIRM PROPER OPERATION OF SYSTEM CONTROLLERS. s 15-15 ®Y P®inte ���tio�tl��C�i'Cantro � t� 5, NOTATE ANY ALARMS OR FAULT CODES. CONFIRM PROPER OPERATION FROM CONTROLLER TO AIR HANDLER. EXHAUSTFANS CONFIRM PROPER OPERATION OF BELT DRIVEN EXHAUST FANS. CHANGE BELT ANNUALLY. INSPECT PULLIES AND BEARINGS FOR SIGNS OF WEAR. GREASE BEARINGS EACH VISIT. CONFIRM PROPER OPERATION OF ELECTRICAL SWITCHES. WIPE OUT INTERIOR OF THE MOTOR COMPARTMENT. 15-16 Hakibor f . nte 1w�' ssri n ""o—g cYControf .5jjst CITY OF NEWPORT BEACH CK JOB LOCATION: CITY OF NEWPORT BEACH - OASIS SENIOR CENTER 801 NARCISSUS AVE CORNA DEL MAR, CA 92625 JOB SUBJECT: PREFROM QUARTERLY HVAC MAINTENANCE EQUIPMENT LISTED: ROOF TOP HVAC PACKAGE UNITS OASIS SENIOR CENTER MODEL UNIT ID MANUFACTURER BUILDING SERVICE LOCATION VOLTAGE FITNESS DANCE I EXERCISE 208 VOLTAGE I AC1 CARRIER 48PG14 CENTER ROOM 3PHASE FITNESS WELLNESS FITNESS 208 VOLTAGE I AC2 CARRIER 48PG08 CENTER CENTER SOUTH 3 PHASE FITNESS WELLNESS FITNESS 208 VOLTAGE / AC3 CARRIER 48PG08 CENTER CENTER NORTH 3 PHASE EVENT KITCHEN AND 208 VOLTAGE / AC4 CARRIER 48PG08 CENTER RESTROOMS 3PHASE EVENT FACILITIES RR'S AND 208 VOLTAGE / AC5 CARRIER 48PG03 CENTER STORAGE 1PHASE EVENT PLATFORM AND 208 VOLTAGE I AC6 CARRIER 48PG05 CENTER STORAGE 1PHASE 1 15-17 H � i* r _" Pdinte �l �tial ner 57�51C1115.` AC7 CARRIER 48PG14 EVENT MAIN EVENT ROOM 208 VOLTAGE I CENTER NORTH 3PHASE AC8 CARRIER 48PG06 EVENT MAIN EVENT ROOM 208 VOLTAGE / CENTER SOUTH EAST 1PHASE AC9 CARRIER 48PG06 EVENT MAIN EVENT ROOM 208 VOLTAGE / CENTER SOUTH WEST 1PHASE INDOOR SPLIT SYSTEM FAN COIL UNIT MODEL UNIT ID MANUFACTURER BUILDING AREA SERVED VOLTAGE SFC-1 CARRIER FX4C OASIS SENIOR MEETING 208 VOLTAGE / 060 CENTER / ADMIN ROOM A 1 PHASE FX4C OASIS SENIOR FAMILY ROOM 208 VOLTAGE 1 SFC-2 CARRIER 030 CENTER/ADMIN LOBBY 1 PHASE FX4C OASIS SENIOR COMPUTER 208 VOLTAGE / SFC-3 CARRIER 036 CENTER/ADMIN ROOM 1 PHASE SFC-4 CARRIER FX4C OASIS SENIOR FAMILY ROOM 208 VOLTAGE 1 030 CENTERIADMIN LOBBY 1 PHASE SFC-5 CARRIER FX4C OASIS SENIOR OFFICES ! 208 VOLTAGE 1 024 CENTER/ADMIN LOBBY 1 PHASE FX4C OASIS SENIOR 208 VOLTAGE I SFC-6 CARRIER OFFICES 018 CENTERIADMIN 1 PHASE SFC-7 CARRIER FX4C OASIS SENIOR OFFICES 208 VOLTAGE / 018 CENTERIADMIN 1 PHASE FX4C OASIS SENIOR 208 VOLTAGE / SFC-8 CARRIER OFFICES 018 CENTERIADMIN 1 PHASE FX4C OASIS SENIOR OFFICES ! 208 VOLTAGE / SFC-9 CARRIER 024 CENTERIADMIN LOBBY 1 PHASE FX4C OASIS SENIOR OFFICES ! 208 VOLTAGE / SFC-10 CARRIER 024 CENTER I ADMIN LOBBY 1 PHASE FX4C OASIS SENIOR OFFICES / 208 VOLTAGE / SFC-11 CARRIER 024 CENTER/ADMIN LOBBY 1 PHASE SFC-12 CARRIER FX4C OASIS SENIOR FAMILY ROOM 208 VOLTAGE 1 030 CENTER / ADMIN LOBBY 1 PHASE FX4C OASIS SENIOR OFFICES / 208 VOLTAGE / SFC-13 CARRIER 024 CENTER / ADMIN LOBBY 1 PHASE 2 15-18 e .i ;� 1bor P®lnte � tioWw O'1Co. roL Sjst SFC-14 CARRIER FX4C OASIS SENIOR OFFICES 208 VOLTAGE / 018 CENTER/ADMIN 1PHASE SFC-15 CARRIER FX4C OASIS SENIOR OFFICES 208 VOLTAGE / 018 CENTER/ADMIN 1PHASE OUTDOOR SPLIT SYSTEM CONDENSER UNIT MODEL UNIT ID MANUFACTURER BUILDING AREA SERVED VOLTAGE 38QRR OASIS SENIOR MEETING 208 VOLTAGE SHP-1 CARRIER 060 CENTER/ADMIN ROOM A / 1 PHASE 38QRR OASIS SENIOR FAMILY ROOM 208 VOLTAGE SHP-2 CARRIER 030 CENTER I ADMIN LOBBY 11 PHASE 38QRR OASIS SENIOR COMPUTER 208 VOLTAGE SHP-3 CARRIER 060 CENTER / ADMIN ROOM / 1 PHASE 38QRR OASIS SENIOR FAMILY ROOM 208 VOLTAGE SHP-4 CARRIER 030 CENTER / ADMIN LOBBY /1 PHASE 38QRR OASIS SENIOR OFFICES ! 208 VOLTAGE SHP-5 CARRIER 024 CENTER/ADMIN LOBBY /1PHASE SHP-6 CARRIER 38QRR OASIS SENIOR OFFICES 208 VOLTAGE 018 CENTER I ADMIN 11 PHASE 380RR OASIS SENIOR 208 VOLTAGE SHP-7 CARRIER OFFICES 018 CENTER I ADM[N I 1 PHASE 38QRR OASIS SENIOR 208 VOLTAGE SHP-8 CARRIER OFFICES 018 CENTER / ADMIN / 1 PHASE 38QRR OASES SENIOR OFFICES / 208 VOLTAGE SHP-9 CARRIER 024 CENTER / ADMIN LOBBY 11 PHASE 38QRR OASIS SENIOR OFFICES 1 208 VOLTAGE SHP-10 CARRIER 024 CENTERIADMIN LOBBY 11PHASE 38QRR OASIS SENIOR OFFICES ! 