HomeMy WebLinkAbout92-19 - Amending Chapter 15.06 Newport Beach Municipal Code to Adopt the National Electrical Code, 1991 EditionORDINANCE NO. 92- 19
AN ORDINANCE OF THE CITY OF NEWPORT BEACH
AMENDING CHAPTER 15.06 NEWPORT BEACH
MUNICIPAL CODE TO ADOPT THE NATIONAL
ELECTRICAL CODE, 1991 EDITION
The City Council of the City of Newport Beach DOES ORDAIN as follows:
•SECTION 1. Chapter 15.06 of the Newport Beach Municipal Code is
adopted to read:
Chapter 15.06
ELECTRICAL CODE
Sections:
15.06.010
Adoption of The National Electrical Code.
15.06.020
Amendment
to
Article
90 -4.
15.06.030
Addition of Article 90 -9.
15.06.040
Amendment
to
Article
110 -5.
15.06.050
Amendment
to
Article
210 -1.
15.06.060
Amendment
to
Article
250- 91(b).
15.06.070
Amendment
to
Article
345 -3(b).
15.06.080
Amendment
to
Article
346 -1(c).
15.06.090
Amendment
to
Article
348 -1.
15.06.100
Amendment
to
Article
350.5.
• 15.06.010 Adoption of the National Electrical Code. The City Council
adopts and incorporates by reference, as though set forth in full in this
Chapter, the 1990 edition of the "National Electrical Code" as published by the
National Fire Protection Association International Conference, subject to the
changes and modifications set forth in this chapter. The City Council also
adopts and incorporates by reference all applicable portions of Title 24,
California Code of Regulations subject to the changes, and modifications set
forth in this chapter.
The various parts of this code, along with the additions, amendments and
deletions adopted in this Chapter, shall constitute and be known as the Newport
Beach "Electrical" Code. A copy of the 1990 National Electrical Code, printed
. in code book form shall be kept on file in the office of the City Clerk.
15.06.020 Amendment to Article 90 -4. Article 90 -4 of the Electrical Code
is amended to read:
90 -4 Enforcement. The Building Official of the City of Newport Beach shall
enforce the provisions of this code and shall have the responsibility for making
interpretations of the rules, for deciding upon the approval of equipment and
1
materials, and for granting the special permission contemplated in a number of
the rules. All administrative provisions including permit process, fees and
inspections for this chapter are contained in the Administrative Code under
Chapter 15.02.
15.06.030 Addition of Article 90 -9. Article 90 -9 is added to the
• Electrical Code to read:
90 -9 Electrical Inspector. Electrical Inspector shall be the Building
Official of the City of Newport Beach and such other person or persons in the
Building Department as are authorized and directed by the Building Official to
carry out under his /her direction and supervision the powers and duties set forth
in this Code.
Whenever the term "Electrical Inspector" is used in any section of this
ordinance such term shall be construed to mean the Building Official or his /her
authorized representative.
15.06.040 Amendment to Article 110 -5. Article 110 -5 of the Electrical
Code is amended to read:
110 -5 - Conductors normally used to carry current shall be of copper,
•except that conductor sizes of #6AWG and larger may be of aluminum. To install
smaller than #6 AWG aluminum conductors, all termination points must have
continuous inspection by a special inspector approved pursuant to Section
15.02.040 of this Code. Where the conductor materials are not specified, the
sizes given in this code shall apply to copper conductors. Where other materials
are used, the size shall be changed accordingly.
For aluminum and copper clad aluminum conductors, see tables 310 -16 through
310 -19 of this code.
15.06.050 Amendment to Article 210 -1. Article 210 -1 of the National
Electrical Code is amended to read:
210 -1 Scope. The provisions of this Article shall apply to branch
circuits supplying lighting or appliance loads or combinations of such loads.
Where motors, or motor - operated appliances, are connected to any circuit
• supplying lighting or other appliance loads, the provisions of both this Article
and Article 430 shall apply. Article 430 shall apply where branch circuit
supplies only motor loads.
N
Accessory uses or other buildings, signs, etc., separately located on the
same lot or premises shall have connecting conductors run underground.
(Agricultural areas excepted.)
Where spare circuit protective devices are provided or space for future
circuit protective devices is provided on the buss in any flush or semi -flush
•mounted panel, then raceways of sufficient capacity to permit utilization of such
space or spaces shall be provided to an approved accessible location. Such
accessible location is defined as follows: Where sufficient attic or underfloor
space is available, a raceway shall terminate conveniently for future use in each
such space. Where this condition does not exist, then such terminations shall
be approved by the Electrical Inspector.
15.06.060 Amendment to Article 250- 91(b). Article 250 -91(b) of the
Electrical Code amended to read:
EXCEPTION NO. 1: No flexible metal conduit shall be permitted for
grounding.
15.06.070 Amendment to Article 345 -3(b). Article 345 -3(b) of the National
Electrical Code is amended to read:
•345 -3(b) Intermediate metal conduit, elbows, couplings, and fittings shall
be permitted in concrete or in above ground areas subject to severe corrosion
when provided with corrosion protection judged suitable for the condition.
(FPN): See Section 300 -6 for protection against corrosion.
15.06.080 Amendment to Article 346 -1(c). Article 346 -1(c) of the National
Electrical Code is amended to read:
346 -1(c) - Ferrous or nonferrous metal conduit, elbows, couplings, and
fittings shall be permitted to be installed in concrete, or in areas subject to
severe corrosion when provided with corrosion protection judged suitable for the
condition. (FPN): See Section 300 -6 for protection against corrosion.
15.06.090 Amendment to Article 348 -1. Article 348 -1 of the Electrical
Code is amended to read:
• 348 -1 Use - Electrical metallic tubing may be used for both exposed and
concealed work inside of structures. Electrical metallic tubing shall not be
installed in a manner which will cause it to be exposed to the outside air or
weather conditions. Electrical metallic tubing protected from corrosion solely
by enamel shall not be used. Electrical metallic tubing shall not be used (1)
where during installation or afterwards, it will be subject to severe physical
3
damage; (2) for installation underground. Where practical, the use of dissimilar
metals throughout the system shall be avoided to eliminate the possibility of
galvanic action. (See Article 300 -6 for limitation in the use of ferrous raceways
and fittings protected from corrosion solely by enamel.)"
15.06.100 Amendment to Article 350 -5. Article 350 -5 of the National
• Electrical Code is amended to read:
350 -5 Grounding. Flexible metal conduit shall not be permitted as a
grounding means.
SECTION 2. That if any section, subsection, sentence, clause or phrase of
this ordinance is, for any reason, held to be invalid or unconstitutional, such
decision shall not affect the validity or constitutionality of the remaining
portions of this ordinance. The City Council hereby declares that it would have
passed this ordinance, and each section, subsection, clause or phrase hereof,
irrespective of the fact that any one or more sections, subsections, sentence,
clauses and phrases be declared unconstitutional.
SECTION 3. This Ordinance shall be published once in the official
newspaper of the City, and the same shall be effective thirty (30) days after the
• date of its adoption.
This Ordinance was introduced at a regular meeting of the City Council of
the City of Newport Beach held on the 11th day of May . 1992, and
was adopted on the 8th day of Jame 1992, by the following
•
vote to wit:
2 ATTES
City Clerk-
AYES, COUNCIL MEMBERS HEDGES, WATT,
TURNER, SANSONE, HART, COX, PLUPHM
NOES, COUNCIL MEMBERS NONE
ABSENT COUNCIL MEMBERS NONE