Plan Check Correction Summary
I Nt9 br
March 18, 2014
City of Newport Beach
Vernon Orwig
Hoag — Site Improvements/Lighting (PC#: 0446-2014)
WBSA
ARCHITECTS
Item Sheet Topic
Discussion
Planning Dept.
1
A000
Campus Plan
Identify the building (its location on Hoag Campus) where
the new patio and landscape are proposed.
Response: Added campus plan with callout for
location of project.
2
A100
Partial Site Plan
Provide dimensions from the patio's posts to the nearest
street curbs.
Response: Added dimensions.
3
E410
Lighting
Photometric Plan
Lighting in the patio is too bright. Please explain the need
to stay this bright. How late will the patio stay open?
Response: We have reduced the number of lighting
fixtures and footcandle levels. See sheet E410.
Building Dept.
1
A211
Keynotes-Misc
Provide spec for Kalwall w/ smoke index/fire resistance.
Response: Added Kalwall UL Card to cover sheet
A000.
2
A211
New Gate
5'-0" Landing and 24" clear approach required.
Response: Plan has been revised to comply.
Electrical/Mechanical/Plumbing Dept.
1
Provide electrical panel load, schedules are to show the
following: Number of fixtures on each circuit; Load at 180
watts per general use receptacle or U.L. nameplate
rating; total wattage per each phase balanced; long
continuous loads [LCL] calculations to be shown at
125%.
Response: Concur — See sheet E030.
2
Provide unique circuit descriptions on panel schedule.
"Existing Load" is not acceptable description. CEC 408.4
Response: Concur— See sheet E030.
3
Electrical circuitry diagrams are to be accurate; provide
numbers next to each circuit on plans.
Response: Concur— See sheet E410.
4
Provide electrical Title 24 and 2008 Calif. Energy
Efficiency Standards. All required compliance forms and
mandatory measures are to be on the plans; LTG-1-C is
required to be on the plans, (LTG-2-C, LTG-3-C, LTG-4-
C, LTG-5-C, LTG-6-C, LTG-7-C, LTG-8-C, LTG-9-C,
OLTG when applicable).
1800 Quail • Newport Beach, California 92660 • wbsarch.com • 949.552.2061
Plan Check Correction Summary
Date:
To:
From:
Re:
March 18, 2014
City of Newport Beach
Vernon Orwig
Hoag — Site Improvements/Lighting (PC#: 0446-2014)
WBSA
ARCHITECTS
Response: Title 24 calculations not required for a
hospital building.
5
Add note to plans, "Comply with City of Newport Beach
amendments to 2013 CEC. Use rigid metal conduit in all
areas exposed to weather. Use ground wire inside all
flexible metal conduits. Metal conduit shall not be
installed in contact with earth."
Response: Concur; See General Note #27, sheet
E030.
End of Summary -