208 VOLTAGE SHP-11 CARRIER 024 CENTER IADMIN LOBBY 11PHASE 38QRR OASIS SENIOR FAMILY ROOM 208 VOLTAGE SHP-12 CARRIER 030 CENTER I ADMIN LOBBY 11 PHASE 380RR OASIS SENIOR OFFICES / 208 VOLTAGE SHP-13 CARRIER 024 CENTER I ADMIN LOBBY I 1 PHASE 3 15-19 .a6®r Pdinte "t'iiorci�� rh- Can tro C S�Js t SHP-14 CARRIER 38QRR OASIS SENIOR OFFICES 208 VOLTAGE 018 CENTER I ADM1N / 1 PHASE SHP-15 CARRIER 38QRR OASIS SENIOR OFFICES 208 VOLTAGE 018 CENTER / ADMIN / 1 PHASE INDOO R HEAT PUMP FAN COIL UNITS (VRFZ) UNIT ID MANUFACTURE MODEL # BUILDIN AREA MANUFACTURE MODEL # VOLTAG R G SERVED R E OASIS PDFY- SENIOR 208 SFC 16- MITSUBISHI P18NMHU CENTER STAFF DAIKIN FSXQ18MVJ VOLTAG 1 LOUNGE U E 1 1 -E / CLASS ROOM PHASE OASIS PDFY- SENIOR MEETIN 208 SFC 16- MITSUBISHI P24NMHU CENTER GROOM DAIKIN FXSQ24MVJ VOLTAG 2A U E/1 -E /CLASS B ROOM PHASE OASIS PDFY- SENIOR MEETIN 208 SFC 16- FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU CENTER G ROOM DAIKIN 2B U Ell -E / CLASS B PHASE ROOM OASIS PDFY- SENIOR MEETIN 208 208 SFC 16 MITSUBISHI P24NMHU CENTER G ROOM DAIKIN FXSQ24MVJ VOLTAG 3A U Ell -E / CLASS C PHASE ROOM OASIS PDFY- SENIOR MEETIN 208 SFC 16- FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU CENTER G ROOM DAIKIN 3B U Ell -E /CLASS C PHASE ROOM SFC 16- PDFY- OASIS MEETIN FXSQ24MVJ 208 MITSUBISHI DAIKIN 4A P24NMHU SENIOR G ROOM U VOLTAG 4 15-20 - y "rtionir9 rH Cn nirof S�� t• -E CENTER D Ell / CLASS PHASE ROOM OASIS 208 PDFY- SENIOR MEETIN SFC 16- FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU CENTER G ROOM DAIKIN 4B U Ell -E /CLASS D PHASE ROOM OASIS 208 PDFY- SENIOR MEETIN SFC 16- FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU CENTER G ROOM DAIKIN 5A U Ell -E / CLASS E PHASE ROOM OASIS 208 PDFY- SENIOR MEETIN SFC 16- FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU CENTER G ROOM DAIKIN 5B U Ell -E /CLASS E PHASE ROOM OASIS 208 PDFY- SENIOR MEETIN SFC 16- FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU CENTER G ROOM DAIKIN 6A U El l -E /CLASS F PHASE ROOM OASIS 208 PDFY- SENIOR MEETIN SFC 16- FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU CENTER G ROOM DAIKIN 6B U Ell -E / CLASS F PHASE ROOM FITNESS 208 PDFY- SFC 17- CENTER ART FXSQ36MVJ VOLTAG MITSUBISHI PE 6NMHU DAIKIN 1A / CLASS CENTER U Ell ROOM PHASE FITNESS 208 PDFY- SFC 17- CENTER ART FXSQ36MVJ VOLTAG MITSUBISHI DAIKIN 1B E3$NMHU /CLASS CENTER U Ell ROOM PHASE FITNESS 208 PDFY- MEETIN SFC 17- CENTER FXSQ24MVJ VOLTAG MITSUBISHI P24NMHU G ROOM DAIKIN 2A I CLASS U E/ 1 -E G ROOM PHASE PDFY- FITNESS MEETIN 208 17 MITSUBISHI P24NMHU CENTER G ROOM DAIKIN UXSQ24MVJ VOLTAG 2BC -E /CLASS G E/1 6 15-21 Harbor P® me t�ms� `yitianlr� cy ControGS�JS ROOM FITNESS PDFY- MEETIN SFC. 17- CENTER MITSUBISHI P24NMHU G ROOM DAIKIN 3A I CLASS -E H ROOM FITNESS PDFY- MEETIN SFC 17- CENTER MITSUBISHI P24NMHU G ROOM DAIKIN 3B I CLASS E H ROOM SPLIT SYSTEM OUTDOOR HEAT PUMP CONDENSER (V RFZ) UNIT ID SHP 16 SHP17 SUPPLY AND EXHAUST FANS UNIT ID EF-1 EF-2 EF-3 PHASE 208 FXSQ24MVJ VOLTAG U Ell PHASE 208 FXSQ24MVJ VOLTAG U Ell PHASE MANUFACTURER MODEL BUILDING MANUFACTURER MODEL* VOLTAGE 208 MITSUBISHI PUNY- FITNESS DAIKIN RXYQ216PTJU VOLTAGE P204 CENTER MITSUBISHI PUHY- FITNESS DAIKIN P144 CENTER MODEL MANUFACTURER AREA SERVED TYPE 120 ROOM 128, 130, UPBLAST COOK ACRUB JANITOR 129 CENTRIFIGAL DOWNBLAST COOK 70ACEB ROOM 137 & 138 CENTRIFIGAL DOWNBLAST COOK 60 ACEB JANITOR 150 CENTRIFIGAL 13 PHASE 208 RXYQ144PTJU VOLTAGE /3PHASE HP VOLTAGE MOTOR 120 1/6 VOLTAGE 11 PHASE 120 1/6 VOLTAGE / 1 PHASE 120 116 VOLTAGE/1 6 15-22 PHASE 135 WELLNESS UPBLAST 120 EF-4 COOK 1/6 VOLTAGE 11 ACRUB CENTER RR'S CENTRIFIGAL PHASE 120 80 DOWNBLAST EF-5 COOK ELECTRICAL 156 1/6 VOLTAGE 11 ACRUB CENTRIFIGAL PHASE 120 UPBLAST 120 EF-6 COOK RR'S 165 & 166 1/6 VOLTAGE! 1 ACRUB CENTRIFIGAL PHASE 120 80 DEW EF-7 COOK ELECTRICAL 173 1/6 VOLTAGE! 1 ACRUB R]FIGA CENTRIFIGAL PHASE 120 80 JANITOR 170, RR DOWNBLAST EF-8 COOK 1/6 VOLTAGE / 1 ACRUB 176,177 CENTRIFIGAL PHASE 120 80 EF-9 COOK DISHWASHER 1/6 VOLTAGE / 1 ACRUB CENTRIFIGAL IGAL PHASE 230 240XP UPSLAST KEF-1 GREENHECK KITCHEN 2 VOLTAGE / 3 CUBE CENTRIFIGAL PHASE 120 90 ASP- ADMIN EAST TIERED SF-1 COOK V3 VOLTAGE / 1 T OUTDOOR AIR ROOFTOP PHASE 120 90 ASP- ADMIN WEST TIERED SF-2 COOK 116 VOLTAGE / 1 T OUTDOOR AIR ROOFTOP PHASE NOTE: HARBOR POINTE WILL SCHEDULE TO BE ONSITE AND ACCESS THE CLASSROOM AIR HANDLERS DURING TIMES OF NON OCCUPANCY TO AVOID DISRUPTIONS WITH PLANNED ACTIVITIES. SCOPE OF WORK: CONDENSERS it 15-23 A cd®r'. -P6inte "�tiu�r�rg e3'Cnntr0f 5t) t INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS. INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS. VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE. VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. BRANCH SELECTOR INSPECT REFRIGERANT PIPING FOR SIGNS OF LEAKS VERIFY SOLENOID OPERATION THROUGH SWITCHING FUNCTION AT THE CONTROLLER. CONTROLLER CONFIRM PROPER OPERATION OF SYSTEM CONTROLLERS. NOTATE ANY ALARMS OR FAULT CODES. CONFIRM PROPER OPERATION FROM CONTROLLER TO AIR HANDLER. PACKAGE UNITS REPLACE FILTERS EACH QUARTER. INSPECT INDOOR BLOWER MOTOR, BEARINGS, BELT, AND PULLEY. LUBRICATE BEARINGS WITH GREASE AS NECESSARY. CHANGE BELT ANNUALLY. INSPECT EVAPORATOR COIL, CONDENSER COILS, AND COMPRESSOR FOR SIGNS OF OIL. 15-24 Harbor 3 Bi®jnt% h�f/o+<+'r9 rh� C�ntrol5��ste COMFIRM COMPRESSOR OPERATION AND AMERAGE DRAW. CONFIRM PROPER OPERATION OF THE CONDENSER FAN MOTOR AND FAN BLADES. INSPECT ELECTRICAL CONNECTIONS, CONTACTORS, RELAYS, AND CAPACITORS. WASH CONDENSER COILS EACH QUARTER. CONFIRM CONDENSATE DRAIN LINES AND DRAIN PANS ARE CLEAR OF OBSTRUCTIONS. VERIFY THERMOSTAT OPERATIONS. CONFIRM SUPPLY AND RETURN AIR TEMPERATURE AT THE REGISTERS. EXHAUST FANS CONFIRM PROPER OPERATION OF BELT DRIVEN EXHAUST FANS. CHANGE BELT ANNUALLY. INSPECT PULLIES AND BEARINGS FOR SIGNS OF WEAR. GREASE BEARINGS EACH VISIT. CONFIRM PROPER OPERATION OF ELECTRICAL SWITCHES. WIPE OUT INTERIOR OF THE MOTOR COMPARTMENT. 9 15-25 H6or Tointe ` C4�`r`tronlnJ r4 Cn niror S135 �,n5 CITY OF NEWPORT BEACH Site: NEWPORT COAST COMMUNITY CENTER JOB LOCATION: CITY OF NEWPORT BEACH - NEWPORT COAST COMMUNITY CENTER 6401 SAN JOAQUIN HILLS ROAD NEWPORT BEACH, CA 92657 JOB SUBJECT: PERFORM QUARTERLY HVAC MAINTENANCE EQUIPMENT LISTED: ROOFTOP PACKAGE UNITS UNIT ID MANUFACTURER MODEL # TONNAGE AREA SERVED VOLTAGE AC1 CARRIER 48PGDO07 6 LOBBY 208 VOLTAGE 3. PHASE COMMUNICATION ROOM 208 VOLTAGE 3 AC2 CARRIER 48PGDO07 6 1A & 1B PHASE 208 VOLTAGE 3 AC3 CARRIER 48PGDO28 25 GYMNASIUM PHASE 208 VOLTAGE 3 AC4 CARRIER 48PGDO28 25 GYMNASIUM PHASE 208 VOLTAGE 3PHASE AC5 CARRIER 48PGD006 5 GALLERY COMMUNICATION ROOM 208 VOLTAGE 3 AC6 CARRIER 48PGDO06 5 #2 PHASE 15-26 A Har�dor 4 Pointe "�tiPni�� �,y Cnntro C S+JS e AC7 CARRIER 48PGDO06 5 COMMUNICATION ROOM 208 VOLTAGE 3 #3 PHASE AC8 CARRIER 48PGDO05 4 PLATFORM C121 208 VOLTAGE 3 PHASE EXHAUST FANS MODEL UNIT ID MANUFACTURER DRIVE AREA SERVED LOCATION VOLTAGE 120- RESTROOM C112 & GYM ROOF 120 VOLT / 1 EF1 COOK BELT ACEB C114 TOP PHASE 80 GYM ROOF 120 VOLT / 1 EF2 COOK BELT WARMING KITCHEN ACEB TOP PHASE 129 VOLT 11 EF3 COOK GC-120 DIRECT STORAGE C103 CEILING PHASE MECH EQUIPMENT 120VOLT11 EF4 COOK GC-140 DIRECT CEILING ROOM C104 PHASE 120 VOLT / 1 EF5 COOK GC-420 DIRECT ELECTRICAL C106 CEILING PHASE 120 VOLT / 1 EF6 COOK GC-140 DIRECT STORAGE C106A CEILING PHASE 80 GYM ROOF 120 VOLT 11 EF7 COOK BELT PLATFORM C121 ACEB TOP PHASE SPLIT SYSTEM FAN COIL UNIT [D FC1 FC2 SPLIT SYSTEM CONDENSER UNIT ID CU1 CU2 MANUFACTURER MODEL# LOCATION VOLTAGE CARRIER 40QNE-009 OFFICE C102 115 VOLT 11 PHASE CARRIER 40QNB-012 OFFICE C106 115 VOLT/ 1 PHASE MANUFACTURER MODEL# LOCATION VOLTAGE CARRIER 38BK-009 GYM ROOF 208 VOLT / 1 PHASE MITSUBISHI 38AN-012-1 GYM ROOF 208 VOLT 11 PHASE 91 15-27 Hak'i6®r Pdin" to '+..�hoc. 'r�tronir� cb Cnncro � S�js SCOPE OF WORK: CONDENSERS INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS. INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN -THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS. VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE. VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. PACKAGE UNITS REPLACE FILTERS EACH QUARTER. INSPECT INDOOR BLOWER MOTOR, BEARINGS, BELT, AND PULLEY. LUBRICATE BEARINGS WITH GREASE AS NECESSARY. CHANGE BELT ANNUALLY. INSPECT EVAPORATOR COIL, CONDENSER COILS, AND COMPRESSOR FOR SIGNS OF OIL. COMFIRM COMPRESSOR OPERATION AND AMERAGE DRAW. CONFIRM PROPER OPERATION OF THE CONDENSER FAN MOTOR AND FAN BLADES. INSPECT ELECTRICAL CONNECTIONS, CONTACTORS, RELAYS, AND CAPACITORS. 15-28 Harbor Ointe h�t`o'+irg rrC'antro[ S�Jst` WASH CONDENSER COILS EACH QUARTER. CONFIRM CONDENSATE DRAIN LINES AND DRAIN PANS ARE CLEAR OF OBSTRUCTIONS. VERIFY THERMOSTAT OPERATIONS. CONFIRM SUPPLY AND RETURN AIR TEMPERATURE AT THE REGISTERS. EXHAUSTFANS CONFIRM PROPER OPERATION OF BELT DRIVEN EXHAUST FANS. CHANGE BELT ANNUALLY. INSPECT PULLIES AND BEARINGS FOR SIGNS OF WEAR. GREASE BEARINGS EACH VISIT. CONFIRM PROPER OPERATION OF ELECTRICAL SWITCHES. 15-29 j He'd or A Bointe C'o °�trorrrr� rb Cn n tr0 � StJs��ri CITY OF NEWPORT BEACH Site: COMMUNITY YOUTH CENTER JOB LOCATION: CITY OF NEWPORT BEACH - COMMUNITY YOUTH CENTER 3000 5TH AVE NEWPORT BEACH, CA 92625 EQUIPMENT LISTED: (5) AIR HANDLERS (5) CONDENSERS (1) ROOF TOP EXHAUST FAN JOB SUBJECT: PERFORM QUARTERLY HVAC MAINTENANCE SCOPE OF WORK: CONDENSERS INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS, INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS. 15-30 tg11t5� i�['ort+ram ch' Cantro � $y5 VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE. VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. EXHAUSTFANS CONFIRM PROPER OPERATION OF BELT DRIVEN EXHAUST FANS. CHANGE BELT ANNUALLY. INSPECT PULLIES AND BEARINGS FOR SIGNS OF WEAR. GREASE BEARINGS EACH VISIT. CONFIRM PROPER OPERATION OF ELECTRICAL SWITCHES. WIPE OUT INTERIOR OF THE MOTOR COMPARTMENT. 15-31 Hw, rninte "�tranir� rr Cantro� S� CITY OF NEWPORT BEACH Site: CLIFF DRIVE COMMUNITY CENTER JOB LOCATION: CITY OF NEWPORT BEACH - CLIFF DRIVE COMMUNITY CENTER 301 RIVERSIDE AVE NEWPORT BEACH, CA 92663 JOB SUBJECT: PERFORM QUARTERLY HVAC MAINTENANCE EQUIPMENT LISTED: LOCATION MANUFACTURER MODEL # SERIAL # OUTSIDE CONDENER MITSUBISHI TBD TBD INSIDE DUCTLESS FAN COIL MITSUBISHI PKA-A36KA7 14MO2327 SCOPE OF WORK: CONDENSERS INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS. 1 15-32 P®inte Y.. 1"s�..._...�e�,,,�`�� .r. '"ter ,5`$`• x C���Fioni�J rh'Cnn1rOC $j5t �n5� INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS. VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE, VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. 15-33 ° tron1w Nrrantro�st]5 CITY OF NEWPORT BEACH JOB LOCATION: CITY OF NEWPORT BEACH - THEATER ARTS CENTER 2501 CLIFF DR. NEWPORT BEACH, CA 92663 JOB SUBJECT: PERFORM QUARTERLY HVAC MAINTENANCE EQUIPMENT LISTED: (3) AIR HANDLERS (3) CONDENSERS (1) ROOF TOP PACKAHE UNIT (1) ROOF TOP EXHAUST FAN LOCATION DOWN STAIRS MECHANICAL ROOM AIR HANDLERS AIR HANDLERS GROUND LEVEL OUTSIDE CONDENSER Lois] ► IN] :Qg61:1N MANUFACTURER MODEL# CARRIER 58CTX045-12 N4H348AKE100 N4H348AKF200 THEATER ARTS CENTER SERIAL # 20WA15373 E110415032 E144219597 1 15-34 �A�o iI�J�,yr-fit �5`,�• 'r�t�on+•y crCnntroC S)St� MAIN FLOOR THEATER ROOM ROOF TOP PACKAGE UNIT BDP 655ANX036000AAAF 2499G43394 ROOF TOP EXHAUST FAN (D/D) ROOF TOP CONDENSER SCOPE OF WORK: CONDENSERS INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS. INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS. VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE. VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. PACKAGE UNITS REPLACE FILTERS EACH QUARTER. INSPECT INDOOR BLOWER MOTOR, BEARINGS, BELT, AND PULLEY. 15-35 Hanbor VI Pointe � ��fio irr� r7 Can L r0 � St�s LUBRICATE BEARINGS WITH GREASE AS NECESSARY. CHANGE BELT ANNUALLY. INSPECT EVAPORATOR COIL, CONDENSER COILS, AND COMPRESSOR FOR SIGNS OF OIL. COMFIRM COMPRESSOR OPERATION AND AMERAGE DRAW. CONFIRM PROPER OPERATION OF THE CONDENSER FAN MOTOR AND FAN BLADES. INSPECT ELECTRICAL CONNECTIONS, CONTACTORS, RELAYS, AND CAPACITORS. WASH CONDENSER COILS EACH QUARTER. CONFIRM CONDENSATE DRAIN LINES AND DRAIN PANS ARE CLEAR OF OBSTRUCTIONS. VERIFY THERMOSTAT OPERATIONS. CONFIRM SUPPLY AND RETURN AIR TEMPERATURE AT THE REGISTERS. EXHAUST FANS CONFIRM PROPER OPERATION OF BELT DRIVEN EXHAUST FANS. CHANGE BELT ANNUALLY. INSPECT PULLIES AND BEARINGS FOR SIGNS OF WEAR. GREASE BEARINGS EACH VISIT. CONFIRM PROPER OPERATION OF ELECTRICAL SWITCHES. WIPE OUT INTERIOR OF THE MOTOR COMPARTMENT. 15-36 H b®r 6&te "fltiohi y rr controC S�JS°e CITY OF NEWPORT BEACH JOB LOCATION: CITY OF NEWPORT BEACH - CARROLL BEEK CENTER 115 AGATE AVE NEWPORT BEACH, CA 92662 Site: CARROLL BEEK CENTER JOB SUBJECT: PERFORM QUARTERLY HVAC MAINTENANCE EQUIPMENT LISTED: LOCATION MANUFACTURER MODEL# SERIAL# CRAWL SPACE ABOVE KITCHEN AIR HANDLER ROOFTOP CONDENSER INTERNATIONAL COMFORT PRODUCTS N4A636GKA101 El54018498 EXHAUST FAN (BELT DRIVEN) SCOPE OF WORK: CONDENSERS 1 15-37 Harbor Pointe 'r�tiorri � rT Cnntro[StJsi INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS. INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS. VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE. VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. EXHAUSTFANS CONFIRM PROPER OPERATION OF BELT DRIVEN EXHAUST FANS. CHANGE BELT ANNUALLY. INSPECT PULLIES AND BEARINGS FOR SIGNS OF WEAR. GREASE BEARINGS EACH VISIT. CONFIRM PROPER OPERATION OF ELECTRICAL SWITCHES. WIPE OUT INTERIOR OF THE MOTOR COMPARTMENT. 15-38 Har,,for Pointe �`rtiort(r� Cy co tro S�jSt CITY OF NEWPORT BEACH nK JOB LOCATION: CITY OF NEWPORT BEACH - BONITA CREEK CENTER 3010 LA VIDA NEWPORT BEACH, CA 92660 Site: BONITA CREEK COMMUNITY CENTER JOB SUBJECT: PERFORM QUARTERLY HVAC MAINTENANCE EQUIPMENT LISTED: LOCATION MANUFACTURER MODEL # SERIAL # GROUND LEVEL CONDENSER BLUERIDGE BM30Y18C FAN COIL (DUCTLESS) BLUERIDGE BM30Yl8WM INDOOR CLOSET (FURNANCE) RHEEM ROOFTOP CONDENSER FUJITSU FAN COIL (DUCTLESS) FUJITSU AOU12RQ BPNO05374 1 15-39 Hr ibor Pointe "f?ronG� Cy contro(Sjst� SCOPE OF WORK: CONDENSERS INSPECT PHYSICAL CONDITION OF THE CONDENSER FOR SIGNS OF OIL AROUND THE CONDENSER COILS OR COMPRESSORS, INSPECT REFRIGERANT LINE SET FOR PROPER INSULATION. WASH THE CONDENSER COILS WITH WATER EACH TIME ONSITE. INSPECT AND CLEAN THE FAN BLADES AND HOUSING. CHECK REFRIGERANT PRESSURES AND OPERATING PARAMETERS. INSPECT ALL ELECTRICAL CONNECTIONS, CONTACTORS AND RELAYS, VERIFY PROPER OPERATION OF THE COMPRESSORS. RECORD RUNNING AMPS, VOLTAGE, AND PRESSURES. AIR HANDLERS REMOVE AND REPLACE AIR FILTERS. REMOVE AND WASH FILTERS WHEN APPLICABLE. VERIFY PROPER OPERATION OF CONDENSATE PUMPS. CLEAN EVAPORATOR COIL SURFACE WITH A BRUSH. CONFIRM PROPER OPERATION OF THE INDOOR FAN MOTOR AND WHEEL. INSPECT AND CLEAN DRAIN PANS, FLUSH DRAIN LINES WITH CO2 WHEN NECESSARY. CONFIRM PROPER OPERATION OF ELECTRONIC EXPANSION VALVES. 15-40 EXHIBIT B SCHEDULE OF BILLING RATES HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page B-1 15-41 COST FILE Section 1: Monthly/Quarterly Preventative Maintenance Pricing COST FOR COST FOR TOTAL CITY FACILITY ADDRESS MONTHLY QUARTERLY ANNUAL MAINTENANCE MAINTENANCE MAINTENANCE COST Corporation Yard 592 Superior Ave $1694.75 $6779.00 Utilities Yard 949 W. 16th St $2501.77 $10007.08 Back Bay Science 600 Shellmaker Rd $645.62 $2582.48 Police Dept. HQ p 870 Santa Barbara $2897.02 $11588.08 Ave Animal Shelter 20282 Riverside Dr $322.81 $1291.24 Fire Station # 1 110 E Balboa Blvd $80.70 $322.80 Fire Station # 2 2807 Newport Blvd $1092.13 $13105.61 Fire Station # 3 868 Santa Barbara Dr $888.50 $3654.00 Fire Station # 4 124 Marine Ave $242.11 $968.44 Fire Station # 5 410 Marigold Ave $706.70 $2826.80 Fire Station # 6 1348 Irvine Ave $80.70 $322.80 Fire Station # 7 20401 SW Acacia St $661.49 $2605.98 Fire Station # 8 6502 Ridge Park Rd $570.79 $2283.17 Lifeguard HQ 70 Newport Pier $621.28 $7455.38 Jr Lifeguard Building 901 East Ocean Front $232.29 $2787.54 CDM Lifeguard HQ 3029 Ocean Blvd $293.37 $3520.47 Balboa Library 100 E Balboa Blvd $674.02 $2696.06 Corona Del Mar 410 Marigold Ave $800.57 $3202.27 Library 15-42 COST FILE The Jetty Snack Shack 3029 Ocean Blvd $254.44 $1017.76 Marina Park 1600 W Balboa Blvd $7294.48 $29,177.92 Oasis Senior Center 801 Narcissus Ave $9338.98 $37,355.92 Newport Coast Community Center 6401 San Joaquin Hills Rd $3240.00 $12,960.00 Community Youth Center 3000 5th Ave $714.00 $2856.00 Cliff Drive Youth Center 301 Riverside Ave $242.67 $970.68 Newport Theater Arts Center 2501 Cliff Dr $726.82 $2907.28 Carroll Beek 115 Agate Ave $417.03 $1668.12 Bonita Creek Community Center 3010 La Vida $551.05 $2204.20 Police Dept. HQ R Refrigeration 870 Santa Barbara Ave $1433.77 $5735.08 Total for all Facilities $2,239.07 $36,970.79 $174,752.16 15-43 COST FILE Section 2: On -Call Repair Services Pricing *For purposes of the project costs score, on -call will be estimated at 100 hours annually UNIT MINIMUM HOURS COST Labor Charge 1 Hours $141.7g Per Hour After Hours Labor (To be used for work performed after 4:30 PM 2 Hours $212.67 Per Hour Monday — Thursday, after 3:30 PM on Fridays, and all of Sat., Sun., and holidays. Replacement Equipment, Parts, Materials, and Equipment Rentals Markup % 15 % (Maximum 15%) CPI ADJUSTMENT: Billing rates may be given up to a 2% annual CPI increase upon the first anniversary of the contract and each anniversary thereafter. 15-44 EXHIBIT C INSURANCE REQUIREMENTS — MAINTENANCEIREPAIRIJANITORIAL SERVICES 1. Provision of Insurance. Without limiting Contractor's indemnification of City, and prior to commencement of Work, Contractor shall obtain, provide and maintain at its own expense during the term of this Agreement, policies of insurance of the type and amounts described below and in a form satisfactory to City. Contractor agrees to provide insurance in accordance with requirements set forth here. If Contractor uses existing coverage to comply and that coverage does not meet these requirements, Contractor agrees to amend, supplement or endorse the existing coverage. 2. Acceptable Insurers. All insurance policies shall be issued by an insurance company currently authorized by the Insurance Commissioner to transact business of insurance in the State of California, with an assigned policyholders' Rating of A- (or higher) and Financial Size Category Class VII (or larger) in accordance with the latest edition of Best's Key Rating Guide, unless otherwise approved by the City's Risk Manager. 3. Coverage Requirements. A. Workers' Compensation Insurance. Contractor shall maintain Workers' Compensation Insurance, statutory limits, and Employer's Liability Insurance with limits of at least one million dollars ($1,000,000) each accident for bodily injury by accident and each employee for bodily injury by disease in accordance with the laws of the State of California, Section 3700 of the Labor Code. Contractor shall submit to City, along with the certificate of insurance, a Waiver of Subrogation endorsement in favor of City, its City Council, boards and commissions, officers, agents, volunteers and employees. B. General Liability Insurance. Contractor shall maintain commercial general liability insurance and, if necessary, umbrella liability insurance, with coverage at least as broad as provided by Insurance Services Office form CG 00 01, in an amount not less than two million dollars ($2,000,000) per occurrence, four million dollars ($4,000,000) general aggregate. The policy shall cover liability arising from premises, operations, products -completed operations, personal and advertising injury, and liability assumed under an insured contract (including the tort liability of another assumed in a business contract). C. Automobile_ Liability Insurance. Contractor shall maintain automobile insurance at least as broad as Insurance Services Office form CA 00 01 covering bodily injury and property damage for all activities of Contractor arising out of or in connection with Work to be performed under this Agreement, including coverage for any owned, hired, non -owned or rented vehicles, in an amount not less than one million dollars ($1,000,000) combined single limit each accident. HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page C-1 15-45 4. Other Insurance Requirements. The policies are to contain, or be endorsed to contain, the following provisions: A. Waiver of Subrogation. All insurance coverage maintained or procured pursuant to this Agreement shall be endorsed to waive subrogation against City, its City Council, boards and commissions, officers, agents, volunteers and employees or shall specifically allow Contractor or others providing insurance evidence in compliance with these requirements to waive their right of recovery prior to a loss. Contractor hereby waives its own right of recovery against City, and shall require similar written express waivers from each of its subcontractors. B. Additional Insured Status. All liability policies including general liability, products and -completed operations, excess liability, pollution liability, and automobile liability, if required, shall provide or be endorsed to provide that City, its City Council, boards and commissions, officers, agents, volunteers and employees shall be included as insureds under such policies. C. Primary and Non Contributory. All liability coverage shall apply on a primary basis and shall not require contribution from any insurance or self-insurance maintained by City. D. Notice of Cancellation. All policies shall provide City with thirty (30) calendar days notice of cancellation (except for nonpayment for which ten (10) calendar days notice is required) or nonrenewal of coverage for each required coverage. 5. Additional Agreements Between the Parties. The parties hereby agree to the following: A. Evidence of Insurance. Contractor shall provide certificates of insurance to City as evidence of the insurance coverage required herein, along with a waiver of subrogation endorsement for workers' compensation and other endorsements as specified herein for each coverage. Insurance certificates and endorsement must be approved by City's Risk Manager prior to commencement of performance. Current certification of insurance shall be kept on file with City at all times during the term of this Agreement. The certificates and endorsements for each insurance policy shall be signed by a person authorized by that insurer to bind coverage on its behalf. At least fifteen (15) days prior to the expiration of any such policy, evidence of insurance showing that such insurance coverage has been renewed or extended shall be filed with the City. If such coverage is cancelled or reduced, Contractor shall, within ten (10) days after receipt of written notice of such cancellation or reduction of coverage, file with the City evidence of insurance showing that the required insurance has been reinstated or has been provided through another insurance company or companies. City reserves the right to HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page C-2 15-46 require complete, certified copies of all required insurance policies, at any time. B. City's Right to Revise Requirements. City reserves the right at any time during the term of the Agreement to change the amounts and types of insurance required by giving Contractor sixty (60) calendar days advance written notice of such change. If such change results in substantial additional cost to Contractor, City and Contractor may renegotiate Contractor's compensation. C. Right to Review Subcontracts. Contractor agrees that upon request, all agreements with subcontractors or others with whom Contractor enters into contracts with on behalf of City will be submitted to City for review. Failure of City to request copies of such agreements will not impose any liability on City, or its employees. Contractor shall require and verify that all subcontractors maintain insurance meeting all the requirements stated herein, and Contractor shall ensure that City is an additional insured on insurance required from subcontractors. For CGL coverage, subcontractors shall provide coverage with a format at least as broad as CG 20 38 04 13. D. Enforcement of Agreement Provisions. Contractor acknowledges and agrees that any actual or alleged failure on the part of City to inform Contractor of non-compliance with any requirement imposes no additional obligations on City nor does it waive any rights hereunder. E. Requirements not Limiting. Requirements of specific coverage features or limits contained in this Section are not intended as a limitation on coverage, limits or other requirements, or a waiver of any coverage normally provided by any insurance. Specific reference to a given coverage feature is for purposes of clarification only as it pertains to a given issue and is not intended by any party or insured to be all inclusive, or to the exclusion of other coverage, or a waiver of any type. If the Contractor maintains higher limits than the minimums shown above, the City requires and shall be entitled to coverage for higher limits maintained by the Contractor. Any available insurance proceeds in excess of the specified minimum limits of insurance and coverage shall be available to the City. F. Self -insured Retentions. Any self -insured retentions must be declared to and approved by City. City reserves the right to require that self - insured retentions be eliminated, lowered, or replaced by a deductible. Self-insurance will not be considered to comply with these requirements unless approved by City. G. City Remedies for Non -Compliance. If Contractor or any subcontractor fails to provide and maintain insurance as required herein, then City shall have the right but not the obligation, to purchase such insurance, to terminate this Agreement, or to suspend Contractor's right to proceed HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page C-3 15-47 until proper evidence of insurance is provided. Any amounts paid by City shall, at City's sole option, be deducted from amounts payable to Contractor or reimbursed by Contractor upon demand. H. Timely Notice of Claims. Contractor shall give City prompt and timely notice of claims made or suits instituted that arise out of or result from Contractor's performance under this Agreement, and that involve or may involve coverage under any of the required liability policies. City assumes no obligation or liability by such notice, but has the right (but not the duty) to monitor the handling of any such claim or claims if they are likely to involve City. Contractor's Insurance. Contractor shall also procure and maintain, at its own cost and expense, any additional kinds of insurance, which in its own judgment may be necessary for its proper protection and prosecution of the Work. HARBOR POINTE AIR CONDITIONING & CONTROL SYSTEMS, INC. Page C-4 15-48